Data Sheet
SS/265GS/AS_3
ABB 2600T Series
Engineered solutions
for all applications
Base accuracy : ±0.04%
Span limits
0.2 to 60000kPa; 0.8inH2O to 8700psi
– 0.3 to 3000kPa abs; 2.25mmHg to 435psia
Reliable sensing system coupled with very latest
digital technologies
provides large turn down ratio up to 100:1
Comprehensive sensor choice
optimize in-use total performance and stability
5–year stability
Flexible configuration facilities
provided locally via local keys combined with LCD
indicator or via hand held terminal or
PC configuration platform
Multiple protocol availability
provides integration with HART®, PROFIBUS PA
and FOUNDATION Fieldbus platforms offering
interchangeability and transmitter upgrade
capabilities
Full compliance with PED Category III
FieldIT
2600T Series Pressure Transmitters
Model 265GS Gauge
Model 265AS Absolute
standard overload
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
2
Operative limits
Temperature limits °C (°F) :
Ambient (is the operating temperature)
Silicone oil filling: –40°C and +85°C (-40°F and +185°F)
Inert filling and white oil: –20°C and +85°C (–4°F and +185°F)
Lower limit for Viton gasket: –20°C (–4°F)
Lower limit for perfluoroelastomer gasket: –15°C (+5°F)
Note : For Hazardous Atmosphere applications see the temperature
range specified on the certificate/approval relevant to the aimed
type of protection.
Process
Lower limit
– –50°C (–58°F); –20°C (–4°F) for Viton gasket.
–15°C (+5°F) for perfluoroelastomer gasket
Upper limit
– Silicone oil, inert fluid and white oil: 121°C (250°F)
Storage
Lower limit: –50°C (–58°F); –40°C (–40°F) for LCD indicators
Upper limit: +85°C (+185°F)
Pressure limits
Overpressure limits (without damage to the transmitter)
0 absolute to
1MPa, 10bar, 145psi for sensor codes C, F
– 0.5MPa, 5bar, 72.5psi for sensor code L
6MPa, 60bar, 870psi for sensor code U
20MPa, 200bar, 2900psi for sensor code R
90MPa, 900bar, 13050psi for sensor code V
0.6MPa, 6bar, 87psi for perfluoroelastomer gasket
Proof pressure
The transmitter can be exposed without leaking to line pressure of up to
1MPa, 10bar, 145psi for sensor codes C, F
– 0.5MPa, 5bar, 72.5psi for sensor code L
6MPa, 60bar, 870psi for sensor code U
20MPa, 200bar, 2900psi for sensor code R
90MPa, 900bar, 13050psi for sensor code V
0.6MPa, 6bar, 87psi for perfluoroelastomer gasket
Note : Lower Range Limit (LRL) for 265AS is 0 abs for all ranges.
Span limits
Maximum span = URL
IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSOR
CODE PROVIDING THE TURNDOWN VALUE AS LOWEST AS
POSSIBLE TO OPTIMIZE PERFORMANCE CHARACTERISTICS.
Zero suppression and elevation
Zero and span can be adjusted to any value within the range limits
detailed in the table as long as:
– calibrated span minimum span
Damping
Adjustable time constant : 0 to 60s.
This is in addition to sensor response time
Turn on time
Operation within specification in less than 2.5s with minimum
damping.
Insulation resistance
> 100M at 1000VDC (terminals to earth)
Functional Specifications
Range and span limits
rosneS
edoC
egnaRreppU
)LRU(timiL
egnaRrewoL
)LRL(timiL
SG562rof
napsmuminiM
SG562
eguag
SA562
etulosba
C
aPk6
rabm06
Hni42
2
O
aPk6
rabm06
Hni42
2
O
aPk2.0
rabm2
Hni8.0
2
O
aPk3.0
rabm3
gHmm52.2
F
aPk04
rabm004
Hni061
2
O
aPk04
rabm004
Hni061
2
O
aPk4.0
rabm4
Hni6.1
2
O
aPk2
rabm02
gHmm51
L
aPk052
rabm0052
Hni0001
2
O
sba0
aPk5.2
rabm52
Hni01
2
O
aPk5.21
rabm521
gHmm8.39
U
aPk0003
rab03
isp534
sba0
aPk03
rab3.0
isp53.4
aPk051
rab5.1
isp7.12
R
aPk00001
rab001
isp0541
sba0
aPk001
rab1
isp5.41
V
aPk00006
rab006
isp0078
sba0
aPk006
rab6
isp78
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
3
Environmental limits
Electromagnetic compatibility (EMC)
Definition Class 3
Radio suppression Limit class B
(according to EN 550011)
Fulfills NAMUR recommendation
Low voltage directive
Comply with 73/23/EEC
Pressure equipment directive (PED)
Comply with 97/23/EEC Category III module H.
Humidity
Relative humidity: up to 100% annual average
Condensing, icing: admissible
Vibration resistance
Accelerations up to 2g at frequency up to 1000Hz
(according to IEC 60068–2–26)
Shock resistance (according to IEC 60068–2–27)
Acceleration: 50g
Duration: 11ms
Wet and dust-laden atmospheres
The transmitter is dust and sand tight and protected against immersion
effects as defined by IEC EN60529 (1989) to IP 67 (IP 68 on request)
or by NEMA to 4X or by JIS to C0920.
Hazardous atmospheres
Transmitters of the type of protection "Intrinsically safe EEx ia"
according to the directions 94 / 9 / EC (ATEX)
Transmitter with 4 to 20mA output signal and HART communication
Marking (DIN EN 50 014): II 1/2 GD T50°C EEx ia IIC T6 or resp.
II 1/2 GD T95°C EEx ia IIC T4
Supply and signal circuit type of protection Intrinsic Safety
EEx ib IIB/IIC resp. EEx ia IIB/IIC
for connection to supply units with maximum values:
II 1/2 GD T50°C EEx ia resp. ib IIC T6 resp.
II 1/2 GD T95°C EEx ia resp. ib IIC T4
for Temperature class T4 resp. T95°C:
Ui = 30V
Ii = 200mA
Pi = 0.8W for T4 with Ta = (–40 to +85)°C / (–40 to +185)°F
Pi = 1.0W for T4 with Ta = (–40 to +70)°C / (–40 to +158)°F
for Temperature class T6 resp. T50°C:
Pi = 0.7W for T6 with Ta = (–40 to +40)°C / (–40 to +104)°F
effective internal capacitance, Ci 10nF
effective internal inductance, negligible.
Fieldbus transmitters (PROFIBUS PA / FOUNDATION Fieldbus)
Marking (DIN EN 50 014): II 1/2 GD T50°C EEx ia IIC T6 or resp.
II 1/2 GD T95°C EEx ia IIC T4
Supply and signal circuit type of protection Intrinsic Safety
EEx ib IIB/IIC resp. EEx ia IIB/IIC
for connection to FISCO supply units with rectangular or
trapezoidal characteristics with maximum values:
II 1/2 G EEx ia respectively ib IIC T4/T6 Ui = 17.5V
Ii = 360mA
Pi = 2.52W
II 1/2 G EEx ia respectively ib IIB T4/T6 Ui = 17.5V
Ii = 380mA
Pi = 5.32W
resp. for connection to supply unit or barrier with linear
characteristics with maximum values:
II 1/2 G EEx ia respectively ib IIC T4/T6 Ui = 24V
li = 250mA
Pi = 1.2W
effective internal inductance Li 10 µH,
effective internal capacitance Ci 0
Maximum permissible ambient temperatures depending on the
temperature class:
T4: –40°C to +85°C (–40°F to +185°F)
T5, T6: –40°C to +40°C (–40°F to +104°F)
Transmitters of the type of protection "flameproof enclosure EEx d"
according to the directions 94 /9 / EC (ATEX)
Transmitter with 4 to 20mA output signal and HART communication
and Fieldbus transmitters (PROFIBUS PA / FOUNDATION Fieldbus)
Marking (DIN EN 50 014): II 1/2 G EEx d IIC T6
Ambient temperature range: –40°C to +75°C (–40°F to +167°F)
Transmitters of category 3 for the application in "Zone 2"
Transmitter with 4 to 20mA output signal and HART communication
according to the directions 94 / 9 / EC (ATEX)
Marking (DIN EN 50 014): II 3 GD T50°C EEx nL IIC T6 or resp.
II 3 GD T95°C EEx nL IIC T4
Operating conditions:
Supply and signal circuit (terminals signal +/-): U 45V
I 22.5mA
Ambient temperature range:
Temperature class T4 Ta=–40°C to +85°C (–40°F to +185°F)
Temperature class T5, T6 Ta=–40°C to +40°C (–40°F to +104°F)
Factory Mutual (FM)
Transmitter with 4 to 20mA output signal and HART communication
Intrinsically safe: Class I; Division 1; Groups A, B, C, D;
Class I; Zone 0; Group IIC; AEx ia IIC
Degree of protection : NEMA Type 4X (indoor or outdoor)
Permissible ambient temperature depending on temperature class
Fieldbus transmitters (PROFIBUS PA/FOUNDATION Fieldbus)
Intrinsically Safe : Class I, II and III; Division 1; Groups A, B,
C, D, E, F, G;
Class I; Zone 0, AEx ia Group IIC T6; T4
Non-incendive Class I, II and III, Division
2; Groups A, B, C, D, F, G
Transmitter with 4 to 20mA output signal and HART communication
and Fieldbus transmitters (PROFIBUS PA/FOUNDATION Fieldbus)
Explosion-Proof: Class I; Division 1; Groups A, B, C, D;
Class II/III, Division 1; Groups E, F, G
Degree of protection : NEMA Type 4X (indoor or outdoor)
Canadian Standard (CSA)
Transmitter with 4 to 20mA output signal and HART communication
and Fieldbus transmitters (PROFIBUS PA/FOUNDATION Fieldbus)
Explosion-Proof: Class I; Division 1; Groups B, C, D
Class II; Division 1; Groups E, F, G
Class III
Degree of protection : NEMA Type 4X (indoor or outdoor)
U
xam
Hµ01=iL,Fn5.01=iC,V03=
erutarepmeTtneibmA erutarepmeT
ssalc I
xam
iP
)F°581+ot04(C°58+ot04 4TAm002W8.0
)F°921+ot04(C°07+ot04 4TAm002W1
)F°401+ot04(C°04+ot04 5TAm52W57.0
)F°401+ot04(C°04+ot04–6TAm52W5.0
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
4
Electrical Characteristics and Options
HART digital communication and 4 to 20mA output
Power Supply
The transmitter operates from 10.5 to 45VDC with no load and is
protected against reverse polarity connection (additional load allows
operations over 45VDC).
Minimum power supply is 14VDC with backlit indicator.
For EEx ia and other intrinsically safe approval power supply must not
exceed 30VDC.
Ripple
Maximum permissible voltage ripple of power supply during the
communication:
7Vpp at f = 50 to 100Hz
1Vpp at f = 100 to 200Hz
0.2Vpp at f = 200 to 300Hz
Load limitations
4 to 20mA and HART total loop resistance :
A minimum of 250 is required for HART communication.
R(k) = Supply voltage – min. operating voltage (VDC)
–––––––––––––––––––––––––––––––––––––––
22.5 mA
Optional indicators
Integral display
2-line, 6-character 19-segment alphanumeric display with additional
bar chart display, optionally with back illumination. User-specific
display:
percentage of the output current or
output current in mA or
free process variable
Diagnostic message, alarms, measuring range infringements and
changes in the configuration are also displayed.
Optional surge protection
Up to 4kV
voltage 1.2µs rise time / 50µs delay time to half value
current 8µs rise time / 20µs delay time to half value
Output signal
Two–wire 4 to 20mA, user-selectable for linear or freely programmable
with 20 reference points output.
HART® communication provides digital process variable (%, mA or
engineering units) superimposed on 4 to 20mA signal, with protocol
based on Bell 202 FSK standard.
Output current limits (to NAMUR standard)
Overload condition
- Lower limit: 3.8mA (configurable down to 3.5mA)
- Upper limit: 20.5mA (configurable up to 22.5mA)
Alarm current
Min. alarm current: configurable from 3.5mA to 4mA,
standard setting: 3.6mA
Max. alarm current: configurable from 20mA to 22.5mA,
standard setting: 21mA
Standard setting: max. alarm current
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
5
PROFIBUS PA output
Device type
Pressure transmitter compliant to Profile 3.0 Class A & B; ident. number
04C2 HEX.
Power supply
The transmitter operates from 10.2 to 32VDC with no polarity.
For EEx ia approval power supply must not exceed 17.5VDC.
Intrinsic safety installation according to FISCO model.
Current consumption
operating (quiescent): 11.7mA
fault current limiting: 17.3mA max.
Output signal
Physical layer in compliance to IEC 1158–2/EN 61158–2 with
transmission to Manchester II modulation, at 31.25kbit/sec.
Output interface
PROFIBUS PA communication according to Profibus DP50170 Part 2/
DIN 19245 part 1–3.
Output update time
40ms
Function blocks
1 Analog Input, 1 Transducer, 1 Physical
Integral display
2-line, 6-character 19-segment alphanumeric display with additional
bar chart display, optionally with back illumination. User-specific
display:
percentage of the output or
OUT (analog input function block)
Diagnostic message, alarms, measuring range infringements and
changes in the configuration are also displayed.
Transmitter failure mode
Permanent self-diagnostic; possible errors indicated in diagnostic
parameters and in the status of process values.
FOUNDATION Fieldbus output
Power supply
The transmitter operates from 10.2 to 32VDC polarity independent.
For EEx ia approval power supply must not exceed 24VDC (entity
certification) or 17.5VDC (FISCO certification), according to FF–816.
Current consumption
operating (quiescent): 11.7mA
fault current limiting: 17.3mA max.
Output signal
Physical layer in compliance to IEC 1158–2/EN 61158–2 with
transmission to Manchester II modulation, at 31.25kbit/sec.
Function blocks/execution period
1 standard Analog Input block/25ms max
Additional blocks
1 custom Pressure with calibration Transducer block
1 enhanced Resource block
Number of link objects
10
Number of VCRs
16
Output interface
FOUNDATION fieldbus digital communication protocol to standard H1,
compliant to specification V. 1.5; FF registration in progress.
Integral display
2-line, 6-character 19-segment alphanumeric display with additional
bar chart display, optionally with back illumination. User-specific
display:
percentage of the output or
OUT (analog input )
Diagnostic message, alarms, measuring range infringements and
changes in the configuration are also displayed.
Transmitter failure mode
Permanent self-diagnostic; possible errors indicated in diagnostic
parameters and in the status of process values.
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
6
Operating influences
Ambient temperature (for turndown up to 15:1)
per 20K (36°F) change between the limits of
–20°C to +65°C (–4 to +150°F)
±(0.03% URL + 0.05% span)
Supply voltage
Within voltage/load specified limits the total effect is less than
0.001% of URL per volt.
Load
Within load/voltage specified limits the total effect is negligible.
Radio frequency interference
Total effect : less than 0.05% of span from 20 to 1000MHz and for
field strengths up to 10V/m when tested with unshielded conduit,
with or without meter.
Common mode interference
No effect from 250Vrms @ 50Hz, or 50VDC
Stability
±0.10% of URL over a thirty-six-month period
Vibration effect
±0.10% of URL (according to IEC 61298–3)
URL
Span
Performance specifications
Stated at reference condition to IEC 60770 ambient temperature of 20°C
(68°F), relative humidity of 65%, atmospheric pressure of 1013hPa
(1013mbar), zero based range for transmitter with isolating diaphragms
ceramic or Hastelloy and silicone oil fill and HART digital trim values equal
to 4–20mA span end points, in linear mode.
Unless otherwise specified, errors are quoted as % of span.
Some performance data (based to URL) are affected by the actual
turndown (TD) as ratio between Upper Range Limit (URL) and calibrated
span.
IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSOR CODE
PROVIDING THE TURNDOWN VALUE AS LOWEST AS POSSIBLE TO
OPTIMIZE PERFORMANCE CHARACTERISTICS.
Dynamic performance (according to IEC 61298–1 definition)
Dead time: 30ms
Time constant (63.2% of total step change):
150 ms for all sensors
Accuracy rating
% of calibrated span, including combined effects of terminal based
linearity, hysteresis and repeatability.
For fieldbus versions SPAN refer to Analog Input Function Block
outscale range
±0.04% for TD from 1:1 to 10:1
±(0.04 + 0.005 x – 0.05)% for TD greater than 10:1
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
7
Physical Specification
(Refer to ordering information sheets for variant availability related to
specific model or versions code)
Materials
Process isolating diaphragms (*)
Ceramic (Al203) gold-plated; Hastelloy C276™;
Hastelloy C276™ gold-plated; AISI 316 L ss.
Process connection (*)
AISI 316 L ss; Hastelloy C276™.
Gasket (only for sensor codes C, F) (*)
Viton™, Perfluoroelastomer, Perbunan (NBR).
Sensor fill fluid
Silicone oil; inert fill (Carbon fluoride); white oil (FDA).
Mounting bracket
AISI 316 L ss.
Sensor housing
AISI 316 L ss.
Electronic housing and covers
Barrel version
– Low-copper content aluminium alloy with baked epoxy finish;
– AISI 316 L ss.
DIN version
Low-copper content aluminium alloy with baked epoxy finish.
Covers O-ring
Viton™.
Local zero and span adjustments
Glass filled polycarbonate plastic (removable).
Tagging
AISI 316ss or plastic data plate attached to the electronics housing.
Calibration
Standard: at maximum span, zero based range, ambient temperature
and pressure;
Optional: at specified range and ambient conditions; or at operating
temperature.
Optional extras
Mounting brackets
For vertical and horizontal 60mm. (2in) pipes or wall mounting.
Integral display
plug-in rotatable LCD indicator
Supplemental customer tag
AISI 316 ss tag fastened to the transmitter with stainless steel wire for
customer's tag data up to a maximum of 30 characters and spaces.
Surge protection
not available with ATEX-EEx nL or PROFIBUS PA / FOUNDATION
Fieldbus with Intrinsic Safety EEx i or FM-Intrinsically Safe.
Cleaning procedure for oxygen service (not for sensor V)
Test Certificates (test, design, calibration, material traceability)
Tag and manual language
Communication connectors
Process connections
1/2in NPT female or male; DIN EN837–1 G 1/2in Form B or Form D for
convex seal; front bonded diaphragm; for ball valve.
Electrical connections
Two 1/2 NPT or M20x1.5 threaded conduit entries, direct on
housing.
Communication connector:
– HART: straight or angle Harting Han 8U connector and one plug.
– PROFIBUS PA, FOUNDATION Fieldbus : M12x1 or 7/8
(without mating female plug)
Terminal block
HART version: four terminals for signal/external meter wiring up to
2.5mm2 (14AWG) and four connection points for test and
communication purposes.
Fieldbus versions: two terminals for signal (bus connection) wiring
up to 2.5mm2 (14AWG).
Grounding
Internal and external 4mm2 (12AWG) ground termination points are
provided.
Mounting position
Transmitter can be mounted in any position.
Electronics housing may be rotated by 360°. A positive stop
prevents over travel.
Mass (without options)
1.2kg approx (3lb); add 1.5kg (3.4lb) for AISI housing.
Add 650g (1.5lb) for packing.
Packing
Carton 24 x 14 x 19cm approx (10 x 6 x 8in).
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
8
Configuration
Transmitter with HART communication and 4 to 20 mA
Standard configuration
Transmitters are factory calibrated to customer's specified range.
Calibrated range and tag number are stamped on the type plate. If
calibration range and tag data are not specified, the transmitter will be
supplied configured as follows:
4 mA Zero
20 mA Upper Range Limit (URL)
Output Linear
Damping 0.125s
Transmitter failure mode 21mA
Any or all the above configurable parameters, including Lower range–value
and Upper range-value which must be the same unit of measure, can be
easily changed using the HART hand–held communicator or by a PC
running the configuration software SMART VISION with DTM for 2600T.
The transmitter database is customized with specified flange type and
material, o–ring and filling liquid.
Transmitter with PROFIBUS PA communication
Transmitters are factory calibrated to customer's specified range.
Calibrated range and tag number are stamped on the type plate. If
calibration range and tag data are not specified, the transmitter will be
supplied configured as follows:
Measure Profile Pressure
Engineering Unit mbar/bar
Output scale 0% Lower Range Limit (LRL)
Output scale 100% Upper Range Limit (URL)
Output Linear
Hi-Hi Limit Upper Range Limit (URL)
Hi Limit Upper Range Limit (URL)
Low Limit Lower Range Limit (LRL)
Low-Low Limit Lower Range Limit (LRL)
Limits hysteresis 0.5% of output scale
PV filter 0.125s.
Address 126
Any or all the above configurable parameters, including Lower range–value
and Upper range-value which must be the same unit of measure, can be
easily changed by a PC running the configuration software SMART VISION
with DTM for 2600T.
The transmitter database is customized with specified flange type and
material, o–ring and filling liquid.
Transmitter with FOUNDATION Fieldbus
communication
Transmitters are factory calibrated to customer's specified range.
Calibrated range and tag number are stamped on the type plate. If
calibration range and tag data are not specified, the transmitter will be
supplied configured as follows:
Measure Profile Pressure
Engineering Unit mbar/bar
Output scale 0% Lower Range Limit (LRL)
Output scale 100% Upper Range Limit (URL)
Output Linear
Hi-Hi Limit Upper Range Limit (URL)
Hi Limit : Upper Range Limit (URL)
Low Limit Lower Range Limit (LRL)
Low-Low Limit Lower Range Limit (LRL)
Limits hysteresis 0.5% of output scale
PV filter 0.125s
Address Not necessary
Any or all the above configurable parameters, including lower range value
and upper range value which must be the same unit of measure, can be
changed by any FOUNDATION Fieldbus compatible configurator.
The transmitter database is customized with specified flange type and
material, o–ring and filling liquid.
™ Hastelloy is a Cabot Corporation trademark
™ Viton is a Dupont de Nemour trademark
(*) Wetted parts of the transmitter.
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
9
56 (2.20)
29
(1.14)
9 (0.35) 58 (2.28)
114 (4.49) 23 (0.91)
28
(1.10)
20 (0.79)
MOUNTING DIMENSIONS (not for construction unless certified) - dimensions in mm (in)
Transmitter with barrel housing
Additional tag
plate
Housing rotation
stop screw
Terminal side
Clearance for
cover removal
Process
connection
Space must be
available to rotate
the key-board cover
83 (3.27)
42
(1.65)
Electrical
connections
(with gland)
Identification
plate
Captive screw
for keys unit
cover
Housing cover
Electrical connection
(with plug)
Plate with keys legend
140 (5.51)
A
124 (4.88)
76 (2.99)
26 (1.02)
70 (2.76)
Dimension "A" is dependent upon range and process connection:
with LCD indicator
noitcennocssecorP sedocrosneS
F,C
sedocrosneS
V,R,U,L
daerhtelamTPN412/1)16.6(861)18.6(371
daerhtelamefTPN412/1)22.6(851 )56.6(961
Vrosnes-)77.6(271
BmroFni2/1G738NENID)85.6(761)18.6(371
DmroFni2/1G738NENID
laesxevnocrof )10.7(871)02.7(381
mgarhpaiddednobtnorF---txenees
noitcennocevlavllabroF----txenees
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
10
Transmitter with DIN housing
20 (0.79)
70 (2.76)
61 (2.40)
48 (1.89)
47 (1.85)
56 (2.20)
*28 (1.10)
* dimensions of sensor code L, U, R, V
136 (5.35) / *140 (5.51)
124 (4.88)
12 (0.47)
*16 (0.63)
76 (2.99)
A
100 (3.94)
26
(1.02)
58 (2.28)
23 (0.91)
20 (0.79)
130 (5.12)
83 (3.27)
Additional tag
plate
Electrical connection
(with gland)
Housing rotation
stop screw
Housing
cover
Process
connection
Terminal
side
Identification
plate
Groove for screws (wall
or pipe mounting)
Captive screw for
keys unit cover
Plate with
keys legend
Dimension "A" is dependent upon range and process connection:
Space must be
available to rotate
the key-board cover
noitcennocssecorP sedocrosneS
F,C
sedocrosneS
V,R,U,L
daerhtelamTPN412/1)16.6(861)18.6(371
daerhtelamefTPN412/1)22.6(851 )56.6(961
Vrosnes-)77.6(271
BmroFni2/1G738NENID)85.6(761)18.6(371
DmroFni2/1G738NENID
laesxevnocrof )10.7(871)02.7(381
mgarhpaiddednobtnorF---txenees
noitcennocevlavllabroF----txenees
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
11
Transmitter with front bonded diaphragm (Barrel housing)
29.6
(1.17)
25 (0.98)
G1in
25 (0.98)
222 (8.74)
272 (10.71)
76 (2.99)
146 (5.75)
29
(1.14)
37
(1.46)
20
(0.79)
A
ø 50
ø 21.3-0.2
G 1/2
ø 19.4 +0.1
21
15
-0.2
min.
10.5
ø 18.2 +0.1
0.1 A
Transmitter with ball valve connection (Barrel housing)
Weld-on adaptor and socket
Front bonded diaphragm
Chamfer after tapping
Burrless.
width across
flats 27mm
groove for sealing
ring DIN 3869-21
(18.5x23.9x1.5)
G 1/2 B
groove for O-ring (15x2)
width across
flats 36mm
Washer
Conical seal
metal / metal
(hygienic design)
The diaphragm is
process-bonded
diaphragm~Ø: ~20 (0.79)
Vent hose
10 (0.39)
18 (0.71)
20.5
(0.81)
28
(1.10)
56
(2.20)
58 (2.28)
114 (4.49)
172 (6.77)
9 (0.35)
29
(1.14)
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
12
Possible mounting with bracket (optional) for Barrel housing
Pipe mounting
110 (4.33)
23 (0.91)
197 (7.76)
9(0.35)
20 (0.79)
58 (2.28)
39
(1.54)
114 (4.49)
72 (2.83)
20 (0.79)
97 (3.82)
118 (4.65)
60 (2.36)
44(1.73)
98 (3.86)
60 (2.36)
44
(1.73)
177 (6.97)
23 (0.91)
58 (2.28)
39
(1.54) 20 (0.79)
114 (4.49)
9(0.35)
97 (3.82)
Possible mounting with bracket (optional) for DIN housing
110 (4.33)
23 (0.91)
154 (6.06)
20 (0.79) 58 (2.28)
39
(1.54)
26
(1.02)
101 (3.99)
72 (2.83)
20 (0.79)
11 (0.43)
81 (3.19)
100 (3.94) 23 (0.91)
58 (2.28)
39
(1.54) 26
(1.02) 20 (0.79)
Pipe mounting Wall mounting
Wall mounting
Note : Bracket both for pipe and wall mounting provides four holes of 11mm (0.44in) diameter on square with 72mm (2.84in) side
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
13
Harting pin identification
(view onto socket)
+
21
89 (3.5)
51 (2.01)
26 (1.02)
Electrical connections
Standard Terminal block and fieldbus connector versions
Harting Han 8U connector
Screw terminals for
0.5...2.5mm2 – wires
Test sockets for 4...20mA
(not in function with fieldbus
transmitters)
Earthing/potential
equalizing terminal Output signal/
power supply
Cable entry
2
1
4
3
13
42
7/8” connector
M12 x 1 connector
NOITACIFITNEDI)elam(NIP
NOITADNUOF
subdleiF
SUBIFORP
AP
11
1
11
22
2
22
33
3
33
44
4
44
-FF
+FF
DLEIHS
DNUORG
+AP
DNUORG
AP
DLEIHS
Mating female plug NOT SUPPLIED
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
14
BASIC ORDERING INFORMATION model 265GS Gauge Pressure Transmitter
Select one character or set of characters from each category and specify complete catalog number.
Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required.
LEDOMESAB 1
ts
5ot
ht
sretcarahc 2 6 5 G SXXXXXX
%40.0YCARUCCAESABrettimsnarTerusserPeguaG
stimilnapS-ROSNES 6
ht
retcarahc
aPk6dna2.0
aPk04dna4.0
aPk052dna5.2
aPk0003dna03
aPk00001dna001
aPk00006dna006
rabm06dna2
rabm004dna4
rabm0052dna52
rab03dna3.0
rab001dna1
rab006dna6
Hni42dna8.0
2
O
Hni061dna6.1
2
O
Hni0001dna01
2
O
isp534dna53.4
isp0541dna5.41
isp0078dna78
C
F
L
U
R
V
)strapdettew(diulflliF/lairetammgarhpaiD 7
ht
retcarahc
ssL613ISIA
672CyolletsaH
detalp-dlog672CyolletsaH
ssL613ISIA
672CyolletsaH
detalp-dlog672CyolletsaH
ssL613ISIA
672CyolletsaH
cimareC
lioenociliS
lioenociliS
lioenociliS
diulftrenI
diulftrenI
diulftrenI
)ADF(lioetihW
)ADF(lioetihW
gnillifoN
mgarhpaiddednobtnorfrofylno)2etoN(
)2etoN(
)2etoN(
mgarhpaiddednobtnorfrofylno)2,1setoN(
)2,1setoN(
)2,1setoN(
mgarhpaiddednobtnorfrofylno)2etoN(
)2etoN(
)3etoN(
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
S
K
G
A
F
E
N
Z
J
)strapdettew(lairetamnoitcennocssecorP –8
ht
retcarahc
ssL613ISIA
ssL613ISIA
ssL613ISIA
ssL613ISIA
ssL613ISIA
ssL613ISIA
672CyolletsaH
672CyolletsaH
672CyolletsaH
672CyolletsaH
1
/
2
elamefTPNni
G1738NENID
1
/
2
Bni
G
1
/
2
mgarhpaiddednobtnorfni
1
/
2
elamTPNni
G1738NENID
1
/
2
Dni
noitcennocevlavllabroF
1
/
2
elamefTPNni
G1738NENID
1
/
2
Bni
1
/
2
elamTPNni
G1738NENID
1
/
2
Dni
)2etoN(
)2etoN(
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
B
P
S
T
U
V
E
D
K
Y
teksaG 9
ht
retcarahc
notiV
)aPM6.0=PWM(remotsaleoroulfreP
nanubreP
enoN
)3,1setoN(
)3etoN(
)3etoN(
)2etoN(
ECAN
ECAN
ECAN
5
6
8
N
noitcennoclacirtcelednalairetamgnisuoH –01
h
retcarahc
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
rotcennocU8naHgnitraH
rotcennocsubdleiF
1
/
2
TPNni
)02MC(5.1x02M
)02MC(5.1x02M
rotcennocU8naHgnitraH
rotcennocsubdleiF
)ASC,MFelbaliavatoN(
)ASC,MF,dxEEXETAelbaliavatoN()4etoN(
)ASC,MF,dxEEXETAelbaliavatoN()4etoN(
)ASC,MFelbaliavatoN(
)ASC,MFelbaliavatoN(
)ASC,MF,dxEEXETAelbaliavatoN()4etoN(
)ASC,MF,dxEEXETAelbaliavatoN()4etoN(
A
B
E
G
S
T
J
K
W
snoitpolanoitiddA/tuptuO 11
ht
retcarahc
Am02ot4dnanoitacinummoclatigidTRAH
Am02ot4dnanoitacinummoclatigidTRAH
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
)6,5etoN(
)5etoN(
H
1
APSUBIFORP
APSUBIFORP
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
)6,5etoN(
)6etoN(
P
2
subdleiFNOITADNUOF
subdleiFNOITADNUOF
)6,5etoN(
)6etoN(
F
3
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
15
ADDITIONAL ORDERING INFORMATION for model 265GS
Add one or more 2-digit code(s) after the basic ordering information to select all required options
XX XXXX XXXX XXXX XXXX XXXX
noitacifitreclacirtcelE aixEEytefaScisnirtnIDG2/1yrogetaCIIpuorGXETA
)2etoN(dxEEfoorpemalFG2/1yrogetaCIIpuorGXETA
detimilygreneLnxEE"N"noitcetorpfoepyTDG3yrogetaCIIpuorGXETA
efaSyllacisnirtnI)MF(lautuMyrotcaF
)2etoN()lebalSSdnanoitcennoclacirtceleTPNni2/1htiwylno(foorPnoisolpxE)MF(lautuMyrotcaF
)gnidnep(efaSyllacisnirtnInoitaicossAdradnatSnaidanaC
)2etoN(foorPnoisolpxEnoitaicossAdradnatSnaidanaC
1E
2E
3E
AE
BE
DE
EE
DCLlargetnI
yalpsidlargetniDCLlatigiD
yalpsidlargetniDCLlatigidtilkcaB
1L
2L
)lairetamdnaepahs(tekcarbgnitnuoM
gnitnuomepiproF
gnitnuomllawroF
ssL613ISIA
ssL613ISIA
2B
4B
egruS
)7etoN(rotcetorPtneisnarT/egruS 1S
launamgnitarepO
namreG 1M
egaugnalgat&slebaL
)W,K,JedocgnisuoHcinortcelENIDhtiwelbaliavaton(leetssselniatsninamreG
)foorPnoisolpxE-lautuMyrotcaFrofelbatiuston(citsalphsilgnEdnanamreG
1T
AT
etalpgatlanoitiddA
leetssselniatsnI 1I
erudecorpnoitaraperP
PteksagnotiVF,Cedocrosnesrofdnalliftrenihtiwelbaliavaylno(gninaelcecivresnegyxO
xam
;isp5403/rab012/aPM12=
T
xam
)F°041/C°06=
1P
setacifitreC
noitarbilacfoB.1.340201NEetacifitrecnoitcepsnI
01452NIDotgnidroccaegatsssenilnaelcehtfoB.1.340201NEetacifitrecnoitcepsnI
eludomrosnesehtfotsetegakaelmuilehfoB.1.340201NEetacifitrecnoitcepsnI
tseterusserpehtfoB.1.340201NEetacifitrecnoitcepsnI
ngisedtnemurtsnifo1.240201NEredroehthtiwecnailpmocfoetacifitreC
lavorppadyolLrehcsinamreG
1C
3C
4C
5C
6C
8C
ytilibaecartlairetaM
strapdettewssecorpfo1.240201NEredroehthtiwecnailpmocfoetacifitreC
)40201NEecnailpmocfoetacifitrechtiwstrapllams(strapdettewssecorpfoB.1.340201NEetacifitrecnoitcepsnI
strapdettewssecorpdnagniraeberusserpehtfo2.2-40201NEtropertseT
1H
3H
4H
rotcennoC
)gulpelamefgnitamtuohtiw(8/7subdleiF
)gulpelamefgnitamtuohtiw(1x21MsubdleiF
yrtnethgiartsU8naHgnitraH
yrtneelgnaU8naHgnitraH
)8,6setoN(
)8,6setoN(
)8,5setoN(
)9,5setoN(
1U
2U
3U
4U
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
16
Note 1: Suitable for oxygen service
Note 2: Not available with Sensor code C, F
Note 3: Not available with Sensor code L, U, R, V
Note 4: Select type in additional ordering code
Note 5: Not available with Electronic Housing code G, W
Note 6: Not available with Electronic Housing code E, K
Note 7: Not available with ATEX-EEx nL (code E3) or PROFIBUS PA / FOUNDATION Fieldbus (code 2 or 3) with Intrinsic Safety EEx i (code E1) or
FM-Intrinsically Safe (code EA).
Note 8: Not available with Electronic housing code T, S, A, B, J
Note 9: Not available with Electronic housing code T, S, A, B, J, K
Hastelloy is a Cabot Corporation trademark
Viton is a Dupont de Nemour trademark
Standard delivery items (can be differently specified by additional ordering code)
General purpose (no Ex design)
No meter/display, no mounting bracket, no surge protection
English manual and labels (stainless steel nameplate for Barrel housing code A, B, E, G, S, T; plastic nameplate for DIN housing code J, K, W)
Configuration with kPa and deg. C units
No test, inspection or material traceability certificates
THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'S
RESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING.
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
17
BASIC ORDERING INFORMATION model 265AS Absolute Pressure Transmitter
Select one character or set of characters from each category and specify complete catalog number.
Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required.
LEDOMESAB 1
ts
5ot
ht
sretcarahc 2 6 5 A SXXXXXX
%40.0YCARUCCAESABrettimsnarTerusserPetulosbA
stimilnapS-ROSNES 6
ht
retcarahc
aPk6dna3.0
aPk04dna2
aPk052dna5.21
aPk0003dna051
rabm06dna3
rabm004dna02
rabm0052dna521
rab03dna5.1
gHmm54dna52.2
gHmm003dna51
gHmm5781dna8.39
isp534dna7.12
C
F
L
U
)strapdettew(diulflliF/lairetammgarhpaiD 7
ht
retcarahc
ssL613ISIA
672CyolletsaH
detalp-dlog672CyolletsaH
ssL613ISIA
672CyolletsaH
detalp-dlog672CyolletsaH
ssL613ISIA
672CyolletsaH
cimareC
lioenociliS
lioenociliS
lioenociliS
diulftrenI
diulftrenI
diulftrenI
)ADF(lioetihW
)ADF(lioetihW
gnillifoN
mgarhpaiddednobtnorfrofylno)2etoN(
)2etoN(
)2etoN(
mgarhpaiddednobtnorfrofylno)2,1setoN(
)2,1setoN(
)2,1setoN(
mgarhpaiddednobtnorfrofylno)2etoN(
)2etoN(
)3etoN(
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
S
K
G
A
F
E
N
Z
J
)strapdettew(lairetamnoitcennocssecorP –8
ht
retcarahc
ssL613ISIA
ssL613ISIA
ssL613ISIA
ssL613ISIA
ssL613ISIA
ssL613ISIA
672CyolletsaH
672CyolletsaH
672CyolletsaH
672CyolletsaH
1
/
2
elamefTPNni
G1738NENID
1
/
2
Bni
G
1
/
2
mgarhpaiddednobtnorfni
1
/
2
elamTPNni
G1738NENID
1
/
2
Dni
noitcennocevlavllabroF
1
/
2
elamefTPNni
G1738NENID
1
/
2
Bni
1
/
2
elamTPNni
G1738NENID
1
/
2
Dni
)2etoN(
)2etoN(
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
ECAN
B
P
S
T
U
V
E
D
K
Y
teksaG 9
ht
retcarahc
notiV
)aPM6.0=PWM(remotsaleoroulfreP
nanubreP
enoN
)3,1setoN(
)3etoN(
)3etoN(
)2etoN(
ECAN
ECAN
ECAN
5
6
8
N
noitcennoclacirtcelednalairetamgnisuoH –01
h
retcarahc
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(yollamuinimulA
)noisrevlerraB(ssL613ISIA
)noisrevlerraB(ssL613ISIA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
)noisrevNID(yollamuinimulA
1
/
2
TPNni
)02MC(5.1x02M
rotcennocU8naHgnitraH
rotcennocsubdleiF
1
/
2
TPNni
)02MC(5.1x02M
)02MC(5.1x02M
rotcennocU8naHgnitraH
rotcennocsubdleiF
)ASC,MFelbaliavatoN(
)ASC,MF,dxEEXETAelbaliavatoN()4etoN(
)ASC,MF,dxEEXETAelbaliavatoN()4etoN(
)ASC,MFelbaliavatoN(
)ASC,MFelbaliavatoN(
)ASC,MF,dxEEXETAelbaliavatoN()4etoN(
)ASC,MF,dxEEXETAelbaliavatoN()4etoN(
A
B
E
G
S
T
J
K
W
snoitpolanoitiddA/tuptuO 11
ht
retcarahc
Am02ot4dnanoitacinummoclatigidTRAH
Am02ot4dnanoitacinummoclatigidTRAH
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
)6,5etoN(
)5etoN(
H
1
APSUBIFORP
APSUBIFORP
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
snoitpolanoitiddaoN
)"edocgniredrolanoitiddA"ybderedroebot(detseuqersnoitpO
)6,5etoN(
)6etoN(
P
2
subdleiFNOITADNUOF
subdleiFNOITADNUOF
)6,5etoN(
)6etoN(
F
3
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
18
ADDITIONAL ORDERING INFORMATION for model 265AS
Add one or more 2-digit code(s) after the basic ordering information to select all required options
XX XXXX XXXX XXXX XXXX XXXX
noitacifitreclacirtcelE aixEEytefaScisnirtnIDG2/1yrogetaCIIpuorGXETA
)2etoN(dxEEfoorpemalFG2/1yrogetaCIIpuorGXETA
detimilygreneLnxEE"N"noitcetorpfoepyTDG3yrogetaCIIpuorGXETA
efaSyllacisnirtnI)MF(lautuMyrotcaF
)2etoN()lebalSSdnanoitcennoclacirtceleTPNni2/1htiwylno(foorPnoisolpxE)MF(lautuMyrotcaF
)gnidnep(efaSyllacisnirtnInoitaicossAdradnatSnaidanaC
)2etoN(foorPnoisolpxEnoitaicossAdradnatSnaidanaC
1E
2E
3E
AE
BE
DE
EE
DCLlargetnI
yalpsidlargetniDCLlatigiD
yalpsidlargetniDCLlatigidtilkcaB
1L
2L
)lairetamdnaepahs(tekcarbgnitnuoM
gnitnuomepiproF
gnitnuomllawroF
ssL613ISIA
ssL613ISIA
2B
4B
egruS
)7etoN(rotcetorPtneisnarT/egruS 1S
launamgnitarepO
namreG 1M
egaugnalgat&slebaL
)W,K,JedocgnisuoHcinortcelENIDhtiwelbaliavaton(leetssselniatsninamreG
)foorPnoisolpxE-lautuMyrotcaFrofelbatiuston(citsalphsilgnEdnanamreG
1T
AT
etalpgatlanoitiddA
leetssselniatsnI 1I
erudecorpnoitaraperP
PteksagnotiVF,Cedocrosnesrofdnalliftrenihtiwelbaliavaylno(gninaelcecivresnegyxO
xam
;isp5403/rab012/aPM12=
T
xam
)F°041/C°06=
1P
setacifitreC
noitarbilacfoB.1.340201NEetacifitrecnoitcepsnI
01452NIDotgnidroccaegatsssenilnaelcehtfoB.1.340201NEetacifitrecnoitcepsnI
eludomrosnesehtfotsetegakaelmuilehfoB.1.340201NEetacifitrecnoitcepsnI
tseterusserpehtfoB.1.340201NEetacifitrecnoitcepsnI
ngisedtnemurtsnifo1.240201NEredroehthtiwecnailpmocfoetacifitreC
lavorppadyolLrehcsinamreG
1C
3C
4C
5C
6C
8C
ytilibaecartlairetaM
strapdettewssecorpfo1.240201NEredroehthtiwecnailpmocfoetacifitreC
)40201NEecnailpmocfoetacifitrechtiwstrapllams(strapdettewssecorpfoB.1.340201NEetacifitrecnoitcepsnI
strapdettewssecorpdnagniraeberusserpehtfo2.2-40201NEtropertseT
1H
3H
4H
rotcennoC
)gulpelamefgnitamtuohtiw(8/7subdleiF
)gulpelamefgnitamtuohtiw(1x21MsubdleiF
yrtnethgiartsU8naHgnitraH
yrtneelgnaU8naHgnitraH
)8,6setoN(
)8,6setoN(
)8,5setoN(
)9,5setoN(
1U
2U
3U
4U
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
19
Note 1: Suitable for oxygen service
Note 2: Not available with Sensor code C, F
Note 3: Not available with Sensor code L, U
Note 4: Select type in additional ordering code
Note 5: Not available with Electronic Housing code G, W
Note 6: Not available with Electronic Housing code E, K
Note 7: Not available with ATEX-EEx nL (code E3) or PROFIBUS PA / FOUNDATION Fieldbus (code 2 or 3) with Intrinsic Safety EEx i (code E1) or
FM-Intrinsically Safe (code EA).
Note 8: Not available with Electronic housing code T, S, A, B, J
Note 9: Not available with Electronic housing code T, S, A, B, J, K
Hastelloy is a Cabot Corporation trademark
Viton is a Dupont de Nemour trademark
Standard delivery items (can be differently specified by additional ordering code)
General purpose (no Ex design)
No meter/display, no mounting bracket, no surge protection
English manual and labels (stainless steel nameplate for Barrel housing code A, B, E, G, S, T; plastic nameplate for DIN housing code J, K, W)
Configuration with kPa and deg. C units
No test, inspection or material traceability certificates
THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'S
RESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING.
2600T Pressure Transmitters
Model 265GS, 265AS SS/265GS/AS_3
ABB Ltd
Howard Road, St. Neots
Cambridgeshire, PE19 3EU
UK
Tel: +44(0)1480 475321
Fax: +44(0)1480 217948
ABB Inc.
125 E. County Line Road
Warminster, PA 18974
USA
Tel: +1 215 674 6000
Fax: +1 215 674 7183
SS/265GS/AS_3
ABB has Sales & Customer Support
expertise in over 100 countries worldwide
www.abb.com/instrumentation
The Company’s policy is one of continuous product
improvement and the right is reserved to modify the
information contained herein without notice.
Printed in Italy (01.04)
© ABB 2004
ABB Automation Products GmbH
Schillerstrasse 72
D-32425 Minden
Germany
Tel: +49 (0) 551 905 534
Fax: +49 (0) 551 905 555