Critical Power from GE
Overview
The Compact Power Line platform
is designed to provide highly reliable
DC power for 48V distributed power
architectures. A single shelf conguration
provides up to 14kW of 48V output
power in 1U high and mounts in 19-
inch or 23-inch wide frames. The CPL
product platform is easily expandable
for future growth, and is a reliable DC
power solution for mission-critical
enterprise and telecommunications
network equipment.
Shelf Options
The CP product line provides several
shelf options with common or split DC
output congurations. There are two
families of CPL shelves; one used with
a Pulsar Edge controller, the other used
without a controller or with a customer’s
own controller using industry standard
PMBus/I2C communications. J85480S1
and J2014003 shelves have four slots
for rectiers or converters (PEMs) and
use PMBus/I2C for communications.
J2007001 and J2014004 shelves have
four slots with an additional space for
a full-feature Pulsar Edge Controller.
The Pulsar Edge controller has secure
Ethernet connectivity to facilitate
remote network management to
monitor and control rectiers, batteries,
and distribution. CPL is ideal for a
broad range of applications requiring
highly ecient 48V DC power.
Rectier Options
CPL family of rectiers are single phase,
constant power rectiers with rear power
entry that provide from 2000 Watts to
3500 Watts of highly reliable DC power.
The class leading density, constant
output power characteristics, extended
temperature range, universal AC input,
and compact size are key attributes that
make this rectier the right choice for
your power needs. CPL converters share
the same form factor as CPL rectiers
and provide wide range 40V-72V DC
input and regulated 48-54V DC output.
Airow direction is front to rear.
Pulsar Edge Controller
CPL family of products support the
Pulsar Edge controller delivering
large system intelligence in a small
system form factor. Secure Ethernet
connectivity with SNMP helps facilitate
remote network management.
Shelf Options
J85480S1 and J2007001 shelves provide
1RU rack density up to 11kW and support
appliance connector (C13 or C19) AC
connection options. The shelves support
2kW, 2.5kW and 2.7kW power supplies.
Up to four modules can be installed in a
single 1RU shelf. J2014003 and J2014004
shelves provide 1RU rack density up to
14kW with AC connectivity provided
by high reliability Molex connectors. Up
to four modules can be installed in a
single 1RU shelf. The shelves support
3kW and 3.5kW power supplies.
Advantages
Compact 48V DC
distributed power system
Efficiency
approaching 97%
Maximum power in
minimal space
Scalable to 80 kW
Powering enterprise and
telecommunications
networks
Compact Power Line
48V DC Critical Power Solution
2Compact Power Line, CPB-CPL | www.gecriticalpower.com
The CPL series of rectiers are specically designed to operate as an integral
part of a complete distributed power system or can be easily integrated into
an OEM design. The high-density, front-to-back airow rectier is designed for
minimal space utilization and is highly expandable for future growth.
The power modules are available with many features including PoE isolation, RS485
communications bus for use with GE battery plant controllers in forming an energy
reserve system and redundant I2C communications bus for use with a customer’s
embedded controller. This exible and sophisticated feature set makes this front
end power supply an excellent choice for power in a variety of application spaces.
Specications: AC-DC Power Supplies
INPUT 2000 2725 3000 3500
Voltage Range
- Low-Line
- High-Line
120Vac Nominal (1200W)
208, 240, 277Vac Nominal
120Vac Nominal (1500W)
208, 240, 277Vac Nominal
Input Frequency 47 – 63 Hz 47 – 66 Hz
Input Current 11.9 Arms @ 110Vac
13.1 Arms @ 240Vac
15.5 Arms @ 110Vac
16 Arms @ 240Vac
Inrush Transient 25Apk Typical 25Apk Typical
Power Factor 0.98 from 50% to 100% Load 0.97 Min, 0.995 Typical
Ride through (at 1240VAC, 25C) 1/2 Cycle Min, Full Cycle Typical
2EMI/EMC Exceeds FCC and CISPR22 (EN55022) - Class A
High Accuracy AC Measurement No Optional
1 measurement starts at zero crossing of the ac voltage, and voltage devayed to 40V
2 for loads below 1200W
Applications
Key Features
Enterprise Networks
OEM Telecom Equipment
Power Over Ethernet
VoIP/Soft Switches
SAN/NAS/iSCSI Applications
LAN/WAN/MAN Applications
Indoor Wireless
Routers and Switches
Industrial
Laser
Broadcast
Test and Measurement
Mission Critical
High Reliability
Compact 1RU Form Factor
PMBus Compliant Dual I2C and
RS485 Serial Bus Communications
Front Panel LED Indicators
Internal Variable-Speed Fan Control
Constant Power; 52 – 58 Vdc
Programmable Output Voltage;
44 – 58 Vdc
Universal AC Input
PoE Compliant Versions Available
CE Marked
RoHS 6 Compliant
Hot Pluggable
CPL Power Supplies
3
Compact Power Line, CPB-CPL | www.gecriticalpower.com
OUTPUT 2000 2500
Voltage Range -40 to -72 Vdc
Input Current 60Adc max 75Adc max
Inrush Current 60Adc max 100Adc max
Holdup Time 6ms
EMI/EMC Exceeds FCC and CISPR22 (EN55022) - Class A
Voltage Default 54Vdc
Voltage Adjust Range 44 - 58 Vdc
Rated Output Current 0.1 to 37A 0.1 to 46.3A
Rated Output Power 2000W 2500W
Ripple (5Hz to 20MHz)
- RMS
- Peak to Peak
250mVrms
500mVpk-pk
Over Voltage Protection
- Delayed
- Immediate
60Vdc
65Vdc
Over Temperature
- Warning
- Shutdown
5C
20C
PoE Isolation Yes Yes
OUTPUT 2000 2725 3000 3500
Voltage Adjust Range
- Hardware set via Margin Pin
- Set by either I2C for
44-58Vdc
42-58Vdc
Rated Output Current
- Low Line
- High Line1
25
38.4
25
52.4
28.9
57.8
28.9
67.3
Rated Output Power
- Low Line
- High Line
1200W
2000W
1200W
2725W
1500W
3000W
1500W
3500W
Psophometric Noise 9mVrms
Ripple (5Hz to 20MHz)
- RMS
- Peak to Peak
100mVrms max
250mVp-p max
Over Voltage Protection
- Delayed
- Immediate
<60Vdc
>65Vdc
Three restart attempts are implemented within a 1 minute window prior to a latched shutdown.
Over Temperature
- Warning
- Shutdown
- Restart Attempt Hys-
5C
20C
10C
PoE Isolation per IEEE 802.3 Optional No
1 at full power @ 52V @ 200-240Vac
Specications: AC-DC Power Supplies (Cont.)
Specications: DC-DC Power Supplies
Specications: All AC-DC Models and All DC-DC Models
MECHANICAL
Length (in./mm) 13.85 / 351.2
Width (in./mm) 4 / 101.6
Height (in./mm) 1.63 / 41.4
Weight (lb / kg) 5 / 2.27
4Compact Power Line, CPB-CPL | www.gecriticalpower.com
Specications: All AC-DC Models and All DC-DC Models (Cont.)
Front Panel LEDs
Outline Drawings
ENVIRONMENTAL 2000/2725 3000/3500
Operating Temperature1-40°C to +75°C (-40°F to 167°F) -40°C to +55°C (-40°F to 131°F)
Storage Temperature -40°C to +85°C (-40°F to 185°F)
Power De-Rating > +55°C (derates @ 2% per °C)
Relative Humidity 95% max, non-condensing
Altitude 4,000m max (13,000 ft)
Altitude De-Rating Above 1524/5000 m/ft; 3962/13000 m/ft max (derates at 2C/1000ft)
Audible Noise 55dBA, full load
1 designed to start at an ambient as low as -40°C but may not meet operational limits until above -5°C
GENERAL 2000/2725 3000/3500
Cooling Internal variable speed fan cooled, microprocessor fan speed control
Air Flow Direction Front to Rear
Eciency (30-80% of FL, 240VAC @ 25°C) 94.5% Min
96.5% Typical
94.2% Min
96.1% Typical
Heat Dissipaation AC-DC 2000/2725 100 W/341 BTU @ 80% load
153 W/522 BTU @ 100% load
DC-DC 2000 -> 176W / 601 BTU
2500 -> 220W / 751 BTU
AC-DC 3000/3500 190 W/648 BTU @ 80% load
250 W/853 BTU @ 100% Load
SAFETY AND STANDARDS COMPLIANCE 2000/2725 3000/3500
Zone 4 Per Telcordia GR-63-CORE, all oors when installed in CPL shelf
Safety CE mark to Low Voltage Directive 2006/95/EC UL 609501-1 Recognized
CAN/CSA C22.2 No. 60950-1-03 Certied VDE 0805-1 Licensed to IEC60950-1
RoHS Compliant to RoHS EU Directive 2002/95/EC
EMC FCC and CISPR22 (EN 55022) Class A
ESD EN/IEC 61000-4-2 Level 3
SYMBOL ANALOG MODE I2C MODE RS485 MODE
ON: Input OK
BLINKING: Input Out of Limits
ON: Output OK
BLINKING: Overload
ON: Over-temperature Warning ON: Over-temperature Warning
BLINKING: Service ON: Over-temperature Warning
ON: Fault ON: Fault
BLINKING: Not Communicating
DIMENSIONS
5
Compact Power Line, CPB-CPL | www.gecriticalpower.com
Pulsar Edge Controller (For Applications in J2007001
and J2014004 shelves)
The CPL Pulsar Edge controller delivers large system intelligence in a small system form factor. This family of
controllers functions as a network interface controller (NIC) and as a full-featured battery plant controller to the
Compact Power Line (CPL) platform. Its thin modular plug-in form factor minimizes shelf space. The Pulsar Edge
CP841A controller is utilized in bulk power applications in data centers and enterprise applications.
Ethernet connectivity with SNMP facilitates remote network management access through its
front-accessible RS232 or USB port and is aided by the EasyView2 graphical user interface.
Applications
Telecommunications Networks
Transmission Equipment
Fiber in the Loop
Routers/Switches
Data Networks
PBX
Enterprise Networks -
Voice, Data, PoE
Key Features
Remote Access and Features
Integrated 10/100Base-T Ethernet
Network
- TCP/IP
- SNMP V2c for management
- SMTP for email
- Telnet for command line interface
- DHCP for plug-n-play
- FTP for rapid backup and upgrades
- HTTP for standard web pages
and browsers
- Compatible with Galaxy Manager
and other management packages
- Shielded RJ-45 interface
referenced to chassis ground
Password protected security levels:
User, Super-User, Administrator for
all access Ground-referenced RS232
system port ANSI T1.317 command-
line interface
Modem access support
- Remote via external modem
- Callback security
EasyView2, Windows-based GUI
software for local terminal or
Modem access
Secure Protocols:
- SNMP V3
- SSL
- SSH
- IPv6
Standard System Features
Monitor and control of more than 40
connected devices
- Maximum of 32 rectifiers
- Maximum of 6 distribution
control cards
- Robust RS485 system bus
Standard and user defined
system alarms
- Alarm test
- Assignable alarm severity:
Critical, Major, Minor, Warning,
and Record-only
Rectifier management features
- Automatic rectifier restart
- Active Rectifier Management
(energy eff iciency)
- Remote rectifier (on/off)
- Reserve Operation
- Automatic rectifier
sequence control
- N + X redundancy check
Multiple Low Voltage Load and
Low Voltage Battery Disconnect
thresholds (4)
Configuration, statistics, and history
- All stored in non-volatile memory
- Remote/local backup and restore
of configuration data
Industry standard defaults
- Customer specific
configurations available
Remote/ local software upgrade
Basic, busy hour, and trend statistics
Detailed event history
User defined events and
derived channels
Standard Battery Management Features
Float/boost mode control
- Manual boost
- Manual timed boost locally, T1.317,
and remotely initiated
- Auto boost terminated by time
or current
Battery discharge testing
- Manual (local/remote)
- Periodic
As a battery plant controller, it provides a complete set of features to monitor and control rectiers,
batteries, and distribution. A exible set of congurable inputs allow the CP841A to monitor a wide
variety of system equipment and incorporate appropriate state information enabling a centralized point
of management. The controller utilizes secure network management protocols allowing for advanced network
supervision. GE Galaxy Manager* software is the centralized visibility and control component of a comprehensive
power management system designed to meet engineering, operations, and maintenance needs. The Galaxy Manager
client-server architecture enables remote access to system controllers across the power network.
6Compact Power Line, CPB-CPL | www.gecriticalpower.com
- Plant Battery Test (PBT)
input driven
- Configurable threshold or
20% algorithm
- Graphical discharge data
- Rectifiers on-line during test
Slope thermal compensation
- High temperature
- Low temperature
- Step temperature
- STC Enable/Disable,
low temperature
Enable/Disable
- Configurable mV/°C slopes
State of charge indication
High temperature disconnect setting
Reserve-time prediction
Recharge current limit
Emergency Power-Off input
Integrated Monitoring Inputs/Outputs
System plant voltage (accuracy ±0.5%,
resolution 0.01V)
One system shunt (accuracy ±1% full
scale, resolution 1A)
- Battery or load
- Mounted in the return side
of DC bus
Up to 15 binary inputs
- Six inputs close/open to battery
- 9 input close/open to return
(number is dependent upon
number of output alarms)
- User assignable
Up to 5 user assignable Form-C
output alarms (50VDC @ .3A)
1-Wire* bus devices
- Up to 16 temperature
probes (QS873)
- Up to 6 mid-string monitors (ES771)
Galaxy Manager Compatible
Centralized web server and database
with multiple user access to live or
managed data with drill down to
problem details
Monitor and control of more than 40
connected devices
Management information from polling
or alarms received from alarm traps
from multiple sites are available on
one screen via the inter/intranet
Trend user selected data over time
Automatic or manual
report generation
Standard engineering tools like
reserve time calculators and cable
voltage drop analyzer
CONTROLLER GENERAL
Operating Voltage ±24 Vdc, ±48 Vdc
(Range: ±18 to ±60 Vdc)
Input Power Less than 7W
Operating Temperature Range -40°C to +75°C (-40°F to 167°F)
Storage Temperature Range -40°C to +85°C (-40°F to 185°F)
Operating Relative Humidity 0 - 95% (non-condensing)
Physical Specications 1.75 in. H, 0.75 in. W, 8.00 in. D; 0.5lb
45mm H, 20mm W, 204mm D; 227g
CONTROLLER AGENCY CERTIFICATIONS
Radiated Emissions FCC, Class B; EN 55022, Class B
Safety UL Unlisted Component as Part of CPL or SPS Power System
RoHS Compliant to RoHS EU Directive 2002/95/EC
EMC FCC/EN55022 Class B, CISPR22 Level B
ESD EN 61000-4-2 level 4
Specications
Pulsar Edge Controller Key Features (Cont.)
7
Compact Power Line, CPB-CPL | www.gecriticalpower.com
Ordering Information – Compact Power Line
48V DC Critical Power Solution
The Compact Power Line platform is designed to provide highly reliable DC power for 48V distributed power architectures. When embedded into
an OEM design, GE can assist with the integration into the OEM design, Otherwise an external shelf can be used to provide power. A single shelf
conguration provides up to 14kW of 48V output power in 1U high and mounts in 19-inch or can be adapted to 23-inch wide frames. The CPL product
platform is easily expandable for future growth by stacking multiple shelves. CPL is a reliable DC power solution for mission-critical enterprise and
telecommunications network equipment.
The CPL product line provides several shelf options. J85480S1 and J2014003 shelves have four slots for either rectiers or converters (PEMs). These
shelves are primarily used without a controller or with a customer’s controller using PMBus or I2C communications. J2007001 and J2014004 shelves
have four slots with space for a full-feature Pulsar Edge Network Interface Controller (NIC). The Pulsar Edge controller has secure Ethernet connectivity
with SNMPv3 to facilitate remote network management to monitor and control rectiers, batteries, and distribution. These shelves are used with
either shelf mounted distribution or external distribution panels for small battery plant applications.
Features – Model J85480S1 and J2014003
Features – Model J2007001 and J2014004
Fits into a standard 19” rack
Two DC Outputs may be common or split. Each output bus is
rated for 100A with two-hole lug landings for 2 AWG wire.
Choose between IEC-320 C13 or C19 or other AC input connections
Analog or dual/redundant I2C communications
Adjustable mounting ears for near flush front or multiple set back positions
Fits into a standard 19” rack
Single DC output rated for 200A with two-hole
lug landings for up to 2/0 AWG cable
Choose between IEC-320 or Molex Mini-Fit SR for AC input
Single, dual or quad input feeds
RS485 communications
Adjustable mounting ears with multiple set back positions
Up to 3 shelves may be interconnected with bus
straps for DC outputs for a 600A system
Plug-N-Play CP841A controller with front access craft
port, rear access LAN and alarm connections
Select Shelves include distribution modules
J2007 or J2014004
Rectier Shelf
J85480 or J2014003
Rectier Shelf
J2007 Converter Shelf
J85480 Converter Shelf
SHELF SERIES USAGE COMMUNICATIONS POWER SUPPLY INPUT CONNECTOR
J85480S1 CP2000/CP2725 PM Bus/I2CRear
J2007001 CP2000/CP2725 RS485 Rear
J2014004 CP3000/CP3500 RS485 Rear
J2014003 CP3000/CP3500 PM Bus/I2CRear
Embedded Only CP3000AC-Fxx PM Bus/I2C or RS485 Front
Embedded Only CP2500DC-Fxx PM Bus/I2C or RS485 Front
Simplied Shelf Identication Matrix
8Compact Power Line, CPB-CPL | www.gecriticalpower.com
DIMENSIONS
Outline Drawings - J85480S1 Shelves
J8540S1 Converter Shelf Options
LIST MAX
POWER
DC INPUT
PLUG
DC OUTPUT MAX POWER
SUPPLY
FEATURES ORDER CODE
BUS TERMINATION SETPOINT OTHER
14 10kW Qty 2 (1 per
2 rectiers)
Split Double Hole Lugs
1/4in x 5/8in Spacing
CP2500DC (+) 48Vdc POE, Analog, I2CCC109124764
LIST MAX
POWER
AC INPUT
PLUG
DC OUTPUT MAX
RECTIFIER
SIZE
FEATURES ORDER CODE
BUS TERMINATION SETPOINT OTHER
20 11kW IEC-320, C19 Common DH Lugs CP2725 (+) 54Vdc Analog, I2CCC109147344
21 Split -54Vdc CC109147328
23 8kW IEC-320, C13 Common CP2000 (+) 54Vdc POE, Analog, I2CCC109150447
Notes
Split shelves L21 and Vout (-) is split, however Vout (+) is paralleled among the 4 rectifiers. Vout (+) should be grounded.
All lists, up to 2 shelves can be paralleled for a single I2C line. Up to eight shelves may be paralleled for current shared power delivery.
All lists, shelf configured set point ensures inter-operability among all rectifiers from CP2000 to CP2725. Rectifiers will proportionately current share relative
to their output power capacity.
All Shelves are RoHS 6 compliant. Order should reflect J85480S1LxxZ where xx is the list number and Z indicates compliance to RoHS 6.
J85480S1 Rectier Shelf Options
9
Compact Power Line, CPB-CPL | www.gecriticalpower.com
J2014003 Rectier Shelf Options
LIST MAX
POWER
AC INPUT
CONNECTOR
DC OUTPUT FEATURES OTHER ORDER CODE
BUS TERMINATION RECTIFIER SIZE SET POINT
114kW Molex Mini-Fit Sr Common Double Hole Lugs
1/4in x 5/8in Spacing
CP3000/
CP3500
54Vdc Analog I2C150040608
DIMENSIONS
Outline Drawings - J2014003 Shelves
10 Compact Power Line, CPB-CPL | www.gecriticalpower.com
DC Output Types: Common Output Bus for Terminal Lug Connection
DC Output Types: Split Output Bus for Terminal Lug Connection
DESCRIPTION SCHEMATIC
Each Lug Connection rated for 100A
with 2 gauge wire (200A for shelf)
Rectier 1
Rectier 2
Rectier 3
Rectier 4
Rear Bulk DC
Output Connections
2 hole 1/4” studs
on 5/8” centers
Rear Bulk DC
Output Connections
2 hole 1/4” studs
on 5/8” centers
V-
V+ V+
V-
DESCRIPTION SCHEMATIC
Vdc( - ) has Split buses Vdc( + ) is common
to both sections.
Each bus may be independently controlled
Multiple shelves may not be paralleled together.
Each Lug Connection rated for 100A with 2 gauge
wire (200A for shelf)
Rectier 1
Rectier 2
Rectier 3
Rectier 4
Rear Bulk DC
Output Connections
2 hole 1/4” studs
on 5/8” centers
Rear Bulk DC
Output Connections
2 hole 1/4” studs
on 5/8” centers
V-
V+ V+
V-
11
Compact Power Line, CPB-CPL | www.gecriticalpower.com
J1 Communication Signals – J85480S1 (J1 Connector – Pin Out)
J2 Communication J85480S1 and J2014003 Shelves (J2 Connector – Pin Out)
PIN SIGNAL PIN SIGNAL PHOTO
1POWER_CAP_1 16 SDA_1
2POWER_CAP_2 17 Fault
3POWER_CAP_3 18 Alert#_0
4POWER_CAP_4 19 Enable side B
5MOD_PRES_1 20 Logic_GRD
6MOD_PRES_2 21 Enable Side A
7MOD_PRES_3 22 Logic_GRD
8MOD_PRES_4 23 Alert#_1
9PFW_1 24 5VA
10 PFW_2 25 OTW
11 PFW_3 26 Reset
12 PFW_4 27 Iso. barrier n/c
13 SCL_0 28 Iso. barrier n/c
14 SCL_1 29 Shelf_Addr_B
15 SDA_0 30 Shelf_Addr_A
Control Interface cable (part # CC848854034)
PIN SIGNAL PIN SIGNAL PHOTO
1SCL_0 8Alert#_1
2SCL_0 9Isolation n/c
3SDA_0 10 Isolation n/c
4SDA_1 11 Ishare - B
5Alert#_0 12 Ishare - A
65VA 13 8V_INT - B
7Logic_GRD 14 8V_INT - A
Shelf-to-shelf cable connection (part # CC848848952)
J1 Communication Signals – J2014003 Shelves (J1 Connector – Pin Out)
PIN SIGNAL PIN SIGNAL PHOTO
1POWER_CAP_1 16 SDA_1
2POWER_CAP_2 17 Fault
3POWER_CAP_3 18 Alert#_0
4POWER_CAP_4 19 Enable side B
5MOD_PRES_1 20 Logic_GRD
6MOD_PRES_2 21 Enable Side A
7MOD_PRES_3 22 Logic_GRD
8MOD_PRES_4 23 Alert#_1
9PFW_1 24 5VA
10 PFW_2 25 OTW
11 PFW_3 26 Reset
12 PFW_4 27 Iso. barrier n/c
13 SCL_0 28 Iso. barrier n/c
14 SCL_1 29 VProg
15 SDA_0 30 Rack ID
Control Interface cable (part # CC848854034)
12 Compact Power Line, CPB-CPL | www.gecriticalpower.com
DIMENSIONS
J2007001L14 DC PEM Shelf Options
LIST MAX
POWER
DC INPUT
PLUG
DC OUTPUT MAX POWER
SUPPLY
FEATURES ORDER CODE
BUS TERMINATION SETPOINT OTHER
14 10kW 2 x 1/4-20 x
5/8 in DH Lug
Common 2 x 1/4-20 x 5/8 in
DH Lug
CP2500DC Variable, set by
Edge Controller
RS485 CC109157657
Outline Drawings - J2007001 Shelves
J2007001 Rectier Shelf Options
LIST MAX RECTIFER SIZE AC INPUT DC OUTPUT REAR VIEW OF SHELF
32725 Watts Single AC feed
(terminal blocks for
6ga wire and 3/4”
conduit tting)
DC output bus is
rated for 200A for
two 2ga or one
2/0 gauge
two- hole lugs
(1/4-20 studs on
5/8” centers).
42725 Watts Individual feed
(Molex Mini-Fit SR)
62725 Watts Individual feed
(IEC-320 C19 Cords)
Notes:
1. CP841A Pulsar Edge Controller ships separately.
2. Up to 3 shelves may be interconnected.
DC Output Bus AC Signal
13
Compact Power Line, CPB-CPL | www.gecriticalpower.com
DIMENSIONS
J2014004 Rectier Shelf
LIST MAX
POWER
AC INPUT
PLUG
DC OUTPUT MAX POWER
SUPPLY
FEATURES ORDER CODE
BUS TERMINATION SETPOINT OTHER
114kW Molex Mini
Fit Sr
Common 2pr x 1/4-20 x 5/8 in
DH Lug
CP3500 Variable, set by
Edge Controller
RS485 150040609
Notes: 1. CP841A Pulsar Edge Controller ships separately. 2. Up to 3 shelves may be interconnected.
Outline Drawings - J2014004 Shelves
14 Compact Power Line, CPB-CPL | www.gecriticalpower.com
J2007001 and J2014004 Shelves System Controller Overview
EDGE CONTROLLER PHOTO
CP841A_3C3R_S J1 has 3 alarm inputs with a common return
and 3 output relays; Power Major,
Power Minor, 1 Selectable
Communication Signals for J2007001 and J2014004 Shelves
J1 provides alarm outputs and inputs based on the controller installed (see
table on next page). Inputs are “Dry”, no voltage, contact Closures or Opens
to a common return on pin 6. Outputs are relay contacts. Both input and
output alarms are customer dened on the controller’s web pages.
J2 provides alarm inputs (see table on next page). Alarm inputs
are contact Closures or Opens to the non-grounded side of the dc
bus [-48V]. Pins 6, 7, 8 provide -48V for these alarm inputs.
J3 battery thermal probe (QS873A) or battery mid-string
voltage monitor (ES771) with battery thermal probe.
J4 shelf to shelf communication connection J5 LAN/Ethernet.
J7 provides distribution control for shelves with external
distribution. See table on next page.
J1 Connector – Pin Out
PIN SIGNALS FOR SPS841A_3C3R SIGNALS FOR SPS841A_0I5R
1ALM1 Input Alarm Relay 3 Rtn
2ALM2 Input Alarm Relay 2 Rtn
3Alarm Relay 1 Rtn Alarm Relay 1 Rtn
4Power Minor Rtn Power Minor Rtn
5Power Major Rtn Power Major Rtn
6ALM1, 2, 6C RTNS Alarm Relay 3
7ALM6 Input Alarm Relay 2
8Alarm Relay 1 Alarm Relay 1
9Power Minor Power Minor
10 Power Major Power Major
15
Compact Power Line, CPB-CPL | www.gecriticalpower.com
J2 Connector
J7 Connector
PIN SIGNAL
1ALM6 Input
2 -
3ALM3 Input
4ALM4 Input
5ALM5 Input
6-48V
7-48V
8-48V
PIN SIGNAL
1FAJ
2Coil Rtn
3LVD_NC
4LVD_NO
5Shunt-
6OS
7Coil1
8Coil2
9LVD Status Rtn
10 Shunt+
Battery Monitoring
Temperature/Voltage probes are needed for battery monitoring. They are connected to each battery or battery string
to provide slope thermal compensation, temperature alarms and voltage imbalance alarms.
Refer to ordering guide for diagram and part numbers.
16 Compact Power Line, CPB-CPL | www.gecriticalpower.com
CP2000/CP2725 Shelves
MOUNTING BRACKETS
1U bracket for 23”
frame mount
CC848844803
2U bracket for 23”
frame mount
848683009
Wall mount bracket CC848864504
COMMUNICATION CABLES
10’ Communication
Cable (J1)
CC848854034
Shelf to shelf
communication cable
CC848848952
AC INPUT, DC OUTPUT CABLES
C13 plug with 5-15P plug, 10’ CC848776105
C13 plug with L6-20P plug, 10’ CC848820317
C13 plug, unterminated, 10’ 847861192
C19 plug, with 5-15P plug, 8’ CC848850792
C19 plug, with L6-20P plug, 8’ CC848850842
C19 plug, unterminated, 8’ CC848847368
DC output cable, 2 GA, 10’ 848748987
RECTIFIER
CP2000AC54TEZ CC109158440
CP2000AC54TEP CC109167565
CP2725AC54TEP CC109167532
CP2725AC54TEZ CC109149423
RECTIFIER SLOT FILLER
Central
Oce White
CC848822263
RECTIFIER SHELF OPTIONS
List 20 CC109147344
List 21 CC109147328
List 23 CC109150447
J85480S1 Family Shelves Ordering Guide
J85480S1 Converter Shelf Ordering Guide
MOUNTING BRACKETS
1U bracket for 23”
frame mount
CC848844803
Wall mount bracket CC848864504
DC INPUT CABLES
DC input cable, 10 GA, 4’ CC848794908
DC OUTPUT CABLES
DC output cable, 2 GA 10’ 848748987
DC Bus for 1/4” Faston Connections
(2 required)
CC848886192
RECTIFIER SLOT FILLER
Central Oce
White
CC848822263
CONVERTER (PEM) OPTIONS
CP2000DC54PEZ CC109162104
CP2500DC54PEZ CC109170528
CONVERTER SHELF OPTIONS
List 14 CC109124764
AC DC
17
Compact Power Line, CPB-CPL | www.gecriticalpower.com
CP2000/CP2725 Shelves (Cont.)
J2007001 Family Shelves Ordering Guide
J2007001L014 Converter Shelf Ordering Guide
ALARM AND COMMUNICATION CABLES
15’ Alarm or distribution cable (J1 or J7) CC848865980
50’ Alarm or distribution cable (J1 or J7) CC848817651
150’ Alarm or distribution cable (J1 or J7) CC848817668
15’ Alarm input cable (J2) CC848853614
Shelf to shelf communication cable (J3, J4) CC848847780
RECTIFIER SHELF OPTIONS
List 3 CC109147542
List 4 CC109140043
List 6 (Shown) CC109140027
(Rohs5)
150047190
(Rohs6)
RECTIFIER
CP2000AC54TEZ CC109158440
CP2000AC54TEP CC109167565
CP2725AC54TEP CC109167532
CP2725AC54TEZ CC109149423
RECTIFIER SLOT FILLER
Central Oce White CC848822263
MOUNTING BRACKETS
1U bracket for 23”
frame mount
CC848844803
2U bracket for 23”
frame mount
848683009
Wall mount bracket CC848864504
AC INPUT, DC OUTPUT CABLES
C19 plug, with 5-15P plug, 8’ CC848850792
C19 plug, with L6-20P plug, 8’ CC848850842
C19 plug, unterminated, 8’ CC848847368
Molex Mini-Fit SR, unterminated,
8awg, 10’ (2 cables provided)
848710711
DC output cable, 2ga, 10’ 848748987
DC Bus Bar Strap (2 required) CC848844324
CONTROLLER
CP841A_3C3R_S 150032047
Slot Filler CC848847871
RECTIFIER SLOT FILLER
Central
Oce White
CC848822263
CONVERTER (PEM) OPTIONS
CP2000DC54PEZ CC109162104
CP2500DC54PEZ CC109170528
CONTROLLER
CP841A_3C3R_S 150032047
Slot Filler CC848847871
CONVERTER SHELF OPTIONS
List 14 CC109157657
MOUNTING BRACKETS
1U bracket for 23”
frame mount
CC848844803
Wall mount bracket CC848864504
DC OUTPUT CABLES
DC output cable, 2 GA 10’ 848748987
DC Bus for 1/4” Faston Connections (2 required) CC848886192
RECTIFIER SLOT FILLER
Central Oce White CC848822263
18 Compact Power Line, CPB-CPL | www.gecriticalpower.com
CP3000/CP3500 Shelves
J2014003 Shelf Ordering Guide
J2014004 Shelf Ordering Guide
MOUNTING BRACKETS
1U bracket for 23”
frame mount
CC848844803
2U bracket for 23”
frame mount
848683009
Wall mount bracket CC848864504
AC INPUT, DC OUTPUT CABLES
Molex Mini-Fit SR, unterminated, 8awg, 36” (Single Cable) CC848763301
Molex Mini-Fit SR, unterminated, 8awg, 10’ (Single Cable) CC848793026
Molex Mini-Fit SR, unterminated, 8awg, 10’ (2 cables provided) 848710711
DC output cable, 2ga, 10’ 848748987
DC Bus Bar Strap (2 required) CC848844324
RECTIFIER SHELF OPTIONS
J2014003001
List 1
150040608
RECTIFIER SHELF OPTIONS
J2014004001 List 1 150040609
RECTIFIER
CP3000AC54TEZ 150033916
CP3000AC54TECZ 150041904
CP3500AC54TEZ 150030396
CP3500AC54TECZ 150041901
RECTIFIER
CP3000AC54TEZ 150033916
CP3000AC54TECZ 150041904
CP3500AC54TEZ 150030396
CP3500AC54TECZ 150041901
RECTIFIER SLOT FILLER
Central Oce White CC848822263
RECTIFIER SLOT FILLER
Central Oce White CC848822263
MOUNTING BRACKETS
1U bracket for 23”
frame mount
CC848844803
Wall mount bracket CC848864504
AC INPUT, DC OUTPUT CABLES
Molex Mini-Fit SR, unterminated,
8awg, 36” (Single Cable)
CC848763301
Molex Mini-Fit SR, unterminated,
8awg, 10’ (Single Cable)
CC848793026
Molex Mini-Fit SR, unterminated,
8awg, 10’ (2 cables provided)
848710711
DC output cable, 2ga, 10’ 848748987
DC Bus Bar Strap (2 required) CC848844324
CONTROLLER
CP841A_3C3R_S 150032047
Slot Filler CC848847871
SHELF OPTIONS
List 1 CC109157657
ALARM AND COMMUNICATION CABLES
15’ Alarm or distribution cable (J1 or J7) CC848865980
50’ Alarm or distribution cable (J1 or J7) CC848817651
150’ Alarm or distribution cable (J1 or J7) CC848817668
15’ Alarm input cable (J2) CC848853614
Shelf to shelf communication cable (J3, J4) CC848847780
19
Compact Power Line, CPB-CPL | www.gecriticalpower.com
BATTERY MANAGEMENT ACCESSORIES PHOTO
A: QS873A Thermal Probe CC109142980
B: 10’ probe to controller wireset CC848817024
C: 1’ probe to probe wireset CC848822560
C: 5’ probe to probe wireset 848719803
C: 10’ probe to probe wireset CC848822321
ES771A Voltage Monitor Card 108958422
D: 2 1/2’ ES771A to probe wireset CC848791517
D: 6’ ES771A to probe wireset CC848797290
D: 10’ ES771A to probe wireset 848719829
G: 4’ ES771A to ES771A or controller wireset CC848791500
G: 10’ ES771A to ES771A or controller wireset 848652947
POWER MODULE OUTPUT POWER/INPUT VOLTAGE OUTPUT VOLTAGE PROTECTION PHYSICAL
CP2000AC54TEZ/TEP 2000W / 200-277VAC
1200W / 100-120VAC
Hardware set
44 - 58Vdc
Software set
42 - 58Vdc
15A breaker, 14 gauge wire Length: 13.85”/351.8mm
Width: 4.00”/101.6mm
Height: 1.66”/42.2mm
Weight: 4.6lb/2.1kg
CP2500DC54PEZ 2500W / 40-72VDC 70A breaker, 8 gauge wire
CP2725AC54TEZ/TEP 2725W / 200-277VAC
1200W / 100-120VAC
20A breaker, 12 gauge wire
CP2000DC54-PEZ 2000W / 40-72VDC 60A breaker, 8 gauge wire
CP3000AC54TEZ/TECZ 3000W / 200-277VAC
1500W / 100-120VAC
30A breaker, 10 gauge wire
CP3500AC54TEZ/TECZ 3500W / 200-277VAC
1500W / 100-120VAC
20A breaker, 12 gauge wire
Notes: PE sux denotes PoE compliance. Z sux denotes RoHS 6 compliance. TE sux denotes Total Eciency* architecture.
MECHANICAL J85480S-1 J2014003 J2007001L014 J2007001 J2014004
Height 1.71 inches/43.4mm 1.71 inches/43.4mm 1.71 inches/43.4mm 1.71 inches/43.4mm 1.71 inches/43.4mm
Width (with mounting ears) 19 inches/483mm 19 inches/483mm 19 inches/483mm 19 inches/483mm 19 inches/483mm
Depth 16.25 inches/413mm 17.25 inches/438mm 19.5 inches/497mm 17.06 inches/433mm 16.9 inches/429mm
Weight (without rectiers) 9.25lbs/4.2kg 9.5lbs/4.3kg 9.5lb/4.3kg 8.75lbs/4.0kg 9lbs/4.1kg
Note: dimensions of specic model numbers may vary
Specications
Shelves
Rectiers
Management Visibility
Galaxy Manager* software is the centralized visibility and control component
of a comprehensive power management system designed to meet engineering,
operations and maintenance needs. The Galaxy Manager client-server architecture
enables remote access to system controllers across the power network.
Dashboard display with one-click access to
management information database
Trend analysis
Scheduled or on demand reports
Fault, configuration, asset, and performance management
Training
GE oers on-site and classroom training options based on certication curriculum.
Technical training can be tailored to individual customer needs. Training enables
customers and partners to more eectively manage and support the power
infrastructure. We have built our training program on practical learning objectives
that are relevant to specic technologies or infrastructure design objectives.
Service & Support
GE eld service and support personnel are trusted advisors to our customers
– always available to answer questions and help with any project, large or
small. Our certied professional services team consists of experts in every
aspect of power conversion with the resources and experience to handle
large turnkey projects along with custom approaches to complex challenges.
Proven systems engineering and installation best practices are designed
to safely deliver results that exceed our customers’ expectations.
Warranty
GE is committed to providing quality products and solutions. We have
developed a comprehensive warranty that protects you and provides a
simple way to get your products repaired or replaced as soon as possible.
For full warranty terms and conditions please go to
www.gecriticalpower.com.
Reliability
Proven field performance
Advanced alarming
N+1 modularity
Intelligence
Industry leading controller features
Ethernet interface for
remote access
Centralized network management
Investment Protection
Minimal space requirements
Versatile configurations
Efficient operation
On Time Delivery
Standard building blocks
8-16 week availability
24/7 support
*Registered trademark of the General Electric Company.
The GE brand, logo, and lumination are trademarks of the General Electric Company. © 2016 General Electric Company.
Information provided is subject to change without notice. All values are design or typical values when measured under
laboratory conditions.
CPB-CPL, Rev. 03/2016