Rechargeable Sealed Lead-Acid Battery
PERFORMANCE SPECIFICATIONS
Nominal Voltage....................................................................................................................................................... 12 volts (6 cells in series)
Nominal Capacity
20 hour rate (600mA to 10.50 volts) ......................................................................................................................................... 12.0 A.H.
10 hour rate (1.1A to 10.50 volts) ............................................................................................................................................. 11.0 A.H.
5 hour rate (2.1A to 10.20 volts) ............................................................................................................................................. 10.5 A.H.
1 hour rate (7.25A to 09.00 volts) .......................................................................................................................................... 7.25 A.H.
Approximate Weight........................................................................................................................................................ 8.5 pounds (3.86 kg)
Energy Density (20 hour rate)............................................................................................. 1.69 Watt-hours/cubic inch (103.6 Watt-hours/l)
Specific Energy (20 hour rate).................................................................................................. 16.9 Watt-hours/pound (37.3 Watt-hours/kg)
Internal Resistance (Fully Charged Battery).................................................................................................... 16 milliohms (approximately)
Maximum Discharge Current ( <_ 7 Min.).................................................................................................................................. 36 amperes
Maximum Short-Duration Discharge Current ( <_ 10 Sec.)..................................................................................................... 120 amperes
Terminal configurations ..................................... ”F2”: Quick disconnect tabs, 0.250” x 0.032”- Mate with AMP. INC FASTON “250” series
Shelf Life — % of nominal capacity at 68o F (20o C)
1 Month.......................................................................................................................................................................................... 97%
3 Months.................................................................................................................................................................................... 91%
6 Months.................................................................................................................................................................................... 83%
Operating Temperature Range
Charge.................................................................................................................................................................... -4oF (-20oC) to 122oF (50oC)
Discharge............................................................................................................................................................... -4oF (-20oC) to 140oF (60oC)
Case................................................................................................................................................................................................. ABS Plastic
PS-12120
12 V olt 12.0 Amp. Hrs.
Features:
Absorbent Glass Mat (AGM) technology for
superior performance.
Valve regulated, spill proof construction
allows safe operation in any position.
Power/volume ratio yielding unrivaled
energy density.
Rugged ABS plastic case and cover
Approved for transport by air. D.O.T., I.A.T.A.,
F.A.A. and C.A.B. certified.
U.L. recognized under file number MH 20845.
Sealed Rechargeable
MODEL PS-12120 F2
12 Volt 12.0 Amp. Hr.
Power-Sonic Corporation
Battery
www.power-sonic.com
B
A
T
T
E
R
Y
M
U
S
T
B
E
R
E
C
Y
C
L
E
D
Pb
NONSPILLABLE
120
100
80
60
40
20
00 200 400 600 800 1000 1200
Number of Cycles
CHARGING
Cycle Applications: Limit initial current to 3.6A. Charge until battery
voltage (under charge) reaches 14.40 to 14.70 volts at 68oF (20oC). Hold
at 14.40 to 14.70 volts until current drops to approximately 120mA. Battery
is fully charged under these conditions, and charger should either be
disconnected or switched to “float” voltage.
“Float” or “Stand-By” Service: Hold battery across constant voltage
source of 13.50 to 13.80 volts continuously . When held at this voltage,
the battery will seek its own current level and maintain itself in a fully
charged condition.
NOTE: Due to the self-discharge characteristics of this type of battery , it
is imperative that they be charged after 6-9 months of storage, otherwise
permanent loss of capacity might occur as a result of sulfation.
Terminal Voltage
14.0
13.0
12.0
11.0
10.0
9.0
8.0
(V)
Ambient Temperature 20oC (68oF)
1.2 2.4 6 12 24 36 48 1 2 4 6 8 10 20 40
Discharge Time
min. hrs.
Final
Voltage 24A
12A 6A 2.4A 1.2A 0.6A
Discharge Time
20
15
10
5
2
1
30
10
5
0.6 1.2 2.4 6 12 24
Discharge Current (A)
min. hrs.
Final
Voltage
10.5V 10.2V
9.60V
9.0V
8.10V
40oC (104oF)
20oC (68oF)
0oC (32oF)
TECHNICAL DATA: PS-12120
T olerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions.
All data subject to change without notice.
Physical Dimensions: in. (mm)
SALES & MARKETING
3106 Spring Street
Redwood City, CA 94063 USA
Tel: 650-364-5001 Fax: 650-366-3662
national-sales@power-sonic.com www.power-sonic.com customer-service@power-sonic.com
PRINTED IN U.S.A.
CUSTOMER SERVICE
7550 Panasonic Way
San Diego, CA 92154 USA
Tel: 619-661-2030 Fax: 619-661-3648
1. Discharge Current 0.2C (Final Voltage 1.7V/Cell)
2. Charge Current: 0.1C
3. Ambient Temperature: 20oC to 25oC (68oF to 77oF)
Shelf Life and Storage
Capacity Retention Ratio (%)
100
80
60
40
00 2 4 6 8 10 12 14 16 18 20
Standing Period (Months)
40oC
(104oF) 30oC
(86oF) 20oC
(68oF)
5oC
(41oF)
Charge may fail
to restore full
capacity. Do not
let batteries reach
this state.
Charging before
use is necessary
to help recover
full capacity.
Charging is not
necessary unless
100% of capacity
is required.
Life Characteristics in Stand-By Use
Life Characteristics in Cyclic Use
Retention Capacity (%)
Discharge Characteristics
Discharge Time vs. Discharge Current
Discharge
Depth 30%
Discharge
Depth 100% Discharge
Depth 50%
5.95 (151)
3.86 (98)
3.70 (94)
3.94 (100)
1 1/04 1 M
ISO 9001-2000
FM39170
Ambient Temperature 20˚C (68˚F)
Float Charging Voltage
2.25 - 2.30 V/Cell
Retention Capacity (%)
100
80
60
40
20
00 1 2 3 4
Years
6.35
0.8
3.4
Terminals: F2 (mm)