Specifications are subject to change without notice (18.07.06) 1
Monitoring Relays
Product Description Ordering Key
Housing
Function
Type
Item number
Output
Power supply
TRMS 3-phase phase sequence, phase loss and
asymmetry monitoring relays
Detect when all 3 phases are present and have the
correct sequence
Detect if asymmetry level is below the set value
Measure on own power supply
Selection of measuring range by DIP-switches
Adjustable asymmetry on relative scale
Adjustable delay function (0.1 to 30 s)
Output: 8 A relay SPDT N.E.
For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DPB02) or plug-in module (PPB02)
22.5 mm Euronorm housing (DPB02)
or 36 mm plug-in module (PPB02)
LED indication for relay, alarm and power supply ON
Type Selection
Mounting Output Supply: 208 to 240 VAC Supply: 380 to 415 VAC Supply: 380 to 480 VAC
DIN-rail SPDT DPB 02 C M23 DPB 02 C M48
Plug-in SPDT PPB 02 C M23 PPB 02 C M48
Input
L1, L2, L3, N DPB02: Terminals L1, L2, L3, N
PPB02: Terminals 5, 6, 7, 11
Measure on own supply
Note: Connect the neutral only
if it is intrinsically at the star
centre
Measuring ranges
208 to 240 VAC 177 to 275 VAC
380 to 480 VAC (DPB02CM48) 323 to 550 VAC
380 to 415 VAC (PPB02CM48) 323 to 475 VAC
Ranges
Asymmetry 2 to 22%
of the nominal voltage
True RMS 3-Phase, Phase Sequence/Loss - Asymmetry
Types DPB02, PPB02
Input Specifications
Output SPDT relay
Rated insulation voltage 250 VAC
Contact ratings (AgSnO2)µ
Resistive loads AC 1 8 A @ 250 VAC
DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC
DC 13 2.5 A @ 24 VDC
Mechanical life 30 x 106operations
Electrical life 105operations
(at 8 A, 250 V, cos ϕ=1)
Operating frequency 7200 operations/h
Dielectric strength
Dielectric voltage 2kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Output Specifications
DPB 02 C M23
3-phase or 3-phase+neutral
line voltage monitoring relay
for phase sequence, phase
loss and asymmetry with
built-in time delay function.
Supply ranges from 208 to
480 VAC covered by two
multi voltage relays.
DPB02 PPB02
No
ot
te
e:The input voltage
must not exceed the maxi-
mum rated voltage or drop
below the minumum rated
voltage reported above.
2Specifications are subject to change without notice (18.07.06)
DPB02, PPB02
Mode of Operation
Connected with the 3 phas-
es (and neutral) DPB02 and
PPB02 operate when all 3
phases are present at the
same time, the phase
sequence is correct and the
asymmetry is under the set
level.
Asymmetry is defined as fol-
lows:
when measuring phase-
phase voltages and also as
follows:
when measuring phase-neu-
tral voltages.
If the asymmetry exceeds
the set level the red LED
starts flashing 2 Hz and the
output relay releases after
the set time period. If the
phase sequence is incorrect
or one phase is lost, the output
relay releases immediately.
Only 200 ms delay occurs.
The failure is indicated by the
red LED flashing 5 Hz after
the alarm condition occurs.
Example 1
(mains network monitoring)
The relay monitors asymme-
try, phase loss and correct
phase sequence.
Example 2
(load monitoring)
The relay releases in case of
interruption of one or more
phases or when the asym-
metry exceeds the set level.
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038)
through terminals:
L1, L2, L3, N (DPB02)
5, 6, 7, 11 (PPB02)
M23 - Delta Voltage: 208 to 240 VAC ± 15%
45 to 65 Hz
M48 (DIN-rail) - Delta Voltage: 380 to 480 VAC ± 15%
45 to 65 Hz
M48 (DIN-rail) - Star Voltage: 220 to 277 VAC ± 15%
45 to 65 Hz
M48 (Plug-in) - Delta Voltage: 380 to 415 VAC ± 15%
45 to 65 Hz
M48 (Plug-in) - Star Voltage: 220 to 240 VAC ± 15%
45 to 65 Hz
Rated operational power
DPB02CM23, PPB02CM23 13 VA @ 230 VAC, 50 Hz
DPB02CM48, PPB02CM48 13 VA @ 400 VAC, 50 Hz
Supplied by L1 and L2
Supply Specifications
Power ON delay 1 s ± 0.5 s or 6 s ± 0.5 s
Reaction time
Incorrect phase sequence or
total phase loss < 200 ms
Asymmetry
Alarm ON delay < 200 ms (delay < 0.1 s)
Alarm OFF delay < 200 ms (delay < 0.1 s)
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C
Delay ON alarm ± 10% on set value ± 50 ms
Repeatability ± 0.5% on full-scale
Indication for
Power supply ON LED, green
Alarm ON LED, red (flashing 2 Hz
during delay time)
Output relay ON LED, yellow
Environment
Degree of protection IP 20
Pollution degree 3 (DPB02), 2 (PPB02)
Operating temperature
@ Max. voltage, 50 Hz -20 to 60°C, R.H. < 95%
@ Max. voltage, 60 Hz -20 to 50°C, R.H. < 95%
Storage temperature -30 to 80°C, R.H. < 95%
Housing
Dimensions DPB02 22.5 x 80 x 99.5 mm
PPB02 36 x 80 x 94 mm
Weight Approx. 120 g
Screw terminals
Tightening torque Max. 0.5 Nm
acc. to IEC 60947
Approvals UL, CSA
CE marking Yes
EMC Electromagnetic Compatibility
Immunity According to EN 61000-6-2
Emissions According to EN 61000-6-3
General Specifications
max{|Vph-ph|}
nom. voltage
max{|Vph-n|}
nom. voltage
Specifications are subject to change without notice (18.07.06) 3
DPB02, PPB02
Adjust the input range set-
ting the DIP switches 3 and
4 as shown below.
Select the desired function
setting the DIP switches 1
and 2 as shown below.
To access the DIP swiches
open the grey plastic cover
as shown below
Selection of asymmetry
and time delay:
Centre knob:
Setting of asymmetry on rel-
ative scale.
Lower knob:
Setting of delay on alarm
time on absolute scale (0.1
to 30 s).
Function/Range/Level and Time Delay Setting
Power ON delay
ON: 6 s ± 0.5 s
OFF: 1 s ± 0.5 s
Monitored voltage
ON: Phase-Neutral
OFF: Phase-Phase
Measuring range
SW3 ON ON OFF OFF
SW4 ON OFF ON OFF
M23 Ph-Ph 208 VAC 220 VAC 230 VAC 240 VAC
Voltage
M48 Ph-Ph 380 VAC 400 VAC 415 VAC 480 VAC
Voltage DPB02 only
M48 Ph-N 220 VAC 230 VAC 240 VAC 277 VAC
Voltage DPB02 only
Operation Diagrams
4Specifications are subject to change without notice (18.07.06)
DPB02, PPB02
Dimensions
22.5
80
83.5
99.5
63
28.5
DIN-rail Plug-in
36
80
94
28.5
63
90
Wiring Diagrams
DPB02 PPB02