Low Voltage Products & Systems 1.A
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Contactors
Contactors
Index
Continued next page
Motor protection & control panorama ......................... 1.1 – 1.6
Features ............................................................................................................................. 1.1
3 Pole
Mini-contactors ..........................................................................................................1.2 - 1.3
Contactors .................................................................................................................1.2 - 1.3
Main accessories .......................................................................................................1.2 - 1.3
Overload relays ..........................................................................................................1.2 - 1.3
Manual motor starters ................................................................................................1.2 - 1.3
4 Pole
Mini-contactors ..........................................................................................................1.3 - 1.4
Contactors ................................................................................................................ 1.3 - 1.4
Control relays & mini-control relays .............................................................................1.3 - 1.4
Specialty contactors
Bar contactors ...................................................................................................1.3 - 1.4
DC circuit switching ...........................................................................................1.3 - 1.4
Definite purpose.................................................................................................1.3 - 1.4
Lighting contactors ............................................................................................1.3 - 1.4
Capacitive switching ..........................................................................................1.3 - 1.4
Railway applications...........................................................................................1.3 - 1.4
Dynamic braking / DC drives..............................................................................1.3 - 1.4
Across the line contactors ....................................... 1.7 – 1.166
Features .................................................................................................................................. 1.7
General information
Technical terms and definitions ..........................................................................................1.8
IEC Standards, utilization categories ..................................................................................1.9
Motor ratings ................................................................................................................... 1.10
Pilot duty ratings and overload trip classes ......................................................................1.11
AF Series contactors .............................................................................................1.12 - 1.13
Selection
AF non-reversing, 3 pole .................................................................................................. 1.14
AF mechanically interlocked & reversing, 3 pole ............................................................... 1.15
AFZ non-reversing, 3 pole ................................................................................................1.16
AFZ mechanically interlocked, reversing, 3 pole ...............................................................1.17
A non-reversing, 3 pole ....................................................................................................1.18
A mechanically interlocked, reversing, 3 pole ...................................................................1.19
AE non-reversing, 3 pole .................................................................................................1.20
AE mechanically interlocked, reversing, 3 pole ................................................................. 1.21
AL non-reversing, 3 pole .................................................................................................. 1.22
AL mechanically interlocked, reversing, 3 pole .................................................................1.23
AS / ASL non-reversing, reversing 3 pole .........................................................................1.24
AS / ASL non-reversing, spring-terminated, 3 pole ..........................................................1.25
B miniature non-reversing, mechanically interlocked, 3 pole .............................................1.26
BC miniature non-reversing, mech. interlocked, 3 pole ....................................................1.27
AF / AFZ NEMA rated, non-reversing, 3-pole ...................................................................1.28
AF / AFZ NEMA rated, mech. interlocked, reversing, 3-pole.............................................1.29
A, AL, AE NEMA rated, non-reversing, 3-pole .................................................................. 1.30
A, AL, AE NEMA rated, mech. interlocked, reversing .......................................................1.31
AF, AFZ, and EK 4-pole ...................................................................................................1.32
A, AL, and AE 4-pole ....................................................................................................... 1.33
B, BC miniature, 4-pole ...................................................................................................1.34
Additional coil voltages .............................................................................................................1.35
Accessory fitting details ..................................................................................................1.36 - 1.44
Coordination with short-circuit protection devices ..................................................................... 1.45
Auxiliary contact blocks ..................................................................................................1.46 - 1.51
Surge suppressors for contactor coils.............................................................................1.52 - 1.53
Interface relays ...............................................................................................................1.54 - 1.55
Mechanical & electrical interlocks ....................................................................................1.56 - 1.57
Mechanical latching unit ...........................................................................................................1.58
Electronic timers .......................................................................................................................1.59
Electronic timers for wye-delta starters ...........................................................................1.60 - 1.61
Connection kits (reversing & phase-to-phase) ...........................................................................1.62
Connection sets (wye-delta) ......................................................................................................1.63
Coupling units ................................................................................................................1.64 - 1.65
Terminal enlargements/extensions & shorting bars .................................................................... 1.66
Terminal control leads, blocks & lug kits .................................................................................... 1.67
Terminal shrouds ......................................................................................................................1.68
Function markers, protective covers & coil terminal blocks........................................................1.69
Mounting plates ........................................................................................................................ 1.70
Adapter plates & accessories ...................................................................................................1.71
Replacement parts .........................................................................................................1.72 - 1.74
Terminal marking and positioning ....................................................................................1.75 - 1.82
Technical data ..............................................................................................................1.83 - 1.146
Approximate dimensions ............................................................................................1.147 - 1.166
Capacitive contactors .......................................... 1.167 – 1.174
Features .............................................................................................................................. 1.167
Contactors for capacitive switching ........................................................................................1.168
Selection
UA, UA...RA 3 pole ........................................................................................................ 1.169
Technical data ............................................................................................................1.170 - 1.173
Approximate dimensions ........................................................................................................1.174
Definite purpose contactors .................................1.175 - 1.184
Features .............................................................................................................................. 1.175
DP non-reversing 1, 2, 3 & 4 pole ........................................................................................... 1.176
Accessories ............................................................................................................................ 1.177
Technical data ............................................................................................................1.178 - 1.179
Approximate dimensions ............................................................................................1.180 - 1.183
Dynamic braking / DC drive ................................. 1.185 – 1.194
Features .............................................................................................................................. 1.185
Selection
EHDB, DA75 2- & 3-pole, non-reversing ........................................................................ 1.186
EHDB, DA75 2 & 3 pole, mechanically-interlocked ........................................................1.187
Replacement parts .....................................................................................................1.188 - 1.189
Technical data ............................................................................................................1.190 - 1.191
Approximate dimensions ............................................................................................1.192 - 1.193
Lighting contactors .............................................. 1.195 – 1.200
Features .............................................................................................................................. 1.195
A9 - A300 Electrically & mechanically held ..................................................................1.196 - 1.197
Accessories ............................................................................................................................ 1.198
Factory modifications ..............................................................................................................1.198
Railway application contactors ........................... 1.201 – 1.206
Features .............................................................................................................................. 1.201
Reference standards...............................................................................................................1.202
Selection
Standard devices, ring-tongue, 3-pole ........................................................................... 1.203
Traction-specic, ring-tongue, 3-pole .............................................................................1.204
Traction-specic, ring-tongue, 4-pole & relays................................................................1.205
Accessories ............................................................................................................................ 1.206
1 - Contactors
1.B Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Contactors
Index
DC Circuit switching contactors .......................... 1.207 – 1.214
Features .............................................................................................................................. 1.207
Selection
GA75 - GAE75 ..............................................................................................................1.208
GAF185 - GAF2050.......................................................................................................1.209
Technical data ............................................................................................................1.210 - 1.211
Connections ...........................................................................................................................1.212
Approximate dimensions ............................................................................................1.213 - 1.214
Bar contactors ...................................................... 1.215 – 1.224
Features .............................................................................................................................. 1.215
Overview ..................................................................................................................1.216 - 1.217
Bar contactors for the AC circuits switching................................................................1.218 - 1.219
Bar contactors for the DC circuits switching ...............................................................1.220 - 1.221
Questionnaire .............................................................................................................1.222 - 1.223
Low Voltage Products & Systems 1.1
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Motor protection and control
Panorama
Panorama
Motor protection & control
Simple, sustainable integration
Complete 3- & 4-pole ranges
High performance and quality
Ease of installation
AF contactors with electronic coils:
- Wide input ranges
- Unified AC/DC voltages
- Chatter-proof / hum-free
- Dips withstand
- Integral surge suppression
Global certification and approvals
The right choice for many applications
Pumps & compressors
HVAC equipment
Power supplies and batteries
Material handling
Alternative energy
Traction / rail
Mobile equipment
Miniature contactors for compact equipment up to 5 hp / 5.5 kW
Standard contactors for all industrial applications up to 2700 A
Motor starting up to 1150 hp / 900 kW
Contactors for heavy duty applications up to 5000 A, 1500V
Motor starting solutions
Simple, compact assembly
Close couplers, busbar and terminal
accessories
Systems concept:
- Reduced panel space
- Time / cost saving
- Secure assembly
1.2 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
IEC
AC-3 Rated operational power
θ55 °C*, 400 V
kW 45.5 45.5 7.5 45.5 7.5 11 15 18.5 18.5 22 30 37 45 55 75 90 110 140 160 200 250
315 400
475 560
UL/CSA
3-phase motor rating
480 V
hp 3 5 5 7.5 10 57.5 10 15 20 30 40 50 60 60 75 100 125 150 200 250 350 400
500 600
800 900
AC Control supply Type B6 B7 AS09 AS12 AS16 AF09
AF09Z
AF12
AF12Z
AF16
AF16Z
AF26
AF26Z
AF30
AF30Z
AF38
AF30Z A40 A50 A63 A75 A95 A110 A145 A185 A210 A260 A300 AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050
DC Control supply Type BC6 BC7 ASL09 ASL12 ASL16 AF09
AF09Z
AF12
AF12Z
AF16
AF16Z
AF26
AF26Z
AF30
AF30Z
AF38
AF38Z AL40 AE50 AE63 AE75 AF95 AF110 AF145 AF185 AF210 AF260 AF300 AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050
AC / DC Control supply Type AF09
AF09Z
AF12
AF12Z
AF16
AF16Z
AF26
AF26Z
AF30
AF30Z
AF38
AF38Z AF50 AF63 AF75 AF95 AF110 AF145 AF185 AF210 AF260 AF300 AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050
IEC
AC-3 Rated operational current
θ 55 °C*, 400 V
A 9 12 9 12 15.5 9 12 18 26 32 38 37 50 65 75 96 110 145 185 210 260 305 400 460 580 750 860 1050
AC-1 Rated operational current
θ 40 °C, 690 V
A 16 20 22 24 24 25 28 30 45 50 50 60 100 115 125 145 160 250 275 350 400 500 600 700 800 1050 1260 1350 1650 2050
UL/CSA
General use rating
600 V
A 12
(300 V)
16 20 20 20 25 28 30 45 50 50 60 80 90 105 125 150 230 250 300 350 400 550 650 750 900 1210 1350 1650 2100
NEMA
NEMA Size
00 0 1 23 4 5 6 7 8
* θ ≤ 60 °C for AS(L)09 ... AS(L)16 and AF09 ... AF38 contactors
Pages 1.26...1.27 Pages 1.24...1.25 Pages 1.14...1.17 AF Series - pages 1.14...1.15; A Series - pages 1.18...1.19; AE Series - pages 1.20...1.21;
AL Series - pages 1.22...1.23; NEMA rated contactors - pages 1.28...1.31
Main accessories
Auxiliary contact blocks
Pages 1.46...1.51
Front mounting
CAF6 CA3-10
(1 x N.O.)
,
CA3-01
(1 x N.C.)
CA4-10
(1 x N.O.),
CA4-01
(1 x N.C.)
CA5-10
(1 x N.O.),
CA5-01
(1 x N.C.)
Side mounting
CA6 CAL4-11
(1 x N.O. + 1 x N.C.)
CAL5-11
(1 x N.O. + 1 x N.C.)
CAL18-11
(1 x N.O. + 1 x N.C.)
Timers
Page 1.59
Electronic
TEF3-ON, TEF3-OFF TEF4-ON, TEF4-OFF TEF5-ON, TEF5-OFF
Interlocking units (1)
Pages 1.56...1.57
Mechanical
VM3 VM4 VM5-1 VM300H / VM300V VM750H / VM750V VM1650H
Mechanical / Electrical
VEM4 VE5-1 VE5-2
Connection
kits Page 1.62
For reversing contactors
BSM6-30 BER16C-3 BER16-4 BER38-4 BER40V BEM75-30 BEM110-30 BEM185-30 BEM300-30 BEM460-30 BEM750-30
Surge suppressors
Pages 1.52...1.53
AF contactors have built-in surge
protection
Varistor (AC/DC)
RV-BC6 RV5
(24…440 V)
RV5
(24440 V)
RC type (AC)
RC5-1
(24…440 V)
RC5-1
(24440 V)
RC5-2
(24440 V)
RC5-3
(250...440V)
Transil diode (DC)
RD7 RT5
(12…264 V)
RT5
(12264 V)
(1) See available reversing contactors VB6, VB7 and VAS09 ... VAS16
Overload relaysChapter 2
Thermal relays
Class 10
(10A or 20 for TA42DU to TA80DU)
T16
(0.10…16 A)
T16
(0.10…16 A)
TF42
(0.10…38 A)
TA42DU
(18…42 A)
TA75DU
(18…80 A)
TA80DU
(2980 A)
TA110DU
(65110 A)
TA200DU
(66200 A)
TA450DU/SU
(130310 A) class 30 for SU
Electronic relays
Class 10E, 20E, 30E
E16DU
(0.10…18.9 A)
EF19
(0.10…18.9 A)
EF19
(0.10…18.9 A),
EF45
(9…45 A)
E45DU
(9...45 A)
E80DU
(2780 A)
E140DU
(50140 A)
E200D-U
(60200 A)
E320DU
(100320 A)
E500DU
(150…500 A)
E800DU
(250800 A)
E1250DU
(375…1250 A)
Accessories for
thermal overload relays
Wall/separate mounting kit
DB16
(T16 only),
DB16E
(E16DU only)
DB42
(TF42 only)
DB80, DB45E, DB80E DB80, DB200,
D140E
DB200
Manual motor starters Chapter 4 Circuit breakers Chapter 17
Thermal / magnetic
protection
Class
10
MS116
for class 10A (0.16…32 A)
MS116
for class 10A (0.16…32 A)
MS450
(28…50 A)
MS132
(0.10…32 A)
MS132
(0.10…32 A)
MS495
(28…100 A)
Tmax
Circuit breaker and accessories
Class
20
MS451
(28…50 A)
MS496
(28…100 A)
Magnetic only types
MO132
(0.10…32 A)
Accessories
For contactor mounting
BEA7/132 BEA16-3 BEA16-4 BEA38-4
BEA40/450
BEA50/450, BEA75/495
Auxiliary trip units, auxiliary
contacts, busbars
HKF1, HK1, UA1, AA1,
PS1, S1, SK1, CK1
HKF1, HK1, UA1, AA1, PS1, S1, SK1, CK1 HK4, HKS4, UA4, AA4, PS4, S4, SK4
Contactors for all industrial
applications and motor starting
3-pole contactors Mini
contactors
Low Voltage Products & Systems 1.3
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
IEC
AC-3 Rated operational power
θ55 °C*, 400 V
kW 45.5 45.5 7.5 45.5 7.5 11 15 18.5 18.5 22 30 37 45 55 75 90 110 140 160 200 250
315 400
475 560
UL/CSA
3-phase motor rating
480 V
hp 3 5 5 7.5 10 57.5 10 15 20 30 40 50 60 60 75 100 125 150 200 250 350 400
500 600
800 900
AC Control supply Type B6 B7 AS09 AS12 AS16 AF09
AF09Z
AF12
AF12Z
AF16
AF16Z
AF26
AF26Z
AF30
AF30Z
AF38
AF30Z A40 A50 A63 A75 A95 A110 A145 A185 A210 A260 A300 AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050
DC Control supply Type BC6 BC7 ASL09 ASL12 ASL16 AF09
AF09Z
AF12
AF12Z
AF16
AF16Z
AF26
AF26Z
AF30
AF30Z
AF38
AF38Z AL40 AE50 AE63 AE75 AF95 AF110 AF145 AF185 AF210 AF260 AF300 AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050
AC / DC Control supply Type AF09
AF09Z
AF12
AF12Z
AF16
AF16Z
AF26
AF26Z
AF30
AF30Z
AF38
AF38Z AF50 AF63 AF75 AF95 AF110 AF145 AF185 AF210 AF260 AF300 AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050
IEC
AC-3 Rated operational current
θ 55 °C*, 400 V
A 9 12 9 12 15.5 9 12 18 26 32 38 37 50 65 75 96 110 145 185 210 260 305 400 460 580 750 860 1050
AC-1 Rated operational current
θ 40 °C, 690 V
A 16 20 22 24 24 25 28 30 45 50 50 60 100 115 125 145 160 250 275 350 400 500 600 700 800 1050 1260 1350 1650 2050
UL/CSA
General use rating
600 V
A 12
(300 V)
16 20 20 20 25 28 30 45 50 50 60 80 90 105 125 150 230 250 300 350 400 550 650 750 900 1210 1350 1650 2100
NEMA
NEMA Size
00 0 1 23 4 5 6 7 8
* θ ≤ 60 °C for AS(L)09 ... AS(L)16 and AF09 ... AF38 contactors
Pages 1.26...1.27 Pages 1.24...1.25 Pages 1.14...1.17 AF Series - pages 1.14...1.15; A Series - pages 1.18...1.19; AE Series - pages 1.20...1.21;
AL Series - pages 1.22...1.23; NEMA rated contactors - pages 1.28...1.31
Main accessories
Auxiliary contact blocks
Pages 1.46...1.51
Front mounting
CAF6 CA3-10
(1 x N.O.)
,
CA3-01
(1 x N.C.)
CA4-10
(1 x N.O.),
CA4-01
(1 x N.C.)
CA5-10
(1 x N.O.),
CA5-01
(1 x N.C.)
Side mounting
CA6 CAL4-11
(1 x N.O. + 1 x N.C.)
CAL5-11
(1 x N.O. + 1 x N.C.)
CAL18-11
(1 x N.O. + 1 x N.C.)
Timers
Page 1.59
Electronic
TEF3-ON, TEF3-OFF TEF4-ON, TEF4-OFF TEF5-ON, TEF5-OFF
Interlocking units (1)
Pages 1.56...1.57
Mechanical
VM3 VM4 VM5-1 VM300H / VM300V VM750H / VM750V VM1650H
Mechanical / Electrical
VEM4 VE5-1 VE5-2
Connection
kits Page 1.62
For reversing contactors
BSM6-30 BER16C-3 BER16-4 BER38-4 BER40V BEM75-30 BEM110-30 BEM185-30 BEM300-30 BEM460-30 BEM750-30
Surge suppressors
Pages 1.52...1.53
AF contactors have built-in surge
protection
Varistor (AC/DC)
RV-BC6 RV5
(24…440 V)
RV5
(24…440 V)
RC type (AC)
RC5-1
(24…440 V)
RC5-1
(24…440 V)
RC5-2
(24…440 V)
RC5-3
(250...440V)
Transil diode (DC)
RD7 RT5
(12…264 V)
RT5
(12…264 V)
(1) See available reversing contactors VB6, VB7 and VAS09 ... VAS16
Overload relaysChapter 2
Thermal relays
Class 10
(10A or 20 for TA42DU to TA80DU)
T16
(0.10…16 A)
T16
(0.10…16 A)
TF42
(0.10…38 A)
TA42DU
(18…42 A)
TA75DU
(18…80 A)
TA80DU
(29…80 A)
TA110DU
(65…110 A)
TA200DU
(66…200 A)
TA450DU/SU
(130…310 A) class 30 for SU
Electronic relays
Class 10E, 20E, 30E
E16DU
(0.10…18.9 A)
EF19
(0.10…18.9 A)
EF19
(0.10…18.9 A),
EF45
(9…45 A)
E45DU
(9...45 A)
E80DU
(27…80 A)
E140DU
(50…140 A)
E200D-U
(60…200 A)
E320DU
(100…320 A)
E500DU
(150…500 A)
E800DU
(250…800 A)
E1250DU
(375…1250 A)
Accessories for
thermal overload relays
Wall/separate mounting kit
DB16
(T16 only),
DB16E
(E16DU only)
DB42
(TF42 only)
DB80, DB45E, DB80E DB80, DB200,
D140E
DB200
Manual motor starters Chapter 4 Circuit breakers Chapter 17
Thermal / magnetic
protection
Class
10
MS116
for class 10A (0.16…32 A)
MS116
for class 10A (0.16…32 A)
MS450
(28…50 A)
MS132
(0.10…32 A)
MS132
(0.10…32 A)
MS495
(28…100 A)
Tmax
Circuit breaker and accessories
Class
20
MS451
(28…50 A)
MS496
(28…100 A)
Magnetic only types
MO132
(0.10…32 A)
Accessories
For contactor mounting
BEA7/132 BEA16-3 BEA16-4 BEA38-4
BEA40/450
BEA50/450, BEA75/495
Auxiliary trip units, auxiliary
contacts, busbars
HKF1, HK1, UA1, AA1,
PS1, S1, SK1, CK1
HKF1, HK1, UA1, AA1, PS1, S1, SK1, CK1 HK4, HKS4, UA4, AA4, PS4, S4, SK4
NEW!!
AF2650
General use: 2700A
AC-1: 2650A
1.4 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Mini contactors Contactors
IEC
AC-1 Rated operational current
θ 40 °C, 690 V
A16 20 25 30 45 55 70 100 125 200 250 300 350 550 800 1000
UL/CSA
General use rating
600 V A12
(300 V)
16 25 30 45 55 80 80 105 170 200 250 300 420 540
AC Control supply Type B6 B7 AF09
AF09Z
AF16
AF16Z
AF26
AF26Z
AF38
AF38Z A45 A50 A75 EK110 EK150 EK175 EK210 EK370 EK550 EK1000
DC Control supply Type BC6 BC7 AF09
AF09Z
AF16
AF16Z
AF26
AF26Z
AF38
AF38Z AE45 AE50 AE75 EK110 EK150 EK175 EK210 EK370 EK550 EK1000
AC / DC Control supply Type AF09
AF09Z
AF16
AF16Z
AF26
AF26Z
AF38
AF38Z AF45 AF50 AF75 ———————
Page 1.34 Page 1.32 Page 1.32...1.33 Page 1.32
4-pole contactors
Mini control relays - Chapter 6 Control relays - Chapter 6
IEC
AC-15 Rated operational current
400 V A 3 3 3
UL/CSA
Pilot duty
A 600 A 600, Q 300 A 600, Q 600
2 2 3 1 4 0 2 2 3 1 4 0 2 2 3 1 4 0
AC Control supply Type K6-22Z K6-31Z K6-40E NS22E NS31E NS40E NF22E NF31E NF40E
DC Control supply Type KC6-22Z KC6-31Z KC6-0E NSL22E NSL31E NSL40E NF22E NF31E NF40E
AC / DC Control supply Type NF22E NF31E NF40E
Control relays
Chapter 6
Bar contactors – Pages 1.215...1.224
Lighting contactors Pages 1.195...1.200
Railway applications Pages 1.201...1.206
DC-1 Rated current up to 5000 A
DC-3/DC-5 Rated current up to 2000 A
1500 V with poles in series
IOR.. 63-..-CC to IOR.. 5100-..-CC
AC-1 Rated current up to 5000 A
AC-3 Rated power up to 1500 kW
(1520 A - 440 V)
IOR.. 63-..-MT to IOR.. 5100-..-MT
For tungsten and ballast loads up to 400 A.
Up to 12 poles, open and enclosed
(UL Type 1)
Traction-specic (rail) devices with low-smoke
plastic and ring-tongue termination
Specialty contactors
Pages 1.167...1.224
DC Circuit switching Definite purpose Capacitive switching Dynamic braking / DC drive Pages 1.185...1.194
Pages 1.207...1.214 Pages 1.175...1.182
Pages 1.167...1.174
100 A, 440 V, DC-1
GA75, GAE75 types
275...2050A, 1000V, DC-1
GAF185...GAF2050 types
20...90 FLA
DP20...DP90 types
12.5 to 80 kvar
UA16..RA to UA110..RA types
UA16 to UA110 types
2 DC-rated N.O. power poles
with optional 3rd N.C. pole for dynamic braking
AC/DC Coupling: LOR.. contactors
Slip ring motor control: FOR .. contactors
Field discharge: AM(F)-CC-JORE
contactors
AC/DC Switching (N.C./N.O. main poles):
NOR & JOR contactors
Latching contactors for energy saving
and safety requirements: AMA or AME
contactors
Low Voltage Products & Systems 1.5
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Mini contactors Contactors
IEC
AC-1 Rated operational current
θ 40 °C, 690 V
A16 20 25 30 45 55 70 100 125 200 250 300 350 550 800 1000
UL/CSA
General use rating
600 V A12
(300 V)
16 25 30 45 55 80 80 105 170 200 250 300 420 540
AC Control supply Type B6 B7 AF09
AF09Z
AF16
AF16Z
AF26
AF26Z
AF38
AF38Z A45 A50 A75 EK110 EK150 EK175 EK210 EK370 EK550 EK1000
DC Control supply Type BC6 BC7 AF09
AF09Z
AF16
AF16Z
AF26
AF26Z
AF38
AF38Z AE45 AE50 AE75 EK110 EK150 EK175 EK210 EK370 EK550 EK1000
AC / DC Control supply Type AF09
AF09Z
AF16
AF16Z
AF26
AF26Z
AF38
AF38Z AF45 AF50 AF75 ———————
Page 1.34 Page 1.32 Page 1.32...1.33 Page 1.32
Mini control relays - Chapter 6 Control relays - Chapter 6
IEC
AC-15 Rated operational current
400 V A 3 3 3
UL/CSA
Pilot duty
A 600 A 600, Q 300 A 600, Q 600
2 2 3 1 4 0 2 2 3 1 4 0 2 2 3 1 4 0
AC Control supply Type K6-22Z K6-31Z K6-40E NS22E NS31E NS40E NF22E NF31E NF40E
DC Control supply Type KC6-22Z KC6-31Z KC6-0E NSL22E NSL31E NSL40E NF22E NF31E NF40E
AC / DC Control supply Type NF22E NF31E NF40E
Bar contactors – Pages 1.215...1.224
Lighting contactorsPages 1.195...1.200
Railway applicationsPages 1.201...1.206
DC-1 Rated current up to 5000 A
DC-3/DC-5 Rated current up to 2000 A
1500 V with poles in series
IOR.. 63-..-CC to IOR.. 5100-..-CC
AC-1 Rated current up to 5000 A
AC-3 Rated power up to 1500 kW
(1520 A - 440 V)
IOR.. 63-..-MT to IOR.. 5100-..-MT
For tungsten and ballast loads up to 400 A.
Up to 12 poles, open and enclosed
(UL Type 1)
Traction-specic (rail) devices with low-smoke
plastic and ring-tongue termination
DC Circuit switching Definite purpose Capacitive switching Dynamic braking / DC drivePages 1.185...1.194
Pages 1.207...1.214 Pages 1.175...1.182
Pages 1.167...1.174
100 A, 440 V, DC-1
GA75, GAE75 types
275...2050A, 1000V, DC-1
GAF185...GAF2050 types
20...90 FLA
DP20...DP90 types
12.5 to 80 kvar
UA16..RA to UA110..RA types
UA16 to UA110 types
2 DC-rated N.O. power poles
with optional 3rd N.C. pole for dynamic braking
1.6 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Notes
Low Voltage Products & Systems 1.7
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Across the line contactors
General purpose and motor applications
A-line contactors (9…300)
3- & 4-pole contactors
General purpose up to 400 A
Motor applications up to 300 hp, 250 kW
NEMA Sizes 00…5
Additional ratings including denite purpose & eleva-
tor duty
AC or DC coil input voltages
B / BC contactors
3 & 4 pole contactors
Compact solutions up to 5 hp, 5.5 kW
Quick-connect & PCB mount options
AC or DC coil input voltages
EK contactors
4-pole contactors
AC-1 up to 1000 A
AC or DC coil input voltages
AF series contactors (9…2650)
3- & 4-pole contactors
General purpose up to 2700 A
Motor applications up to 1150 hp, 900 kW
NEMA Sizes 00…8
DC switching up to 600V
Electronic AC/DC coil input voltages
PLC interface (AF400…AF2650)
Wide variety of accessories
Systems concept coupling units & bus kits
Additional ratings including denite purpose,
elevator duty & capacitive switching
AS / ASL contactors (9…16)
3-pole contactors
For high-volume applications up to 10 hp
Bulk packaging available
AC or DC coil input voltages
Across the line
Contactors
3-pole contactors
Standards
& approvals
AF09(Z)…
AF38(Z)
A/E/L9…
A/E/L40
A/E/F50…
A/E/F75
A/F95…
A/F110
A/F145…
AF750,
AF1350,
AF1650
AF1250,
AF2050,
AF2650
AS/L09…
AS/L16
B/C6…
B/C7
R
E312527 E312527 E312527 E312527 E36588 E73397 E312527 E191658
LR56745 LR56745 LR16332


Note: B/C6...7 quick-connect and PCB-mount are UL recognized.
4-pole contactors
Standards
& approvals
AF09(Z)…
AF38(Z)
A/E/L9…
A/E/L26
A/E/F45…
A/E/F75
EK110…
EK550 EK1000 B/C6…
B/C7
R
E319322 E312527 E312527 E36588 E191658
LR56745 LR56745 LR15332


Note: B/C6...7 quick-connect and PCB-mount are UL recognized.
1.8 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Altitude
Refers to the height of the site where the equipment is located, expressed in
meters above the sea level.
Ambient temperature
Temperature of the air surrounding the unit.
Circuits
• Auxiliary circuit
All the conducting parts of a contactor, intended to be included in a circuit
different from the main circuit and the control circuit of the contactor e.g.
signalization, interlocking circuits etc …
• Control circuit
All the conducting parts of a contactor (other than the main circuit) included in
a circuit used for the closing operation, or opening operation, or both, of the
contactor.
• Main circuit
All the conducting parts of a contactor included in the circuit which it is designed
to close or open.
Coil operating range
Expressed as a multiple of the rated control circuit voltage Uc for the lower and
upper limits.
Cycle duration
Total time of the on-load + off-load period.
Endurance / durability
• Electrical endurance
Number of on-load operating cycles (i.e. with current on the main contacts) a
contactor can achieve, varies depending on the utilization category.
• Mechanical endurance
Number of off-load operating cycles (i.e. without current on the main contacts) a
contactor can achieve.
Inching
Energizing a motor once or repeatedly for short periods to obtain small
movements of the driven mechanism.
Insulation class according to the VDE 0110 and NFC 20-040
Characterizes contactors suitability in accordance with environment and
utilization conditions. A contactor can be classied depending on its own
clearance and creepage distances in the insulation classes A, B, C, D which
correspond to different insulation voltage values.
The insulation class C is applicable to most of the industrial applications.
Equipment described in this catalogue correspond to insulation class C.
Intermittent duty
Duty in which the main contacts of a contactor remain closed for periods of time
insufcient to allow the contactor to reach thermal equilibrium, the current-
carrying periods being separated by off-load periods of sufcient duration to
restore equality of temperature with the cooling medium.
Mounting positions
Stated by the manufacturer. Please note restrictions when applicable.
On-load factor
Ratio of the current ow time to the total time of the cycle x 100.
Plugging
Stopping or reversing a motor quickly by interchanging two supply leads whilst
the motor is running.
Rated breaking capacity; Rated making capacity
Value of r.m.s current a contactor can break or make at a xed voltage value,
within the conditions specied by the standards, depending on the utilization
category.
General information
Technical terms and denitions
Rated control circuit voltage Uc
Control voltage value for which the control circuit of the unit is sized.
Rated insulation voltage Ui
Voltage value which designates the unit and to which dielectric tests, clearance
and creepage distances are referred.
Rated impulse withstand voltage Uimp
The highest peak value of an impulse voltage of prescribed form 1.2/50, which
does not cause breakdown under specied conditions of test.
Rated operating current Ie
Current value stated by the manufacturer and taking into account the rated
operating voltage Ue, the rated frequency, the rated duty, the utilization category,
the electrical contact life and the type of the protective enclosure.
Rated operating voltage Ue
Voltage value to which utilization characteristics of the contactor are referred, i.e.
phase to phase voltage in 3 phase circuits.
Conventional thermal current Ith
Value of current the contactor can withstand with poles in closed position, in
free air for an eight hour duty, without the temperature rise of its various parts
exceeding the limits specied by the standards.
Resistance to shocks
Requirements applicable for instance to vehicles, crane operation or switchgear
slide-in module systems.
At the quoted permissible «g» values, contactors must not undergo a change in
switching state and O/L relays must not trip.
Resistance to vibrations
Requirements applicable to all the vehicles, vessels and other similar transport
systems. At the quoted amplitude and vibration frequency values, the unit must
be capable to achieve the required duty.
Short-circuit protection coordination
Achieved by using back-up protection devices such as circuit-breakers, H.R.C.
fuses or standard fuses.
Co-ordination types a, b, c are dened in IEC 292-1 publication, VDE 0660, NFC
63-650 standards. Co-ordination types "1" and "2" are dened in IEC 947-4-1.
• Type 1 co-ordination
There has been no discharge of parts beyond the enclosure. Damage to the
contactor and the overload relay is acceptable.
• Type 2 co-ordination
No damage to the overload relay or other parts has occurred, except that welding
of contactor or starter contacts is permitted, if they are easily separated.
Switching frequency
Number of operating cycles per hour.
Time
• Closing time
Time between energization of the coil until the moment the contacts of the rst
current path to be closed actually close.
• Opening time
Time from the beginning of state causing breaking until the moment when the
contacts of the last current path to be opened are open.
• Minimal operation time
Shortest control duration to ensure complete closing or opening of a contactor.
• Short time current permissible
Value of current which the contactor can withstand in closed position for a short
time period and within specied conditions.
• Time constant
Ratio of inductance to the resistance : L/R = mH/Ohm = ms.
Low Voltage Products & Systems 1.9
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General information
IEC Standards, utilization categories
Standards
• IEC standards 158-1: “Contactors” and series IEC 292 :
“Motor-starters” have been revised and replaced by the new IEC 947-4-1 (1990-05): “Contactors and Motor-starters” referring to IEC 947-1 (1988): “General rules”
The new standards will constitute the basis of the future European and National standards, not yet revised.
Therefore the ratings indicated in this catalog are established according to the former and the future standards.
• Main changes and additions in the new standards are:
• Revision and extension of the utilization categories (see hereafter)
• Replacement of the coordination classes types a, b, c by new types: “1” (approximately equivalent to former class “a”) and “2” (approximately equivalent to former
class “c”) with additional requirements.
• Classication of the thermal overload relays in tripping classes: 10 A; 10; 20 and 30 depending on their tripping times, at 1.5 and 7.2 times their setting current, in order
to cover motor applications depending on their starting times. Class 10 A is adapted for motors according to IEC 34-1.
• Introduction of tests to verify the connecting capability and the mechanical strength of terminals.
Utilization categories
A contactor duty is characterized by the utilization category plus indication of the rated operating voltage and the rated operating current (see at Rated …), or the motor
characteristics.
Utilization categories for contactors according to IEC 947-4-1
Alternating current: AC-1 Non-inductive or slightly inductive loads, resistance furnaces. Power factor 0.7 - 0.8 (slightly inductive).
AC-2 Slip-ring motors: starting, switching-off.
AC-3 Squirrel-cage motors: starting, switching-off motors during running. Power factor 0.4 - 0.5 (AC-3).
AC-4 Squirrel-cage motors: starting, plugging, inching.
AC-5a Switching of electric discharge lamp controls.
AC-5b Switching of incandescent lamps.
AC-6a Switching of transformers.
AC-6b Switching of capacitor banks
AC-8a Hermetic refrigerant compressor motor control with manual resetting of overload releases
AC-8b Hermetic refrigerant compressor motor control with automatic resetting of overload releases.
Direct current: DC-1 Non-inductive or slightly inductive loads, resistance furnaces.
DC-3 Shunt motors: starting, plugging, inching. Dynamic breaking of d.c. motors.
DC-5 Series motors: starting, plugging, inching. Dynamic breaking of d.c. motors.
DC-6 Switching of incandescent lamps
Alternating current: AC-12 Control of resistive loads and solid state loads with isolation by opto couplers.
AC-13 Control of solid state loads with transformer isolation.
AC-14 Control of small electromagnetic loads (≤ 72 VA).
AC-15 Control of electromagnetic loads (> 72 VA).
Direct current: DC-12 Control of resistive loads and solid state loads with isolation by opto couplers.
DC-13 Control of electromagnets.
DC-14 Control of electromagnetic loads having economy resistors in circuit.
Utilization categories for contactor relays according to IEC 947-5-1
Utilization categories AC-1, AC-2, AC-3, AC-4 and DC-1, DC-3, DC-5 are maintained with slightly more severe tests.
Other categories have been added in order to standardize specic applications. In fact some contactor applications and the specic criteria characterizing the types of
load controlled can modify the recommended utilization characteristics. These major applications are, for example :
Switching of capacitor banks
This application is characterized by high current peaks when switching-on the contactor and presence of harmonic currents on uninterrupted duty. For this application,
IEC 947-4-1 has dened an utilization category AC-6b. Practical ratings have to be dened according to tests or, in absence of tests, by a calculation indicated in IEC
947-4-1.
Switching of transformers
This application is characterized by high current peaks on contactor closing due to magnetization phenomena. The corresponding utilization category according to IEC
947-4-1 is AC-6a. Ratings are derived from test-values for AC-3 or AC-4 according to formula given in IEC 947-4-1.
Switching of lighting circuits
The current peaks on contactor closing and power factor vary depending on the type of lamps, the switching method used and if compensation systems are tted or
not.
IEC 947-4-1 contains two standard utilization categories
AC-5a for switching of the electric discharge lamps.
AC-5b for switching of incandescent lamp.
1.10 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General information
Motor ratings
Horsepower to full-load Amperes for AC induction motors
Horse-
power
(hp)
Full Load Amperes (FLA)
110…120 v ac 200 v ac 208 v ac 220…240 v ac 380…415 v ac 440…480 v ac 550…600 v ac
Single
phase
Three
phase
Single
phase
Three
phase
Single
phase
Three
phase
Single
phase
Three
phase
Single
phase
Three
phase
Single
phase
Three
phase
Single
phase
Three
phase
1/10 3.0 - - - - - 1.5 - 1.0 - - - - -
1/8 3.8 - - - - - 1.9 - 1.2 - - - - -
1/6 4.4 - 2.5 - 2.4 - 2.2 - 1.4 - - - - -
1/4 5.8 - 3.3 - 3.2 - 2.9 - 1.8 - - - - -
1/3 7.2 - 4.1 - 4.0 - 3.6 - 2.3 - - - - -
1/2 9.8 4.4 5.6 2.5 5.4 2.4 4.9 2.2 3.2 1.3 2.5 1.1 2.0 0.9
3/4 13.8 6.4 7.9 3.7 7.6 3.5 6.9 3.2 4.5 1.8 3.5 1.6 2.8 1.3
116.0 8.4 9.2 4.8 8.8 4.6 8.0 4.2 5.1 2.3 4.0 2.1 3.2 1.7
1-1/2 20.0 12.0 11.5 6.9 11.0 6.6 10.0 6.0 6.4 3.3 5.0 3.0 4.0 2.4
2 24.0 13.6 13.8 7.8 13.2 7.5 12.0 6.8 7.7 4.3 6.0 3.4 4.8 2.7
3 34.0 19.2 19.6 11.0 18.7 10.6 17.0 9.6 10.9 6.1 8.5 4.8 6.8 3.9
5 56.0 30.4 32.2 17.5 30.8 16.7 28.0 15.2 17.9 9.7 14.0 7.6 11.2 6.1
7-1/2 80.0 44.0 45.0 25.3 44.0 24.2 40.0 22.0 27.0 14.0 21.0 11.0 16.0 9.0
10 100.0 56.0 57.5 32.2 55.0 30.8 50.0 28.0 33.0 18.0 26.0 14.0 20.0 11.0
15 135.0 84.0 - 48.3 - 46.2 68.0 42.0 44.0 27.0 34.0 21.0 27.0 17.0
20 - 108.0 - 62.1 - 59.4 88.0 54.0 56.0 34.0 44.0 27.0 35.0 22.0
25 - 136.0 - 78.2 - 74.8 110.0 68.0 70.0 44.0 55.0 34.0 44.0 27.0
30 - 160.0 - 92.0 - 88.0 136.0 80.0 87.0 51.0 68.0 40.0 54.0 32.0
40 - 208.0 - 120.0 - 114.0 176.0 104.0 112.0 66.0 88.0 52.0 70.0 41.0
50 - 260.0 - 150.0 - 143.0 216.0 130.0 139.0 83.0 108.0 65.0 86.0 52.0
60 - - - 177.0 - 169.0 - 154.0 - 103.0 - 77.0 - 62.0
75 - - - 221.0 - 211.0 - 192.0 - 128.0 - 96.0 - 77.0
100 - - - 285.0 - 273.0 - 248.0 - 165.0 - 124.0 - 99.0
125 - - - 359.0 - 343.0 - 312.0 - 208.0 - 156.0 - 125.0
150 - - - 414.0 - 396.0 - 360.0 - 240.0 - 180.0 - 144.0
200 - - - 552.0 - 528.0 - 480.0 - 320.0 - 240.0 - 192.0
250 - - - - - - - 604.0 - 403.0 - 302.0 - 242.0
300 - - - - - - - 722.0 - 482.0 - 361.0 - 289.0
350 - - - - - - - 828.0 - 560.0 - 414.0 - 336.0
400 - - - - - - - 954.0 - 636.0 - 477.0 - 382.0
450 - - - - - - - 1030.0 - - 515.0 - 412.0
500 - - - - - - - 1180.0 - 786.0 - 590.0 - 472.0
Full-load motor-running currents in Amperes corresponding to various AC horsepower ratings as published in Table 50.1 of UL 508.
Low Voltage Products & Systems 1.11
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General information
Pilot duty ratings and overload trip classes
Pilot duty ratings for AC control circuit contacts
Contact
rating
designation
Continuous
thermal, test
current (A)
Maximum current, 50/60 Hz (A)
120 v ac 240 v ac 480 v ac 600 v ac Volt-amperes
Make Break Make Break Make Break Make Break Make Break
A150 10 60 6.00 - - - - - - 7200 720
A300 10 60 6.00 30 3.00 - - - - 7200 720
A600 10 60 6.00 30 3.00 15 1.50 12 1.20 7200 720
B150 5 30 3.00 - - - - - - 3600 360
B300 5 30 3.00 15 1.50 - - - - 3600 360
B600 5 30 3.00 15 1.50 7.5 0.75 6 0.60 3600 360
C150 2.5 15 1.5 - - - - - - 1800 180
C300 2.5 15 1.5 7.5 0.75 - - - - 1800 180
C600 2.5 15 1.5 7.5 0.75 3.75 0.375 3.00 0.30 1800 180
D150 1.0 3.60 0.60 - - - - - - 432 72
D300 1.0 3.60 0.60 1.80 0.30 - - - - 432 72
E150 0.5 1.80 0.30 - - - - - - 216 36
Mechanical switching ratings and test values as published in Table 1-4-1 of NEMA ICS 5-2000 (R2005, R2010)
Pilot duty ratings for DC control circuit contacts
Contact
rating
designation
Continuous
thermal, test
current (A)
Maximum current, 50/60 Hz (A)
120 v dc 250 v dc 301 to 600 v dc Volt-amperes
Make / Break Make / Break Make / Break Make / Break
N150 10 2.2 - - 275
N300 10 2.2 1.1 - 275
N600 10 2.2 1.1 0.40 275
P150 5.0 1.1 - - 138
P300 5.0 1.1 0.55 - 138
P600 5.0 1.1 0.55 0.20 138
Q150 2.5 0.55 - - 69
Q300 2.5 0.55 0.27 - 69
Q600 2.5 0.55 0.27 0.10 69
R150 1.0 0.22 - - 28
R300 1.0 0.22 0.11 - 28
Mechanical switching ratings and test values as published in Table 1-4-1 of NEMA ICS 5-2000 (R2005, R2010)
Overload trip classes
Trip class Tripping time Tp (seconds)
10A 2 < Tp ≤ 10
10 4 < Tp ≤ 10
20 6 < Tp ≤ 20
30 9 < Tp ≤ 30
Trip classes as published in Table 2 of UL 60947-4-1A.
Pilot duty rating explanation
A - 600
Max. thermal
current
Max. voltage
1.12 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General information
AF Series contactors
AF09 - AF110
Application
AF series contactors (9...110) are primarily used for controlling single and three phase
motors and switching power circuits up to 600V AC, 240V DC
Description
AF series contactors are provided in either three or four power pole congurations
with a variety of accessories including auxiliary contacts, close coupling adaptors,
interlocks, and busbars.
Control circuit types
AF series contactor coils are designed to utilize both AC (50/60 Hz) and DC control
circuit inputs ranging from 12…500V. Surge suppression is included.
Contactor types
3 NO pole: AF09…AF110
4 NO pole: AF09…AF75
2 NO / 2 NC pole: AF09…AF75
Mounting hole pattern identical from AF09…
AF38. Only three different patterns for contactors
AF09…AF110
Quick DIN-rail mount & dismount (no tools
required AF09…AF38)
35 x 7.5mm for AF09…AF38
35 x 15mm for AF09…AF75
75mm for AF45…AF110
Integral surge suppression AF09…AF110
Actuator for side-mount accessories
Mechanical interlocks with no additional width for
AF09…AF38
Contoured sides for easy access to panel
mounting holes
Terminals on AF09…AF110 contactors are deliv-
ered in open position with captive screws (screws
of unused terminals must be tightened)
IP20 degree protection according to IEC/EN
60947-1; protection from live parts according to
VDE0106 Part. 100.
Detachable coil terminals (AF09…AF38)
Can be pre-wired prior to installation
Can easily be rotated from top (standard)
to bottom
Front-mount coil termination available
Stops for attaching front-mount accessories
Function markers included as standard on
AF09...AF38; available as accessory
AF50…AF110
Clear indication of coil voltages and frequen-
cies
Terminal screws:
Posidrive (+,-) No 2 AF09…AF75
M8 hex threaded socket screw for
AF95…AF110
Catalog number explanation
For reference only – not all combinations will produce
valid catalog numbers
AF09 - 30 -10 - 13
Contactor series &
frame size
Power pole configuration
• 30 = 3 NO
• 40 = 4 NO
• 22 = 2 NO / 2 NC
Coil voltage code
(see product selection pages)
Auxiliary pole configuration
• 00 - No auxiliary provided
• 10 = 1 NO
• 01 = 1 NC
• 11 = 1 NO / 1 NC
• 22 = 2 NO / 2 NC
Low Voltage Products & Systems 1.13
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
1 L1 3 L2
A1 A2
5 L3
UL
General information
AF Series contactors
AF145 - AF2650
Application
AF series contactors (145...2650) are primarily used for controlling single and three
phase motors and switching power circuits up to 1000V AC, 600V DC.
Description
AF series contactors are provided in a three power pole conguration
with a variety of accessories including auxiliary contacts, close coupling adaptors,
interlocks, and busbars.
Control circuit types
AF series contactor coils are designed to utilize both AC (50/60 Hz) and DC control
circuit inputs ranging from 24…500V. Surge suppression is included.
Contactor types
3 NO pole: AF145…AF2650
Only 5 different mounting hole patterns for
contactors AF145…AF2650
Integral surge suppression AF145…AF2650
Mechanical interlocks for horizontal and
vertical assembly
Clear indication of contactor ratings and
approvals on contactor face
Wide variety of bus kits available for revers-
ing and wye-delta congurations, as well
as close couplers for MCCB and fusible
disconnects
Assembly screws on contactor face allow
for replacement coils, contacts, and arc
chutes to be swapped without removing the
contactor from the installation or detaching
any conductors
Clear indication of coil voltages and fre-
quencies
Integral 24V DC PLC interface AF400…
AF2650
AF2650 - 30 -11 - 70
Contactor series &
frame size
Power pole configuration
• 30 = 3 NO
Coil voltage code
(see product selection pages)
Auxiliary pole configuration
• 00 - No auxiliary provided
• 11 = 1 NO / 1 NC
• 22 = 2 NO / 2 NC
Catalog number explanation
For reference only – not all combinations will produce
valid catalog numbers
1.14 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
AF non-reversing, 3-pole
For applications up to 1150 hp, 900 kW
Electronic AC/DC operated coils
Electrical ratings 1Non-reversing Electrical ratings 12 Mechanically interlocked Reversing
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07 Standard
auxiliary
contacts
3Catalog
number
UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07 Standard
auxiliary
contacts Catalog
number
3
Standard
auxiliary
contacts Catalog
number
3
Rated operational cur-
rent Ie, AC-1, AC-3 (A)
Rated operational power Pe, AC-3,
55°C (kW) 2
AC general
purpose
ratings (A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase,
50/60 Hz (hp)
AC general
purpose
ratings (A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines,
three phase, 50/60 Hz (hp)
AC-1
40°C
AC-3
55°C 2
220…
240V
380...
400V 690V 600V 200...
208V
220...
240V
440…
480V
550…
600V NO NC 600V 200...
208V
220...
240V
440...
480V
550...
600V NO NC NO NC
25 9 2.2 4 5.5 25 9 2 2 5 7.5 1- AF09-30-10-Δ 25 9 2 2 5 7.5 2 2 AF09M-30-22-Δ 2 2 AF09R-30-22-Δ
-1AF09-30-01-Δ - - - - - - - - - - - -
28 12 3 5.5 7.5 28 11 3 3 7.5 10 1- AF12-30-10-Δ 28 11 3 3 7.5 10 2 2 AF12M-30-22-Δ 2 2 AF12R-30-22-Δ
-1AF12-30-01-Δ - - - - - - - - - - - -
30 18 4 7.5 9 30 17 5 5 10 15 1- AF16-30-10-Δ 30 17 5 5 10 15 2 2 AF16M-30-22-Δ 2 2 AF16R-30-22-Δ
-1AF16-30-01-Δ - - - - - - - - - - - -
45 26 6.5 11 15 45 24.2 7.5 7.5 15 20 - - AF26-30-00-Δ 45 24.2 7.5 7.5 15 20 - 2 AF26M-30-02-Δ - 2 AF26R-30-02-Δ
50 32 9 15 18.5 50 30.8 10 10 20 25 - - AF30-30-00-Δ 50 30.8 10 10 20 25 - 2 AF30M-30-02-Δ - 2 AF30R-30-02-Δ
50 38 11 18.5 22 50 - - - - - - - AF38-30-00-Δ - - - - - - - - - - - -
100 50 15 22 30 80 54 15 20 40 50 1 1 AF50-30-11-Δ 80 54 15 20 40 50 2 2 AF50M-30-11-Δ 2 2 AF50R-30-11-Δ
115 65 18.5 30 37 90 68 20 25 50 60 1 1 AF63-30-11-Δ 90 68 20 25 50 60 2 2 AF63M-30-11-Δ 2 2 AF63R-30-11-Δ
125 75 22 37 40 105 80 25 30 60 75 1 1 AF75-30-11-Δ 105 80 25 30 60 75 2 2 AF75M-30-11-Δ 2 2 AF75R-30-11-Δ
145 96 25 45 55 150 88 30 30 60 75 1 1 AF95-30-11-Δ 150 88 30 30 60 75 2 2 AF95M-30-11-Δ 2 2 AF95R-30-11-Δ
160 110 30 55 75 150 104 30 40 75 100 1 1 AF110-30-11-Δ 150 104 30 40 75 100 2 2 AF110M-30-11-Δ 2 2 AF110R-30-11-Δ
250 145 45 75 110 230 130 40 50 100 125 1 1 AF145-30-11-Δ 230 130 40 50 100 125 2 2 AF145M-30-11-Δ 2 2 AF145R-30-11-Δ
275 185 55 90 132 250 156 50 60 125 150 1 1 AF185-30-11-Δ 250 156 50 60 125 150 2 2 AF185M-30-11-Δ 2 2 AF185R-30-11-Δ
350 210 59 110 160 300 192 60 75 150 200 1 1 AF210-30-11-Δ 300 192 60 75 150 200 2 2 AF210M-30-11-Δ 2 2 AF210R-30-11-Δ
400 260 80 140 200 350 248 75 100 200 250 1 1 AF260-30-11-Δ 350 248 75 100 200 250 2 2 AF260M-30-11-Δ 2 2 AF260R-30-11-Δ
500 305 90 160 250 400 302 100 100 250 300 1 1 AF300-30-11-Δ 400 302 100 100 250 300 2 2 AF300M-30-11-Δ 2 2 AF300R-30-11-Δ
600 400 110 200 315 550 414 125 150 350 400 1 1 AF400-30-11-Δ 550 414 125 150 350 400 2 2 AF400M-30-11-Δ 2 2 AF400R-30-11-Δ
700 460 132 250 355 650 480 150 200 400 500 1 1 AF460-30-11-Δ 650 480 150 200 400 500 2 2 AF460M-30-11-Δ 2 2 AF460R-30-11-Δ
800 580 160 315 500 750 604 250 250 500 600 1 1 AF580-30-11-Δ 750 604 250 250 500 600 2 2 AF580M-30-11-Δ 2 2 AF580R-30-11-Δ
1050 750 220 400 600 900 722 250 300 600 700 1 1 AF750-30-11-Δ 900 722 250 300 600 700 2 2 AF750M-30-11-Δ 2 2 AF750R-30-11-Δ
1260 - - - - 1210 - - - - - 1 1 AF1250-30-11-Δ - - - - - - - - - - - -
1350 860 257 475 750 1350 954 - 400 800 1000 1 1 AF1350-30-11-Δ - - - - - - - - - - - -
1650 1050 315 560 900 1650 1050 - 450 900 1150 1 1 AF1650-30-11-Δ - - - - - - - - - - - -
2050 - - - - 2100 - - - - - 1 1 AF2050-30-11-Δ - - - - - - - - - - - -
2650 - - - - 2700 - - - - - 1 1 AF2650-30-11-Δ - - - - - - - - - - - -
Coil voltage selection chart (Δ)
Rated control circuit
voltage Uc 4
AF09…
AF38
AF50…
AF300
AF400…
AF750 AF1250 AF1350…
AF2650
20...60V DC 11 72 - - -
24...60V AC 11 ----
24...60V DC - - 68 68 -
48...130V AC/DC 12 69 69 69 -
100...250V AC/DC 13 70 70 70 70
250...500V AC/DC 14 - 71 - -
Example(s):
24V DC input voltage: AF16-30-10-11
120V AC input voltage: AF300-30-11-70
1 For selection purposes; for complete electrical ratings, see Technical Data.
2 AF09... AF38 at 60°C.
3 Auxiliary contacts integral for AF09…AF16; all others side-mount.
4 AC coil input voltage(s) at 50/60 Hz unless specied.
Control inputs
AF400...AF2650 are equipped with integral low voltage inputs, allowing for direct
PLC control:
AF09…AF16 AF95…AF110 AF210…AF300 AF1350…AF2650 AF09R…AF16R AF95R…AF110R
R
Low Voltage Products & Systems 1.15
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Electrical ratings 1Non-reversing Electrical ratings 12 Mechanically interlocked Reversing
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07 Standard
auxiliary
contacts
3Catalog
number
UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07 Standard
auxiliary
contacts Catalog
number
3
Standard
auxiliary
contacts Catalog
number
3
Rated operational cur-
rent Ie, AC-1, AC-3 (A)
Rated operational power Pe, AC-3,
55°C (kW) 2
AC general
purpose
ratings (A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase,
50/60 Hz (hp)
AC general
purpose
ratings (A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines,
three phase, 50/60 Hz (hp)
AC-1
40°C
AC-3
55°C 2
220…
240V
380...
400V 690V 600V 200...
208V
220...
240V
440…
480V
550…
600V NO NC 600V 200...
208V
220...
240V
440...
480V
550...
600V NO NC NO NC
25 9 2.2 4 5.5 25 9 2 2 5 7.5 1- AF09-30-10-Δ 25 9 2 2 5 7.5 2 2 AF09M-30-22-Δ 2 2 AF09R-30-22-Δ
-1AF09-30-01-Δ - - - - - - - - - - - -
28 12 3 5.5 7.5 28 11 3 3 7.5 10 1- AF12-30-10-Δ 28 11 3 3 7.5 10 2 2 AF12M-30-22-Δ 2 2 AF12R-30-22-Δ
-1AF12-30-01-Δ - - - - - - - - - - - -
30 18 4 7.5 9 30 17 5 5 10 15 1- AF16-30-10-Δ 30 17 5 5 10 15 2 2 AF16M-30-22-Δ 2 2 AF16R-30-22-Δ
-1AF16-30-01-Δ - - - - - - - - - - - -
45 26 6.5 11 15 45 24.2 7.5 7.5 15 20 - - AF26-30-00-Δ 45 24.2 7.5 7.5 15 20 - 2 AF26M-30-02-Δ - 2 AF26R-30-02-Δ
50 32 9 15 18.5 50 30.8 10 10 20 25 - - AF30-30-00-Δ 50 30.8 10 10 20 25 - 2 AF30M-30-02-Δ - 2 AF30R-30-02-Δ
50 38 11 18.5 22 50 - - - - - - - AF38-30-00-Δ - - - - - - - - - - - -
100 50 15 22 30 80 54 15 20 40 50 1 1 AF50-30-11-Δ 80 54 15 20 40 50 2 2 AF50M-30-11-Δ 2 2 AF50R-30-11-Δ
115 65 18.5 30 37 90 68 20 25 50 60 1 1 AF63-30-11-Δ 90 68 20 25 50 60 2 2 AF63M-30-11-Δ 2 2 AF63R-30-11-Δ
125 75 22 37 40 105 80 25 30 60 75 1 1 AF75-30-11-Δ 105 80 25 30 60 75 2 2 AF75M-30-11-Δ 2 2 AF75R-30-11-Δ
145 96 25 45 55 150 88 30 30 60 75 1 1 AF95-30-11-Δ 150 88 30 30 60 75 2 2 AF95M-30-11-Δ 2 2 AF95R-30-11-Δ
160 110 30 55 75 150 104 30 40 75 100 1 1 AF110-30-11-Δ 150 104 30 40 75 100 2 2 AF110M-30-11-Δ 2 2 AF110R-30-11-Δ
250 145 45 75 110 230 130 40 50 100 125 1 1 AF145-30-11-Δ 230 130 40 50 100 125 2 2 AF145M-30-11-Δ 2 2 AF145R-30-11-Δ
275 185 55 90 132 250 156 50 60 125 150 1 1 AF185-30-11-Δ 250 156 50 60 125 150 2 2 AF185M-30-11-Δ 2 2 AF185R-30-11-Δ
350 210 59 110 160 300 192 60 75 150 200 1 1 AF210-30-11-Δ 300 192 60 75 150 200 2 2 AF210M-30-11-Δ 2 2 AF210R-30-11-Δ
400 260 80 140 200 350 248 75 100 200 250 1 1 AF260-30-11-Δ 350 248 75 100 200 250 2 2 AF260M-30-11-Δ 2 2 AF260R-30-11-Δ
500 305 90 160 250 400 302 100 100 250 300 1 1 AF300-30-11-Δ 400 302 100 100 250 300 2 2 AF300M-30-11-Δ 2 2 AF300R-30-11-Δ
600 400 110 200 315 550 414 125 150 350 400 1 1 AF400-30-11-Δ 550 414 125 150 350 400 2 2 AF400M-30-11-Δ 2 2 AF400R-30-11-Δ
700 460 132 250 355 650 480 150 200 400 500 1 1 AF460-30-11-Δ 650 480 150 200 400 500 2 2 AF460M-30-11-Δ 2 2 AF460R-30-11-Δ
800 580 160 315 500 750 604 250 250 500 600 1 1 AF580-30-11-Δ 750 604 250 250 500 600 2 2 AF580M-30-11-Δ 2 2 AF580R-30-11-Δ
1050 750 220 400 600 900 722 250 300 600 700 1 1 AF750-30-11-Δ 900 722 250 300 600 700 2 2 AF750M-30-11-Δ 2 2 AF750R-30-11-Δ
1260 - - - - 1210 - - - - - 1 1 AF1250-30-11-Δ - - - - - - - - - - - -
1350 860 257 475 750 1350 954 - 400 800 1000 1 1 AF1350-30-11-Δ - - - - - - - - - - - -
1650 1050 315 560 900 1650 1050 - 450 900 1150 1 1 AF1650-30-11-Δ - - - - - - - - - - - -
2050 - - - - 2100 - - - - - 1 1 AF2050-30-11-Δ - - - - - - - - - - - -
2650 - - - - 2700 - - - - - 1 1 AF2650-30-11-Δ - - - - - - - - - - - -
AF mechanically interlocked, reversing, 3-pole
For applications up to 700 hp, 600 kW
Electronic AC/DC operated coils
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 4AF09…AF30 AF50…AF300 AF400…AF750
20...60V DC 11 72 -
24...60V AC 11 - -
24...60V DC - - 68
48...130V AC/DC 12 69 69
100...250V AC/DC 13 70 70
250...500V AC/DC 14 - 71
Example(s):
24V DC input voltage: AF16M-30-22-11
120V AC input voltage: AF300R-30-11-70
1 For selection purposes; for complete electrical ratings, see Technical Data.
2 For ratings according to IEC/EN 60947-4-1, refer to AF non-reversing selection table or Technical Data.
3 AF09R(M)…AF30R(M) assembled using connection clips, AF50R(M)…AF750R(M) mounted on common baseplate.
4 AC coil input voltage(s) at 50/60 Hz unless specied.
AF09…AF16 AF95…AF110 AF210…AF300 AF1350…AF2650 AF09R…AF16R AF95R…AF110R
Reversing vs. mechanically interlocked
Full voltage reversing contactors are pre-assembled using two (2) contactors, a
mechanical interlock, an electrical interlock, and reversing busbars. Mechanically
interlocked contactors are offered less the reversing bus.
R
1.16 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
AFZ non-reversing, 3-pole
For applications up to 25 hp, 22 kW
Low power consumption, electronic AC/DC operated coils
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 3 AF09Z… AF38Z
12…20V DC 20
24...60V AC 21
20...60V DC 21
48...130V AC/DC 22
100...250V AC/DC 23
Example(s):
24V DC input voltage: AF16Z-30-10-21
120V AC input voltage: AF30Z-30-00-23
Electrical ratings 1Non-reversing Electrical ratings 12 Mechanically interlocked Reversing
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary
contacts 2Catalog
number
UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary contacts Catalog
number
3
Standard
auxiliary
contacts
Catalog
number
3
Rated operational current
Ie AC-1, AC-3 (A)
Rated operational power Pe, AC-3,
60°C (kW)
AC general
purpose
ratings (A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase,
50/60 Hz (hp)
AC general
purpose
ratings
(A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase, 50/60 Hz
(hp)
AC-1,
40°C
AC-3,
60°C
220…
240V
380…
400V 690V 600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC 600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC NO NC
25 9 2.2 4 5.5 25 9 2 2 5 7.5 1- AF09Z-30-10-Δ 25 9 2 2 5 7.5 2 2 AF09MZ-30-22-Δ 2 2 AF09RZ-30-22-Δ
-1AF09Z-30-01-Δ - - - - - - - - - - - -
28 12 3 5.5 7.5 28 11 3 3 7.5 10 1- AF12Z-30-10-Δ 28 11 3 3 7.5 10 2 2 AF12MZ-30-22-Δ 2 2 AF12RZ-30-22-Δ
-1AF12Z-30-01-Δ - - - - - - - - - - - -
30 18 4 7.5 9 30 17 5 5 10 15 1- AF16Z-30-10-Δ 30 17 5 5 10 15 2 2 AF16MZ-30-22-Δ 2 2 AF16RZ-30-22-Δ
-1AF16Z-30-01-Δ - - - - - - - - - - - -
45 26 6.5 11 15 45 24.2 7.5 7.5 15 20 - - AF26Z-30-00-Δ 45 24.2 7.5 7.5 15 20 - 2 AF26MZ-30-02-Δ - 2 AF26RZ-30-02-Δ
50 32 9 15 18.5 50 30.8 10 10 20 25 - - AF30Z-30-00-Δ 50 30.8 10 10 20 25 - 2 AF30MZ-30-02-Δ - 2 AF30RZ-30-02-Δ
50 38 11 18.5 22 50 - - - - - - - AF38Z-30-00-Δ - - - - - - - - - - - -
1 For selection purposes, for complete electrical ratings, see Technical Data
2 Auxiliary contacts integral for AF09Z... AF16Z
3 AC coil input voltage(s) at 50/60 Hz unless specied.
AF09Z... AF16Z AF26Z... AF38Z
Low Voltage Products & Systems 1.17
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
AFZ mechanically interlocked, reversing, 3-pole
For applications up to 25 hp, 18.5 kW
Low power consumption, electronic AC/DC operated coils
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 4 AF09Z… AF38Z
12…20V DC 20
24...60V AC 21
20...60V DC 21
48...130V AC/DC 22
100...250V AC/DC 23
Example(s):
24V DC input voltage: AF16ZM-30-22-21
120V AC input voltage: AF30ZR-30-02-23
Electrical ratings 1Non-reversing Electrical ratings 12 Mechanically interlocked Reversing
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary
contacts 2Catalog
number
UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary contacts Catalog
number
3
Standard
auxiliary
contacts
Catalog
number
3
Rated operational current
Ie AC-1, AC-3 (A)
Rated operational power Pe, AC-3,
60°C (kW)
AC general
purpose
ratings (A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase,
50/60 Hz (hp)
AC general
purpose
ratings
(A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase, 50/60 Hz
(hp)
AC-1,
40°C
AC-3,
60°C
220…
240V
380…
400V 690V 600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC 600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC NO NC
25 9 2.2 4 5.5 25 9 2 2 5 7.5 1- AF09Z-30-10-Δ 25 9 2 2 5 7.5 2 2 AF09MZ-30-22-Δ 2 2 AF09RZ-30-22-Δ
-1AF09Z-30-01-Δ - - - - - - - - - - - -
28 12 3 5.5 7.5 28 11 3 3 7.5 10 1- AF12Z-30-10-Δ 28 11 3 3 7.5 10 2 2 AF12MZ-30-22-Δ 2 2 AF12RZ-30-22-Δ
-1AF12Z-30-01-Δ - - - - - - - - - - - -
30 18 4 7.5 9 30 17 5 5 10 15 1- AF16Z-30-10-Δ 30 17 5 5 10 15 2 2 AF16MZ-30-22-Δ 2 2 AF16RZ-30-22-Δ
-1AF16Z-30-01-Δ - - - - - - - - - - - -
45 26 6.5 11 15 45 24.2 7.5 7.5 15 20 - - AF26Z-30-00-Δ 45 24.2 7.5 7.5 15 20 - 2 AF26MZ-30-02-Δ - 2 AF26RZ-30-02-Δ
50 32 9 15 18.5 50 30.8 10 10 20 25 - - AF30Z-30-00-Δ 50 30.8 10 10 20 25 - 2 AF30MZ-30-02-Δ - 2 AF30RZ-30-02-Δ
50 38 11 18.5 22 50 - - - - - - - AF38Z-30-00-Δ - - - - - - - - - - - -
AF09ZR... AF16ZR
Reversing vs. mechanically interlocked
Full voltage reversing contactors are pre-assembled using two (2) contactors, a
mechanical interlock, an electrical interlock, and reversing busbars. Mechanically
interlocked contactors are offered less the reversing bus.
1 For selection purposes, for complete electrical ratings, see Technical Data
2 For ratings according to IEC/EN 60947-4-1, refer to AFZ non-reversing selection table or Technical Data.
3 AF09ZR(M)…AF30ZR(M) assembled using connection clips.
4 AC coil input voltage(s) at 50/60 Hz unless specied.
1.18 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
A non-reversing, 3-pole
For applications up to 300 hp, 250 kW
AC operated coils
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 3A9…A300
24V AC 81
48V AC 83
110…120V AC, 60 Hz 84
230…240V AC, 60 Hz 80
480V AC, 60 Hz 51
600V AC, 60 Hz 55
Example(s):
24V AC input voltage: A16-30-10-81
120V AC input voltage: A300-30-11-84
Electrical ratings 1Non-reversing Electrical ratings 12 Mechanically interlocked Reversing
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary
contacts 2Catalog
number
UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary contacts Catalog
number
3
Standard
auxiliary
contacts
Catalog
number
3
Rated operational
current
Ie AC-1, AC-3 (A)
Rated operational power Pe, AC-3,
55°C (kW)
AC general
purpose
ratings
(A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase,
50/60 Hz (hp)
AC general
purpose rat-
ings (A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase, 50/60
Hz (hp)
AC-1,
40°C
AC-3,
55°C
220…
240V
380…
400V 690V 600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC 600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC NO NC
25 9 2.2 4 5.5 21 9 2 2 5 7.5 1-A9-30-10-Δ 21 9 2 2 5 7.5 2 2 A9M-30-10-Δ 2 2 A9R-30-10-Δ
-1A9-30-01-Δ - - - - - - - - - - - -
27 12 3 5.5 7.5 25 11 3 3 7.5 10 1-A12-30-10-Δ 25 11 3 3 7.5 10 2 2 A12M-30-10-Δ 2 2 A12R-30-10-Δ
-1A12-30-01-Δ - - - - - - - - - - - -
30 17 4 7.5 9 30 17 5 5 10 15 1-A16-30-10-Δ 30 17 5 5 10 15 2 2 A16M-30-10-Δ 2 2 A16R-30-10-Δ
-1A16-30-01-Δ - - - - - - - - - - - -
45 26 6.5 11 15 40 28 7.5 10 20 25 1-A26-30-10-Δ 40 28 7.5 10 20 25 2 2 A26M-30-10-Δ 2 2 A26R-30-10-Δ
-1A26-30-01-Δ - - - - - - - - - - - -
55 32 9 15 18.5 50 34 10 10 25 30 1- A30-30-10-Δ 50 34 10 10 25 30 2 2 A30M-30-10-Δ 2 2 A30R-30-10-Δ
-1A30-30-01-Δ - - - - - - - - - - -
60 37 11 18.5 22 60 42 10 15 30 40 1- A40-30-10-Δ 60 42 10 15 30 40 2 2 A40M-30-10-Δ 2 2 A40R-30-10-Δ
-1A40-30-01-Δ - - - - - - - - - - -
100 50 15 22 30 80 54 15 20 40 50 1 1 A50-30-11-Δ 80 54 15 20 40 50 2 2 A50M-30-11-Δ 2 2 A50R-30-11-Δ
115 65 18.5 30 37 90 68 20 25 50 60 1 1 A63-30-11-Δ 90 68 20 25 50 60 2 2 A63M-30-11-Δ 2 2 A63R-30-11-Δ
125 75 22 37 40 105 80 25 30 60 75 1 1 A75-30-11-Δ 105 80 25 30 60 75 2 2 A75M-30-11-Δ 2 2 A75R-30-11-Δ
145 96 25 45 55 150 88 30 30 60 75 1 1 A95-30-11-Δ 150 88 30 30 60 75 2 2 A95M-30-11-Δ 2 2 A95R-30-11-Δ
160 110 30 55 75 150 104 30 40 75 100 1 1 A110-30-11-Δ 150 104 30 40 75 100 2 2 A110M-30-11-Δ 2 2 A110R-30-11-Δ
250 145 45 75 110 230 130 40 50 100 125 1 1 A145-30-11-Δ 230 130 40 50 100 125 2 2 A145M-30-11-Δ 2 2 A145R-30-11-Δ
275 185 55 90 132 250 156 50 60 125 150 1 1 A185-30-11-Δ 250 156 50 60 125 150 2 2 A185M-30-11-Δ 2 2 A185R-30-11-Δ
350 210 59 110 160 300 192 60 75 150 200 1 1 A210-30-11-Δ 300 192 60 75 150 200 2 2 A210M-30-11-Δ 2 2 A210R-30-11-Δ
400 260 80 140 200 350 248 75 100 200 250 1 1 A260-30-11-Δ 350 248 75 100 200 250 2 2 A260M-30-11-Δ 2 2 A260R-30-11-Δ
500 305 90 160 250 400 302 100 100 250 300 1 1 A300-30-11-Δ 400 302 100 100 250 300 2 2 A300M-30-11-Δ 2 2 A300R-30-11-Δ
Planned legacy product; recommend AF series contactors. Planned legacy product; recommend AF series contactors.
R
A30... A40 A50... A75 A145... A185
1 For selection purposes, for complete electrical ratings, see Technical Data
2 Auxiliary contacts integral for A9... A40
3 AC coil input voltage(s) at 50/60 Hz unless specied. For additional coil voltages, see page 1.35.
Low Voltage Products & Systems 1.19
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
A mechanically interlocked, reversing, 3-pole
For applications up to 300 hp, 250 kW
AC operated coils
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 4A9…A300
24V AC 81
48V AC 83
110…120V AC, 60 Hz 84
230…240V AC, 60 Hz 80
480V AC, 60 Hz 51
600V AC, 60 Hz 55
Example(s):
24V AC input voltage: A16M-30-10-81
120V AC input voltage: A300R-30-11-84
Electrical ratings 1Non-reversing Electrical ratings 12 Mechanically interlocked Reversing
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary
contacts 2Catalog
number
UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary contacts Catalog
number
3
Standard
auxiliary
contacts
Catalog
number
3
Rated operational
current
Ie AC-1, AC-3 (A)
Rated operational power Pe, AC-3,
55°C (kW)
AC general
purpose
ratings
(A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase,
50/60 Hz (hp)
AC general
purpose rat-
ings (A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase, 50/60
Hz (hp)
AC-1,
40°C
AC-3,
55°C
220…
240V
380…
400V 690V 600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC 600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC NO NC
25 9 2.2 4 5.5 21 9 2 2 5 7.5 1-A9-30-10-Δ 21 9 2 2 5 7.5 2 2 A9M-30-10-Δ 2 2 A9R-30-10-Δ
-1A9-30-01-Δ - - - - - - - - - - - -
27 12 3 5.5 7.5 25 11 3 3 7.5 10 1-A12-30-10-Δ 25 11 3 3 7.5 10 2 2 A12M-30-10-Δ 2 2 A12R-30-10-Δ
-1A12-30-01-Δ - - - - - - - - - - - -
30 17 4 7.5 9 30 17 5 5 10 15 1-A16-30-10-Δ 30 17 5 5 10 15 2 2 A16M-30-10-Δ 2 2 A16R-30-10-Δ
-1A16-30-01-Δ - - - - - - - - - - - -
45 26 6.5 11 15 40 28 7.5 10 20 25 1-A26-30-10-Δ 40 28 7.5 10 20 25 2 2 A26M-30-10-Δ 2 2 A26R-30-10-Δ
-1A26-30-01-Δ - - - - - - - - - - - -
55 32 9 15 18.5 50 34 10 10 25 30 1- A30-30-10-Δ 50 34 10 10 25 30 2 2 A30M-30-10-Δ 2 2 A30R-30-10-Δ
-1A30-30-01-Δ - - - - - - - - - - -
60 37 11 18.5 22 60 42 10 15 30 40 1- A40-30-10-Δ 60 42 10 15 30 40 2 2 A40M-30-10-Δ 2 2 A40R-30-10-Δ
-1A40-30-01-Δ - - - - - - - - - - -
100 50 15 22 30 80 54 15 20 40 50 1 1 A50-30-11-Δ 80 54 15 20 40 50 2 2 A50M-30-11-Δ 2 2 A50R-30-11-Δ
115 65 18.5 30 37 90 68 20 25 50 60 1 1 A63-30-11-Δ 90 68 20 25 50 60 2 2 A63M-30-11-Δ 2 2 A63R-30-11-Δ
125 75 22 37 40 105 80 25 30 60 75 1 1 A75-30-11-Δ 105 80 25 30 60 75 2 2 A75M-30-11-Δ 2 2 A75R-30-11-Δ
145 96 25 45 55 150 88 30 30 60 75 1 1 A95-30-11-Δ 150 88 30 30 60 75 2 2 A95M-30-11-Δ 2 2 A95R-30-11-Δ
160 110 30 55 75 150 104 30 40 75 100 1 1 A110-30-11-Δ 150 104 30 40 75 100 2 2 A110M-30-11-Δ 2 2 A110R-30-11-Δ
250 145 45 75 110 230 130 40 50 100 125 1 1 A145-30-11-Δ 230 130 40 50 100 125 2 2 A145M-30-11-Δ 2 2 A145R-30-11-Δ
275 185 55 90 132 250 156 50 60 125 150 1 1 A185-30-11-Δ 250 156 50 60 125 150 2 2 A185M-30-11-Δ 2 2 A185R-30-11-Δ
350 210 59 110 160 300 192 60 75 150 200 1 1 A210-30-11-Δ 300 192 60 75 150 200 2 2 A210M-30-11-Δ 2 2 A210R-30-11-Δ
400 260 80 140 200 350 248 75 100 200 250 1 1 A260-30-11-Δ 350 248 75 100 200 250 2 2 A260M-30-11-Δ 2 2 A260R-30-11-Δ
500 305 90 160 250 400 302 100 100 250 300 1 1 A300-30-11-Δ 400 302 100 100 250 300 2 2 A300M-30-11-Δ 2 2 A300R-30-11-Δ
Planned legacy product; recommend AF series contactors. Planned legacy product; recommend AF series contactors.
R
A95M... A110M A95R... A110R
Reversing vs. mechanically interlocked
Full voltage reversing contactors are pre-assembled using two (2) contactors, a
mechanical interlock, an electrical interlock, and reversing busbars. Mechanically
interlocked contactors are offered less the reversing bus.
1 For selection purposes, for complete electrical ratings, see Technical Data
2 For ratings according to IEC/EN 60947-4-1, refer to A non-reversing selection table or Technical Data.
3A9R(M)…A16R(M) mounted on 35mm DIN rail, A26R(M)…A300R(M) mounted on common baseplate.
4 AC coil input voltage(s) at 50/60 Hz unless specied. For additional coil voltages, see page 1.35.
1.20 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
AE non-reversing, 3-pole
For applications up to 75 hp, 40 kW
DC operated, double-wound coils
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 3AE9…AE75
12V DC 80
24V DC 81
48V DC 83
125V DC 87
220V DC 88
240V DC 89
Example: 125V DC input voltage: AE75-30-11-87
R
Electrical ratings 1Non-reversing
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary
contacts 2Catalog
number
Rated operational
current
Ie AC-1, AC-3 (A)
Rated operational power Pe, AC-3,
55°C (kW)
AC general
purpose
ratings (A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase,
50/60 Hz (hp)
AC-1,
40°C
AC-3,
55°C
220…
240V
380…
400V 690V 600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC
25 9 2.2 4 5.5 21 9 2 2 5 7.5 1 1 AE9-30-11-Δ
27 12 3 5.5 7.5 25 11 3 3 7.5 10 1 1 AE12-30-11-Δ
30 17 4 7.5 9 30 17 5 5 10 15 1 1 AE16-30-11-Δ
45 26 6.5 11 15 40 28 7.5 10 20 25 1 1 AE26-30-11-Δ
55 32 9 15 18.5 50 34 10 10 25 30 1 1 AE30-30-11-Δ
60 37 11 18.5 22 60 42 10 15 30 40 1 1 AE40-30-11-Δ
100 50 15 22 30 80 54 15 20 40 50 1 1 AE50-30-11-Δ
115 65 18.5 30 37 90 68 20 25 50 60 1 1 AE63-30-11-Δ
125 75 22 37 40 105 80 25 30 60 75 1 1 AE75-30-11-Δ
Planned legacy product; recommend AF series contactors.
Uc (DC)
A1 A2
B2 - Holding
B1 - Pull-in
A3
NC contact in
4th contactor
pole
AE9 to AE40
Uc (DC)
A1 A2
B2 - Holding
B1 - Pull-in
CDL5 (AE45 to AE75)
Varistor
A3
U
AE45 to AE75
Double wound coils
1 For selection purposes, for complete electrical ratings, see Technical Data
2 All auxiliary contacts are side-mount.
3 For additional coil voltages, see page 1.35.
A50... AE75
Low Voltage Products & Systems 1.21
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 4AE9…AE75
12V DC 80
24V DC 81
48V DC 83
125V DC 87
220V DC 88
240V DC 89
Example: 125V DC input voltage: AE75R-30-11-87
R
AE mechanically interlocked, reversing, 3-pole
For applications up to 75 hp, 40 kW
DC operated, double-wound coils
Electrical ratings 12 Mechanically interlocked Reversing
UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary
contacts Catalog
number
3
Standard auxiliary
contacts Catalog
number
3
AC general
purpose
ratings
(A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase, 50/60 Hz
(hp)
600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC NO NC
21 9 2 2 5 7.5 2 2 AE9M-30-11-Δ 2 2 AE9R-30-11-Δ
25 11 3 3 7.5 10 2 2 AE12M-30-11-Δ 2 2 AE12R-30-11-Δ
30 17 5 5 10 15 2 2 AE16M-30-11-Δ 2 2 AE16R-30-11-Δ
40 28 7.5 10 20 25 2 2 AE26M-30-11-Δ 2 2 AE26R-30-11-Δ
50 34 10 10 25 30 2 2 AE30M-30-11-Δ 2 2 AE30R-30-11-Δ
60 42 10 15 30 40 2 2 AE40M-30-11-Δ 2 2 AE40R-30-11-Δ
80 54 15 20 40 50 2 2 AE50M-30-11-Δ 2 2 AE50R-30-11-Δ
90 68 20 25 50 60 2 2 AE63M-30-11-Δ 2 2 AE63R-30-11-Δ
105 80 25 30 60 75 2 2 AE75M-30-11-Δ 2 2 AE75R-30-11-Δ
Planned legacy product; recommend AF series contactors.
Reversing vs. mechanically interlocked
Full voltage reversing contactors are pre-assembled using two (2) contactors, a
mechanical interlock, an electrical interlock, and reversing busbars. Mechanically
interlocked contactors are offered less the reversing bus.
1 For selection purposes, for complete electrical ratings, see Technical Data
2 For ratings according to IEC/EN 60947-4-1, refer to AE non-reversing selection table or Technical Data.
3 AE9R(M)…AE16R(M) mounted on 35mm DIN rail, AE26R(M)…AE75R(M) mounted on common baseplate.
4 For additional coil voltages, see page 1.35.
AE50M... AE75M AE50R...AE75R
1.22 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
AL non-reversing, 3-pole
For applications up to 40 hp, 18.5 kW
Low power consumption, DC operated coils
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 3AL9…
AL40
12V DC 80
24V DC 81
48V DC 83
125V DC 87
220V DC 88
240V DC 89
Example(s):
24V DC input voltage: AL30-30-10-81
125V DC input voltage: AL40-30-10-87
Electrical ratings 1Non-reversing & reversing
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary
contacts 2Catalog
number
Rated operational
current
Ie AC-1, AC-3 (A)
Rated operational power Pe, AC-3,
55°C (kW)
AC general
purpose
ratings (A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase,
50/60 Hz (hp)
AC-1,
40°C
AC-3,
55°C
220…
240V
380…
400V 690V 600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC
25 9 2.2 4 5.5 21 9 2 2 5 7.5 1-AL9-30-10-Δ
-1AL9-30-01-Δ
27 12 3 5.5 7.5 25 11 3 3 7.5 10 1-AL12-30-10-Δ
-1AL12-30-01-Δ
30 17 4 7.5 9 30 17 5 5 10 15 1-AL16-30-10-Δ
-1AL16-30-01-Δ
45 26 6.5 11 11 40 28 7.5 10 20 25 1-AL26-30-10-Δ
-1AL26-30-01-Δ
55 32 9 15 15 50 34 10 10 25 30 1- AL30-30-10-Δ
-1AL30-30-01-Δ
60 37 11 18.5 18.5 60 42 10 15 30 40 1- AL40-30-10-Δ
-1AL40-30-01-Δ
Planned legacy product; recommend AF series contactors.
AL9-30-10-81 AL26-30-10-81 AL40-30-10-81
R
1 For selection purposes, for complete electrical ratings, see Technical Data
2 Auxiliary contacts integral for AL9... AL40.
3 For additional coil voltages, see page 1.35.
Low Voltage Products & Systems 1.23
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
AL mechanically interlocked, reversing, 3-pole
For applications up to 40 hp, 18.5 kW
Low power consumption, DC operated coils
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 4AL9…
AL40
12V DC 80
24V DC 81
48V DC 83
125V DC 87
220V DC 88
240V DC 89
Example(s):
24V DC input voltage: AL30M-30-10-81
125V DC input voltage: AL40R-30-10-87
Electrical ratings 1Non-reversing & reversing
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary
contacts 2Catalog
number
Rated operational
current
Ie AC-1, AC-3 (A)
Rated operational power Pe, AC-3,
55°C (kW)
AC general
purpose
ratings (A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase,
50/60 Hz (hp)
AC-1,
40°C
AC-3,
55°C
220…
240V
380…
400V 690V 600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC
25 9 2.2 4 5.5 21 9 2 2 5 7.5 1-AL9-30-10-Δ
-1AL9-30-01-Δ
27 12 3 5.5 7.5 25 11 3 3 7.5 10 1-AL12-30-10-Δ
-1AL12-30-01-Δ
30 17 4 7.5 9 30 17 5 5 10 15 1-AL16-30-10-Δ
-1AL16-30-01-Δ
45 26 6.5 11 11 40 28 7.5 10 20 25 1-AL26-30-10-Δ
-1AL26-30-01-Δ
55 32 9 15 15 50 34 10 10 25 30 1- AL30-30-10-Δ
-1AL30-30-01-Δ
60 37 11 18.5 18.5 60 42 10 15 30 40 1- AL40-30-10-Δ
-1AL40-30-01-Δ
Planned legacy product; recommend AF series contactors.
Electrical ratings 12 Mechanically interlocked Reversing
UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary
contacts Catalog
number
Standard auxiliary
contacts Catalog
number
AC general
purpose
ratings
(A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase, 50/60 Hz
(hp)
600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC NO NC
21 9 2 2 5 7.5 2 2 AL9M-30-10-Δ 2 2 AL9R-30-10-Δ
- - - - - - - - - - - -
25 11 3 3 7.5 10 2 2 AL12M-30-10-Δ 2 2 AL12R-30-10-Δ
- - - - - - - - - - - -
30 17 5 5 10 15 2 2 AL16M-30-10-Δ 2 2 AL16R-30-10-Δ
- - - - - - - - - - - -
40 28 7.5 10 20 25 2 2 AL26M-30-10-Δ 2 2 AL26R-30-10-Δ
- - - - - - - - - - - -
50 34 10 10 25 30 2 2 AL30M-30-10-Δ 2 2 AL30R-30-10-Δ
- - - - - - - - - - -
60 42 10 15 30 40 2 2 AL40M-30-10-Δ 2 2 AL40R-30-10-Δ
- - - - - - - - - - -
Planned legacy product; recommend AF series contactors.
R
Reversing vs. mechanically interlocked
Full voltage reversing contactors are pre-assembled using two (2) contactors, a
mechanical interlock, an electrical interlock, and reversing busbars. Mechanically
interlocked contactors are offered less the reversing bus.
1 For selection purposes, for complete electrical ratings, see Technical Data
2 For ratings according to IEC/EN 60947-4-1, refer to AL non-reversing selection table or Technical Data.
3 AL9R(M)…AL16R(M) mounted on 35mm DIN rail, AL26R(M)…AL40R(M) mounted on common baseplate.
4 For additional coil voltages, see page 1.35.
AL9M...AL16M AL9R...AL16R
1.24 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
AS / ASL non-reversing, reversing 3-pole
For applications up to 10 hp, 7.5 kW
AC or DC operated coils, bulk packaged for high volume
Electrical ratings 1Non-reversing and reversing
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary
contacts 2Catalog
number
Rated operational
current
Ie AC-1, AC-3 (A)
Rated operational power Pe, AC-3,
60°C (kW)
AC general
purpose
ratings (A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase,
50/60 Hz (hp)
AC-1,
40°C
AC-3,
60°C
220…
240V
380…
400V 690V 600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC
Type AS, AC controlled, non-reversing
22 9 2.2 4 4 20 9 2 2 5 7.5
1- AS09-30-10-ΔM
-1AS09-30-01-ΔM
3 2 AS09-30-32-ΔM
24 12 3 5.5 5.5 20 11 2 3 7.5 10
1- AS12-30-10-ΔM
-1AS12-30-01-ΔM
3 2 AS12-30-32-ΔM
24 15.5 4 7.5 7.5 20 15.2 3 5 10 10
1- AS16-30-10-ΔM
-1AS16-30-01-ΔM
3 2 AS16-30-32-ΔM
Type ASL, DC controlled, non-reversing
22 9 2.2 4 4 20 9 2 2 5 7.5
1- ASL09-30-10-ΔM
-1ASL09-30-01-ΔM
3 2 ASL09-30-32-ΔM
24 12 3 5.5 5.5 20 11 2 3 7.5 10
1- ASL12-30-10-ΔM
-1ASL12-30-01-ΔM
3 2 ASL12-30-32-ΔM
24 15.5 4 7.5 7.5 20 15.2 3 5 10 10
1- ASL16-30-10-ΔM
-1ASL16-30-01-ΔM
3 2 ASL16-30-32-ΔM
Type AS, AC controlled, reversing
22 9 2.2 4 4 20 9 2 2 5 7.5 - 2 VAS09EM-ΔM
24 12 3 5.5 5.5 20 11 2 3 7.5 10 - 2 VAS12EM-ΔM
24 15.5 4 7.5 7.5 20 15.2 3 5 10 10 - 2 VAS16EM-ΔM
Type ASL, DC controlled, reversing
22 9 2.2 4 4 20 9 2 2 5 7.5 - 2 VASL09EM-ΔM
24 12 3 5.5 5.5 20 11 2 3 7.5 10 - 2 VASL12EM-ΔM
24 15.5 4 7.5 7.5 20 15.2 3 5 10 10 - 2 VASL16EM-ΔM
AS(L)09...AS(L)16 single stack AS(L)09...AS(L)16 double stack VAS(L)09...VAS(L)
Coil voltage selection chart (Δ)
Rated control circuit
voltage Uc 3
AS09…
AS16
ASL09…
ASL16
VAS09…
VAS16
VASL09…
VASL16
12V DC - 80 - -
24V AC 20 - 20 -
24V DC - 81 - 81
48V DC - 83 - 83
115V AC 24 - 24 -
120V AC, 60 Hz 16 - 16 -
125V DC - 87 - 87
220V DC - 88 - 88
230V AC 26 - 26 -
400V AC 28 - 28 -
Example(s):
24V DC input voltage: ASL09-30-10-81M; 115V AC input voltage: AS16-30-01-24M
Standard bulk pack quantities (M)
Contactors Quantity
AS(L)09…16-30-10 40
AS(L)09…16-30-01 40
AS(L)09…16-30-32 20
VAS09…VAS16 18
1 For selection purposes, for complete electrical ratings, see Technical Data
2 3/2 auxiliary congurations include 1 NO integral contact with permanently attached 2/2 front-
mount accessory.
3 AC coil input voltage(s) at 50/60 Hz unless specied. Additional voltages pg. 1.35.
Low Voltage Products & Systems 1.25
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
AS / ASL non-reversing, spring-terminated, 3 pole
For applications up to 10 hp, 7.5 kW
AC or DC operated coils, bulk packaged for high volume
Electrical ratings 1Non-reversing
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary
contacts 2Catalog
number
Rated operational
current
Ie AC-1, AC-3 (A)
Rated operational power Pe, AC-3,
60°C (kW)
AC general
purpose
ratings (A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase,
50/60 Hz (hp)
AC-1,
40°C
AC-3,
60°C
220…
240V
380…
400V 690V 600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC
Type AS, AC controlled, spring-terminated, non-reversing
20 9 2.2 4 4 12 9 2 2 5 7.5
1- AS09-30-10S-ΔM
-1AS09-30-01S-ΔM
3 2 AS09-30-32S-ΔM
22 12 3 5.5 5.5 12 11 2 3 7.5 10
1- AS12-30-10S-ΔM
-1AS12-30-01S-ΔM
3 2 AS12-30-32S-ΔM
22 15.5 4 7.5 7.5 15.2 15.2 3 5 10 10
1- AS16-30-10S-ΔM
-1AS16-30-01S-ΔM
3 2 AS16-30-32S-ΔM
Type ASL, DC controlled, spring-terminated, non-reversing
20 9 2.2 4 4 12 9 2 2 5 7.5
1- ASL09-30-10S-ΔM
-1ASL09-30-01S-ΔM
3 2 ASL09-30-32S-ΔM
22 12 3 5.5 5.5 12 11 2 3 7.5 10
1- ASL12-30-10S-ΔM
-1ASL12-30-01S-ΔM
3 2 ASL12-30-32S-ΔM
22 15.5 4 7.5 7.5 15.2 15.2 3 5 10 10
1- ASL16-30-10S-ΔM
-1ASL16-30-01S-ΔM
3 2 ASL16-30-32S-ΔM
AS(L)09...AS(L)16 spring terminated, single stack AS(L)09...AS(L)16 spring terminated, double stack
Coil voltage selection chart (Δ)
Rated control circuit voltage
Uc 3
AS09…
AS16
ASL09…
ASL16
12V DC - 80
24V AC 20 -
24V DC - 81
48V DC - 83
115V AC 24 -
120V AC, 60 Hz 16 -
125V DC - 87
220V DC - 88
230V AC 26 -
400V AC 28 -
Example(s):
24V DC input voltage: ASL09-30-10S-81M
115V AC input voltage: AS16-30-01S-24M
Standard bulk pack quantities (M)
Contactors Quantity
AS(L)09…16-30-10 40
AS(L)09…16-30-01 40
AS(L)09…16-30-32 20
VAS09…VAS16 18
1 For selection purposes, for complete electrical ratings, see Technical Data
2 3/2 auxiliary congurations include 1 NO integral contact with permanently attached 2/2 front-mount accessory.
3 AC coil input voltage(s) at 50/60 Hz unless specied. Additional voltages pg. 1.35.
1.26 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
B miniature non-reversing, mechanically interlocked, 3-pole
For applications up to 5 hp, 5.5 kW
AC operated coils, screw, quick-connect & PCB mount termination
Electrical ratings 1Non-reversing &
mechanically interlocked
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary
contacts Catalog
number
Rated operational
current
Ie AC-1, AC-3 (A)
Rated operational power Pe, AC-3,
55°C (kW)
AC general
purpose
ratings (A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase,
50/60 Hz (hp)
AC-1,
40°C
AC-3,
55°C
220…
240V
380…
400V 690V 600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC
Type B, screw terminated, non-reversing
20 8 2.2 4 3 12 26.8 12311- B6-30-10-Δ
-1B6-30-01-Δ
20 12 3 5.5 3 16 9.6 2 3 5 5 1- B7-30-10-Δ
-1B7-30-01-Δ
Type B, quick-connect (flat pin), non-reversing
16 8 2.2 4 3 12 26.8 12311- B6-30-10-FΔ
-1B6-30-01-FΔ
16 12 3 5.5 3 16 9.6 2 3 5 5 1- B7-30-10-FΔ
-1B7-30-01-FΔ
Type B, printed circuit board mount (solder pin), non-reversing
12 8 2.2 4 3 8 2 6.8 12311- B6-30-10-PΔ
-1B6-30-01-PΔ
12 12 3 5.5 3 16 9.6 2 3 5 5 1- B7-30-10-PΔ
-1B7-30-01-PΔ
Type B, screw terminated, mechanically interlocked
20 8 2.2 4 3 12 26.8 12312 - VB6-30-10-Δ
- 2 VB6-30-01-Δ
20 12 3 5.5 3 16 9.6 2 3 5 5 2 - VB7-30-10-Δ
- 2 VB7-30-01-Δ
Type B, quick-connect (flat pin), mechanically interlocked
16 8 2.2 4 3 12 26.8 12312 - VB6-30-10-FΔ
- 2 VB6-30-01-FΔ
16 12 3 5.5 3 16 9.6 2 3 5 5 2 - VB7-30-10-FΔ
- 2 VB7-30-01-FΔ
Type B, printed circuit board mount (solder pin), mechanically interlocked
12 8 2.2 4 3 8 26.8 12312 - VB6-30-10-PΔ
- 2 VB6-30-01-PΔ
12 12 3 5.5 3 16 9.6 2 3 5 5 2 - VB7-30-10-PΔ
- 2 VB7-30-01-PΔ
NOTE: Quick-connect and PCB mount versions are UL recognized only.
R
B6...B7 B6(-F)...B7(-F) B6(-P)...B7(-P) VB6...VB7
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 3(V)B6…(V)B7
24V AC 01
48V AC 03
110…127V AC 84
220…240V AC 80
380…415V AC 85
Example(s):
24V AC input voltage: B6-30-10-01
120V AC input voltage: VB7-30-10-84
1 For selection purposes, for complete electrical ratings, see Technical Data
2 300V AC max.
3 AC coil input voltage(s) at 50/60 Hz unless specied. Additional voltages pg. 1.35.
Low Voltage Products & Systems 1.27
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
BC miniature non-reversing, mech. interlocked, 3 pole
For applications up to 5 hp, 5.5 kW
DC operated coils, screw, quick-connect & PCB mount termination
Electrical ratings 1Non-reversing &
mechanically interlocked
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Standard auxiliary
contacts Catalog
number
Rated operational
current
Ie AC-1, AC-3 (A)
Rated operational power Pe, AC-3,
55°C (kW)
AC general
purpose
ratings (A)
Maximum
motor
switching
current
(A)
AC motor ratings, breaking all lines, three phase,
50/60 Hz (hp)
AC-1,
40°C
AC-3,
55°C
220…
240V
380…
400V 690V 600V 200...
208V
220…
240V
440…
480V
550…
600V NO NC
Type BC, screw terminated, non-reversing
20 8 2.2 4 3 12 26.8 12311- BC6-30-10-Δ
-1BC6-30-01-Δ
20 12 3 5.5 3 16 9.6 2 3 5 5 1- BC7-30-10-Δ
-1BC7-30-01-Δ
Type BC, quick-connect (flat pin), non-reversing
16 8 2.2 4 3 12 26.8 12311- BC6-30-10-FΔ
-1BC6-30-01-FΔ
16 12 3 5.5 3 16 9.6 2 3 5 5 1- BC7-30-10-FΔ
-1BC7-30-01-FΔ
Type BC, printed circuit board mount (solder pin), non-reversing
12 8 2.2 4 3 8 26.8 12311- BC6-30-10-PΔ
-1B6C-30-01-PΔ
12 12 3 5.5 3 16 9.6 2 3 5 5 1- BC7-30-10-PΔ
-1BC7-30-01-PΔ
Type BC, screw terminated, mechanically interlocked
20 8 2.2 4 3 12 26.8 12312 - VBC6-30-10-Δ
- 2 VBC6-30-01-Δ
20 12 3 5.5 3 16 9.6 2 3 5 5 2 - VBC7-30-10-Δ
- 2 VBC7-30-01-Δ
Type BC, quick-connect (flat pin), mechanically interlocked
16 8 2.2 4 3 12 26.8 12312 - VBC6-30-10-FΔ
- 2 VBC6-30-01-FΔ
16 12 3 5.5 3 16 9.6 2 3 5 5 2 - VBC7-30-10-FΔ
- 2 VBC7-30-01-FΔ
Type BC, printed circuit board mount (solder pin), mechanically interlocked
12 8 2.2 4 3 8 26.8 12312 - VBC6-30-10-PΔ
- 2 VBC6-30-01-PΔ
12 12 3 5.5 3 16 9.6 2 3 5 5 2 - VBC7-30-10-PΔ
- 2 VBC7-30-01-PΔ
NOTE: Quick-connect and PCB mount versions are UL recognized only.
R
BC6...BC7 BC6(-F)...BC7(-F) BC6(-P)...BC7(-P) VBC6(-P)...VBC7(-P)
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 3(V)BC6…(V)BC7
12V DC 07
24V DC 01
48V DC 16
110…125V DC 04
220…240V DC 05
Example(s):
24V DC input voltage: BC6-30-10-01
125V DC input voltage: VBC7-30-10-04
1 For selection purposes, for complete electrical ratings, see Technical Data
2 300V AC max.
3 For addtional coil voltages, see page 1.35.
1.28 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
AF / AFZ NEMA rated, non-reversing, 3-pole
Class A controllers Sizes 00…8
Electronic AC/DC operated coils
Electrical ratings 1Non-reversing
NEMA
size
Continous
current
rating
(A)
NEMA ICS 2-2000 (R2005) Standard auxiliary
contacts 2Catalog
number
AC motor ratings, breaking all lines (hp)
Single phase, 50/60 Hz Three phase, 60 Hz
120V 230V 200V 230V 380…
415V 3460V 575V NO NC
Type AF
00 9 1/3 11.5 1.5 1.5 2 2 1- AF09N00-30-10-Δ
-1AF09N00-30-10-Δ
01812335551- AF12N0-30-10-Δ
-1AF12N0-30-10-Δ
127 2 3 7.5 7.5 10 10 10 - - AF26N1-30-00-Δ
2 45 3 7.5 10 15 25 25 25 1 1 AF50N2-30-11-Δ
3 90 - - 25 30 50 50 50 1 1 AF75N3-30-11-Δ
4 135 - - 40 50 75 100 100 1 1 AF145N4-3011-Δ
5 270 - - 75 100 150 200 200 1 1 AF260N5-3011-Δ
6 540 - - 150 200 300 400 400 1 1 AF460N6-3011-Δ
7810 - - - 300 - 600 600 1 1 AF750N7-3011-Δ
8 1215 - - - 450 - 900 900 1 1 AF1650N83011-Δ
Type AFZ, low-consumption coils
00 9 1/3 11.5 1.5 1.5 2 2 1- AF09N00Z-30-10-Δ
-1AF09N00Z-30-01-Δ
01812335551- AF12N0Z-30-10-Δ
-1AF12N0Z-30-01-Δ
127 2 3 7.5 7.5 10 10 10 - - AF26N1Z-30-00-Δ
AF26N1(Z) AF50N2...AF75N3 AF260N5 AF1650N
Coil voltage selection chart (Δ)
Rated control circuit
voltage Uc 3
AF09N00…
AF26N1
AF09N00Z…
AF26N1Z
AF50N2…
AF260N5
AF460N6…
AF750N7
AF1650N8
12…20V DC - 20 - - -
20...60V DC 11 21 72 - -
24...60V AC 11 21 - - -
24...60V DC - - - 68 -
48...130V AC/DC 12 22 69 69 -
100...250 V AC/DC 13 23 70 70 70
250...500 V AC/DC 14 - - 71 -
Example(s):
24V DC input voltage: AF26N1-30-00-11
120V AC input voltage: AF750N7-3011-70
1 For selection purposes, for complete electrical ratings, see Technical Data.
2 Auxiliary contacts integral for AF09N00...AF16N0; side-mount for AF50N2...AF1650N8
3 50 Hz.
4 AC coil input voltage(s) at 50/60 Hz unless specied.
Control inputs
AF460N6...AF1650N8 are equipped with integral low voltage inputs, allowing for
direct PLC control.
Low Voltage Products & Systems 1.29
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
AF / AFZ NEMA rated, mech. interlocked, reversing, 3P
Class A controllers Sizes 00…7
Electronic AC/DC operated coils
Electrical ratings 12 Mechanically interlocked Reversing
NEMA ICS 2-2000 (R2005) Standard auxiliary
contacts Catalog
number
2
Standard auxiliary
contacts Catalog
number
2
NEMA
size
Continous
current
rating
(A)
AC motor ratings, breaking all lines,
Three phase, 60 Hz (hp)
200V 230V 460…
575V NO NC NO NC
Type AF
00 9 1.5 1.5 2 2 2 AF09N00M-3022-Δ 2 2 AF09N00R-3022-Δ
- - - - - -
0 18 3 3 5 2 2 AF12N0M-3022-Δ 2 2 AF12N0R-3022-Δ
- - - - - -
127 7.5 7.5 10 - 2 AF26N1M-3002-Δ - 2 AF26N1R-3002-Δ
2 45 10 15 25 2 2 AF50N2M-3011-Δ 2 2 AF50N2R-3011-Δ
3 90 25 30 50 2 2 AF75N3M-3011-Δ 2 2 AF75N3R-3011-Δ
4 135 40 50 100 2 2 AF145N4M-11-Δ 2 2 AF145N4R-11-Δ
5 270 75 100 200 2 2 AF260N5M-11-Δ 2 2 AF260N5R-11-Δ
6 540 150 200 400 2 2 AF460N6M-11-Δ 2 2 AF460N6R-11-Δ
7810 - 300 600 2 2 AF750N7M-11-Δ 2 2 AF750N7R-11-Δ
Type AFZ, low-consumption coils
00 9 1.5 1.5 2 2 2 AF09N00MZ-3022-Δ 2 2 AF09N00RZ-3022-Δ
- - - - - -
0 18 3 3 5 2 2 AF12N0MZ-3022-Δ 2 2 AF12N0RZ-3022-Δ
- - - - - -
127 7.5 7.5 10 - 2 AF26N1MZ-3002-Δ - 2 AF26N1RZ-3002-Δ
AF09N00R…AF16N0R
Coil voltage selection chart (Δ)
Rated control circuit
voltage Uc 3
AF09N00…
AF26N1
AF09N00Z…
AF26N1Z
AF50N2…
AF260N5
AF460N6…
AF750N7
12…20V DC - 20 - -
20...60V DC 11 21 72 -
24...60V AC 11 21 - -
24...60V DC - - - 68
48...130V AC/DC 12 22 69 69
100...250 V AC/DC 13 23 70 70
250...500 V AC/DC 14 - - 71
Example(s):
24V DC input voltage: AF26N1R-3002-11
120V AC input voltage: AF750N7R-11-70
1 For selection purposes, for complete electrical ratings, see Technical Data.
2 For ratings according to IEC/EN 60947-4-1, refer to AF NEMA rated, non-reversing selection table or Technical Data.
3 AF09N00R(M)…AF26N1R(M) assembled using connection clips, AF50N2R(M)…AF750N7R(M) mounted on common baseplate.
4 AC coil input voltage(s) at 50/60 Hz unless specified.
Reversing vs. mechanically interlocked
Full voltage reversing contactors are pre-assembled using two (2) contactors, a
mechanical interlock, an electrical interlock, and reversing busbars. Mechanically
interlocked contactors are offered less the reversing bus.
1.30 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
A, AL, AE NEMA rated, non-reversing, 3-pole
Class A controllers Sizes 00…5
AC or DC operated coils
Electrical ratings 1Non-reversing
NEMA
size
Continous
current
rating
(A)
NEMA ICS 2-2000 (R2005) Standard auxiliary
contacts 2Catalog
number
AC motor ratings, breaking all lines (hp)
Single phase, 50/60 Hz Three phase, 60 Hz
120V 230V 200V 230V 380…
415V 3460V 575V NO NC
Type A, AC operated coils
00 9 1/3 11.5 1.5 1.5 2 2 1- A9N00-30-10-Δ
01812335551- A16N0-30-10-Δ
127 2 3 7.5 7.5 10 10 10 1- A26N1-30-10-Δ
2 45 3 7.5 10 15 25 25 25 1 1 A50N2-30-11-Δ
3 90 - - 25 30 50 50 50 1 1 A75N3-30-11-Δ
4 135 - - 40 50 75 100 100 1 1 A145N4-30-11-Δ
5 270 - - 75 100 150 200 200 1 1 A260N5-30-11-Δ
Type AL, DC operated coils
00 9 1/3 11.5 1.5 1.5 2 2 1- AL9N00-30-10-Δ
01812335551- AL16N0-30-10-Δ
127 2 3 7.5 7.5 10 10 10 1- AL26N1-30-10-Δ
Type AE, double-wound DC operated coils
00 9 1/3 11.5 1.5 1.5 2 2 1- AE9N00-30-11-Δ
01812335551- AE16N0-30-11-Δ
127 2 3 7.5 7.5 10 10 10 1- AE26N1-30-11-Δ
2 45 3 7.5 10 15 25 25 25 1 1 AE50N2-30-11-Δ
3 90 - - 25 30 50 50 50 1 1 AE75N3-30-11-Δ
Planned legacy product; recommend AF series contactors.
A26N1 A145N4
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 4A9N00…
A260N5
AL9N00…
AL26N1
AE9N00…
AE75N3
12V DC - 80 80
24V AC 81 - -
24V DC - 81 81
110…120V AC, 60Hz 84 - -
125V DC - 87 87
220V DC - 88 88
230..240V AC, 60 Hz 80 - -
240V DC - 89 89
480V AC, 60 Hz 51 - -
600V AC, 60 Hz 55 - -
Example(s):
24V DC input voltage: AL26N1-30-10-81
120V AC input voltage: A260N5-3011-84
1 For selection purposes, for complete electrical ratings, see Technical Data.
2 Auxiliary contacts integral for A9N00...A26N1 & AL9N00...AL26N1; side-mount for A50N2...A260N5 & AE9N00...AE75N3.
3 50 Hz.
4 AC coil input voltage(s) at 50/60 Hz unless specied. Additional voltages pg. 1.35.
Low Voltage Products & Systems 1.31
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
A, AL, AE NEMA rated, mech. interlocked, reversing
Class A controllers Sizes 00…5; AC or DC operated coils
Electrical ratings 12 Mechanically interlocked Reversing
NEMA ICS 2-2000 (R2005) Standard auxiliary
contacts Catalog
number
2
Standard auxiliary
contacts Catalog
number
2
NEMA
size
Continous
current
rating
(A)
AC motor ratings, breaking all lines,
Three phase, 60 Hz (hp)
200V 230V 460…
575V NO NC NO NC
Type A, AC operated coils
00 9 1.5 1.5 2 2 2 A9N00M-10-Δ 2 2 A9N00R-10-Δ
0 18 3 3 5 2 2 A16N0M-10-Δ 2 2 A16N0R-10-Δ
127 7.5 7.5 10 2 2 A26N1M-10-Δ 2 2 A26N1R-10-Δ
2 45 10 15 25 2 2 A50N2M-11-Δ 2 2 A50N2R-11-Δ
3 90 25 30 50 2 2 A75N3M-11-Δ 2 2 A75N3R-11-Δ
4 135 40 50 100 2 2 A145N4M-11-Δ 2 2 A145N4R-11-Δ
5 270 75 100 200 2 2 A260N5M-11-Δ 2 2 A260N5R-11-Δ
Type AL, DC operated coils
00 9 1.5 1.5 2 2 2 AL9N00M-10-Δ 2 2 AL9N00R-10-Δ
0 18 3 3 5 2 2 AL16N0M-10-Δ 2 2 AL16N0R-10-Δ
127 7.5 7.5 10 2 2 AL26N1M-10-Δ 2 2 AL26N1R-10-Δ
Type AE, double-wound DC operated coils
00 9 1.5 1.5 2 2 2 AE9N00M-11-Δ 2 2 AE9N00R-11-Δ
0 18 3 3 5 2 2 AE16N0M-11-Δ 2 2 AE16N0R-11-Δ
127 7.5 7.5 10 2 2 AE26N1M-11-Δ 2 2 AE26N1R-11-Δ
2 45 10 15 25 2 2 AE50N2M-11-Δ 2 2 AE50N2R-11-Δ
3 90 25 30 50 2 2 AE75N3M-11-Δ 2 2 AE75N3R-11-Δ
Planned legacy product; recommend AF series contactors.
Coil voltage selection chart (Δ)
Rated control circuit voltage
Uc 4
A9N00…
A260N5
AL9N00…
AL26N1
AE9N00…
AE75N3
12V DC - 80 80
24V AC 81 - -
24V DC - 81 81
110…120V AC, 60Hz 84 - -
125V DC - 87 87
220V DC - 88 88
230..240V AC, 60 Hz 80 - -
240V DC - 89 89
480V AC, 60 Hz 51 - -
600V AC, 60 Hz 55 - -
Example(s):
24V DC input voltage: AL26N1M-10-81
120V AC input voltage: A260N5R-11-84
1 For selection purposes, for complete electrical ratings, see Technical Data.
2 For ratings according to IEC/EN 60947-4-1, refer to A, AL, AE NEMA rated, non-reversing selection table or Technical Data.
3 A(E)(L)9N00R(M)…A(E)(L)16N0R(M) mounted on 35mm DIN rail, A(E)(L)26N1R(M)…A260N5R(M) mounted on common baseplate.
4 AC coil input voltage(s) at 50/60 Hz unless specied. Additional voltages pg. 1.35.
Reversing vs. mechanically interlocked
Full voltage reversing contactors are pre-assembled using two (2) contactors, a
mechanical interlock, an electrical interlock, and reversing busbars. Mechanically
interlocked contactors are offered less the reversing bus.
A9N00M...A16N0 A/E50N2...A/E75N3
1.32 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
AF, AFZ, and EK 4-pole
For resistive & slightly inductive applications up to 1000 A
AC & DC control
Electrical ratings 14-pole (4 NO & 2 NO / 2 NC)
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Main (power) pole
conguration 2
Standard auxiliary
contacts Catalog
number
Rated operational current Ie, AC-1 (A) AC general purpose ratings, 600V (A) NO NC NO NC
Type AF, electronic AC/DC controlled
25 25 4 - - - AF09-40-00-Δ
2 2 - - AF09-22-00-Δ
30 30 4 - - - AF16-40-00-Δ
2 2 - - AF16-22-00-Δ
45 45 4 - - - AF26-40-00-Δ
2 2 - - AF26-22-00-Δ
55 55 4 - - - AF38-40-00-Δ
2 2 - - AF38-22-00-Δ
70 65 4 - - - AF45-40-00-Δ
2 2 - - AF45-22-00-Δ
100 80 4 - - - AF50-40-00-Δ
125 105 4 - - - AF75-40-00-Δ
2 2 - - AF75-22-00-Δ
Type EK, AC or DC controlled
200 170 4 - 1 1 EK110C4P-ΔL
250 200 4 - 1 1 EK150C4P-ΔL
300 250 4 - 1 1 EK175C4P-ΔL
350 300 4 - 1 1 EK210C4P-ΔL
550 420 4 - 1 1 EK370C4P-ΔL
800 540 4 - 1 1 EK550C4P-ΔL
1000 - 4 - 1 1 EK1000C4P-ΔL
Type AFZ, electronic AC/DC controlled, low consumption
25 25 4 - - - AF09Z-40-00-Δ
2 2 - - AF09Z-22-00-Δ
30 30 4 - - - AF16Z-40-00-Δ
2 2 - - AF16Z-22-00-Δ
45 45 4 - - - AF26Z-40-00-Δ
2 2 - - AF26Z-22-00-Δ
55 55 4 - - - AF38Z-40-00-Δ
2 2 - - AF38Z-22-00-Δ
R
AF09(Z)...AF16(Z) AF26(Z)...AF38(Z) AF45...AF75 EK175...EK210
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 3AF09…
AF38
AF09Z…
AF38Z
AF45…
AF75
EK110…
EK1000
12…20V DC - 20 - -
20...60V DC 11 21 72 -
24...60V AC 11 21 - -
24V AC, 60 Hz - - - F
24V DC - - - Y
48...130V AC/DC 12 22 69 -
110V 50 Hz, 120V 60 Hz - - - 1
125V DC - - - Q
100...250 VAC/DC 13 23 70 -
220V DC - - - R
240V AC, 60 Hz - - - 2
250...500 V AC/DC 14 - - -
480V AC, 60 Hz - - - 4
600V AC, 60 Hz - - - 6
1 For selection purposes, for complete electrical ratings, see Technical Data.
2 2 NO & 2 NC contactors are not suitable for a reversing starter or wye-delta starter or for con-
trolling a single load from 2 separate supplies. Please see technical data.
3 AC coil input voltage(s) at 50/60 Hz unless specied. Additional voltages pg. 1.35.
Example(s):
24V DC input voltage: EK110C4P-YL
120V AC input voltage: AF75-40-11-70
Low Voltage Products & Systems 1.33
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
A, AL, and AE 4-pole
For resistive & slightly inductive applications up to 125 A
AC or DC control
Electrical ratings 14-pole (4 NO & 2 NO / 2 NC)
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Main (power) pole
conguration 2
Standard auxiliary
contacts Catalog
number
Rated operational current Ie, AC-1 (A) AC general purpose ratings, 600V (A) NO NC NO NC
Type A, AC controlled
25 21 4 - - - A9-40-00-Δ
2 2 - - A9-22-00-Δ
30 30
4 - - - A16-40-00-Δ
2 2 - - A16-22-00-Δ
- 4 - - A16-04-00-Δ
45 40 4 - - - A26-40-00-Δ
2 2 - - A26-22-00-Δ
70 65 4 - - - A45-40-00-Δ
2 2 - - A45-22-00-Δ
100 80 4 - - - A50-40-00-Δ
125 105 4 - - - A75-40-00-Δ
2 2 - - A75-22-00-Δ
Type AL, DC controlled
25 21 4 - - - AL9-40-00-Δ
2 2 - - AL9-22-00-Δ
30 30 4 - - - AL16-40-00-Δ
2 2 - - AL16-22-00-Δ
45 40 4 - - - AL26-40-00-Δ
2 2 - - AL26-22-00-Δ
Type AE, DC controlled
70 65 4 - - - AE45-40-00-Δ
2 2 - - AE45-22-00-Δ
100 80 4 - - - AE50-40-00-Δ
125 105 4 - - - AE75-40-00-Δ
2 2 - - AE75-22-00-Δ
Planned legacy product; recommend AF series contactors.
R
A9...A16 A45...A75
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 3A9…A75 AL9…AL26 AE9…AE75
12V DC - 80 80
24V AC 81 - -
24V DC - 81 81
110…120V AC, 60Hz 84 - -
125V DC - 87 87
220V DC - 88 88
230..240V AC, 60 Hz 80 - -
240V DC - 89 89
480V AC, 60 Hz 51 - -
600V AC, 60 Hz 55 - -
Example(s):
24V DC input voltage: AL26-40-00-81
120V AC input voltage: A75-40-00-84
1 For selection purposes, for complete electrical ratings, see Technical Data.
2 2 NO & 2 NC contactors are not suitable for a reversing starter or wye-delta starter or for controlling a single load from 2 separate supplies. Please see technical data.
3 AC coil input voltage(s) at 50/60 Hz unless specied. For additional voltages, see page 1.35.
1.34 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
B, BC miniature, 4-pole
For resistive & slightly inductive applications up to 20 A
AC or DC control
Electrical ratings 14-pole (4 NO & 2 NO / 2 NC)
IEC/EN 60947-4-1 UL 508, 60947-4-1A
CSA C22.2 No.14, 60947-4-1-07
Main (power) pole
conguration
Standard auxiliary
contacts Catalog
number
Rated operational current Ie, AC-1 (A) AC general purpose ratings, 600V (A) NO NC NO NC
Type B, AC controlled, screw terminated
20 12 34 - - - B6-40-00-Δ
2 2 - - B6-22-00-Δ
20 16 4 - - - B7-40-00-Δ
2 2 - - B7-22-00-Δ
Type B, AC controlled, quick-connect (flat pin)
16 12 34 - - - B6-40-00-FΔ
2 2 - - B6-22-00-FΔ
16 16 4 - - - B7-40-00-FΔ
2 2 - - B7-22-00-FΔ
Type B, AC controlled, printed circuit board mount (solder pin)
12 8 3 4 - - - B6-40-00-PΔ
2 2 - - B6-22-00-PΔ
12 16 4 - - - B7-40-00-PΔ
2 2 - - B7-22-00-PΔ
Type BC, DC controlled, screw terminated
20 12 34 - - - BC6-40-00-Δ
2 2 - - BC6-22-00-Δ
20 16 4 - - - BC7-40-00-Δ
2 2 - - BC7-22-00-Δ
Type BC, DC controlled, quick-connect (flat pin)
16 12 34 - - - BC6-40-00-FΔ
2 2 - - BC6-22-00-FΔ
16 16 4 - - - BC7-40-00-FΔ
2 2 - - BC7-22-00-FΔ
Type BC, DC controlled, printed circuit board mount (solder pin)
12 8 34 - - - BC6-40-00-PΔ
2 2 - - BC6-22-00-PΔ
12 16 4 - - - BC7-40-00-PΔ
2 2 - - BC7-22-00-PΔ
NOTE: Quick connect and PCB mount versions are UL recognized only.
B(C)6...B(C)7 B(C)6(-F)...B(C)7(-F) B(C)6(-P)...B(C)7(-P)
R
Coil voltage selection chart (Δ)
Rated control circuit voltage Uc 2B6…B7 BC6…BC7
12V AC - 07
24V AC 01 -
24V DC - 01
48V AC 03 -
48V DC - 16
110…127V AC 84 -
110…125V DC - 04
220…240V AC 80 -
220…240V DC - 05
380…415V AC 85 -
Example(s):
24V DC input voltage: BC6-40-00-01
120V AC input voltage: B7-22-00-84
1 For selection purposes, for complete electrical ratings, see Technical Data.
2 AC coil input voltage(s) at 50/60 Hz unless specied. Additional voltages pg. 1.35.
3 300V AC max.
Low Voltage Products & Systems 1.35
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Additional coil voltages
3 & 4 pole contactors
AC & DC operated coils
Coils for AC operated contactors (Δ) Coils for DC operated contactors (Δ)
For
contactors
AC voltages Coil
code
For
contactors
AC voltages Coil
code
For
contactors
DC voltages
V - DC
Coil
code
V - 50 Hz V - 60 Hz V - 50 Hz V - 60 Hz
A9…A300,
A9N00…
A260N5
24 24 81
(V)B6…
(V)B7
24 24 01
AE9…AE75,
AE9N00…
AE75N3,
AL9…AL40,
AL9N00…
AL26N1
12 80
26 28 16 42 42 02 24 81
28 32 17 48 48 03 42 82
42 42 82 110...127 110...127 84 48 83
48 48 83 220…240 220…240 80 50 21
60 60 73 380…415 380…415 85 60 84
100 100…110 74 2
EK110…
EK1000
- 24 F 75 85
110 110…120 84 24 - N 110 86
110…115 115…127 89 3- 48 G125 87
120 140 29 110 120 1220 88
125…127 150 30 - 208 B240 89
175 208 34 - 240 2 250 38
190 220 36 220…230 - J
(V)BC6…
(V)BC7
12 07
220…230 230…240 80 - 380 Z 24 01
230…240 240…260 88 380…400 440 3 42 02
230…240 277 42 400…415 - M 48 16
230/400 - 62 1- 480 4 60 03
- 230/400 63 1500 - 5 110…125 04
380…400 400…415 85 - 600 6 220…240 05
400…415 415…440 86
(V)AS09…
(V)AS16
24 24 20
EK110…
EK1000
24 Y
400…415 480 51 42 42 21 48 W
415…440 440…460 87 48 48 22 110 P
440 500 53 110 110 23 125 Q
500 600 55 115 115 24 220 R
550 - 56 - 120 16 440 T
660…690 - 58 220 220 25
(V)ASL09…
(V)ASL16
12 80
230 230 26 24 81
240 240 27 48 83
- 277 17 60 84
380 - 13 110 86
400 400 28 125 87
415 415 29 220 88
240 89
1.36 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
AF09(Z)...AF38(Z), AF09N00(Z)...AF26N1(Z), 3-pole
Accessory tting details
Main accessory fitting details
Many configurations of accessories are possible depending on whether these are front-mounted or side-mounted.
Contactor
types
Main
poles
Built-in
auxiliary
contacts
Front-mounted accessories Side-mounted accessories
Auxiliary contact blocks & electronic timers Electrical and Auxiliary contact
blocks
mechanical interlock set
TEF4... or (between 2 contactors)
Left side Right side
1-pole CA4 / CC4 2-pole CAT4-11 4-pole CA4 VEM4 2-pole CAL4-11
Max. N.C. built-in and add-on N.C. auxiliary contacts: 4 N.C. max. on positions 1, 2, 3, 4 and 3 N.C. max. on positions 1 ±30°, 5
AF09 ... AF16
Sz. 00...0
3 0 0 14 max.
or
1
or
1
+
1
2 max. –––
+
1
+
1
3 max.
+
1
+
1
or
1
AF09 ... AF16
AF26 ... AF38
Sz. 00...1
3
3
0
0
1
0
0
0
4 max.
or
1
or
1
+
1
2 max.
or
1
+
1
+
1
3 max.
+
1
+
1
or
1
NOTE: Fitting details same for AF...Z contactors
Overload relays fitting details (1)
Contactor types Thermal overload relays Electronic overload relays
AF09 ... AF38, Sz. 00...1 TF42 (0.10...38 A) EF19 (0.10...18.9 A)
AF26 ... AF38, Sz. 1 EF45 (9...38 A)
The addition of an overload relay on the contactor does not prevent tting of many other accessories as shown above.
(1) Direct mounting - No kit required.
Contactor and main accessories (other accessories available)
VEM4 mechanical and electrical interlock set including:
– VM4 mechanical interlock unit with 2 xing clips
– VE4 electrical interlock block with A2-A2 connection
A2
VE4 2
AF contactor
4-pole CA4 1
1 2-pole CAT4-11
1-pole CA4, CC4 1
VM4 2
1-pole
CA4, CC4 1
2-pole CAL4-11 1
2-pole CAL4-11 1
AF contactor
(without top mounted
coil terminal block)
TF42
EF.. 4
Fixing clips
2
TF42
EF.. 4
A2
AF contactor
1-pole
CA4, CC4 1
3 Timer TEF4...
2
1 Auxiliary contacts ......................................... Page 1.46
2 Mech./Elect. interlocks ................................. Page 1.56
3 Electronic timers ........................................... Page 1.59
Reversing kits ............................................... Page 1.62
Wye-delta kits ............................................... Page 1.63
Coupling units .............................................. Page 1.64
4 Thermal & electronic overload relays ..............Chapter 2
Manual motor protectors ...............................Chapter 4
Low Voltage Products & Systems 1.37
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
A/E/L30...A/E/L40; A/E/F50...A/E/F75; A/E/F50NZ...A/E/F75N3
3-pole contactors
Accessory tting details
Main accessory fitting details
Many configurations of accessories are possible depending on whether these are front-mounted or side-mounted.
Contactor
types
Main
poles
Built-in
auxiliary
contacts
Front-mounted accessories Side-mounted accessories
Auxiliary contact blocks Electronic timer Auxiliary contact
blocks
Interlock unit
1-pole CA5-.. 4-pole CA5-.. TEF5 2-pole CAL5-11 VM5-.. or VE5-..
A30...A40 3 0 101 to 5 x CA5-..
or
1 x CA5-.. (4-pole)
or
1 x TEF5
+
1 to 2 x CAL5-11
or
1 x VM5-1 or VE5-1
3 0 0 1(2) + 1 x 1-pole CA5-.. + 1 x CA5-.. (1-pole) +1 x CAL5-11
A50 ... A75 3 0 0 0 1 to 6 x CA5-..
or
1 x CA5-.. (4-pole)
or
1 x TEF5
+
1 to 2 x CAL5-11
or
1 x VE5-2
Sz. 2...3 + 2 x 1-pole CA5-.. + 2 x CA5-.. (1-pole) +1 x CAL5-11
AL30...AL40 3 0 101 to 5 x CA5-.. (2)
or
1 x CA5-.. (4-pole) (2)
or
1 x CAL5-11 (3)
+
1 x VM5-1 or VE5-1 (1)
3 0 0 1+ 1 x 1-pole CA5-..
AE50 ... AE75 3 0 0 0 1 to 6 x CA5-..
or
1 x CA5-.. (4-pole)
or
1 x TEF5
+
1 x CAL5-11
or
1 x VE5-2
Sz. 2...3 + 2 x 1-pole CA5-.. + 2 x CA5-.. (1-pole)
AF50 ... AF75 3 0 0 0 1 to 6 x CA5-..
or
1 x CA5-.. (4-pole)
or
1 x TEF5
+
1 to 2 x CAL5-11
or
1 x VE5-2
Sz. 2...3 + 2 x 1-pole CA5-.. + 2 x CA5-.. (1-pole) +1 x CAL5-11
(1) With VE5-1 interlock unit, a maximum of 3 N.O. auxiliary contacts are permitted. VE5-1, VM5-1 not allowed in mounting position 1 ±30°.
(2) 2 N.C. CA5-.. auxiliary contacts maximum in mounting position 5.
(3) CAL5-11 not allowed in mounting position 1±30°.
Overload relays fitting details (4)
Contactor types Thermal overload relays Electronic overload relays
A30...A40, AL30...AL40 TA25DU (0.1...32 A) or TA42DU (18...42 A) E45DU (9...45 A)
A50 … A75, AE50 … AE75, AF50 … AF75, Sz. 2...3 TA75DU (18...80 A) E80DU (27...80 A)
The addition of an overload relay on the contactor does not prevent tting of many other accessories as shown above.
(4) Direct mounting - No kit required.
Contactor and main accessories (other accessories available)
RV5/..
4
VE5-1
2
CAL5-11
1
TA
overload relay 5
A.. contactor
CA5-10 1
CA5-22M 1
TP40DA 3
1 Auxiliary contacts ..................................... Page 1.48
2 Mech./elect. interlocks ............................. Page 1.57
3 Electronic timers ....................................... Page 1.59
4 Surge suppressors ................................... Page 1.52
Reversing kits ........................................... Page 1.62
Wye-delta kits ........................................... Page 1.63
Coupling units ...............................Pages 1.64...1.65
5 Thermal & electric overload relays ..............Chapter 2
Manual motor protectors ...........................Chapter 4
1.38 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
A/F95...A/F110, 3-pole
Accessory tting details
Main accessory fitting details
Many configurations of accessories are possible depending on whether these are front-mounted or side-mounted.
Contactor
types
Main
poles
Available
auxiliary
contacts
Front-mounted accessories Side-mounted accessories
Auxiliary contact blocks Auxiliary contact blocks Interlock unit
1-pole CA5- .. 4-pole CA5- .. 2-pole CAL.. VE5-2
A95, A110 3 0 0 0 1 to 6 x CA5-..
or
1 x CA5-.. (4-pole)
+
1 to 2 x CAL18-11
or
1 x VE5-2
+ 2 x 1-pole CA5-.. +1 x CAL18-11
AF95, AF110 3 0 0 0 1 to 6 x CA5-..
or
1 x CA5-.. (4-pole)
+
1 to 2 x CAL18-11
or
1 x VE5-2
+ 2 x 1-pole CA5-.. +1 x CAL18-11
Overload relays fitting details (1)
Contactor types Thermal overload relays Electronic overload relays
A95, A110 TA80DU (29...80 A) or TA110DU (65...110 A) E140DU (50...140 A)
AF95, AF110
The addition of an overload relay on the contactor does not prevent tting of many other accessories as shown above.
(1) Direct mounting - No kit required.
Contactor and main accessories (other accessories available)
VE5-2
2
CAL18-11
1
TA
overload relay 4
A.. contactor
CA5-10 1
CA5-22E 1
RV5/..
3
1 Auxiliary contacts ......................................Page 1.48
2 Mech./elect. interlocks ..............................Page 1.57
3 Surge suppressors ....................................Page 1.52
Reversing kits ............................................Page 1.62
Wye-delta kits ............................................Page 1.63
Coupling units ............................... Pages 1.64...1.65
4 Thermal & electronic overload relays .......... Chapter 2
Low Voltage Products & Systems 1.39
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
2
1
5
4
1
3
A/F145...AF2050; A/F145N4...AF1650N8, 3-pole
Accessory tting details
Main accessory fitting details
Contactor
types
Main
poles
Available
auxiliary
contacts
Side-mounted accessories
Add-on auxiliary contact blocks Mechanical
interlock units
Mounting and positioning
Factory mounted auxiliary contacts
Add-on CAL18-11 auxiliary contacts
Add-on CAL18-11B auxiliary contacts
CAL18-11, CAL18-11B (3)
(for two horizontal
mounted contactors)
Contactors + auxiliary contact blocks
A145 ... A300
AF145 ... AF2050
Sz. 4...8
3 0 1 1 1 x CAL18-11
+
2 x CAL18-11B
BB
Contactors with mechanical interlocking + auxiliary contact blocks
A145 ... A185
AF145 ... AF185
Sz. 4
3 0 1 1 2 x CAL18-11 (1)
+
3 x CAL18-11B (1)
+
VM...H (2)
BB B
A210 ... A300
AF210 ... AF2050
Sz. 5...8
3 0 1 1 2 x CAL18-11 (1)
+
4 x CAL18-11B (1)
+
VM...H (2)
BB
B B
(1) Total number of auxiliary contact blocks for the two contactors. (2) Interlock type, according to the contactor ratings (see "Accessories").
(3) The CEL18-.. auxiliary contact blocks can replace the CAL18-11 and CAL18-11B. Though, no auxiliary contact block can be mounted outside the CEL18-..
Main accessories (other accessories available) AF185 shown on picture
Overload relays fitting details
Contactor types Thermal overload relays Electronic overload relays
A145, A185, Sz. 4 TA200DU (80...200 A) (4) E200DU (60...200 A) (4)
A210, A300, Sz. 5 TA450DU (100...310 A) (4) or TA450SU (130...310 A) (5) E320DU (100...320 A) (4)
AF400, AF460, Sz. 6 E500DU (150...500 A) (5)
AF580, AF750, Sz. 7 E800DU (250...800 A) (5)
AF1350, AF1650, Sz. 8 E1250DU (375...1250 A) (5)
The addition of a thermal or electronic overload relay on the contactor does not prevent tting of many other accessories as shown in "Main accessory tting details" table.
(4) Direct mounting - No kit required.
(5) Mounting kit required (see "Motor protection").
1 Auxiliary contacts ........................................... Page 1.48
2 Mechanical interlocks .................................... Page 1.57
Reversing kits ................................................. Page 1.62
Wye-delta kits ................................................. Page 1.63
3 Coupling units ...................................... Page 1.64...1.65
Lug kits ......................................................... Page 1.67
4 Terminal shrouds ............................................ Page 1.68
5 Thermal & electronic overload relays ...............Chapter 2
1.40 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
AS/L09...AS/L16, 3 pole, w/screw terminals
Accessory tting details
Main accessory fitting details
Many configurations of accessories are possible depending on whether these are front-mounted or side-mounted.
Contactor
types
Main
poles
Built-in
auxiliary
contacts
Front-mounted accessories Side-mounted accessories
Auxiliary contact blocks Electronic timer Mechanical interlock unit
(between 2 contactors)
1-pole CA3 TEF3 VM3 Surge suppressors
AS09...AS16 3 0 102 max.
or
1
+
1
+
RV5
or
RC5-1
30 01
AS09...AS16 3 0 3 2 ––1
+
RV5
or
RC5-1
ASL09...ASL16 3 0 102 max.
or
1
+
1
+
RV5
or
RT5
30 01
ASL09...ASL16 3 0 3 2 ––1
+
RV5
or
RT5
Overload relays fitting details (1)
Contactor types Thermal overload relays
AS09…AS16 T16 (0.10...16 A)
ASL09…ASL16
The addition of an overload relay on the contactor does not prevent tting of many other accessories as shown above.
(1) Direct mounting - No kit required.
Contactor and main accessories (other accessories available)
BEY16C-3
6
BER16C-3
5
BEA16-3 7
MS116 9
VM3
(optional)
VM3
2
T16
8
T16
8
AS
ASL
Contactors
TEF3 3
CA3
1
RV5, RC5-1 or RT5 4
AS
ASL
Contactors
AS
ASL
Contactors
1 Auxiliary contacts ........................................... Page 1.50
2 Mechanical interlocks .................................... Page 1.56
3 Electronic timers ............................................. Page 1.59
4 Surge suppressors ......................................... Page 1.52
5 Reversing kits ................................................. Page 1.62
6 Wye delta kits ................................................. Page 1.63
7 Coupling units ................................................ Page 1.64
8 Thermal overload relays ................................... Chapter 2
9 Manual motor protectors .................................Chapter 4
Low Voltage Products & Systems 1.41
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
AS/L09...AS/L16, 3-pole w/spring terminals
Accessory tting details
Main accessory fitting details
Contactor
types
Main
poles
Built-in
auxiliary
contacts
Front-mounted accessories Side-mounted accessories
Auxiliary contact blocks Mechanical
interlock unit
(between 2 contactors)
1-pole CA3..S VM3 Surge suppressors
AS09..S ... AS16..S 3 0 102 max.
+
1
+
RV5
or
RC5-1
AS09..S ... AS16..S 30 01
AS09..S … AS16..S 3 0 3 2 1
+
RV5
or
RC5-1
ASL09..S ... ASL16..S 3 0 102 max.
+
1
+
RV5
or
RT5
ASL09..S ... ASL16..S 30 01
ASL09..S … ASL16..S 3 0 3 2 1
+
RV5
or
RT5
Contactor and main accessories (other accessories available)
RV5, RC5-1 or RT5 3
VM3
2
AS..S
ASL..S
Contactors
AS..S
ASL..S
Contactors
CA3..S
1
CA3..S 1
1 Auxiliary contacts ........................................... Page 1.50
2 Mechanical interlocks .................................... Page 1.56
3 Surge suppressors ......................................... Page 1.52
4 Coupling units ................................................ Page 1.64
1.42 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
AF09(Z)...AF38(Z), 4-pole
Accessory tting details
Main accessory fitting details
Many configurations of accessories are possible depending on whether these are front-mounted or side-mounted.
Contactor
types
Main
poles
Built-in
auxiliary
contacts
Front-mounted accessories Side-mounted accessories
Auxiliary contact blocks & electronic timers Electrical and
mechanical interlock set
Auxiliary contact blocks
TEF4... or (between 2 contactors)
Left side Right side
1-pole CA4 / CC4 2-pole CAT4-11 4-pole CA4 VEM4 2-pole CAL4-11
Max. add-on N.C. auxiliary contacts: 4 N.C. max. on positions 1, 2, 3, 4 and 3 N.C. max. on positions 1 ±30°, 5
AF09, AF16 4 0 0 0
4 max.
or
1
or
1
+
1
2 max.
or
1
+
1
+
1
3 max.
+
1
+
1
or
1
Max. add-on N.C. auxiliary contacts: 3 N.C. max. on positions 1, 2, 3, 4 and 2 N.C. max. on positions 1 ±30°, 5
AF26, AF38 4 0 0 0
4 max.
or
1
or
1
+
1
2 max.
or
1
+
1
+
1
3 max.
+
1
+
1
or
1
AF09, AF16 2 2 0 0
0
4 max.
or
1
or
1
+
1
AF26, AF38 2 2 0 2 max.
or
1
+
1
+
1
NOTE: Fitting details same for AF...Z contactors.
Contactor and main accessories (other accessories available)
VEM4 mechanical and electrical interlock set including:
– VM4 mechanical interlock unit with 2 xing clips
– VE4 electrical interlock block with A2-A2 connection
A2
VE4
2
AF contactor
4-pole CA4
1
2-pole CAT4-11
TEF4... timer
1-pole CA4, CC4 1
VM4
2
1-pole
CA4, CC4
1
2-pole CAL4-11
1
2-pole CAL4-11 1
AF contactor
(without top mounted
coil terminal block)
Fixing clips
2
A2
AF contactor
1-pole
CA4, CC4 1
2
1 Auxiliary contacts ........................................... Page 1.46
2 Mech./Elec. interlocks ................................... Page 1.57
3 Electronic timers ............................................. Page 1.59
Low Voltage Products & Systems 1.43
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
A/E/F45...A/E/F75, 4-Pole
Accessory tting details
Main accessory fitting details
Many configurations of accessories are possible depending on whether these are front-mounted or side-mounted.
Contactor
types
Main
poles
Available
auxiliary
contacts
Front-mounted accessories Side-mounted accessories
Auxiliary contact blocks Electronic timer Auxiliary contact
blocks
Interlock unit
1-pole CA5-.. 4-pole CA5-.. TP.. A 2-pole CAL5-11 VE5-..
A45 ... A75 4 0 0 0 1 to 6 x CA5-..
or
1 x CA5-.. (4-pole)
or
1 x TEF5...
+
1 to 2 x CAL5-11
or
1 x VE5-2
+ 2 x 1-pole CA5-.. + 2 x CA5-.. (1-pole) + 1 x CAL5-11
2 2 0 0 (1) 1 to 6 x CA5-..
or
1 x CA5-.. (4-pole)
or
1 x TEF5...
+
1 to 2 x CAL5-11
+ 2 x 1-pole CA5-.. + 2 x CA5-.. (1-pole)
AE45 ... AE75 4 0 0 0 1 to 6 x CA5-..
or
1 x CA5-.. (4-pole)
or
1 x TEF5...
+
1 x CAL5-11
or
1 x VE5-2
+ 2 x 1-pole CA5-.. + 2 x CA5-.. (1-pole)
2 2 0 0 (1) 1 to 6 x CA5-..
or
1 x CA5-.. (4-pole)
or
1 x TEF5...
+
1 x CAL5-11
+ 2 x 1-pole CA5-.. + 2 x CA5-.. (1-pole)
AF50 ... AF75 4 0 0 0 1 to 6 x CA5-..
or
1 x CA5-.. (4-pole)
or
1 x TEF5...
+
1 to 2 x CAL5-11
or
1 x VE5-2
+ 2 x 1-pole CA5-.. + 2 x CA5-.. (1-pole) + 1 x CAL5-11
2 2 0 0 (1) 1 to 6 x CA5-..
or
1 x CA5-.. (4-pole)
or
1 x TEF5...
+
1 to 2 x CAL5-11
+ 2 x 1-pole CA5-.. + 2 x CA5-.. (1-pole)
(1) 2 x N.C. CA 5-.. auxiliary contacts maximum.
Contactor and main accessories (other accessories available)
RV5/..
4
VE5-1
2
CAL5-11
1
A.. contactor
CA5-10
1
CA5-22E
1
TEF5... timer 3
1 Auxiliary contacts ........................................... Page 1.48
2 Mech./Elec. interlocks ................................... Page 1.57
3 Electronic timers ............................................. Page 1.59
4 Surge suppressors ......................................... Page 1.52
1.44 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Mounting positions of the auxiliary contact Auxiliary contact types and connecting diagrams
21
22
13
14
CAL16-11 A CAL16-11 B
43
44
31
32
CAL16-11 C
61
62
53
54
CAL16-11 D
83
84
71
72
CCL16-11 E
47
48
35
36
(1)
(1) Contact 35-36 used for some
types of EK... contactors
EK110... EK1000, 4-pole
Accessory tting details
EK... 4-pole contactors
Contactor
types
Main
poles
Available
auxiliary
contacts
Add-on auxiliary contact
blocks
2-pole CAL16-11 ...
Mounting and positioning
Factory mounted auxiliary contacts
Add-on CAL16-11 auxiliary contacts
AC operated, 50 Hz, 60 Hz or 50/60 Hz
EK110 ... EK1000 4 0 1 1
A
+
1 x CAL16-11B
AC DB
+
1 x CAL16-11C
+
1 x CAL16-11D
AC operated, 40...400 Hz
EK110 ... EK210 4 0 2 1
A
40 ...
400 Hz
E
+
1 x CAL16-11C
AC E
40 ...
400 Hz
DC operated
EK110 ... EK1000 4 0 2 1
AE
+
1 x CAL16-11C
AC E
EK ... 4-pole reversing contactors with VH... mechanical and electrical interlock units
"Left hand"
contactors
Interlocking
"Right hand"
contactors
Add-on auxiliary contact
blocks
2-pole CAL16-11 ...
Mounting and positioning
Factory mounted auxiliary contacts
Add-on CAL16-11 auxiliary contacts
AC operated, 50 Hz, 60 Hz or 50/60 Hz
EK110 ... EK150 VH145 EK110, EK150
+
1 x CAL16-11C
AC DB
EK175, EK210 VH300 EK175, EK210 1 x CAL16-11D
EK370 ... EK1000 VH800 EK370 ... EK1000
AC operated, 40...400 Hz
EK110 ... EK150 VH145 EK110, EK150
E E
40 ...
400 Hz
40 ...
400 Hz
EK175, EK210 VH300 EK175, EK210
EK370 ... EK1000 VH800 EK370 ... EK1000
DC operated, 50 Hz, 60 Hz or 50/60 Hz
EK110 ... EK150 VH145 EK110, EK150
EE
EK175, EK210 VH300 EK175, EK210
EK370 ... EK1000 VH800 EK370 ... EK1000
Main accessory fitting details
Auxiliary contacts ................................................ Page 1.48
Low Voltage Products & Systems 1.45
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Coordination with short-circuit protection devices
A motor starter is typically made up of a switching device (contactor) and an overload protection device (see opposite page
"Basic functions").
These two devices must be coordinated with an equipment capable of providing protection against short circuit (SCPD: Short-Circuit Protec-
tion Device).
A complete data base of coordination tables, according to IEC 60947-4-1 (EN 60947-4-1) or UL 508 / UL 60947-4-1, is available on the ABB
Website: see below.
Selection
Results
Search results displayed at the bottom of the selection page.
Only the most appropriate solutions to your application, will be displayed at the bottom of the page.
"Enable Smart Current Search" function featured for the short-circuit current where "near to" selected values also are included in the result.
Possible to print the page to a pdf le or from your printer.
"Clear selection" function to deselect all selected.
Access
To find the coordination tables for motor protection,
please see:
www.abb.com/lowvoltage then go to the right menu:
"Support", select: "Online Product Selection Tools"
then select "Coordination Tables for motor protec-
tion"
Short-circuit protection devices
Air circuit breakers
Fuses
Miniature circuit breaker
Moulded case circuit breaker
Manual motor starter
Starter type
Direct-on-line normal start
Direct-on-line heavy duty
Star-delta normal start
Soft starter normal start
Coordination
IEC type 1 or type 2
UL type A to Type F
http://applications.it.abb.com/SOC/Page/Selection.aspx
1.46 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Auxiliary contact blocks
AF09(Z)...AF38(Z); AF09N00(Z)...AF26N1(Z)
Ordering details (1)
For contactors
Auxiliary contacts
Catalog number
Front-mounted instantaneous auxiliary contact blocks
AF09 ... AF38
4-pole NF
10––CA4-10
01 ––CA4-01
AF09 ... AF16..-30-10 2 2 ––CA4-22M
31 ––CA4-31M
13––CA4-13M
0 4 ––CA4-04M
AF26 ... AF38..-30-00
AF09 ... AF38..-40-00
AF09 ... AF38..-22-00
2 2 ––CA4-22E
31 ––CA4-31E
4 0 ––CA4-40E
AF26 ... AF38..-30-00
AF09 ... AF16..-40-00
0 4 ––CA4-04E
AF09 ... AF16..-30-01 2 2 ––CA4-22U
31 ––CA4-31U
4 0 ––CA4-40U
4-pole NF 4 0 ––CA4-40N
31 ––CA4-31N
2 2 ––CA4-22N
13––CA4-13N
NF..40E 0 4 ––CA4-04N
Front-mounted auxiliary contact blocks with N.O.
leading contact and N.C. lagging contact
AF09 ... AF38
4-pole NF
1 0CC4-10
01CC4-01
Side-mounted instantaneous auxiliary contact blocks
AF09 ... AF38, NF 1 1 CAL4-11
Front-mounted instantaneous auxiliary contact and
A1/A2 coil terminal blocks
AF09 ... AF16..-30-10 1 1 CAT4-11M
AF26 ... AF38..-30-00
AF09 ... AF38..-40-00
AF09 ... AF38..-22-00
1 1 CAT4-11E
AF09 ... AF16..-30-01 1 1 CAT4-11U
(1) For each contactor or contactor relay type, refer to "Accessory tting details"
table.
Note: CAT4 not ttable on AF..Z contactors with DC control voltage 12…20 V DC.
Auxiliary contacts same for AF...Z contactors
CA4-10
CA4-22M
CAT4-11E
CAL4-11
Low Voltage Products & Systems 1.47
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Auxiliary contact blocks
AF09(Z)... AF38(Z); AF09N00(Z)...AF26N1(Z)
Technical data
Types
1-pole CA4, 1-pole CC4, 4-pole CA4, 2-pole CAT4, 2-pole CAL4
Contact utilization characteristics according to IEC
Standards IEC 60947-5-1 and EN 60947-5-1
Rated insulation voltage Ui acc. to IEC 60947-5-1 690 V
Rated impulse withstand voltage Uimp 6 kV
Rated operational voltage Ue max. 24...690 V
Conventional thermal current Ith - θ ≤ 40 °C 16 A
Rated frequency limits 25…400 Hz
Ie / Rated operational current AC-15 24-127 V 50/60 Hz 6 A
acc. to IEC 60947-5-1 220-240 V 50/60 Hz 4 A
400-440 V 50/60 Hz 3 A
500 V 50/60 Hz 2 A
690 V 50/60 Hz 2 A
Making capacity acc. to IEC 60947-5-1 10 x Ie AC-15
Breaking capacity acc. to IEC 60947-5-1 10 x Ie AC-15
Ie / Rated operational current DC-13 24 V DC 6 A / 144 W
acc. to IEC 60947-5-1 48 V DC 2.8 A / 134 W
72 V DC 1 A / 72 W
110 V DC 0.55 A / 60 W
125 V DC 0.55 A / 69 W
220 V DC 0.27 A / 60 W
250 V DC 0.27 A / 68 W
400 V DC 0.15 A / 60 W
500 V DC 0.13 A / 65 W
600 V DC 0.1 A / 60 W
Short-circuit protection device gG type fuse 10 A
Rated short-time withstand current Icw for 1.0 s 100 A
θ = 40 °C for 0.1 s 140 A
Minimum switching capacity 12 V / 3 mA
with failure rate acc. to IEC 60947-5-4 10-7
Heat dissipation per pole at 6 A 0.1 W
Mechanical durability Number of operating cycles 10 million operating cycles
Max. switching frequency 3600 cycles/h
Max. electrical switching frequency AC-15 1200 cycles/h
DC-13 900 cycles/h
Mechanically linked contact acc. to annex L of IEC 60947-5-1 Yes for N.O. and N.C. contacts
Mirror contacts acc. to annex F of IEC 60947-4-1 Yes for N.C. contacts
Contact utilization characteristics according to UL / CSA
Standards UL 508, CSA C22.2 N°14
Max. operational voltage 600 V AC, 600 V DC
Pilot duty A600, Q600
AC thermal rated current 10 A
AC maximum volt-ampere making 7200 VA
AC maximum volt-ampere breaking 720 VA
DC thermal rated current 2.5 A
DC maximum volt-ampere making-breaking 69 VA
Connecting characteristics
Screw terminals (Delivered in open position, screws of un-
used terminals must be tightened)
All terminals M3.5
Connection capacity (min…max.)
Rigid solid
1 x 1...2.5 mm²
2 x 1...2.5 mm²
Flexible with non insulated ferrule
1 x 0.75...2.5 mm²
2 x 0.75...2.5 mm²
Flexible with insulated ferrule
1 x 0.75...2.5 mm²
2 x 0.75…1.5 mm²
L
l Lug
L ≤ 8 mm
I > -
Connection capacity acc. to UL / CSA 1 or 2 x AWG 18…14, solid / stranded
Stripping length 10 mm
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN
60529
IP20
Screwdriver type Flat Ø 5.5 / Pozidriv 2
Tightening torque 1.2 Nm / 11 lb.in
1.48 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Auxiliary contact blocks
A/E/L9...A/E/L40; A/E/F50...AF2050; A/E/F50N2... AF1650N8
Ordering details
For contactors
Number
of
blocks
(1)
Auxiliary contacts
Catalog number
Front-mounted instantaneous auxiliary contact blocks, 1-pole
A9...A40, T/AL9...T/AL40
A45 ... A110
AF45, AF110
AE45 ... AE75, TAE45 ... TAE75
1-5
10 CA5-10
1-6
01 CA5-01
1-6
1 0CC5-10
1-6
01CC5-01
Front-mounted instantaneous auxiliary contact blocks, 4-pole
A45 ... A110
AE45 ... AE75
AF45 ... AF110
TAE45 ... TAE75
1
4 0 CA5-40E
31 CA5-31E
2 2 CA5-22E
0 4 CA5-04E
1 1 1 1 CA5-11/11E
A40-30-10
AL40-30-10
TAL40-30-10
1
31 CA5-31M
2 2 CA5-22M
13 CA5-13M
0 4 CA5-04M
1 1 1 1 CA5-11/11M
A40-30-10
AL40-30-10
TAL40-30-10
1
4 0 CA5-40U
31 CA5-31U
2 2 CA5-22U
0 4 CA5-04U
Side-mounted instantaneous auxiliary contact blocks, 2-pole
A9...A75
T/AL9...T/AL40
AE9...T/AE75
AF45 ... AF75
UA16 ... UA75
1-2
1
1
1-2
1-2
1 1 CAL5-11
A95 ... A300
AF95 ... AF2050 1-2 1 1 CAL18-11
UA95, UA110
A145 ... A300 1-2(2) 1 1 CAL18-11B
AF145 ... AF2050 1 1
(1) For each contactor type, refer to "Accessory tting details" table.
(2) 2 blocks CAL18-11 + 2 blocks CAL18-11B.
Note:
The front-mounted auxiliary contact blocks provided for the A... contactors can be used for the
UA..., GA... and GAE... types
The CAL... auxiliary contact blocks can be used for GA... contactors:
GA75-10-00: 2 x CAL5-11 blocks
GA75-10-11: 1 x CAL5-11 block
GAE75-10-00: 1 x CAL5-11 block
GAE75-10-11: no add-on block.
The CAL... auxiliary contact blocks can be used for UA..RA contactors. See "Accessory tting
details" for this contactor type.
CA5-10
CA5-40E
CAL5-11
CAL18-11
Low-energy side-mounted contact blocks, 1-pole
A145...A300
1-2 10
CEL18-10
AF145...AF2050
1-2 01
CEL18-01
Low Voltage Products & Systems 1.49
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Auxiliary contact blocks
A/E/L9...A/E/L40; A/E/F50...AF2050; A/E/F50N2...AF1650N8
Technical data
Types 1-pole CA5, 4-pole CA5,
1-pole CC5, 2-pole CAL5 2-pole CAL18 1-pole CEL18
Contact utilization characteristics according to IEC
Standards IEC 60947-5-1 and EN 60947-
5-1
Rated insulation voltage Ui acc. to IEC 60947-5-1 690 V 250 V
Rated impulse withstand voltage Uimp 6 kV -
Rated operational voltage Ue max. 24...690 V 125 V
Conventional thermal current Ith - θ40 °C 16 A 0.1
Rated frequency limits Consult factory
Ie / Rated operational current AC-15 24-127 V 50/60 Hz 6 A 0.1 A (AC-14)
acc. to IEC 60947-5-1 220-240 V 50/60 Hz 4 A -
400-440 V 50/60 Hz 3 A -
500 V 50/60 Hz 2 A -
690 V 50/60 Hz 2 A -
Making capacity acc. to IEC 60947-5-1 10 x Ie AC-15 10 x Ie AC-14
Breaking capacity acc. to IEC 60947-5-1 10 x Ie AC-15 10 x Ie AC-14
Ie / Rated operational current DC-13 24 V DC 6 A / 144 W 0.1 A (DC-12)
acc. to IEC 60947-5-1 48 V DC 2.8 A / 134 W 0.1 A (DC-12)
72 V DC 1 A / 72 W 0.1 A (DC-12)
110 V DC 0.55 A / 60 W 0.1 A (DC-12)
125 V DC 0.55 A / 69 W -
220 V DC 0.27 A / 60 W -
250 V DC 0.27 A / 68 W -
Short-circuit protection device gG type fuse 10 A 0.1 (FF type HRC fuses)
Rated short-time withstand current Icw for 1.0 s 100 A -
θ = 40 °C for 0.1 s 140 A -
Minimum switching capacity 17 V / 1 mA (24 V / 50 mA for A/
F95…110)
24 V / 50 mA (0.5M of operating
cycles)
3 V / 1 mA
with failure rate acc. to IEC 60947-5-4 10-7 - -
Heat dissipation per pole at 6 A 0.1 W 0.15 W 0.15 W
Mechanical durability Number of operating cycles 10 million (3M for A/F95…110) "5M (A/F95…185), 3M (A/
F210…750),
0.5M (AF1350…2050)"
1 million
Max. switching frequency 3600 cycles/h 1200 cycles per hour
Max. electrical switching frequency AC-15 1200 cycles/h 1200 cycles per hour (AC-14)
DC-13 900 cycles/h -
Mechanically linked contact acc. to annex L of IEC 60947-5-1 Yes for N.O. and N.C. contacts -
Mirror contacts acc. to annex F of IEC 60947-4-1 Yes for N.C. contacts -
Contact utilization characteristics according to UL / CSA
Standards UL 508, CSA C22.2 N°14
Max. operational voltage 600 V AC, 250 V DC 125 V AC, 24 V DC
Pilot duty A600, Q300 0.1 A (AC), 5 mA (DC)
AC thermal rated current 10 A 0.1 A
AC maximum volt-ampere making 7200 VA 12.5 VA
AC maximum volt-ampere breaking 720 VA 12.5 VA
DC thermal rated current 2.5 A 5 mA
DC maximum volt-ampere making-breaking 69 VA 1.2 VA
Connecting characteristics
Screw terminals (Delivered in open position, screws of unused
terminals must be tightened)
All terminals M3.5
Connection capacity (min…max.)
Rigid solid 1 x 1…4 mm²
2 x 1…4 mm²
Flexible with non insulated ferrule 1 x 0.75...2.5 mm²
2 x 0.75…2.5 mm²
Flexible with insulated ferrule 1 x -
2 x -
L
l Lugs
L ≤ 8 mm
I > 3.7 mm
Connection capacity acc. to UL / CSA 1 or 2 x AWG 18…12, solid / stranded
Stripping length 10 mm
Degree of protection IP20
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Screwdriver type Flat Ø 5.5 / Pozidriv 2
Tightening torque 1 Nm / 9 lb.in
1.50 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
CA3-10
Auxiliary contact blocks
(V)AS/L09...(V)AS/L16; (V)B/C6...(V)B/C7; EK
Ordering details
For contactors For contactor relays
Contact
blocks Catalog number
1-pole auxiliary contact blocks with screw terminals
AS09 ... AS16
ASL09 ... ASL16
NS, NSL
1 CA3-10
1 CA3-01
For contactors For contactor relays
Contact
blocks Catalog number
1-pole auxiliary contact blocks with spring terminals
AS09..S ... AS16..S NS..S, NSL..S
1 CA3-10S
ASL09..S ... ASL16..S
1 CA3-01S
CA3-10S
For contactors Number
of blocks
Auxiliary contacts
Catalog number
2-pole auxiliary contacts N.O. + N.C.
EK 1 1 1 CAL16-11A
1 1 1 CAL16-11B
1 1 1 CAL16-11C
1 1 1 CAL16-11D
1 1 1 CCL16-11E (1)
(1) Mounting of CCL16-11E blocks does not allow an additional second block to
be added on top of it.
All DC operated EK... contactors are equipped with one CCL16-11E on the right
side.
Mounting positions
of the CAL16-11
For contactors
Auxiliary
contacts
Catalog number
Front-mounted instantaneous auxiliary contact blocks (not allowed for
mounting on TBC, B6S, B7S, interface contactors)
1)
B6-, B7-40-00, BC6-, BC7-40-00
VB6, VB7, VBC6, VBC7, VB6A, VB7A
VBC6A, VBC7A
1 1 CAF6-11E
2 0 CAF6-20E
0 2 CAF6-02E
B6-, B7-30-10, BC6-, BC7-30-10
VB6, VB7, VBC6, VBC7, VB6A, VB7A
VBC6A, VBC7A
1 1 CAF6-11M
2 0 CAF6-20M
0 2 CAF6-02M
B6-, B7-30-01, BC6-, BC7-30-01
VB6, VB7, VBC6, VBC7, VB6A, VB7A
VBC6A, VBC7A
1 1 CAF6-11N
2 0 CAF6-20N
0 2 CAF6-02N
Side-mounted instantaneous auxiliary contact block 1)
B6-, B7-40-00, BC6-, BC7-40-00 1 1 CA6-11E
B6-, B7-30-10, BC6-, BC7-30-10 1 1 CA6-11M
B6-, B7-30-01, BC6-, BC7-30-01 1 1 CA6-11N
Side-mounted instantaneous auxiliary contact block with
soldering pins 1)
B6-, B7-40-00-P, BC6-,BC7-40-00-P 1 1 CA6-11E-P
B6-, B7-30-10-P, BC6-, BC7-30-10-P 1 1 CA6-11M-P
B6-, B7-30-01-P, BC6-, BC7-30-01-P 1 1 CA6-11N-P
CA6-11E
CA6-11E-P
Low Voltage Products & Systems 1.51
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Auxiliary contact blocks
(V)AS/L09...(V)AS/L16
Technical data
Types 1-pole CA3 1-pole CA3…S
Contact utilization characteristics according to IEC
Standards IEC 60947-5-1 and EN 60947-5-1
Rated insulation voltage Ui acc. to IEC 60947-5-1 690 V
Rated impulse withstand voltage Uimp 6 kV
Rated operational voltage Ue max. 690 V
Conventional thermal current Ith - θ ≤ 40 °C 10 A
Rated frequency limits 25…400 Hz
Ie / Rated operational current AC-15 24-127 V 50/60 Hz 6 A
acc. to IEC 60947-5-1 220-240 V 50/60 Hz 4 A
400-440 V 50/60 Hz 3 A
500 V 50/60 Hz 2 A
690 V 50/60 Hz 2 A
Making capacity acc. to IEC 60947-5-1 10 x Ie AC-15
Breaking capacity acc. to IEC 60947-5-1 10 x Ie AC-15
Ie / Rated operational current DC-13 24 V DC 6 A / 144 W
acc. to IEC 60947-5-1 48 V DC 2.8 A / 134 W
72 V DC 1 A / 72 W
110 V DC 0.55 A / 60 W
125 V DC 0.55 A / 69 W
220 V DC 0.27 A / 60 W
250 V DC 0.27 A / 68 W
400 V DC -
500 V DC -
600 V DC -
Short-circuit protection device gG type fuse 10 A
Rated short-time withstand current Icw for 1.0 s 100 A
θ = 40 °C for 0.1 s 140 A
Minimum switching capacity 12 V / 3 mA
with failure rate acc. to IEC 60947-5-4 10-7
Heat dissipation per pole at 6 A 0.1 W
Mechanical durability Number of operating cycles 10 million operating cycles
Max. switching frequency 3600 cycles/h
Max. electrical switching frequency AC-15 1200 cycles/h
DC-13 900 cycles/h
Mechanically linked contact acc. to annex L of IEC 60947-5-1 Yes for N.O. and N.C. contacts
Mirror contacts acc. to annex F of IEC 60947-4-1 Yes for N.C. contacts
Contact utilization characteristics according to UL / CSA
Standards UL 508, CSA C22.2 N°14
Max. operational voltage 600 V AC, 250 V DC
Pilot duty A600, Q300
AC thermal rated current 10 A
AC maximum volt-ampere making 7200 VA
AC maximum volt-ampere breaking 720 VA
DC thermal rated current 2.5 A
DC maximum volt-ampere making-breaking 69 VA
Connecting characteristics
Screw terminals (Delivered in open position, screws of unused
termnials must be tightened)
All terminals M3 N/a - Spring terminals
Connection capacity (min…max.) 0.75...2.5 mm²
Rigid solid 1 x
2 x 0.75...2.5 mm²
Flexible with non insulated ferrule 1 x 0.75...2.5 mm²
2 x 0.75...2.5 mm²
Flexible with insulated ferrule 1 x 0.75...2.5 mm² 0.75…1.5 mm²
2 x 0.75…1.5 mm²
L
l Lugs
L ≤ 7.7 mm -
I > 3.2 mm -
Connection capacity acc. to UL / CSA 1 or 2 x AWG 18…14, solid / stranded
Stripping length 9 mm 10 mm
Degree of protection IP20
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Screwdriver type Flat Ø 5.5 / Pozidriv 2 Flat Ø 3.5
Tightening torque 1 Nm / 9 lb.in -
1.52 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Surge suppressors for contactor coils
0
1000
100
(V)
T
(s)
0
1000
100
NOTE: AF Series contactors include integral surge suppressor
Description
The operation of inductive circuits causes overvoltages, in particular on opening of the contactor coil.
The electromagnetic energy stored in the coil during contactor closing is restored on opening in the form
of surges, the slope and amplitude of which may rise to several kilovolts. A number of drawbacks are
observed ranging from interference on the electronic devices to breakdown of insulators and even destruc-
tion of certain sensitive components.
The graph opposite reproduces the oscillogram showing voltage discharges at the terminals of a 42V / 50Hz
coil without peak clipping. The coil was switched by 8 series-connected poles of a contactor relay.
Following a burst of discharges with a very steep slope a damped oscillation emerges with a peak value of
3500V.
Overvoltage Factor
The overvoltage factor k is defined as the ratio of the maximum overvoltage peak value Ûs to the peak
value Ûc of the coil rated control voltage Uc:
Ûs max.
Ûs max.
Ûs max.
k = in DC: k = or in AC: k =
Ûc
Uc
Uc√2
3500
For example the following is obtained for the above graph: k = 60
42 √2
To reduce the harmful effects of these overvoltages, ABB has developed a range of surge suppressors de-
signed to reduce the k factor defined above and to limit or even completely eliminate the high pre-damping
voltage frequencies.
Each case is different, but the technical data tolerances and the generous sizing of parts have enabled us
to reduce the number of variants.
We have chosen the following solutions: transil diodes, varistors and RC blocks.
Note: A varistor is a resistor whose value decreases to a very large extent when a certain voltage is ap-
plied at its terminals.
RC-EH300/48
RV5
RT5
RC5-1
Ordering details
For contactors
Rated control circuit
voltage
Uc
Catalog number
VAC DC
AS09...AS16; A9 ... A110,
AL9...AL40, ASL09...ASL16
AE9 ... AE75,
TAL9...TAL40,
TAE45 ... TAE75
24...50
RV5/50
50...133
RV5/133
110...250
RV5/250
250...440
RV5/440
AS09...AS16
A9...A40 24...50
RC5-1/50
50...133
RC5-1/133
110...250
RC5-1/250
250...440
RC5-1/440
A45 ... A110 24...50
RC5-2/50
50...133
RC5-2/133
110...250
RC5-2/250
250...440
RC5-2/440
A145 ... A300 250...440
RC5-3/440
AL9...AL40
AE9 ... AE75,
TAL9...TAL40,
TAE45 ... TAE75
ASL09...ASL16
12...32
RT5/32
25...65
RT5/65
50...90
RT5/90
77...150
RT5/150
150...264
RT5/264
EK110 ... EK210 24...48
RC-EH300/48
110...415
RC-EH300/415
EK370 ... EK1000 48...110
RC-EH800/110
EK110 ... EK1000 24...125
RC-EH800/110
EK370 ... EK1000 220...600
RC-EH800/600
Low Voltage Products & Systems 1.53
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Surge suppressors for contactor coils
Technical data
Varistor
RV5/50 RV5/133 RV5/250 RV5/440
Rated control circuit voltage Uc
24...50V AC 50...133V AC 110...250V AC 250...440V AC
24...50V DC 50...133V DC 110...250V DC 250...440V DC
Residual overvoltage (clipping voltage)
132V AC 270V AC 480V AC 825V AC
132V DC 270V DC 480V DC 825V DC
Opening time growth factor
none
Operating temperature
-20...+70°C
Advantages
High energy absorption: good damping - Unpolarized system.
Drawback
Clipping as from Uvdr*, thus voltage front up to this point.
*Uvdr = Varistor operating voltage (voltage dependent resistor), tolerance ± 10%.
RC type
RC5-1/50 RC5-1/133 RC5-1/250 RC5-1/440
Rated control circuit voltage Uc
24...50V AC 50...133V AC 110...250V AC 250...440V AC
Residual overvoltage (clipping voltage)
2 to 3 x Uc max.
Opening time growth factor
2...3
Operating temperature
-20...+70°C
Advantages
Very fast clipping - Attenuation of steep fronts and thus of high frequencies.
Transil diode
RT5/32 RT5/65 RT5/90 RT5/150 RT5/264
Rated control circuit voltage Uc
12...32V DC 25...65V DC 50...90V DC 77...150V DC 150...264V DC
Residual overvoltage (clipping voltage)
50V DC 100V DC 150V DC 210V DC 390V DC
Opening time growth factor
1.1...1.2
Operating temperature
-20...+70°C
Advantages
Good energy absorption - Unpolarized system - Simple, reliable system.
Drawback
Delay on drop out which does not however reduce contactor breaking capacity.
Wiring diagrams
A1
A2
A1
A2
Transil diodeVaristor RC type
For contactors
Rated control circuit
voltage UCConnection type Catalog
number
V DC
Surge suppressors for contactor coils
BC6, BC7 24 ... 60 Cable lug RV-BC6/60
Flat pin, 2.8 mm RV-BC6-F/60
50 ... 250 Cable lug RV-BC6/250
Flat pin, 2.8 mm RV-BC6-F/250
380 Cable lug RV-BC6/380
Flat pin, 2.8 mm RV-BC6-F/380
Note: Mini contactors for AC operation have an integrated protective circuit
RV-BC6/250
1.54 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Interface relays
A/E/L9...A110
Application
RA 5-1 interface relays are designed to receive 24 VDC signals delivered
by PLC's or other sources with a low output power and restore them with
sufcient power to operate the coils of the relevant A9 - A110 contactors or
the N control relays.
• IEC only
Description
RA5 interface relays are made up of a miniature electromechanical relay
equipped with a N.O. contact and with a low consumption 24 VDC coil.
The interface relay coil is controlled by the PLC while the N.O. contact
ensures switching of the power contactor.
Coil switching gives rise to overvoltages which have adverse effects on the
electronic devices, insulators and, more generally, on component lifetime.
The RA 5-1 is equipped with surge suppressors:
• on the 24 VDC relay coil via a diode
• on the power contactor coil via a varistor.
Furthermore, the RA 5-1 are protected against relay pole reversal by a diode
inserted between the E1 and E2 input terminals.
Connection
The “E1+” and “E2 –” input terminals must be connected, according to their
polarity, to the PLC output.
The RA 5 is equipped with two terminal pads for connection to the A1 and
A2 terminals of the contactor coil. This coil is supplied between the A0 and
A2 terminals of the RA 5.
A30-30-10 + RA 5
RA 5
U
c
250 VAC 24 VDC
+
RA 5
A0 E2 – E1 +
KM1
A1
A2
PLC
Output
A2
RA 5-1 interface relay for the A 9 – A 110
contactors and N control relays
Mounting
• RA5: terminal pads clamped inside the contactor coil terminals.
Interface relays
Mounting on
contactor types
Control
voltage Uc
Coil
voltages
Catalog
number
N, A9 – A110 24 VDC 24 – 250V, 50, 60 Hz RA5-1
NOTE: The interface relays provided for the A contactors can also b e used for UA, UA..., RA and GA types.
Low Voltage Products & Systems 1.55
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Interface relays
Technical data
General technical data
Compliance with standards IEC 60255-5
Rated insulation voltage Ui
according to
IEC 60947-4-1
V a.c. 250
Permissible ambient temperature:
for free air operation:
– at Uc = 24 V d.c. (between E1 and E2) °C -25 ... +70
– from 0.85 to 1.1 Uc °C -25 ... +55
for storage °C -40 ... +70
Climatic withstand Complies with that of associated contactors
Operating altitude m ≤ 3000
Mounting position No limitation
Fixing Using the contactor A1 and A2 terminal connecting parts
Connecting terminals (delivered in open position) M3.5 (+,-) pozidriv 2 screws with cable clamp
Connecting capacity (min. ... max.)
rigid solid 2 x mm2 1 ... 4
2 x mm2 0.75 ... 2.5
Tightening torque
recommended Nm 1.00
max. Nm 1.20
Degree of protection
according to
IEC 60947-1 / EN 60947-1
Protection against direct contact in acc. with EN 50274
and IEC 60529 / EN 60529 RA5-1 wired and mounted on the associated contactor
Working data
Surge suppression:
for contactor coil Varistor
for interface relay coil Diode
Protection against polarity reversal
between terminals E1 and E2 Diode
Interface relay operating time ms Closing and drop-out ≤ 10
Total operating time,
interface relay + contactor:
– between energization and:
N.O. contact closing ms 20 ... 37
N.C. contact opening ms 17 ... 32
– between de-energization and:
N.O. contact opening ms 17 ... 25
N.C. contact closing ms 20 ... 28
Electrical input data
Control voltage (E1and E2 terminals) Uc
rated value V d.c. 24
max. range at ambient temperature 20 °C V d.c. 19 ... 30
Max. consumption
for Uc = 24 V d.c., θ = 20 °C W 0.3
"0" status (relay open) for Uc V d.c. ≤ 2.4
or Ic mA < 1
"1" status (relay closed) for Uc V d.c. ≥ 19
Max. short supply interruption immunity time
ms 2
Electrical output data
Switching voltage (A 0 and A2 terminals) V a.c. ≤ 250
Electrical durability million of operating cycles 2 (600 cycles/h) on A 9 ... A 75 contactors or N... contactor relay
0.5 (600 cycles/h) on A 95 and A 110 contactors
exible with cable end
1.56 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
A2 A2
01NC
01NC
VEM4
KM1 KM2
Mechanical & electrical interlocks
AF09(Z)...AF38(Z), AF09N00(Z)...AF26N1(Z); AS/L09...AS/L16
Mechanical interlock unit
For contactors Catalog number
AF09 ... AF38..-30-.. VM4
AF09 ... AF38..-40-00
ASL VM3
Note: Includes two fixing clips.
Mechanical and electrical interlock set
For contactors
Auxiliary
contacts
Catalog number
AF09 ... AF16..-30-..
1 1 VEM4
AF26 ... AF38..-30-00
AF09, AF16..-40-00
AF26, AF38..40-00
Note: VEM4 not ttable on AF..Z contactors with DC control voltage 12...20 V
DC.
Fixing clips
For contactors Catalog number
AF09 ... AF38 BB4
AS, ASL BB3
Note: Set of 50 pieces each
VEM4
VM4
BB4
VM3
Low Voltage Products & Systems 1.57
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Mechanical & electrical interlocks
A/E/L9...A/E/L40; A/E/F50...AF2050
A/E/F50N2...AF1650N8; EK
Ordering details (1)
Left side
contactor
Right side
contactor Mounting Catalog number
Mechanical interlock units for two horizontal mounted
contactors (1)
A9...A40 A9,,,A40 Rail mounting VM5-1
A30...A40 A45 … A110 See table below with
VE5-.. type
A45 … A75 A45 A110
A95 … A185 A45 … A110
A95 … A185 A145 … A300 PN.. mounting
plate to be ordered
separately
VM300H
A210 … A300 A145 … A300 VM300H
A210 … A300 AF400 … AF460 VM300/460H
AF400 … AF1250 AF400 … AF1250 VM750H
AF1350 … AF2050 AF1350 … AF2050 Plate included VM1650H
EK370...EK1000 EK370...EK1000 Plate included VH800
(1) Mechanical durability: VM5-1 = 5 millions cycles, VM300H ... VM750H = 1 million
cycles.
The interlock units provided for A... contactors can be used for AF types, AE types &
AL types.
The interlock units provided for A40.. contactors can be used for AL40.. and TAL40..
types.
Top contactor Bottom contactor Mounting Catalog number
Mechanical interlock units for two vertical mounted
contactors (2)
A95 … A185 A145 … A300 Additional plate
(not supplied)
VM300V
A210 … A300 A145 … A300 VM300V
A210 … A300 AF400 … AF460 VM300/460V
AF400 … AF1250 AF400 … AF1250 VM750V
(2) Mechanical durability: VM300V ... VM750V = 1 million cycles.
Left side
contactor
Right side
contactor Mounting Catalog number
Mechanical and electrical interlock units for two
horizontal mounted contactors
A9...A40 A9...A40 Rail mounting VE5-1
A30 … A75 A45 A75 VE5-2
A45 ... A75 A30 ... A75 VE5-2
A45 … A75 A95 A110
PN.. mounting
plate to be ordered
separately
VE5-2 (3)
A95 … A110 A45 … A75 VE5-2 (3)
A95 … A110 A95 … A110 VE5-2
EK110, EK150 EK110, EK150 VH145
EK175, EK210 EK110, EK150 VH300
(3) The combination of A45 ... A75 contactors interlocked with A95, A110 contactors
cannot be mounted on symmetrical rail
(75 mm, IEC/EN 60715).
The interlock units provided for A... contactors can be used for AE, TAE, AF, GA and
GAE types.
The interlock units provided for A40.. contactors can be used for AL40.. and TAL40..
types.
VM300H
VM1650H
VH800
VH145
VM300V
VE5-1
1.58 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Mechanical latching unit
AF(Z), AE & AL
Description
For converting standard contactors into latched contactors.
The WB75-A block contains a mechanical latching device with electromagnetic impulse unlatching (AC or
DC) or manual unlatching.
Captive screw type connecting terminals, built-in cable clamps, M3.5 (+,-) pozidriv 2 screw with screw-
driver guidance; delivered untightened and protected against accidental direct contact.
Operation
After closing, the contactor continues to be held in the closed position by the latching mechanism should
the supply voltage fail at the contactor coil terminals.
Contactor opening can be controlled:
electrically by an impulse* (AC or DC) on the WB75-A block coil.
* the coil is not designed to be permanently energized.
manually by pressing the pushbutton on the front face of the WB75-A block.
Mounting
The WB75-A block is clipped onto the front face of the 1-stack contactor where it takes up two slots. The
two other slots may accept CA5... single pole auxiliary contacts (1 block on each side of the mechanical
latch).
Ordering details
For contactors
Rated control circuit
voltage
Uc Catalog number
V 50 Hz
or DC V 60 Hz
A40 ... A75,
AF45 ... AF75,
AL40,
AE45 ... AE75,
TAL40,
TAE45 ... TAE75,
UA16 ... UA75,
GA75, GAE75
AF09(Z)...AF38(Z)
NF, NFZ
24 24...28 WB75A-01
42 42...48 WB75A-02
48 48...55 WB75A-03
110 110...127 WB75A-04
220...230 220...255 WB75A-06
230...240 230...277 WB75A-05
380...415 380...440 WB75A-07
415...440 440...480 WB75A-08
WB75-A
E1 E2
Terminal marking
Low Voltage Products & Systems 1.59
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Electronic timers
AF09(Z)…AF38(Z), AS(L)09…AS(L)16, A/E/L40…A/E/F75
TEF3-ON
TEF5
Ordering details
For contactors,
contactor relays
Time delay
range
selected by
switch
Delay
type
Rated control
circuit voltage
Uc
V 50/60 Hz or DC
Auxiliary
contacts Catalog
number
AS/L09…AS/L16,
NS(L)
ON-delay 24…240 1 1 TEF3-ON
OFF-delay 24…240 1 1 TEF3-OFF
AF09(Z)…AF38(Z),
NF(Z)
ON-delay 24…240 1 1 TEF4-ON
OFF-delay 24…240 1 1 TEF4-OFF
A/E/L9…A/E/L40,
A/E/F45…A/EF75
ON-delay 24…240 1 1 TEF5-ON
OFF-delay 24…240 1 1 TEF5-OFF
0.1...1 s
1...10 s
10...100 s
ON-delay OFF-delay
1.60 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Electronic timers for wye-delta starters
TE5S-*
Chart
Equivalent diagram
Front face
Application
Utilization
When used in wye-delta starters, the TE5S lags the wye connection and provides a lapse of 50 ms before the switchover to the
delta connection.
Description
According to the type of device chosen, the electronic circuit has a 24 VAC/VDC, 110 – 120 VAC or 220 – 230 VAC supply. An
output relay with reversing contact ensures high current switching. A two-position switch allows selection of one of the two time
delay ranges: 0.8 to 8 s or 6 to 60 s. The 0.1 to 1.0 adjustable knob allows an initial setting without steps within the previously
selected range which can then be adjusted using a stopwatch.
Note: We recommend that you allow for temperature drift for the nal adjustment of the time delay setting. Drift: – 0.2% per °C.
For example, a setting made at 20 °C will yield a time delay shorter by 7% at 55 °C in an enclosure. ( – 0.2% per °C i.e. – 0.2 x 35
= – 7%).
The TE5S, which is not affected by these settings, establishes a xed “lapse” of 50 ms between the opening of contact 15 – 16
and the closing of contact 15 – 18. It is this time delay that prevents from arc short-circuit during wye to delta switching.
Operation
On energization, the green U indicator light (voltage applied) comes on. Contact 15 – 16 then immediately moves to the closed
position.
Count-down of the programmed time immediately commences.
When the time delay has elapsed, contact 15 – 16 opens and at the same time the 50 ms lapse, t2, begins after which contact
15 – 18 moves to the closed position. The yellow R indicator light comes on.
On de-energization, the U and R indicator lights go out and, after the 250 ms resetting time, the device is ready for a new cycle.
Mounting
Mounts on 35mm DIN rail.
Electronic timer
15-18
U
15-16
t1 t2 = 50ms
R
TE 5S
t1 t1+t2
A1A2
16
15
18
TE5S
R
Star-Delta Timer
U
0.1
0.5
1.0
0.8 ... 8s t1
A1 15
16 A218
6 ... 60s
For
contactors
Rated control
voltage Uc
V
Packing
piece
Unit
weight
kg
Catalog
number
A9 – AF750 1
24 AC/D 10.080 TE5S-24
110 – 120 AC 10.080 TE5S-120
220 – 240 AC 10.080 TE5S-240
380 – 440 AC 10.080 TE5S-440
1 Types AF09(Z)...AF38(Z); AF09N00(Z)...AF26N1(Z) and AS/L09...AS/L16 use Type CT-ERS... timers. See Chapter 6.
Low Voltage Products & Systems 1.61
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Electronic timers for wye-delta starters
Technical data
Types TE5S-24 TE5S-120 TE5S-240 TE5S-440
Compliance with standards IEC 60947-5-1, EN 60947-5-1
Rated insulation voltage Ui
according to IEC 60947-5-1 V 440
Rated operational voltage Ue V d.c. 24
according to IEC 60947-5-1 V a.c. 24 ... 240 440
Conventional free air thermal current Ith A 10
Rated operational current Ie acc. to IEC 60947-5-1
AC-15 24-120 V a.c. A 5
220-240 V a.c. A 4
380-440 V a.c. A 3
DC-13 24 V d.c. A 4
Short-circuit protection - gG type fuses A 10
Rated supply voltage Uc V d.c. 24
V a.c. 24 110 ... 120 220 ... 240 380 ... 440
– Rated frequency limits Hz 48 ... 63
– Supply voltage range 0.85 ... 1.1 Uc
– Overvoltage protection Built-in varistor
– Load factor % 100
– Average consumption – in d.c. W 0.7
– in a.c. VA 1.5 3.5 6.5 12.5
Time delay range (t1) selected by switch s 0.8 ... 8 and 6 ... 60
– Temperature drift % per °C -0.2
– Mechanical setting accuracy ±15 % of the setting range
On-load reiteration accuracy
under constant conditions ±2 % after 1 million operating cycles
Minimum time lapse (t2) ms 50
Min. time lapse after 1 million operating cycles ms 40
Resetting time (maximum) ms 250
Front panel display: – green indicator light Energization
– yellow indicator light Output relay activated
Permissible air temperature
– for operation °C -25 ... +60
– for storage °C -40 ... +85
Vibration withstand acc. to
IEC 60068-2-6, EN 60068-2-6 3 g from 10 to 300 Hz in the 3 directions
Shock withstand acc. to 20 g / 11 ms in directions A and C
IEC 60068-2-27, EN 60068-2-27 15 g / 11 ms in direction B
Electrical durability in millions of op. cycles 1
Mechanical durability in millions of op. cycles 5
On-load maximum switching frequency cycles/h 720 600
Fixing on mounting rail acc. to IEC/EN 60715 35 x 7.5 or 35 x 15
Connecting terminals (+,-) pozidriv 1 screw
Connecting capacity
– rigid solid 1 or 2 x mm2 1 ... 2.5
– exible with cable end 1 or 2 x mm2 0.75 ... 2.5
Tightening torque Nm 0.6 ... 0.8 max.
Degree of protection Terminals IP 20
according to IEC 60947-1 / EN 60947-1
and IEC 60529 / EN 60529
1.62 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
A1
A2
A1
A2
315 315
42 6 426
Connection kits
Reversing and phase-to-phase
BER16-4
Reversing connection kits for 3-pole contactors
Left side
contactor
Right side
contactor
Catalog
number
AF09(Z)…AF16(Z) AF09(Z)…AF16(Z) BER16-4
AF26(Z)…AF38(Z) AF26(Z)…AF38(Z) BER38-4
A/E/L9…A/E/L16 A/E/L9…A/E/L16 BER16V
A/E/L26…A/E/L40 A/E/L26…A/E/L40 BER40V
A/E/F50…A/E/F75 A/E/F50…A/E/F75 BEM75-30
A/F95…A/F110 A/F95…A/F110 BEM110-30
A/F145…A/F185 A/F145…A/F185 BEM185-30
A/F210…A/F300 A/F210…A/F300 BEMA300-30
AF400…AF460 AF400…AF460 BEM460-30
AF580…AF750 AF580…AF750 BEM750-30
AS/L09…AS/L16 AS/L09…AS/L16 BER16C-3
VB/C6…VB/C7 - BSM6-30
Phase-to-phase connection kits for 3-pole contactors
Left side
contactor
Right side
contactor
Catalog
number
A/E/F50…A/E/F75 A/E/F50…A/E/F75 BES75-30
A/F95…A/F110 A/F95…A/F110 BES110-30
A/F145…A/F185 A/F145…A/F185 BES185-30
A/F210…A/F300 A/F210…A/F300 BESA300-30
AF400…AF460 AF400…AF460 BES460-30
AF580…AF750 AF580…AF750 BES750-30
Phase-to-phase connection kits for 4-pole contactors
Left side
contactor
Right side
contactor
Catalog
number
A/E/F45…A/E/F75 A/E/F45…A/E/F75 BES75-40
BEM75-30
BEM300-30
BES…
BSM6-30
BER, BEM connection sets BES... for 3-pole connections BES... for 4 N.O. main pole
connections
A1
A2
A1
A2
315 53
426 64
1
2
A1
A2
A1
A2
315 537
426 648
71
82
BER16C-3
Low Voltage Products & Systems 1.63
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Connection sets
Wye-delta
Wye-delta connection kits for 3-pole contactors
Line contactor
1M
Delta contactor
2M
Shorting (wye) contactor
1S
Mechanical / electrical
Interlock between
2M-1S
Catalog
number
AF09(Z)-30 AF09(Z)-30 AF09(Z)-30
VM4 / VEM4 1BEY16-4AF12(Z)-30 AF12(Z)-30 AF09(Z)-30
AF16(Z)-30 AF16(Z)-30 AF09(Z)-30
AF26(Z)-30 AF26(Z)-30 AF26(Z)-30
VM4 / VEM4 1BEY38-4AF30(Z)-30 AF30(Z)-30 AF26(Z)-30
AF38(Z)-30 AF38(Z)-30 AF26(Z)-30
AS/L09-30 AS/L09-30 AS/L09-30
VM3 1BEY16C-3AS/L12-30 AS/L12-30 AS/L09-30
AS/L16-30 AS/L16-30 AS/L12-30
A/E/L9-30 A/E/L9-30 A/E/L9-30
VE5-1 BEY16V-2A/E/L12-30 A/E/L12-30 A/E/L9-30
A/E/L16-30 A/E/L16-30 A/E/L12-30
A/E/L26-30 A/E/L26-30 A/E/L16-30 VE5-1 BEY26-2
A/E/L30-30 A/E/L30-30 A/E/L26-30 VE5-1 BEY40-2
A/E/L40-30 A/E/L40-30 A/E/L26-30
A/E/F50-30 A/E/F50-30 A/E/L30-30 VE5-2 BED50U
A/E/F63-30 A/E/F63-30 A/E/L40-30 VE5-2 BED50U
A/E/F75-30 A/E/F75-30 A/E/F50-30 VE5-2 BED50U
A/F95-30 A/F95-30 A/E/F75-30 VE5-2 BED95U
A/F110-30 A/F110-30 A/F95-30 VE5-2 BED110U
A/F145-30 A/F145-30 A/F110-30 VM300H BED145U
A/F185-30 A/F185-30 A/F145-30 VM300H BED185U
A/F210-30 A/F210-30 A/F185-30 VM300H BED210U
A/F260-30 A/F260-30 A/F210-30 VM300H BED300U
A/F300-30 A/F300-30 A/F260-30
AF400-30 AF400-30 A/F260-30 VM300/460H BED400U
AF460-30 AF460-30 A/F300-30
AF400-30 VM750H BED460U
AF580-30 AF580-30 AF400-30 VM750H BED580U
AF460-30
AF750-30 AF750-30 AF580-30 VM750H BED750U
BED 110
BED 400
BEY16-4
BEY16C-3
1 Mechanical/electrical interlock optional.
A1
A2
A1
A2
3 1 5 3 1 5
4 2 6 4 2 6
A1
A2
3 1 5
4 2 6
BEY / BED connection kits
1.64 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Coupling units
Manual motor protectors
MS132 + AF Contactor BEA16-4 BEA16-3
Close couplers for contactors
Manual motor protector
Miniature
contactors AF contactors AS contactors A / AE Contactors
Catalog
number
B6...B7
BC6...BC7
AF09...AF16
AF09Z...AF16Z
AF26...AF38
AF26Z...AF38Z
AF50...AF75
AF95...AF110
AS09...AS16
ASL09...ASL16
A50...A75, AE50...AE75
A95...A110
MS116-0.16…16
BEA7/132
BEA16-4
BEA26-4
BEA16-3
MS116-20…25 BEA16-4
BEA38-4
MS116-32 BEA38-4
MS132-0.16…10
BEA7/132
BEA16-4
BEA26-4
BEA16-3
MS132-12…16
BEA7/132
BEA16-4
BEA38-4
BEA16-3
MS132-20…25 BEA16-4
BEA38-4
MS132-32 BEA38-4
MS45x-40…50 BEA50/450
MS49x-40…100 BEA75/495
MS495-40…100 BEA110/495
Note: For spring terminated AS/ASL, use part number BEA16-3U with integral wire leads for spring terminals.
Low Voltage Products & Systems 1.65
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Coupling units
MCCB/MCP/Fusible disconnects
Ordering details
For contactors MCCB/MCP Catalog number
Vertical assembly
A145, A185, AF145, AF185 T3 BEA185/T3
A145, A185, AF145, AF185 T4 BEA185/T4
A210, AF210 T4 BEA210/T4
A210 ... A300, AF210 ... AF300 T5 BEA300/T5
AF400 ... AF750 T6 BEA750/T6
AF400 ... AF750 T5 BEA750/T5
Vertical assembly with control wire terminals
(also
suitable when using busbar kits for starter combinations)
A145, A185, AF145, AF185 T3 BEA185D/T3
A145, A185, AF145, AF185 T4 BEA185D/T4
A210, AF210 T4 BEA210D/T4
A210 ... A300, AF210 ... AF300 T5 BEA300D7T5
AF400 ... AF750 T6 BEA750D/T6
AF400 ... AF750 T5 BEA750D/T5
Horizontal assembly (also suitable when using busbar kits for
starter combinations)
A210 ... A300, AF210 ... AF300 T5 BEA300H/T5
AF400, AF460 T4 BEA460H/T4
BEA300
BEA...D
BEA300H
Ordering details
For contactors Switch Catalog number
Vertical assembly
A145 ... A185 OESA250 BEF185/OESA250
A210 ... A300 OESA250 to OESA400 BEF300/OESA400
AF400, AF460 OESA400 BEF460/OESA400
AF460 ... AF750 OESA630 to OESA800 BEF750/OESA800
Horizontal assembly
A145, A185 OESA250...LR BEF185H/OESA250
A210 ... A300 OESA250...LR to OESA400...LR BEF300H/OESA400
AF400, AF460 OESA400...LR BEF460H/OESA400
Note: The BEF... connection bars provided for the A145 ... A300 contactors can
be used for the AF145 ... AF300 contactors.
BEF300/OESA400
BEF300H/OESA400
1.66 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Terminal enlargements/extensions &
Shorting bars
LW... Terminal enlargements
For contactors
Dimensions
Catalog number
hole Ø
mm
bar
mm
A95, A110 6.5 15 x 3 LW110
A145, A185 10.5 20 x 5 LW185
A210 ... A300 10.5 25 x 5 LW300
AF400, AF460 10.5 25 x 5 LW460
AF580, AF750 13 40 x 6 LW750
AF1250 13 50 x 10 LW1250
Note: The LW... pieces provided for the A... contactors can be used for the AF, AE, TAE and
UA types.
LX... Terminal extension
For contactors
Dimensions
Catalog number
hole Ø
mm
bar
mm
A145, A185 8.5 20 x 5 LX185
A210 ... A300 10.5 20 x 5 LX300
AF400, AF460 10.5 25 x 5 LX460
AF580, AF750 13 40 x 6 LX750
Note: The LX... pieces provided for the A... contactors can be used for the AF types.
Shorting bars
Poles For contactors
max. nominal con-
tinuous current with
"n" poles
Cable cross-sectional
area
Catalog number
1
Amm²
2-Pole
A145, A185 300 LP185
A210 ... A300 475 LP300
AF400, AF460 725 LP460
AF580, AF750 1200 LP750
A45 ... A75 200 95 LH75
3-Pole
A95, A110 240 LY110
A145, A185 400 LY185
A210 ... A300 670 LY300
AF400, AF460 1000 LY460
AF580, AF750 1650 LY750
A40 140 50 LF40
A45 ... A75 275 150 LF75
Note: The strips and shorting bars provided for the A... contactors can be used for the AF,
AL, AL..Z, AE, TAL and TAE types.
LH... LF...
LP185
LY185
1 LP460 ... LP750, LY185 ... LY750 not insulated. Use terminal shrouds. Types LH... and LF..., not insulated, includes terminal.
Terminal connecting strips and shorting bars
For
contactors
max. nominal continuous
current with "n" poles Cable
cross-
sectional
area Catalog number
in parallel in series
2 poles 3 poles 4 poles 2 poles
AAAA mm²
AF09 30 33 -25 6LY16-4
AF12 32 36 -27
AF16 34 40 -30
AF26 50 60 -45 10 LY38-4
LY16-4
LW...
LW...
Low Voltage Products & Systems 1.67
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Terminal control leads, blocks & lug kits
Ordering details
For contactors Catalog number
Right and left on A45 ... A75 LK75-L
Opposite on A45 ... A75 LK75-F
Right and left on A95 ... A110 LK110
Note: The LK... terminals provided for the A... contactors can be used for the
AF, AE, AM, TAE, UA, GA and GAE types.
LK75-L
LK75-F
LK... positioning
Terminal lug kits
For contactors
Wire Tightening
torque Spare terminal
hardware included
1
Catalog
number
Range Capacity To conductor
AF145…AF185
A145…A185 4 AWG…300 MCM 1275 in.-lb ATK185
ATK185HK
AF210…AF300
A210…A300
4 AWG…400 MCM 1375 in.-lb ATK300
ATK300HK
4 AWG…500 MCM 2 375 in.-lb ATK300/2
ATK300/2HK
AF400…AF580 2/0 AWG…500 MCM 2 275 in.-lb ATK580/2
ATK580/2HK
AF580…AF750 2/0 AWG…500 MCM 3 375 in.-lb ATK750/3
ATK750/3HK
AF1350 4/0 AWG…500 MCM 4 375 in.-lb ATK1350/4
AF1350…AF1650 1/0 AWG…750 MCM 4 500 in.-lb ATK1650/4
1/0 AWG…750 MCM 6 500 in.-lb ATK1650/6
Note: AF1250, AF2050 & AF2650 intended for busbar connection only. Terminal hardware supplied separately.
Use of lug kits for AF1350 & AF1650 in general purpose applications reduces the ratings to 1050A and 1350A
respectively. Recommend busbar connection for full ratings.
1 Terminal hardware include with A(F)145…AF750 contactors; hardware for AF1350 & AF1650 available only with purchase of lug kit.
ATK185
ATK750/3
Terminal blocks
For contactors Catalog number
A45, A75 LD-75
A95, A110 LD-110
Note: The LD... terminal blocks provided for the A... contactors can be used
for the AF, AL, AE, TAL, TAE and UA types.
LD75
LD110
Spare terminal hardware kits
For contactors Catalog number
A/F145…A/F185 LE185
A/F210…A/F300 LE300
AF400…AF460 LE460
AF580…AF750 LE750
1.68 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Terminal shrouds
Ordering details
For contactors Catalog number
A145 ... A185 with connectors/busbar LT185-AC
A145 ... A185 with lugs LT185-AL
A145 ... A185 with short. bar LY185
or between A145 and TA200DU
or between A185 and TA200DU
LT185-AY
A210 ... A300 with connectors/busbar LT300-AC
A210 ... A300 with lugs 1LT300-AL
A210 ... A300 with short. bar LY300 LT300-AY
AF400 ... AF460 with connectors/busbar LT460-AC
AF400 ... AF460 with lugs LT460-AL
AF580 ... AF750 with connectors/busbar LT750-AC
AF580 ... AF1250 with lugs LT750-AL
Note: The shrouds provided for the A... contactors can be used for the AF...
types.
LT...-AC
LT ...-AL
LT...-AY
EK shrouds
For contactors Catalog number
EK110, EK150 LT150-EK
EK175, EK210 LT210-EK
EK370, EK550 LT550-EK
EK1000 LT1000-EK
1 Cannot be used with lug kit ATK300/2.
LT210-EK
Low Voltage Products & Systems 1.69
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Function markers, protective covers &
coil terminal blocks
Ordering details
For contactors Catalog number
Additional coil terminal block
Additional coil terminal block for a bottom access to the coil terminals of contactors or
contactor relays.
AF09 ... AF38, NF LDC4
Protective covers
Sealable and transparent protective covers BX4 and non-removable BX4-CA to protect
the devices against accidental contact.
All 1-stack contactors and contactor relays BX4
For 4-pole CA4 and 2-pole CAT4 auxiliary contact blocks BX4-CA
For contactors B/C6...B/C7 LT6-B
Function markers
Box of 16 blank cards (16 markers by card) printable on HTP500 thermal transfer printer
and AMS 500 marking table to identify your contactors, overload relays or manual motor
starters.
Marker dimensions: 7 x 20 mm (.276" x .787").
Box of 16 blank cards - for AF09/Z...AF38/Z, (V)AS/L09...(V)ASL16, NF/Z, NS/L BA4
AMS 500 support plate for 8 BA4 XUSP02633
HTP500 support plate 1SNA235712R2400
50 pcs. - for A9...A110, AF50...AF110, AL9...AL40, AE9...AE75 BA5-50
BX4
LDC4
BA4
Main dimensions mm, inches
45 1.77"
54 2.13"
70 2.76"
80 3.15"
90 3.54"
5 0.20"
5 0.20"
M4 8-32 UNC
ø 4.2 0.17"
BX4
28 1.10"
6
0.24"
44.8 1.76"
BP38-4
LT6-B
BA5-50
1.70 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Mounting plates
Description
Mounting plates with fixing holes for the specified contactors and overload relays.
Ordering details
For contactors For
overload relays
Catalog number
Mounting plates for Direct on line starters
A145, A185 TA200DU, E200DU PN185-11
A210 ... A300 TA450DU, E320DU PN300A-11
AF400, AF460 E500DU PN460-11
AF580, AF750 E800DU PN750-11
For two contactors side
by side with space for
mechanical interlock
For one or two
overload relays
Catalog number
Mounting plates for mechanical interlocked contactors, reversing
starters and two speed starters for double windings
A95, A110 TA80DU, TA110DU PN110-21
A145, A185 TA200DU, E200DU PN185-21
A210 ... A300 TA450DU, E320DU PN300-21
AF400, AF460 E500DU PN460-21
AF580, AF750 E800DU PN750-21
PN300A-11
PN300-21
Mounting plates for two horizontal mounted contactors with or without
a mechanical interlock unit.
To use with: Catalog number
Left hand
contactor Mechanical interlock Right hand
contactor
EK110, EK150 VH145 EK110, EK150 PN210-22
EK175, EK210 VH300 EK175, EK210 PN300-22
(1) Space for mechanical interlock included.
PN...
Low Voltage Products & Systems 1.71
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Adapter plates & accessories
Description
Adapter plates with fixing holes for specified old contactors to new contactors.
Ordering details
From old contactors To new contactor Catalog number
EH65, EH75, EH80, EH90, EG80 A95, A110 PR110-1
EH100, EH145 A110, A145 PR145-1
EH150, EH160, EH175, EH210, EG160 A185, A210 PR210-1
EH250, EH260, EH300 A210 ... A300 PR300-1
EH370, EH550, EG315 AF400 ... AF580 PR460-1
EH700, EH800 AF750 PR750-1
OKYM150, OKYM175 A185 PR185-2
OKYM200, OKYM250 A210 ... A300 PR300-2
OKYM315 AF400, AF460 PR400-2
OKYM400 AF400, AF460 PR460-2
OKYM500 AF580 PR580-2
EH550, EG630, OKYM630 AF580, AF750 PR750-2
Note: The adapter plates provided for the A... contactors can also be used for the AF... contactors.
PR300-1
PR400-2
h
l
L
Dimensions (mm)
Type of the plate Dimensions Fixing holes
L I h mm
PR110-1 151 106 11.2 2 x ø 7
PR145-1 180 122 11.5 4 x ø 7
PR210-1 200 132 11.5 4 x ø 7
PR300-1 200 172 11.5 4 x ø 7
PR460-1 278 198 11.5 4 x ø 7
PR750-1 283 244 11.5 4 x ø 7
PR185-2 202 152 11.2 4 x ø 11
PR300-2 202 152 11.2 4 x ø 11
PR400-2 278 151 11.5 4 x ø 11
PR460-2 278 176 11.5 4 x ø 11
PR580-2 283 176 11.5 4 x ø 11
PR750-2 283 255 11.5 4 x ø 14
Note: The adapter plates provided for the A... contactors can also be used for the AF... contactors.
Fixing holes according to the plate types
Mounting piece
Mounting piece for replacement of A / AL26 ... A / AL40 contactors mounted by
screws by AF contactors in 45 mm width.
AF09 ... AF38 BP38-4
BP38-4
1.72 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Replacement parts
Contact kits & arc chutes
3-pole contact kits
For contactors Catalog
number
A/AF/AE/TAE50-30 ZL50
A/AF/AE/TAE63-30 ZL63
A/AF/AE/TAE75-30 ZL75
A/AF95-30 ZL95
A/AF110-30 ZL110
A/AF145 ZL145
A/AF185 ZL185
A/AF210 ZL210
A/AF260 ZL260
A/AF300 ZL300
AF400 ZL400
AF460 ZL460
AF580 ZL580
AF750 ZL750
AF1250 ZL1250
AF1350 ZL1350
AF1650 ZL1650
AF2050 ZL2050
UA50 ZLU50
UA63 ZLU63
UA75 ZLU75
UA95 ZLU95
UA110 ZLU110
4-pole contact kits
A/E/F45 ZLT45
A/E/F50 ZLT50
A/E/F75 ZLT75
EK110 KZK110
EK150 KZK150
EK175 KZK175
EK210 KZK210
EK370 KZK370
EK550 KZK550
EK1000 KZK1000
ZL50
ZL185
ZL1650
ZW...
KZK370
Arc chutes
For contactors Catalog
number
3-pole
A145 ... A185 and AF145 ... AF185 ZW185
A210 ... A300 and AF210 ... AF300 ZW300
AF400, AF460 ZW460
AF580, AF750, AF1250 ZW750
AF1350, AF1650, AF2050 ZW1650
4-pole
EK110 KWK110
EK150 KWK150
EK175 KWK175
EK210 KWK210
EK370 KWK370
EK550 KWK550
EK1000 KWK1000
Low Voltage Products & Systems 1.73
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Replacement parts
Coils
Coils, AC operated
For
contactors
Catalog
number
A9…A16, A9N00…A16N0, UA16 ZA16-Δ
A26…A40, A26N1, UA26 ZA40-Δ
A45…A75, A50N2…A75N3, UA50…UA75, GA75 ZA75-Δ
A95…A110, UA95…UA110 ZA110-Δ
A145…A185, A145N4 ZA185-Δ
A210…A300, A260N5 ZA300-Δ
Coils, DC operated
AE9…AE16, AE9N00…AE16N0 ZAE16-Δ
AE26…AE40, AE26N1 ZAE40-Δ
AE45…AE75, AE50N2…AE75N3, GAE75 ZAE75-Δ
Coils, AC/DC operated (coil and printed circuit board except ZAF1650
AF45…AF75, AF50N2…AF75N3 ZAF75-Δ
AF95…AF110 ZAF110-Δ
AF145…AF185, AF145N4, GAF185 ZAF185-Δ
AF210…AF300, AF260N5, GAF300 ZAF300-Δ
AF400…AF460, AF460N6, GAF460 ZAF460-Δ
AF580…AF1250, AF750N5, GAF750…GAF1250 ZAF750-Δ
AF1350…AF2050, AF1650N8, GAF1650…GAF2050 ZAF1650-Δ
Printed circuit board (G/AF1350…2050) ZP1650
ZA16-81
ZAF1650
Coils, AC operated for A/UA/GA (Δ)
For
contactors
AC voltages Coil
code
V - 50 Hz V - 50 Hz
A9…A300,
A9N00…
A260N5,
UA16…
UA110,
GA75
24 24 81
26 28 16
28 32 17
42 42 82
48 48 83
60 60 73
100 100…110 74 2
105 110…127 26
110 110…120 84
110…115 115…127 89 3
120 140 29
125…127 150 30
175 208 34
190 220 36
220…230 230…240 80
230…240 240…260 88
230…240 277 42
230/400 - 62 1
- 230/400 63 1
380…400 400…415 85
400…415 415…440 86
400 440 50
400…415 480 51
415…440 440…460 87
440 500 53
500 600 55
550 - 56
660…690 - 58
1 For A9…A16, A9N00…A16N0, UA16 only
2 Excludes A145…A300, A145N4
3 A145…A300, A145N4 at 60 Hz, 115V only
Coils, DC operated for AE/GAE
(Δ)
For
contactors
DC voltages
V DC
Coil
code
AE9…AE75,
AE9N00…
AE75N3.
GAE75
12 80
24 81
42 82
48 83
50 21
60 84
75 85
110 86
125 87
220 88
240 89
250 38
Coils, DC operated for AE/GAE (Δ)
AC / DC voltages
V – 50/60 Hz or DC
AF50…
AF300,
AF50N2…
AF260N5,
GAF185…
GAF300
AF400…
AF750,
AF460N6…
AF750N7,
GAF460…
GAF570
AF1250,
GAF1250
AF1350…
AF2050,
AF1650N8,
GAF1650…
GAF2050
20...60V DC 72 - - -
24...60V DC - 68 68 -
48...130V AC/DC 69 69 69 -
100...250V AC/DC 70 70 70 70
250...500V AC/DC - 71 - -
ZP1650
1.74 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Replacement parts
Coils
KH300 Coils, AC operated for EK (Δ)
For
contactors
AC voltages Coil
code
V - 50 Hz V - 50 Hz
EK110…
EK1000
(AC
operated)
- 24 F
24 - N
- 48 G
110 120 1
- 208 B
- 240 2
220…230 - J
- 380 Z
380…400 440 3
400…415 - M
- 480 4
500 - 5
- 600 6
Coils, DC operated for EK (Δ)
For
contactors
DC voltages
V DC
Coil
code
EK110…
EK1000
(DC
operated)
24 Y
48 W
110 P
125 Q
220 R
440 T
Coils, AC or DC operated
For
contactors
Catalog
number
EK110…EK150 KH210-Δ
EK175…EK210 KH300-Δ
EK370…EK1000 KH800-Δ
Note: AC and DC operated contactors DO NOT have the same magnetic structure. Therefore, DC coils will not
t on an AC magnetic structure and vice versa.
Low Voltage Products & Systems 1.75
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Terminal marking and positioning
AF09/Z...AF38/Z, AF09N00/Z...AF26N1/Z
3-pole contactors
Other possible contact combinations with auxiliary contacts
=+
-1
NC
-2
13
NO
14
5L3
6T3
3L2
4T2
1L1
NO
2T1
21
NC
22
A1 A2
A1 A2
A1 A2
2-
2-
13
NO
5L33L2
1L1
146T34T2
NO
2T1
A1 A2
=
++
-3
NO
-4
-1
NC
-2
5L3
6T3
3L2
4T2
1L1
13
NO
2T1
14
A1 A2
21
NC
22
A1 A2
A1 A2
1-
1-
2-
2-
5L33L2
1L1
6T34T22T1
A1 A2 21
NC
NC
22
5L33L2
A1
A2 6T34T2
1L1
2T1
13
NO
NO
14
Combination 11
Combination 11 =
AF09...AF16..-30-10
+
CA4-01
Combination 11 =
AF26...AF38..-30-00
+
CA4-10
+
CA4-01
=+
A1 21
NC
22
33
NO
34 A2
13
NO
5L33L2
1L1
146T34T2
NO
2T1
13
NO
14
5L3
6T3
3L2
4T2
1L1
A1
NO
2T1
21
NC
22
33
NO
34 A2
=+
13
NO
14
5L3
6T3
3L2
4T2
1L1
NO
2T1
A1 A2
31
NC
32
21
NC
22
43
NO
44
53
NO
54
21 31
NCNC
3222
43 53
NO NO
44 54
A1 A2
A1 A2
13
NO
5L33L2
1L1
146T34T2
NO
2T1
A1 A2 21
NC
NC
22
5L33L2
A1
A2 6T34T2
1L1
2T1
13
NO
NO
14
33
NO
NO
34
Combination 21
21
NC
NC
22
5L33L2
A1
A2 6T34T2
1L1
2T1
13
NO
NO
14
43
NO
NO
44
53
NO
NO
54
31
NC
NC
32
Combination 21 =
AF09...AF16..-30-10
+
CAT4-11M
Combination 32 =
AF09...AF16..-30-10
+
CA4-22M
Combination 32
=+
13X
NO
21X
NC
NO
14X
NC
22X
13X
NO
21X
NC
NO
14X
NC
22X
13
NO
NO
14
5L3
6T3
3L2
4T2
1L1
2T1
A1 A2
A1 A2
13
NO
NO
14
5L3
6T3
3L2
4T2
1L1
2T1
A1 A2
A1 A2
13X
NO
NO
14X
21X
NC
NC
22X
5L33L2
A1
A2 6T34T2
1L1
2T1
13
NO
NO
14
Combination 21 =
CAL4-11
+
AF09...AF16..-30-10
Combination 21
Note: Only AF..Z contactor with DC control voltage 12...20 V DC need to respect the connection polarities indicated close to the coil terminals: A1+ for the positive pole and
A2- for the negative pole
Standard devices without addition of auxiliary contacts
Note: Terminal markings for AF09 & AF16 apply to AF NEMA Sz. 00 & 0; terminal markings for AF26 apply to AF NEMA Sz. 1.
AF09...AF38 terminal markings apply to AF..Z type.
13
NO
NO
14
5L3
6T3
3L2
4T2
1L1
2T1
A1 A2
A1 A2
21
NC
NC
22
5L3
6T3
3L2
4T2
1L1
2T1
A1 A2
A1 A2
5L3
6T3
3L2
4T2
1L1
2T1
A1 A2
A1 A2 5L33L2
A1
A2 6T34T2
1L1
2T1
13
NO
NO
14
5L33L2
A1
A2 6T34T2
1L1
2T1
AF09...AF16..-30-10 AF26...AF30..-30-00
5L33L2
A1
A2 6T34T2
1L1
2T1
21
NC
NC
22
AF09...AF16..-30-10 AF09...AF16..-30-01 AF26...AF38..-30-00
AF09...AF16..-30-01
1.76 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Standard devices without addition of auxiliary contacts
7L4
8T4
5L3
6T3
3L2
4T2
1L1
2T1
A1 A2
A1 A2
7
8
R5
R6
R3
R4
1
2
A1 A2
A1 A2 5L33L2
A1
A2 6T38T44T2
1L1
2T1
7L4 R5R3
A1
A2 R6R4
1
2
7
8
AF09 ... AF38..-40-00 AF09 ... AF38..-22-00
AF09 ... AF38..-40-00 AF09 ... AF38..-22-00
Other possible contact combinations with auxiliary contacts
=+
-3
NO
-4
7L4
8T4
5L3
6T3
3L2
4T2
1L1
13
NO
2T1
14
A1 A2
A1 A2
1-
1-
7L4
5L33L2
1L1
8T46T34T22T1
A1 A2
A1 A2
=
++
-3
NO
-4
-1
NC
-2
13
NO
14
21
NC
22
7L4
5L33L2
1L1
8T4
6T34T2
2T1
A1 A2
A1 A2
1-
1-
2-
2-
7L4
5L33L2
1L1
8T4
6T34T2
2T1
A1 A2
A1 A2
5L33L2
A1
A2 6T34T2
1L1
2T1
13
NO
NO
14
7L4
8T4
Combination 10
5L33L2
A1
A2 6T34T2
1L1
2T1
13
NO
NO
14
7L4
8T4
21
NC
NC
22
Combination 10 = AF09 ... AF38..-40-00 + CA4-10 Combination 11 = AF09 ... AF38
..-40-00
+
CA4-10
+
CA4-01
Combination 11
=+
A1 13
NO
14
21
NC
22 A2
7L4
8T4
5L3
6T3
3L2
4T2
1L1
A1
2T1
13
NO
14
21
NC
22 A2
7L4
5L33L2
1L1
8T46T34T22T1
=+
13 21
NCNO
2214
31 43
NC NO
32 44
7L4
8T4
5L3
6T3
3L2
4T2
1L1
2T1
21
NC
22
13
NO
14
31
NC
32
43
NO
44
A1 A2
A1 A2
7L4
5L33L2
1L1
8T46T34T22T1
A1 A2
A1 A2
5L33L2
A1
A2 6T34T2
1L1
2T1
13
NO
NO
14
7L4
8T4
21
NC
NC
22
Combination 11
21
NC
NC
22
5L33L2
A1
A2 6T34T2
1L1
2T1
7L4
8T4
13
NO
NO
14
43
NO
NO
44
31
NC
NC
32
Combination 11 = AF09 ... AF38..-40-00 + CAT4-11E Combination 22 = AF09 ... AF38
..-40-00
+
CA4-22E
Combination 22
=+
13X
NO
21X
NC
NO
14X
NC
22X
13X
NO
21X
NC
NO
14X
NC
22X
7L4
8T4
5L3
6T3
3L2
4T2
1L1
2T1
A1 A2
A1 A2
7L4
8T4
5L3
6T3
3L2
4T2
1L1
2T1
A1 A2
A1 A2
21X
NC
NC
22X
5L33L2
A1
A2 6T34T2
1L1
2T1
7L4
8T4
13X
NO
NO
14X
Combination 11 = CAL4-11 + AF09 ... AF38
-40-00
Combination 11
Note: Only AF..Z contactor with DC control voltage 12...20 V DC need to respect the connection polarities indicated close to the coil terminals: A1+ for the positive pole and A2- for the negative pole
Terminal marking and positioning
AF09/Z...AF38/Z 4-pole contactors
Note: AF09...AF38 terminal markings apply to AF..Z type.
Low Voltage Products & Systems 1.77
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
1-pole auxiliary contacts
-1
NC
-2
-3
NO
-4
-5
NC
-6
-7
NO
-8
CA4-01 CA4-10 CC4-01 CC4-10
2-pole auxiliary contacts
13X /
NO
14X /
21X /
NC
22X /
44X
43X
31X
32X
NC NO
31X /
22X
32X /
21X
43X /
14X
44X /
13X
21
NC
22
33
NO
34
13
NO
14
21
NC
22
-3
NO
-4
-1
NC
-2
CAL4-11
(Left side-mounted)
CAL4-11
(Right side-mounted)
CAT4-11M CAT4-11E CAT4-11U
4-pole auxiliary contacts
13
14
23
24
33
34
43
44
NO NONO NO
31
32
41
42
NCNC
53
54
NO
21
22
NC
3
4
3
4
3
4
3
4
NO NONO NO
CA4-40E CA4-13M CA4-40U
21
22
13
14
43
44
33
34
NO NC NONO
21
22
33
34
43
44
53
54
NONO NO
NC
1
2
3
4
3
4
3
4
NO NC NONO
CA4-31E CA4-31M CA4-31U
21
22
13
14
43
44
31
32
NO NCNC NO
21
22
31
32
43
44
53
54
NO NO
NC NC
1
2
3
4
3
4
1
2
NO NCNC NO
CA4-22E CA4-22M CA4-22U
21
22
11
12
41
42
31
32
NCNC NCNC
31
32
21
22
51
52
41
42
NCNC NCNC
CA4-04E CA4-04M
Terminal markings and positioning
Add-on auxiliary contacts for AF09/Z...AF38/Z
1.78 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
-1
NC
-2
-3
NO
-4
-1
-2
NC
-3
-4
NO
A1+
A2-
1L1 3L2 5L3 13
53NO
2T1 4T2 6T3
NO
NO
43NO31NC21NC
54NO44NO32NC22NC
NONONCNC
14
5L33L2
A1+
A2- 6T34T2
1L1
2T1
53
NO
NO
54
43
NO
NO
44
31
NC
NC
32
21
NC
NC
22
13
NO
NO
14
A1+
A2-
1L1 3L2 5L3 13
NO
2T1 4T2 6T3
NO
14
A1+
A2-
1L1 3L2 5L3 21
NC
2T1 4T2 6T3
NC
22
5L33L2
A1+
A2- 6T34T2
1L1
2T1
13
NO
NO
14
5L33L2
A1+
A2- 6T34T2
1L1
2T1
21
NC
NC
22
ASL../S contactors - DC operated (the polarity A1+, A2- must be respected)
Standard devices without addition of auxiliary contacts
CA3..S 1-pole auxiliary contact blocks
Other possible contact combinations with auxiliary contact blocks added by the user
21
NC
NC
22
5L33L2
A1+
A2- 6T34T2
1L1
2T1
13
NO
NO
14
33
NO
NO
34
21
NC
NC
22
5L33L2
A1+
A2- 6T34T2
1L1
2T1
13
NO
NO
14
A1+
A2-
1L1 3L2 5L3 13
NO
2T1 4T2 6T3
NO
14
A1+
A2-
1L1 3L2 5L3 13
NO
2T1 4T2 6T3
NO
14
=+
-1
-2
NC
2-
2-
21
22
NC
A1+
A2-
1L1 3L2 5L3 13
NO
2T1 4T2 6T3
NO
14
A1+
A2-
1L1 3L2 5L3 13
NO
2T1 4T2 6T3
NO
14
=
++
-1
-2
NC
-3
-4
NO
2-
2-
3-
3-
21
22
NC
33
34
NO
AS/L09...AS/L16-30-10/S AS/L09...AS/L16-30-01/SAS/L09...AS/L16-30-10/SAS/L09...AS/L16-30-01/S
AS/L09...AS/L16-30-32/S AS/L09...AS/L16-30-32/S
Combination 11 Combination 11AS/L09...AS/L16-30-10/S=CA3-01S+
Combination 21 Combination 21=AS/L09...AS/L16-30-10/S CA3-01S CA3-10S+ +
CA3-10/S CA3-01/S
Terminal markings and positioning
AS/L09../S...AS/L16../S & CA3 auxiliary contacts
Low Voltage Products & Systems 1.79
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Terminal markings and positioning
Add-on auxiliary contacts CA5 / CAL5 / CC5 / CAL16
One pole auxiliary contacts (top mounted)
Two pole auxiliary contacts
Four pole auxiliary contacts (Top mounted)
-1
-2
CA5-01
NC
-5
-6
CC5-01
NC
-3
-4
CA5-10
NO
-7
-8
CC5-10
NO
-1
-2
CE5-01
NC
-3
-4
CE5-10
NO
(EM/LB) (EM/LB)
21
22
11
12
41
42
31
32
CA5-04 E
NCNC NCNC
CA5-04 M
31
32
21
22
51
52
41
42
NCNC NCNC
CA5-04 N
61
62
51
52
81
82
71
72
NCNC NCNC
21
22
13
14
43
44
31
32
CA5-22 E
NO NCNC NO
21
22
31
32
43
44
53
54
CA5-22 M
NO NO
NC NC
CA5-22 N
61
62
53
54
83
84
71
72
NO NCNC NO
CA5-31 E
21
22
13
14
43
44
33
34
NO NC NONO
CA5-31 M
21
22
33
34
43
44
53
54
NONO NO
NC
51
52
63
64
73
74
83
84
CA5-31 N
NONO NO
NC
13
14
23
24
33
34
43
44
CA5-40 E
NO NONO NO
CA5-40 N
53
54
63
64
73
74
83
84
NO NONO NO
CA5-11/11 E
21
22
13
14
47
48
35
36
NO NCNC NO
CA5-11/11 M
33
34
21
22
57
58
45
46
NC NO
NO
NC
(EM/LB) (EM/LB)
21X /
22X /
13X /
14X /
NO NC
43X
44X
31X
32X
CAL5-11 (L. h. s. mounted)
NC NO
43X /
44X /
31X /
32X /
21X
22X
13X
14X
CAL5-11 (R. h. s. mounted)
61X /
62X /
53X /
54X /
NO NC
83X
84X
71X
72X
CAL5-11B (L. h. s. mounted) CAL5-11B (R. h. s. mounted)
NC NO
83X /
84X /
71X /
72X /
61X
62X
53X
54X
25X /
26X /
17X /
18X /
NO NC
47X
48X
35X
36X
CCL5-11 (L. h. s. mounted) CCL5-11 (R. h. s. mounted)
NC NO
47X /
48X /
35X /
36X /
25X
26X
17X
18X
21
22
13
14
CAL16-11 A (L. h. s. mounted)
NO NC
CAL16-11 B (R. h. s. mounted)
43
44
31
32
NONC
61
62
53
54
CAL16-11 C (L. h. s. mounted)
NO NC
CAL16-11 D (R. h. s. mounted)
83
84
71
72
NO
NC
CAL16-11E
(L & R. h. s. mounted)
(EM/LB)
47
48
35
36
NO
NC
(EM/LB) (EM/LB)
Legend
L.H.S. = Left hand side mounted
R.H.S. = Right hand side mounted
EM/LB = Early make / Late break
1.80 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Terminal markings and positioning
A9...A75
Standard devices without addition of auxiliary contacts
Other possible contact combinations with auxiliary contacts added by the user
Standard 3 pole devices with factory mounted auxiliary contacts
1R3 R5
2R4 R6
A9 – A26-22-00
A45 – A75-22-00
A1 A2
A2
7
8
1
L1
3
L2
5
L3
2
T1
4
T2
6
T3
A9 ... A26-40-00
A45 ... A75-40-00
A1 A2
A2
7
L4
8
T4
A1
A2
A50 – A110-30-00
UA50 – UA110-30-00
1L1
2T1
5L3
6T3
3L2
4T2
A1
A2
1
2
R5
R6
R3
R4
7
8
A9 – A26-22-00
A45 – A75-22-00
A1
1
L1
3
L2
5
L3
2
T1
4
T2
6
T3
A2
A2
A50 – A110-30-00
UA50 – UA110-30-00
A1
A2
1L1
2T1
3L2
4T2
5L3
6T3
13
NO
NO
14
A9 – A40-30-10
A1
A2
1L1
2T1
3L2
4T2
5L3
6T3
21
NC
NC
22
A9 – A40-30-01
A1
A2
A9 – A26-40-00
A45 – A75-40-00
1L1
2T1
3L2
4T2
5L3
6T3
7L4
8T4
A9 – A40-30-01
1L1 3L2 5L3
2T1 4T2 6T3
A1 A2
A2
21
NC
NC
22
A9 – A40-30-10
1
L1
3
L2
5
L3
2
T1
4
T2
6
T3
A1 A2
A2
13
NO
NO
14
A1
1
L1
2
T1
A2
13X
21X
14X
22X
A2
3
L2
5
L3
4
T2
6
T3
43X
31X
44X
32X
Combination
22
A1
A2
5L3
6T3
3L2
4T2
1L1
2T1
43
NO
NO
44
31
NC
NC
32
21
NC
NC
22
13
NO
NO
14
A9 – A16-30-22
A50 – A110-30-22
5L33L2
A1
A2 6T34T2
1L1
2T1
53
NO
NO
54
43
NO
NO
44
31
NC
NC
32
21
NC
NC
22
13
NO
NO
14
A9 – A40-30-32
A1
A2
1L1
2T1
3L2
4T2
21X
NC
NC
22X
5L3
6T3
13X
NO
NO
14X
A50 – A110-30-11
UA50 – UA110-30-11
A9 – A40-30-32
1
L1
3
L2
5
L3
2
T1
4
T2
6
T3
A1 A2
A2
13
NO
NO
14
NONC
NC NO
21 31 43 53
22 32 44 54
A1
1
L1
2
T1
A2
13X
21X
14X
22X
A2
3
L2
5
L3
4
T2
6
T3
NC
NO
NO
NC
2
A50 ... A110-30-11
UA50 ... UA110-30-11
A9 – A16-30-22
1
L1
3
L2
5
L3
2
T1
4
T2
6
T3
A1 A2
A2
NCNC
NO NO
13 21 31 43
14 22 32 44
A9 – A40-30-10 CA5-01 CA5-10
1
L1
3
L2
5
L3
2
T1
4
T2
6
T3
A1 A2
A2
13
NO
NO
14
Combination
21
=
=
1
L1
3
L2
5
L3
2
T1
4
T2
6
T3
A1 A2
A2
13
NO
NO
14
+ +
+ +
21
22
2-
2-
NC
33
34
3-
3-
NO
-1
-2
NC
-3
-4
NO
A1
A2
5L3
6T3
3L2
4T2
1L1
2T1
21
NC
NC
22
13
NO
NO
14
13
NO
NO
14
13
NO
NO
14
33
NO
NO
34
Combination 21
A9 – A40-30-10 CA5-01
1
L1
3
L2
5
L3
2
T1
4
T2
6
T3
A1 A2
A2
13
NO
NO
14
Combination
11
=
=
1
L1
3
L2
5
L3
2
T1
4
T2
6
T3
A1 A2
A2
13
NO
NO
14
+
+
21
22
2-
2-
NC
-1
-2
NC
43X
31X
44X
32X
A1
1L1
2T1
A2
13X
21X
14X
22X
A2
3L2 5L3
4T2 6T3
NC
NO
NO
NC
NC
NO
NO
NC
A50 – A75-30-11 CAL5-11
=
=
+
+
13 21 31 43
1L1 3L2 5L3
2T1 4T2 6T3
14 22 32 44
6-
6-
5-
5-
A1 A2
A2
NCNC
NO NO
A50 – A110-30-22
A1
A2
Combination 10
1L1
2T1
3L2
4T2
5L3
6T3
7L4
8T4
13
NO
NO
14
1
L1
3
L2
5
L3
2
T1
4
T2
6
T3
Combination
10
A1 A2
A2
7
L4
8
T4
13
14
6-
6-
2-
2-
3-
3-
4- 5-
4- 5-
NO
-3
-4
NO
1
L1
3
L2
5
L3
2
T1
4
T2
6
T3
A1 A2
A2
7
L4
8
T4
1-
1-
6-
6-
2-
2-
3-
3-
4- 5-
4- 5-
A45 – A75-40-00 CA5-10
=
=+
+
5L33L2
A1
A2 6T34T2
1L1
2T1
43X
NO
31X
NC
21X
NC
13X
NO
NO
14X
NC
22X
NC
32X
NO
44X
Combination 22
A1
A2
5L3
6T3
3L2
4T2
1L1
2T1
21
NC
NC
22
13
NO
NO
14
Combination 11
Low Voltage Products & Systems 1.81
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Terminal markings and positioning
AE9...AE75, AL9...AL40
AE Contactors – D.C. operated
AL Contactors – D.C. operated
Standard devices without addition of auxiliary contacts
Other possible contact combinations with auxiliary contacts added by the user
A1
1
L1
3
L2
5
L3
2
T1
4
T2
6
T3
A2
A3
C
D
L
5
AE50 – AE75-30-00
A1
A2
AE50 – AE110-30-00
1L1
2T1
5L3
6T3
3L2
4T2
A1
A2
1
2
R5
R6
R3
R4
7
8
AE45 – AE75-22-00
A1
1
L1
2
T1
A2
13X
21X
14X
22X
A3
3
L2
5
L3
4
T2
6
T3
NC
NO
C
C
L
5
NO
NC
AE95 – AE110-30-11
A1
A2
AE45 – AE75-40-00
1L1
2T1
3L2
4T2
5L3
6T3
7L4
8T4
1R3 R5
2R4 R6
A1 A2
A3
7
8
C
D
L
5
AE45 – AE75-22-00
A1
1
L1
3
L2
5
L3
2
T1
4
T2
6
T3
A2
A3
C
C
L
5
AE95 – AE110-30-00
A1
A2
1L1
2T1
3L2
4T2
21X
NC
NC
22X
5L3
6T3
13X
NO
NO
14X
AE50 – AE110-30-11
A1
1
L1
2
T1
A2
13X
21X
14X
22X
A3
3
L2
5
L3
4
T2
6
T3
NC
NO
C
D
L
5
NO
NC
AE50 – AE75-30-11
A3
A2
3 L2
1 L1
5 L3
4 T2
2 T1
6 T3
A1
U
35 X 36 X
{
VDC
Coil wiring
1
L1
3
L2
5
L3
2
T1
4
T2
6
T3
A1 A2
A3
7
L4
8
T4
C
D
L
5
AE45 – AE75-40-00
A3
A2
1 L1 2 T1
A1
U
15 X 16 X
{
VDC
7 L4 8 T4
Coil wiring
AL9 – AL40-30-01
1L1 3L2 5L3
2T1 4T2 6T3
A1
A2
21
NC
NC
22
A1
A2
1L1
2T1
3L2
4T2
5L3
6T3
21
NC
NC
22
AL9 – AL40-30-01
A1
A2
1L1
2T1
3L2
4T2
5L3
6T3
13
NO
NO
14
AL9 – AL40-30-10
A1
A2
1L1 3L2 5L3 7L4
2T1 4T2 6T3 8T4
AL9 – AL26-40-00
A1
A2
1
R
3
R
5 7
2
R
4
R
6 8
AL9 – AL26-22-00
A1
A2
AL9 – AL26-40-00
1L1
2T1
3L2
4T2
5L3
6T3
7L4
8T4
A1
A2
1
2
R5
R6
R3
R4
7
8
AL9 – AL26-22-00
AL9 – AL40-30-10 CA5-01 CA5-10Combination
21
=
=
+ +
++
1L1 3L2 5L3
2T1 4T2 6T3
A1
A2
13
NO
NO
14
2-
2-
3-
3-
4-
4-
5-
5-
1L1 3L2 5L3
2T1 4T2 6T3
A1
A2
13
NO
NO
14
21
22
NC
33
34
NO
-1
-2
NC
-3
-4
NO
A1
A2
5L3
6T3
3L2
4T2
1L1
2T1
21
NC
NC
22
13
NO
NO
14
13
NO
NO
14
13
NO
NO
14
33
NO
NO
34
Combination 21
AL9 – AL40-30-10
1L1 3L2 5L3
2T1 4T2 6T3
A1
A2
13
NO
NO
14
1.82 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
1 3 5 13 A1
2 4 6 14 A2
A1 13 1 3 5
A2 14 2 4 6
1 3 5 13 A1
2 4 6 14 A2
1 3 5 21 A1
2 4 6 22 A2
B6(7)-40-00 ...
BC6(7)-40-00 ...
B6(7)-30-10 ...
BC6(7)-30-10 ...
B6(7)-30-01 ...
BC6(7)-30-01 ...
VB6(7)-30-10 ...
VBC6(7)-30-10 ...
VB6(7)-30-01 ...
VBC6(7)-30-01 ...
K6-40 E ...
KC6-40 E ...
K6-31 Z ...
KC6-31 Z ...
K6-22 Z ...
KC6-22 Z ...
Miniature control relays
Miniature mechanically interlocked contactors
Miniature contactors
A1 21 1 3 5
A2 22 2 4 6
1 3 5 7 A1
2 4 6 8 A2
1 3 5 21 A1
2 4 6 22 A2
13 23 33 43 A1
14 24 34 44 A2
13 33 43 21 A1
14 34 44 22 A2
13 43 21 31 A1
14 44 22 32 A2
123
1 3 5 7
2 4 6 8
CA6-11E
CA6-11E-F
CA6-11E-P
Side mounted auxiliary contact blocks
13
21
22
14
B6(7)-40-00
B6(7)-40-00-F
B6(7)-40-00-P
BC6(7)-40-00
1 3 5 13
2 4 6 14
CA6-11M
CA6-11M-F
CA6-11M-P
33
21
22
34
B6(7)-30-10
B6(7)-30-10-F
B6(7)-30-10-P
BC6(7)-30-10
1 3 5 21
2 4 6 22
CA6-11N
CA6-11N-F
CA6-11N-P
13
31
32
14
B6(7)-30-01
B6(7)-30-01-F
B6(7)-30-01-P
BC6(7)-30-01
40 E
31Z
22Z
CA6-11K
CA6-11K-F
CA6-11K-P
53
61
62
54
K6 ...
K6 ... F
K6 ...P
KC6 ...
Front mounted auxiliary contact blocks
1 3 5 7
2 4 6 8
1 3 5 13
2 4 6 14
1 3 5 21
2 4 6 22
40 E
31Z
22Z
CAF6 ...
CAF6 ...
CAF6 ...
33 21
34 22
23 33
24 34
21 31
22 32
13 31
14 32
13 33
14 34
11 31
12 32
53 61
54 62
13 33
14 34
51 61
52 62
1 = CAF6-11E
2 = CAF6-20E
3 = CAF6-02E
1 = CAF6-11M
2 = CAF6-20M
3 = CAF6-02M
1 = CAF6-11N
2 = CAF6-20N
3 = CAF6-02N
1 = CAF6-11K
2 = CAF6-20K
3 = CAF6-02K
B6(7)-40-00
B6(7)-40-00-F
B6(7)-40-00-P
BC6(7)-40-00
B6(7)-30-10
B6(7)-30-10-F
B6(7)-30-10-P
BC6(7)-30-10
B6(7)-30-01
B6(7)-30-01-F
B6(7)-30-01-P
BC6(7)-30-01
K6 ...
K6 ... F
K6 ...P
KC6 ...
13 21
14 22
13 23
14 24
11 21
12 22
Terminal markings and positioning
B/C6...B/C7, CA6 & CAF6 auxiliary contacts
NOTE: Only side mounted type or front mounted type auxiliary contact blocks can be used at one time. Auxililiary contact blocks must not be mounted on Interface contactors, Interface control
relays or contactors for connection to PLCs. Two CAF 6 front mounted auxiliary contact blocks can installed on the mechanically interlocked contactors VB(C)6(7).
Low Voltage Products & Systems 1.83
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
IEC Technical data
AF09(Z)...AF38(Z), 3-pole
Utilization characteristics
Main pole - Utilization characteristics according to IEC
Contactor types
AC / DC operated
AF09 AF12 AF16 AF26 AF30 AF38
Standards
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage Ue max.
690 V
Rated frequency (without derating)
50 / 60 Hz
Conventional free-air thermal current Ith
acc. to IEC 60947-4-1, open contactors, θ40 °C 35 A 35 A 35 A 50 A 50 A 50 A
With conductor cross-sectional area 6 mm² 6 mm² 6 mm² 10 mm² 10 mm² 10 mm²
AC-1 Utilization category
For air temperature close to contactor
Ie / Rated operational current AC-1
θ ≤ 40 °C 25 A 28 A 30 A 45 A 50 A 50 A
Ue max. ≤ 690 V, 50/60 Hz θ ≤ 60 °C 25 A 28 A 30 A 40 A 42 A 42 A
θ ≤ 70 °C 22 A 24 A 26 A 32 A 37 A 37 A
With conductor cross-sectional area 4 mm² 6 mm² 6 mm² 10 mm² 10 mm² 10 mm²
AC-3 Utilization category
For air temperature close to contactor θ 60 °C
Ie / Max. rated operational current AC-3 (1)
M
3
3-phase motors
220-230-240 V 9 A 12 A 18 A 26 A 33 A 40 A
380-400 V 9 A 12 A 18 A 26 A 32 A 38 A
415 V 9 A 12 A 18 A 26 A 32 A 38 A
440 V 9 A 12 A 18 A 26 A 32 A 38 A
500 V 9.5 A 12.5 A 15 A 23 A 28 A 33 A
690 V 7 A 9 A 10.5 A 17 A 21 A 24 A
Rated operational power AC-3 (1)
M
3
1500 r.p.m. 50 Hz
1800 r.p.m. 60 Hz
3-phase motors
220-230-240 V 2.2 kW 3 kW 4 kW 6.5 kW 9 kW 11 kW
380-400 V 4 kW 5.5 kW 7.5 kW 11 kW 15 kW 18.5 kW
415 V 4 kW 5.5 kW 9 kW 11 kW 15 kW 18.5 kW
440 V 4 kW 5.5 kW 9 kW 15 kW 18.5 kW 22 kW
500 V 5.5 kW 7.5 kW 9 kW 15 kW 18.5 kW 22 kW
690 V 5.5 kW 7.5 kW 9 kW 15 kW 18.5 kW 22 kW
Rated making capacity AC-3
10 x Ie AC-3 acc. to IEC 60947-4-1
Rated breaking capacity AC-3
8 x Ie AC-3 acc. to IEC 60947-4-1
AC-8a Utilization category
(without thermal overload relay - Ue 400 V 50/60 Hz - θ ≤ 40 °C)
Ie / Rated operational current AC-8a
12 A 16 A 22 A 30 A 40 A 50 A
Rated operational power AC-8a
5.5 kW 7.5 kW 11 kW 15 kW 20 kW 25 kW
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded (2)
Ue ≤ 500 V AC - gG type fuse 25 A 32 A 32 A 50 A 63 A 63 A
Rated short-time withstand current Icw
1 s 300 A 300 A 300 A 700 A 700 A 700 A
at 40 °C ambient temperature,
in free air from a cold state
10 s 150 A 150 A 150 A 350 A 350 A 350 A
30 s 80 A 80 A 80 A 225 A 225 A 225 A
1 min 60 A 60 A 60 A 150 A 150 A 150 A
15 min 35 A 35 A 35 A 50 A 50 A 50 A
Maximum breaking capacity
cos φ = 0.45 at 440 V 250 A 250 A 250 A 500 A 500 A 500 A
at 690 V 106 A 106 A 106 A 200 A 200 A 200 A
Power dissipation per pole
Ie / AC-1 0.8 W 1 W 1.2 W 1.8 W 2.4 W 2.4 W
Ie / AC-3 0.1 W 0.2 W 0.35 W 0.6 W 0.9 W 1.3 W
Max. electrical switching frequency
AC-1 600 cycles/h
AC-3 1200 cycles/h
AC-2, AC-4 300 cycles/h 150 cycles/h
Note: total power loss = power dissipation per pole x number of poles + coil consumption.
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
(2) For the protection of motor starters against short circuits, see "Coordination with short-circuit protection devices".
1.84 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
IEC Technical data
A/E/L40, A/E/F50...A/F110, 3-pole
Utilization characteristics
Main pole - Utilization characteristics according to IEC
Contactor types
AC operated
A40 A50 A63 A75 A95 A110
DC operated
AL40 AE50 AE63 AE75
TAL40 TAE50 TAE75
AC / DC operated
AF50 AF63 AF75 AF95 AF110
Standards
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage Ue max.
690 V 1000 V (690 V for AF.. contactors) 1000 V
Rated frequency (without derating)
50/60 Hz
Conventional free-air thermal current Ith
acc. to IEC 60947-4-1, open contactors, θ40 °C 65 A 100 A 125 A 125 A 145 A 160 A
With conductor cross-sectional area 16 mm² 35 mm² 50 mm² 50 mm² 50 mm² 70 mm²
AC-1 Utilization category
For air temperature close to contactor
Ie / Rated operational current AC-1
θ ≤ 40 °C 60 A 100 A 115 A 125 A 145 A 160 A
Ue max. ≤ 690 V, 50/60 Hz θ ≤ 55 °C 60 A 85 A 95 A 105 A 135 A 145 A
θ ≤ 70 °C (3) 42 A 70 A 80 A 85 A 115 A 130 A
With conductor cross-sectional area 16 mm² 35 mm² 50 mm² 50 mm² 50 mm² 70 mm²
AC-3 Utilization category
For air temperature close to contactor θ 55 °C
Ie / Max. rated operational current AC-3 (1)
M
3
3-phase motors
220-230-240 V 40 A 53 A 65 A 75 A 96 A 110 A
380-400 V 37 A 50 A 65 A 75 A 96 A 110 A
415 V 37 A 50 A 65 A 75 A 96 A 110 A
440 V 37 A 45 A 65 A 70 A 93 A 100 A
500 V 33 A 45 A 55 A 65 A 80 A 100 A
690 V 25 A (4) 35 A 43 A 46 A 65 A 82 A
1000 V 23 A (6) 25 A (6) 28 A (6) 30 A 30 A
Rated operational power AC-3 (1)
M
3
1500 r.p.m. 50 Hz
1800 r.p.m. 60 Hz
3-phase motors
220-230-240 V 11 kW 15 kW 18.5 kW 22 kW 25 kW 30 kW
380-400 V 18.5 kW 22 kW 30 kW 37 kW 45 kW 55 kW
415 V 18.5 kW 25 kW 37 kW 40 kW 55 kW 59 kW
440 V 22 kW 25 kW 37 kW 40 kW 55 kW 59 kW
500 V 22 kW 30 kW 37 kW 45 kW 55 kW 59 kW
690 V 22 kW (4) 30 kW 37 kW 40 kW 55 kW 75 kW
1000 V 30 kW (6) 33 kW (6) 37 kW (6) 40 kW 40 kW
Rated making capacity AC-3
10 x Ie AC-3 acc. to IEC 60947-4-1
Rated breaking capacity AC-3
8 x Ie AC-3 acc. to IEC 60947-4-1
AC-8a Utilization category
(without thermal overload relay - Ue 400 V 50/60 Hz - θ ≤ 40 °C)
Ie / Rated operational current AC-8a
50 A 63 A 85 A 95 A 120 A 140 A
Rated operational power AC-8a
22 kW 30 kW 45 kW 45 kW 55 kW 75 kW
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded (2)
Ue ≤ 500 V AC - gG type fuse 63 A 100 A 125 A 160 A 160 A 200 A
Rated short-time withstand current Icw
1 s 600 A 1000 A 1320 A
at 40 °C ambient temperature,
in free air from a cold state
10 s 400 A 650 A 800 A
30 s 225 A 370 A 500 A
1 min 150 A 250 A 350 A
15 min 65 A 110 A 135 A 135 A 160 A 175 A
Maximum breaking capacity
cos φ = 0.45 at 440 V 820 A (5) 1300 A 1160 A
(cos φ = 0.35 for Ie > 100 A) at 690 V 340 A (5) 630 A 800 A
Power dissipation per pole
Ie / AC-1 3 W 5 W 6.5 W 7 W 6.5 W 7.5 W
Ie / AC-3 1.3 W 1.3 W 1.5 W 2 W 2.7 W 3.6 W
Max. electrical switching frequency
AC-1 600 cycles/h 600 cycles/h (300 for AF.., AE.., TAE..) 300 cycles/h
AC-3 1200 cycles/h 600 cycles/h (300 for AF.., AE.., TAE..) 300 cycles/h
AC-2, AC-4 300 cycles/h 150 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
(2) For the protection of motor starters against short circuits, see "Coordination with short-circuit protection devices".
(3) Unauthorized for TAL.., TAE.. contactors.
(4) AC-3, 690 V values for AL40 and TAL40 contactors: 18.5 kW, Ie = 21 A.
(5) Max. breaking capacity for AL40 and TAL40 contactors: 470 A at 440 V, 175 A at 690 V.
(6) AF contactors excluded.
Low Voltage Products & Systems 1.85
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
IEC Technical data
A/F145...AF300, 3-pole
Utilization characteristics
Main pole - Utilization characteristics according to IEC
Contactor types
AC operated
A145 A185 A210 A260 A300
AC / DC operated
AF145 AF185 AF210 AF260 AF300
Standards
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage Ue max.
1000 V 690 V
Rated frequency (without derating)
50/60 Hz
Conventional free-air thermal current Ith
acc. to IEC 60947-4-1, open contactors, θ40 °C 250 A 275 A 350 A 400 A 500 A (4)
With conductor cross-sectional area (3) 120 mm² 150 mm² 185 mm² 240 mm² 300 mm² (4)
AC-1 Utilization category
For air temperature close to contactor
Ie / Rated operational current AC-1
θ ≤ 40 °C 250 A 275 A 350 A 400 A 500 A (4)
Ue max. ≤ 690 V, 50/60 Hz θ ≤ 55 °C 230 A 250 A 300 A 350 A 400 A (4)
θ ≤ 70 °C 180 A 180 A 240 A 290 A 325 A (4)
Ie / Rated operational current AC-1
θ ≤ 40 °C 180 A 200 A –––
Ue max. ≤ 1000 V, 50/60 Hz θ ≤ 55 °C 180 A 200 A –––
θ ≤ 70 °C 180 A 180 A –––
With conductor cross-sectional area 120 mm² 150 mm² 185 mm² 240 mm² 300 mm² (4)
AC-3 Utilization category
For air temperature close to contactor θ 55 °C
Ie / Max. rated operational current AC-3 (1)
M
3
3-phase motors
220-230-240 V 145 A 185 A 210 A 260 A 305 A
380-400 V 145 A 185 A 210 A 260 A 305 A
415 V 145 A 185 A 210 A 260 A 300 A
440 V 145 A 185 A 210 A 240 A 280 A
500 V 145 A 170 A 210 A 240 A 280 A
690 V 120 A 170 A 210 A 220 A 280 A
1000 V 80 A 95 A –––
Rated operational power AC-3 (1)
M
3
1500 r.p.m. 50 Hz
1800 r.p.m. 60 Hz
3-phase motors
220-230-240 V 45 kW 55 kW 59 kW 80 kW 90 kW
380-400 V 75 kW 90 kW 110 kW 140 kW 160 kW
415 V 75 kW 90 kW 110 kW 140 kW 160 kW
440 V 75 kW 90 kW 110 kW 140 kW 160 kW
500 V 90 kW 110 kW 132 kW 180 kW 200 kW
690 V 110 kW 132 kW 160 kW 200 kW 250 kW
1000 V 110 kW 132 kW –––
Rated making capacity AC-3
10 x Ie AC-3 acc. to IEC 60947-4-1
Rated breaking capacity AC-3
8 x Ie AC-3 acc. to IEC 60947-4-1
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded (2)
Ue ≤ 500 V AC - gG type fuse 315 A 355 A 400 A 500 A 500 A
Rated short-time withstand current Icw
1 s 1800 A 2000 A 2500 A 3500 A 3500 A
at 40 °C ambient temperature,
in free air from a cold state
10 s 1200 A 1500 A 1700 A 2400 A 2400 A
30 s 800 A 1000 A 1200 A 1500 A 1500 A
1 min 600 A 800 A 1000 A 1100 A 1100 A
15 min 280 A 320 A 400 A 500 A 500 A
Maximum breaking capacity
cos φ = 0.45 at 440 V 1500 A 2000 A 2300 A 2600 A 3000 A
(cos φ = 0.35 for Ie > 100 A) at 690 V 1200 A 1600 A 2000 A 2400 A 2500 A
Power dissipation per pole
Ie / AC-1 13 W 16 W 18 W 25 W 32 W
Ie / AC-3 5 W 8 W 9 W 14 W 18 W
Max. electrical switching frequency
AC-1 300 cycles/h 300 cycles/h
AC-3 300 cycles/h 300 cycles/h
AC-2, AC-4 150 cycles/h 150 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
(2) For the protection of motor starters against short circuits, see "Coordination with short-circuit protection devices".
(3) Conductors with preparation.
(4) Use terminal extension / enlargement pieces (LX 300 / LW 300).
1.86 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
IEC Technical data
AF400...AF2050, 3-pole
Utilization characteristics
Main pole - Utilization characteristics according to IEC
Contactor types
AC / DC operated
AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050
Standards
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage Ue max.
1000 V
Rated frequency (without derating)
50/60 Hz
Conventional free-air thermal current Ith
acc. to IEC 60947-4-1, open contactors, θ40 °C 600 A 700 A 800 A 1050 A 1260 A 1350 A 1650 A 2050 A
With conductor cross-sectional area (3)
2x185 mm² 2x240 mm² 2x240 mm² 800 mm² (4) 1000 mm² (4) 1000 mm² (5) 1500 mm² (5) 2000 mm² (5)
AC-1 Utilization category
For air temperature close to contactor
Ie / Rated operational current AC-1
θ ≤ 40 °C 600 A 700 A 800 A 1050 A 1260 A 1350 A 1650 A 2050 A
Ue max. ≤ 690 V, 50/60 Hz θ ≤ 55 °C 500 A 600 A 700 A 875 A 1040 A 1150 A 1450 A 1750 A
θ ≤ 70 °C 400 A 480 A 580 A 720 A 875 A 1000 A 1270 A 1500 A
Ie / Rated operational current AC-1
θ ≤ 40 °C 600 A 700 A 800 A 1000 A 1260 A 1350 A 1650 A 2050 A
Ue max. ≤ 1000 V, 50/60 Hz θ ≤ 55 °C 500 A 600 A 700 A 875 A 1040 A 1150 A 1450 A 1750 A
θ ≤ 70 °C 400 A 480 A 580 A 720 A 875 A 1000 A 1270 A 1500 A
With conductor cross-sectional area
2x185 mm² 2x240 mm² 2x240 mm² 800 mm² (4) 1000 mm² (4) 1000 mm² (5) 1500 mm² (5) 2000 mm² (5)
AC-3 Utilization category
For air temperature close to contactor θ 55 °C
Ie / Max. rated operational current AC-3 (1)
M
3
3-phase motors
220-230-240 V 400 A 460 A 580 A 750 A 860 A 1050 A
380-400 V 400 A 460 A 580 A 750 A 860 A 1050 A
415 V 400 A 460 A 580 A 750 A 860 A 1050 A
440 V 400 A 460 A 580 A 750 A 860 A 1050 A
500 V 400 A 460 A 580 A 750 A 800 A 950 A
690 V 350 A 400 A 500 A 650 A 800 A 950 A
1000 V 155 A 200 A 250 A 300 A
Rated operational power AC-3 (1)
M
3
1500 r.p.m. 50 Hz
1800 r.p.m. 60 Hz
3-phase motors
220-230-240 V 110 kW 132 kW 160 kW 220 kW 257 kW 315 kW
380-400 V 200 kW 250 kW 315 kW 400 kW 475 kW 560 kW
415 V 220 kW 250 kW 355 kW 425 kW 500 kW 600 kW
440 V 220 kW 250 kW 355 kW 450 kW 560 kW 670 kW
500 V 250 kW 315 kW 400 kW 520 kW 560 kW 700 kW
690 V 315 kW 355 kW 500 kW 600 kW 750 kW 900 kW
1000 V 220 kW 280 kW 355 kW 400 kW
Rated making capacity AC-3
10 x Ie AC-3 acc. to IEC 60947-4-1
Rated breaking capacity AC-3
8 x Ie AC-3 acc. to IEC 60947-4-1
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded (2)
Ue ≤ 500 V AC - gG type fuse 630 A 800 A 1000 A 1000 A Please consult us for coordination with circuit-breaker
Rated short-time withstand current Icw
1 s 4600 A 4600 A 7000 A 7000 A 8000 A 10000 A 12000 A 12000 A
at 40 °C ambient temperature,
in free air from a cold state
10 s 4400 A 4400 A 6400 A 6400 A 7200 A 8000 A 10000 A 10000 A
30 s 3100 A 3100 A 4500 A 4500 A 5200 A 6000 A 7500 A 7500 A
1 min 2500 A 2500 A 3500 A 3500 A 4000 A 4500 A 5500 A 5500 A
15 min 840 A 840 A 1300 A 1300 A 1500 A 1600 A 2200 A 2200 A
Maximum breaking capacity
cos φ = 0.45 at 440 V 4000 A 5000 A 6000 A 7500 A 10000 A 12000 A 8400 A
(cos φ = 0.35 for Ie > 100 A) at 690 V 3500 A 4500 A 5000 A 7000 A –––
Power dissipation per pole
Ie / AC-1 30 W 42 W 32 W 50 W 80 W 80 W 80 W 125W
Ie / AC-3 16 W 21 W 17 W 28 W 50 W 50 W
Max. electrical switching frequency
AC-1 300 cycles/h 300 cycles/h 300 cycles/h 60 cycles/h 60 cycles/h
AC-3 300 cycles/h 300 cycles/h 60 cycles/h
AC-2, AC-4 60 cycles/h 60 cycles/h 60 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
(2) For the protection of motor starters against short circuits, see "Coordination with short-circuit protection devices".
(3) Conductors with preparation.
(4) Max. connection bar width 50 mm.
(5) Max. connection bar width 100 mm.
Low Voltage Products & Systems 1.87
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
UL/NEMA/CSA Technical data
AF09(Z)...AF38(Z); AF09N00(Z)...AF26N1(Z), 3-pole
Utilization characteristics
Main pole - Utilization characteristics according to UL / NEMA / CSA
Contactor types
AC / DC operated
AF09 AF12 AF16 AF26 AF30 AF38
Standards
UL 508, CSA C22.2 N°14
Max. operational voltage
600 V
NEMA size
00 0 1
NEMA continuous amp rating
Thermal current 9 A 18 A 27 A
NEMA maximum horse power ratings 1-phase, 60 Hz
115 V AC 1/3 hp 1 hp 2 hp
230 V AC 1 hp 2 hp 3 hp
NEMA maximum horse power ratings 3-phase, 60 Hz
200 V AC 1-1/2 hp 3 hp 7-1/2 hp
230 V AC 1-1/2 hp 3 hp 7-1/2 hp
460 V AC 2 hp 5 hp 10 hp
575 V AC 2 hp 5 hp 10 hp
UL / CSA general use rating
600 V AC 25 A 28 A 30 A 45 A 50 A 50 A
With conductor cross-sectional area AWG 10 AWG 10 AWG 10 AWG 8 AWG 8 AWG 8
UL / CSA maximum 1-phase motor rating
Full load current 120 V AC 13.8 A 16 A 20 A 24 A 24 A 24 A
240 V AC 10 A 12 A 17 A 17 A 28 A 28 A
Horse power rating 120 V AC 3/4 hp 1 hp 1-1/2 hp 2 hp 2 hp 2 hp
240 V AC 1-1/2 hp 2 hp 3 hp 3 hp 5 hp 5 hp
UL / CSA maximum 3-phase motor rating
Full load current (1) 200-208 V AC 7.8 A 11 A 17.5 A 25.3 A 32.2 A 32.2 A
220-240 V AC 6.8 A 9.6 A 15.2 A 22 A 28 A 28 A
440-480 V AC 7.6 A 11 A 14 A 21 A 27 A 27 A
550-600 V AC 9 A 11 A 17 A 22 A 27 A (2) 27 A (2)
Horse power rating (1) 200-208 V AC 2 hp 3 hp 5 hp 7-1/2 hp 10 hp 10 hp
220-240 V AC 2 hp 3 hp 5 hp 7-1/2 hp 10 hp 10 hp
440-480 V AC 5 hp 7-1/2 hp 10 hp 15 hp 20 hp 20 hp
550-600 V AC 7-1/2 hp 10 hp 15 hp 20 hp 25 hp (2) 25 hp (2)
Max. electrical switching frequency
For general use 600 cycles/h
For motor use 1200 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see “Motor rated operational powers and currents”.
(2) For contactors produced since week 49-2011.
General technical data
Contactor types
AC / DC operated
AF09 AF12 AF16 AF26 AF30 AF38
Rated insulation voltage Ui
acc. to IEC 60947-4-1 690 V
acc. to UL / CSA 600 V
Rated impulse withstand voltage Uimp.
6 kV
Electromagnetic compatibility
Devices complying with IEC 60947-1 / EN 60947-1 - Environment A
Ambient air temperature close to contactor
Operation Fitted with thermal overload relay -25...+60 °C
Without thermal overload relay -40...+70 °C
Storage -60...+80 °C
Climatic withstand
Category B according to IEC 60947-1 Annex Q
Maximum operating altitude (without derating)
3000 m
Mechanical durability
Number of operating cycles 10 millions operating cycles
Max. switching frequency 3600 cycles/h
Shock withstand
acc. to IEC 60068-2-27 and EN 60068-2-27
Mounting position 1
B2
AAB1
C2
C1
Shock direction 1/2 sinusoidal shock for 11 ms: no change in contact position, closed or open position
A30 g
B1 25 g closed position / 5 g open position
B2 15 g
C1 25 g
C2 25 g
Vibration withstand
5...300 Hz
acc. to IEC 60068-2-6 4 g closed position / 2 g open position
1.88 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Main pole - Utilization characteristics according to UL / NEMA / CSA
Contactor types
AC operated
A40 A50 A63 A75 A95 A110
DC operated
AL40, TAL40 AE50, TAE50 AE63 AE75, TAE75
AC / DC operated
AF50 AF63 AF75 AF95 AF110
Standards
UL 508, CSA C22.2 N°14
Max. operational voltage
600 V
NEMA size
23
NEMA continuous amp rating
Thermal current 45 A 90 A
NEMA maximum horse power ratings 1-phase, 60 Hz
115 V AC 3 hp ––––
230 V AC 7-1/2 ––––
NEMA maximum horse power ratings 3-phase, 60 Hz
200 V AC 10 hp 25 hp
230 V AC 15 hp 30 hp
460 V AC 25 hp 50 hp
575 V AC 25 hp 50 hp
UL / CSA general use rating
600 V AC 60 A 80 A 90 A 105 A 125 A 150 A
With conductor cross-sectional area AWG 6 AWG 4 AWG 3 AWG 2 AWG 1 AWG 1/0
UL / CSA maximum 1-phase motor rating
Full load current 120 V AC 34 A 34 A 56 A 80 A 80 A 100 A
240 V AC 40 A 40 A 50 A 68 A 88 A 110 A
Horse power rating 120 V AC 3 hp 3 hp 5 hp 7.5 hp 7.5 hp 10 hp
240 V AC 7.5 hp 7.5 hp 10 hp 15 hp 20 hp 25 hp
UL / CSA maximum 3-phase motor rating
Full load current (1) 200-208 V AC 32.2 A 48.3 A 62.1 A 78.2 A 92 A 92 A
220-240 V AC 42 A 54 A 68 A 80 A 80 A 104 A
440-480 V AC 40 A 52 A 77 A 77 A 77 A 96 A
550-600 V AC 41 A 52 A 77 A 77 A 77 A 99 A
Horse power rating (1) 200-208 V AC 10 hp 15 hp 20 hp 25 hp 30 hp 30 hp
220-240 V AC 15 hp 20 hp 25 hp 30 hp 30 hp 40 hp
440-480 V AC 30 hp 40 hp 60 hp 60 hp 60 hp 75 hp
550-600 V AC 40 hp 50 hp 75 hp 75 hp 75 hp 100 hp
Max. electrical switching frequency
For general use 600 cycles/h 600 cycles/h (300 for AF.., AE..) 300 cycles/h
For motor use 1200 cycles/h 600 cycles/h (300 for AF.., AE..) 300 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see “Motor rated operational powers and currents”.
UL/NEMA/CSA Technical data
A/E/L40; A/E/F50...A/F110, A/E/F50N2...A/E/F75N3, 3-pole
Utilization characteristics
General technical data
Contactor types
AC operated
A40 A50 A63 A75 A95 A110
DC operated
AL40, TAL40 AE50, TAE50 AE63 AE75, TAE75
AC / DC operated
AF50 AF63 AF75 AF95 AF110
Rated insulation voltage Ui
acc. to IEC 60947-4-1 1000 V
acc. to UL 600 V
Rated impulse withstand voltage Uimp.
8 kV
Electromagnetic compatibility
AF contactors complying with IEC 60947-1 / EN 60947-1 - Environment A
Ambient air temperature close to contactor
Operation Fitted with thermal overload relay -25...+55 °C
Without thermal overload relay -40…+70 °C (
55 °C max. for TAL.., and TAE.. contactor
)
Storage -60...+80 °C -40...+70 °C
Climatic withstand
acc. to IEC 60068-2-30 and 60068-2-11
UTE C 63-100 specification II
acc. to IEC 60068-2-30
Maximum operating altitude (without derating)
3000 m
Mechanical durability
Number of operating cycles 10 millions operating cycles (5 millions for AE.. and TAE..)
Max. switching frequency 3600 cycles/h (300 for AF contactors)
Shock withstand
acc. to IEC 60068-2-27 and EN 60068-2-27
Mounting position 1
B2
AAB1
C2
C1
Shock direction 1/2 sinusoidal shock for 11 ms: no change in contact position, closed or open position (2)
A20 g
B1 10 g closed position / 5 g open position
B2 15 g
C1 20 g
C2 20 g
(2) These values are not valid for rail mounting with contactors A95 ... A110 and AF95 ... AF110.
For AL40, TAL40
A : 20 g closed position / 10 g open position
B1 : 15 g closed position / 5 g open position
B2 : 10 g closed position / 10 g open position
C1 : 20 g closed position / 8 g open position
C2 : 14 g closed position / 8 g open position
Low Voltage Products & Systems 1.89
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
UL/NEMA/CSA Technical data
A/F145...A/F300; A/F145N4...A/F260N5, 3-pole
Utilization characteristics
Main pole - Utilization characteristics according to UL / NEMA / CSA
Contactor types
AC operated
A145 A185 A210 A260 A300
AC / DC operated
AF145 AF185 AF210 AF260 AF300
Standards
UL 508, CSA C22.2 N°14
Max. operational voltage
600 V
NEMA size
4 5
NEMA maximum horse power ratings 1-phase, 60 Hz
115 V AC –––––
230 V AC –––––
NEMA maximum horse power ratings 3-phase, 60 Hz
200 V AC 40 hp 75 hp
230 V AC 50 hp 100 hp
460 V AC 100 hp 200 hp
575 V AC 200 hp 200 hp
UL / CSA general use rating
600 V AC 230 A 250 A 300 A 350 A 400 A
UL / CSA maximum 1-phase motor rating
Full load current 240 V AC –––––
Horse power rating 240 V AC –––––
UL / CSA maximum 3-phase motor rating
Full load current (1) 200-208 V AC 119.6 A 149.5 A 166.8 A 220.8 A 285.2 A
220-240 V AC 130 A 145 A 192 A 248 A 248 A
440-480 V AC 124 A 156 A 180 A 240 A 302 A
550-600 V AC 125 A 144 A 192 A 242 A 289 A
Horse power rating (1) 200-208 V AC 40 hp 50 hp 60 hp 75 hp 100 hp
220-240 V AC 50 hp 60 hp 75 hp 100 hp 100 hp
440-480 V AC 100 hp 125 hp 150 hp 200 hp 250 hp
550-600 V AC 125 hp 150 hp 200 hp 250 hp 300 hp
Max. electrical switching frequency
For general use 300 cycles/h
For motor use 300 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see “Motor rated operational powers and currents”.
General technical data
Contactor types
AC operated
A145 A185 A210 A260 A300
AC / DC operated
AF145 AF185 AF210 AF260 AF300
Rated insulation voltage Ui
acc. to IEC 60947-4-1 1000 V
acc. to UL 600 V
Rated impulse withstand voltage Uimp.
8 kV
Electromagnetic compatibility
AF contactors complying with IEC 60947-1 / EN 60947-1 - Environment A
Ambient air temperature close to contactor
Operation Fitted with thermal overload relay -25 to +55 °C
Fitted with electronic overload relay -25 to +70 °C
Without electronic overload relay -40 to +70 °C
Storage -40 to +70 °C
Climatic withstand
acc. to IEC 60068-2-30
Maximum operating altitude (without derating)
3000 m
Mechanical durability
Number of operating cycles 5 millions operating cycles
Max. switching frequency 3600 cycles/h (300 for AF… contactors)
Shock withstand
acc. to IEC 60068-2-27 and EN 60068-2-27
Mounting position 1
B2
AAB1
C2
C1
ABB
Shock direction 1/2 sinusoidal shock for 30 ms: no change in contact position, closed or open position
A5 g
B1 5 g
B2 5 g
C1 5 g
C2 5 g
1.90 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
UL/NEMA/CSA Technical data
AF400...AF2050; AF460N6...AF1650N8, 3-pole
Utilization characteristics
Main pole - Utilization characteristics according to UL / NEMA / CSA
Contactor types
AC / DC operated
AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050
Standards
UL 508, CSA C22.2 N°14
Max. operational voltage
600 V
NEMA size
678
NEMA maximum horse power ratings 1-phase, 60 Hz
115 V AC
230 V AC
NEMA maximum horse power ratings 3-phase, 60 Hz
200 V AC 150 hp –– –––
230 V AC 200 hp 300 hp 450 hp
460 V AC 400 hp 600 hp 900 hp
575 V AC 400 hp 600 hp 900 hp
UL / CSA general use rating
600 V AC 550 A 650 A 750 A 900 A 1210 A 1350 A 1650 A 2100 A
UL / CSA maximum 1-phase motor rating
Full load current 120 V AC ––––––––
240 V AC ––––––––
Horse power rating 120 V AC ––––––––
240 V AC ––––––––
UL / CSA maximum 3-phase motor rating
Full load current (1) 200-208 V AC 358.8 A 414 A 552 A 692.3 A 954 A 1030 A
220-240 V AC 360 A 480 A 604 A 722 A 954 A 1030 A
440-480 V AC 414 A 477 A 590 A 722 A 954 A 1030 A
550-600 V AC 382 A 472 A 578 A 672 A 944A 1050 A
Horse power rating (1) 200-208 V AC 125 hp 150 hp 200 hp 250 hp ––––
220-240 V AC 150 hp 200 hp 250 hp 300 hp 400 A 450 hp
440-480 V AC 350 hp 400 hp 500 hp 600 hp 800 A 900 hp
550-600 V AC 400 hp 500 hp 600 hp 700 hp 1000 A 1150 hp
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded
Fuse rating 1000 A 1200 A Please consult us for coordination
with circuit-breaker
Fuse type, 600 V L
Max. electrical switching frequency
For general use 300 cycles/h 60 cycles/h
For motor use 300 cycles/h 60 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see “Motor rated operational powers and currents”.
General technical data
Contactor types
AC / DC operated
AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050
Rated insulation voltage Ui
acc. to IEC 60947-4-1 1000 V
acc. to UL 600 V
Rated impulse withstand voltage Uimp.
8 kV
Electromagnetic compatibility
AF contactors complying with IEC 60947-1 / EN 60947-1 - Environment A
Ambient air temperature close to contactor
Operation Fitted with electronic overload relay -25 to +70 °C
Without electronic overload relay -40 to +70 °C
Storage -40 to +70 °C
Climatic withstand
acc. to IEC 60068-2-30
Maximum operating altitude (without derating)
3000 m
Mechanical durability
Number of operating cycles 3 millions operating cycles 0.5 million operating cycles
Max. switching frequency 300 cycles/h 60 cycles/h
Shock withstand
acc. to IEC 60068-2-27 and EN 60068-2-27
Mounting position 1
B2
AAB1
C2
C1
ABB
Shock direction 1/2 sinusoidal shock for 30 ms: no change in contact position, closed or open position
A5 g
B1 5 g
B2 5 g
C1 5 g
C2 5 g
Low Voltage Products & Systems 1.91
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General technical data
AF09(Z)...AF38(Z), 3-pole
Coil & mounting characteristics
Magnet system characteristics
Contactor types
AC / DC operated
AF09 AF12 AF16 AF26 AF30 AF38
Coil operating limits
AC supply At θ60 °C 0.85 x Uc min...1.1 x Uc max.
At θ 70 °C 0.85 x Uc min...Uc max.
acc. to IEC 60947-4-1
DC supply At θ60 °C 0.85 x Uc min...1.1 x Uc max.
At θ 70 °C (AF) 0.85 x Uc min...Uc max. - (AF..Z) 0.85 x Uc min...1.1 x Uc max.
AC control voltage
Rated control circuit voltage Uc 24...500 V AC
50/60 Hz
Coil consumption Average pull-in value (AF) 50 VA - (AF..Z) 16 VA
Average holding value (AF) 2.2 VA / 2 W - (AF..Z) 1.7 VA / 1.5 W
DC control voltage
Rated control circuit voltage Uc 12...500 V DC
Coil consumption Average pull-in value (AF) 50 W - (AF..Z) 12...16 W
Average holding value (AF) 2 W - (AF..Z) 1.7 W
PLC-output control
(AF..Z) ≥ 500 mA 24 V DC
Drop-out voltage
≤ 60 % of Uc min.
Voltage sag immunity
(AF..Z) conditions of use on request
acc. to SEMI F47-0706
Dips withstand
(AF..Z) 22 ms average
-20 °C θ ≤ +60°C
Operating time
Between coil energization and: N.O. contact closing 40...95 ms
N.C. contact opening 38...90 ms
Between coil de-energization and: N.O. contact opening 11...95 ms
N.C. contact closing 13...98 ms
Mounting characteristics and conditions for use
Contactor types
AC / DC operated
AF09 AF12 AF16 AF26 AF30 AF38
Mounting positions
Max. N.C. built-in and add-on N.C. auxiliary contacts:
see accessory fitting details for a 3-pole contactor AF09 ... AF38
Mounting distances
The contactors can be assembled side by side
Fixing
On rail according to IEC 60715, EN 60715 35 x 7.5 mm or 35 x 15 mm
By screws (not supplied) 2 x M4 screws placed diagonally
1.92 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General technical data
A40...A110, 3-pole
Coil & mounting characteristics
Magnet system characteristics
Contactor types
AC operated
A40 A50 A63 A75 A95 A110
Coil operating limits
AC supply At θ55 °C 0.85...1.1 x Uc at θ70 °C 0.85...1.1 x Uc
acc. to IEC 60947-4-1 Please also refer to "Mounting characteristics and conditions for use"
AC control voltage
Rated control circuit voltage Uc at 50 Hz 24…690 V
at 60 Hz 24…690 V
Coil consumption Average pull-in value 50 Hz 120 VA 180 VA 350 VA
60 Hz 140 VA 210 VA 450 VA
50/60 Hz (1) 125 VA / 120 VA 190 VA / 180 VA 410 VA / 365 VA
Average holding value 50 Hz 12 VA / 3 W 18 VA / 5.5 W 22 VA / 6.5 W
60 Hz 12 VA / 3 W 18 VA / 5.5 W 26 VA / 8 W
50/60 Hz (1) 12 VA / 3 W 18 VA / 5.5 W 27 VA / 7.5 W
Drop-out voltage
Approx. 40...65 % of Uc
Operating time
Between coil energization and: N.O. contact closing 8…21 ms 8…27 ms 10…25 ms
N.C. contact opening 6…18 ms 7…22 ms 7…22 ms
Between coil de-energization and: N.O. contact opening 4…11 ms 4…11 ms 7…15 ms
N.C. contact closing 7…14 ms 7…14 ms 10…18 ms
(1) 50/60 Hz coils: see "Voltage code table".
Mounting characteristics and conditions for use
Contactor types
AC operated
A40 A50 A63 A75 A95 A110
Mounting positions
Pos. 5Pos. 6
Pos. 3
Pos. 2
Pos. 1Pos. 1 ± 30°
+30° -30°
Pos. 4
Max. built-in and add-on N.O. or N.C. auxiliary contacts: see accessory fitting details for 3-pole
contactor A40 ... A110
Control voltage / Ambient temperature
Mounting
positions
1, 1±30°, 2, 3, 4, 5 at θ ≤ 55 °C 0.85…1.1 x Uc 0.85…1.1 x Uc
at θ ≤ 70 °C Uc 0.85…1.1 x Uc
6at θ ≤ 55 °C
0.95...1.1 x Uc
Unauthorized
at θ ≤ 70 °C Unauthorized Unauthorized
Mounting distances
The contactors can be assembled side by side
Fixing
On rail according to IEC 60715, EN 60715 35 x 7.5 mm or
35 x 15 mm
35 x 15 mm or
75 x 25 mm
By screws (not supplied) 2 x M4 screws
placed diagonally
2 x M6 screws
placed diagonally
2 x M6 screws
placed diagonally
Low Voltage Products & Systems 1.93
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General technical data
AL40, AE50...AE75, 3-pole
Coil & mounting characteristics
Magnet system characteristics
Contactor types
DC operated
AL40 AE50 AE63 AE75
Coil operating limits
DC supply at θ55 °C 0.85...1.1 x Uc
Please also refer to "Mounting characteristics and conditions for use"
acc. to IEC 60947-4-1
DC control voltage
Rated control circuit voltage Uc 12...250 V DC
Coil consumption Average pull-in value 3.5 W 200 W
Average holding value 3.5 W 4 W
Drop-out voltage
approx. 10...30 % of Uc approx. 15...40 % of Uc
Coil time constant
Open L/R 38 ms 3 ms
Closed L/R 62 ms 15 ms
Operating time
Between coil energization and: N.O. contact closing 55…110 ms 13…30 ms
N.C. contact opening 25…75 ms 10…27 ms
Between coil de-energization and: N.O. contact opening (1) 12…18 ms 5…15 ms
N.C. contact closing (1) 18…28 ms 8…18 ms
(1) The use of surge suppressors increases the opening time with a factor of 1.1 to 1.5 for a RV5 surge suppressor and a factor of 1.5 to 3 for a RT5 surge suppressor.
Mounting characteristics and conditions for use
Contactor types
DC operated
AL40 AE50 AE63 AE75
Mounting positions
Pos. 5Pos. 6
Pos. 3
Pos
. 2
Pos. 1Pos. 1 ± 30°
+30° -30°
Pos. 4
Max. built-in and add-on N.O. or N.C. auxiliary contacts:
see accessory fitting details for 3-pole contactor AL40, AE50 … AE75
Control voltage / Ambient temperature
Mounting
positions
1, 1±30°, 2, 3, 4, 5 at θ ≤ 55 °C 0.85 x Uc…1.1 x Uc
at θ ≤ 70 °C Uc
6at θ ≤ 55 °C Unauthorized 0.95 x Uc…1.1 x Uc
at θ ≤ 70 °C Unauthorized
Mounting distances
The contactors can be assembled side by side
Fixing
On rail according to IEC 60715, EN 60715 35 x 7.5 mm or
35 x 15 mm
35 x 15 mm or 75 x 25 mm
By screws (not supplied) 2 x M4 screws
placed diagonally
2 x M6 screws placed diagonally
1.94 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General technical data
AF50...AF110, 3-pole
Coil & mounting characteristics
Magnet system characteristics
Contactor types
AC / DC operated
AF50 AF63 AF75 AF95 AF110
Coil operating limits
AC or DC supply At θ70 °C 0.85 x Uc min...1.1 x Uc max.
Please also refer to "Mounting characteristics and conditions for use"
acc. to IEC 60947-4-1
AC control voltage
Rated control circuit voltage Uc 48…250 V 50/60 Hz
50/60 Hz
Coil consumption Average pull-in value 210 VA 350 VA
Average holding value 7 VA / 2.8 W 7 VA / 3.5 W
DC control voltage
Rated control circuit voltage Uc 20…250 V DC
Coil consumption Average pull-in value 190 W 400 W
Average holding value 2.8 W 2 W
Drop-out voltage
55 % of Uc min.
Voltage sag immunity
Conditions of use on request
acc. to SEMI F47
Dips withstand
≥ 20 ms
Operating time
Between coil energization and: N.O. contact closing 30…100 ms 30…80 ms
N.C. contact opening 27…95 ms 27…77 ms
Between coil de-energization and: N.O. contact opening 30…110 ms 55…125 ms
N.C. contact closing 35…115 ms 60…130 ms
Mounting characteristics and conditions for use
Contactor types
AC / DC operated
AF50 AF63 AF75 AF95 AF110
Mounting positions
Max. built-in and add-on N.O. or N.C. auxiliary contacts:
see accessory fitting details for 3-pole contactor AF50 ... AF110
Control voltage / Ambient temperature
Mounting
positions
1, 1±30°, 2, 3, 4, 5 at θ ≤ 70 °C 0.85 x Uc min…1.1 x Uc max.
6Unauthorized
Mounting distances
The contactors can be assembled side by side
Fixing
On rail according to IEC 60715, EN 60715 35 x 15 mm or 75 x 25 mm
By screws (not supplied) 2 x M6 screws placed diagonally
Pos. 5Pos. 6
Pos. 3
Pos
. 2
Pos. 1Pos. 1 ± 30°
+30° -30°
Pos. 4
Low Voltage Products & Systems 1.95
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General technical data
A145...A300, 3-pole
Coil & mounting characteristics
Magnet system characteristics
Contactor types
AC operated
A145 A185 A210 A260 A300
Coil operating limits
AC supply At θ70 °C 0.85...1.1 x Uc
acc. to IEC 60947-4-1 Please also refer to "Mounting characteristics and conditions for use"
AC control voltage
Rated control circuit voltage Uc at 50 Hz 24…690 V
at 60 Hz 24…690 V
Coil consumption Average pull-in value 50 Hz 550 VA 1350 VA
60 Hz 600 VA 1550 VA
50/60 Hz (1) 700 VA / 650 VA 1700 VA / 1550 VA
Average holding value 50 Hz 35 VA / 11 W 60 VA / 16 W
60 Hz 40 VA / 12 W 65 VA / 19 W
50/60 Hz (1) 44 VA / 13 W 80 VA / 21 W
Drop-out voltage
Approx. 40…65% of Uc min.
Operating time
Between coil energization and: N.O. contact closing 13…27 ms 17…35 ms
N.C. contact opening 8…22 ms 12…30 ms
Between coil de-energization and: N.O. contact opening 5…10 ms 7…13 ms
N.C. contact closing 9…13 ms 10…16 ms
(1) 50/60 Hz coils: see "Voltage code table".
Mounting characteristics and conditions for use
Contactor types
AC operated
A145 A185 A210 A260 A300
Mounting positions
Pos. 5Pos. 6
Pos. 3
Pos
. 2
Pos. 1Pos. 1 ± 30°
+30° -30°
Pos. 4
Max. add-on N.O. or N.C. auxiliary contacts: see accessory fitting details for 3-pole contactor
A145 ... A300
Control voltage / Ambient temperature
Mounting
positions
1, 1±30°, 2, 3, 4, 5 at θ ≤ 70 °C 0.85 x Uc…1.1 x Uc
6Unauthorized
Mounting distances
The contactors can be assembled side by side
Fixing
On rail according to IEC 60715, EN 60715
By screws (not supplied) 4 x M5
1.96 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General technical data
AF145...AF300, 3-pole
Coil & mounting characteristics
Magnet system characteristics
Contactor types
AC / DC operated
AF145 AF185 AF210 AF260 AF300
Coil operating limits
AC or DC supply At θ70 °C 0.85 x Uc min...1.1 x Uc max.
Please also refer to "Mounting characteristics and conditions for use"
acc. to IEC 60947-4-1
AC control voltage
Rated control circuit voltage Uc 48…250 V AC
50/60 Hz
Coil consumption Average pull-in value 430 VA 470 VA
Average holding value 12 VA / 3.5 W 10 VA / 2.5 W
DC control voltage
Rated control circuit voltage Uc 20…250 V DC
Coil consumption Average pull-in value 500 W 520 W
Average holding value 2 W 2 W
Drop-out voltage
55 % of Uc min.
Voltage sag immunity
Conditions of use on request
acc. to SEMI F47
Dips withstand
≥ 20 ms
Operating time
Between coil energization and: N.O. contact closing 30…115 ms
N.C. contact opening 30…115 ms
Between coil de-energization and: N.O. contact opening 25…80 ms
N.C. contact closing 25…80 ms
Mounting characteristics and conditions for use
Contactor types
AC / DC operated
AF145 AF185 AF210 AF260 AF300
Mounting positions
Max. add-on N.O. or N.C. auxiliary contacts: see accessory fitting details for 3-pole contactor
AF145 ... AF2050
Control voltage / Ambient temperature
Mounting
positions
1, 1±30°, 2, 3, 4, 5 at θ ≤ 70 °C 0.85 x Uc min…1.1 x Uc max.
6Unauthorized
Mounting distances
The contactors can be assembled side by side
Fixing
On rail according to IEC 60715, EN 60715
By screws (not supplied) 4 x M5
Pos. 5Pos. 6
Pos. 3
Pos
. 2
Pos. 1Pos. 1 ± 30°
+30° -30°
Pos. 4
Low Voltage Products & Systems 1.97
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General technical data
AF400...AF2050, 3-pole
Coil & mounting characteristics
Magnet system characteristics
Contactor types
AC / DC operated
AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050
Coil operating limits
AC or DC supply At θ70 °C 0.85 x Uc min...1.1 x Uc max.
Please also refer to "Mounting characteristics and conditions for use"
acc. to IEC 60947-4-1
AC control voltage
Rated control circuit voltage Uc 48…500 V AC 100…250 V
50/60 Hz
Coil consumption Average pull-in value 890 VA 850 VA 1900 VA
Average holding value 12 VA / 4 W 12 VA / 4.5 W 48 VA / 17 W
DC control voltage
Rated control circuit voltage Uc 24…500 V DC 100…250 V
Coil consumption Average pull-in value 990 W 950 W 1700 W
Average holding value 4 W 4.5 W 16 W
Drop-out voltage
55 % of Uc min.
Voltage sag immunity
Conditions of use on request
acc. to SEMI F47
Dips withstand
≥ 20 ms
Operating time
Coil supply between A1 - A2
Between coil energization and: N.O. contact closing 50…120 ms 50…80 ms
N.C. contact opening 50…120 ms 50…80 ms
Between coil de-energization and: N.O. contact opening 33…70 ms 35…55 ms
N.C. contact closing 33…70 ms 35…55 ms
Control input for PLC's
Between coil energization and: N.O. contact closing 40…60 ms 40...90 ms 40…65 ms
N.C. contact opening 40…60 ms 40...90 ms 40…65 ms
Between coil de-energization and: N.O. contact opening 10…30 ms 10…30 ms
N.C. contact closing 10…30 ms 10…30 ms
Mounting characteristics and conditions for use
Contactor types
AC / DC operated
AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050
Mounting positions
Max. add-on N.O. or N.C. auxiliary contacts: see accessory fitting details for 3-pole contactor
AF400 ... AF2050
Control voltage / Ambient temperature
Mounting
positions
1, 1±30°, 2, 3, 4, 5 at θ ≤ 70 °C 0.85 x Uc min…1.1 x Uc max.
6Unauthorized
Mounting distances
The contactors can be assembled side by side
Fixing
On rail according to IEC 60715, EN 60715
By screws (not supplied) 4 x M5 4 x M6 4 x M8
Pos. 5Pos. 6
Pos. 3
Pos. 2
Pos. 1Pos. 1 ± 30°
+30° -30°
Pos. 4
1.98 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General technical data
AF09(Z)...AF38(Z), 3-pole
Terminal characteristics
Connecting characteristics
Contactor types
AC / DC operated
AF09 AF12 AF16 AF26 AF30 AF38
Main terminals
Screw terminals with cable clamp
Connection capacity (min. ... max.)
Main conductors (poles)
Rigid Solid (≤ 4 mm²) 1 x 1...6 mm² 2.5...10 mm²
Stranded (≥ 6 mm²) 2 x 1...6 mm² 2.5...10 mm²
Flexible with non insulated ferrule 1 x 0.75...6 mm² 1.5...10 mm²
2 x 0.75...6 mm² 1.5...10 mm²
Flexible with insulated ferrule 1 x 0.75...4 mm² 1.5...10 mm²
2 x 0.75...2.5 mm² 1.5...4 mm²
L
6
Bars or lugs L < 9.6 mm 12.5 mm
Connection capacity acc. to UL/CSA (solid/stranded) 1 or 2 x AWG 16...10 AWG 14...8
Stripping length 10 mm 14 mm
Tightening torque 1.5 Nm / 13 lb.in 2.5 Nm / 22 lb.in
Auxiliary conductors
(built-in auxiliary terminals + coil terminals)
Rigid solid 1 x 1...2.5 mm²
2 x 1...2.5 mm²
Flexible with non insulated ferrule 1 x 0.75...2.5 mm²
2 x 0.75...2.5 mm²
Flexible with insulated ferrule 1 x 0.75...2.5 mm²
2 x 0.75...1.5 mm²
L
6
Lugs L < 8 mm
Connection capacity acc. to UL/CSA (solid/stranded) 1 or 2 x AWG 18...14
Stripping length 10 mm
Tightening torque
Coil terminals 1.2 Nm / 11 lb.in
Built-in auxiliary terminals 1.2 Nm / 11 lb.in
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Main terminals IP20
Coil terminals IP20
Built-in auxiliary terminals IP20
Screw terminals
Delivered in open position, screws of unused terminals must be tightened
Main terminals M3.5 M4
Screwdriver type Flat Ø 5.5 / Pozidriv 2 Flat Ø 6.5 / Pozidriv 2
Coil terminals M3.5
Screwdriver type Flat Ø 5.5 / Pozidriv 2
Built-in auxiliary terminals M3.5
Screwdriver type Flat Ø 5.5 / Pozidriv 2
Low Voltage Products & Systems 1.99
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General technical data
A/E/L40, A/E/F50...A/F110, 3-pole
Terminal characteristics
Connecting characteristics
Contactor types
AC operated
A40 A50 A63 A75 A95 A110
DC operated
AL40 AE50 AE63 AE75
TAL40 TAE50 TAE75
AC / DC operated
AF50 AF63 AF75 AF95 AF110
Main terminals
Screw terminals
with double
connector
2 x (5.6 x 6.5 mm)
Screw terminals
with single
connector
(13 x 10 mm)
Screw terminals
with single
connector
(14 x 14 mm)
Connection capacity (min. ... max.)
Main conductors (poles)
Rigid Solid (≤ 4 mm²) 1 x 2.5...16 mm² 6...50 mm² 10...95 mm²
Stranded (≥ 6 mm²) 2 x 2.5...16 mm² 6...25 mm² 6...35 mm²
Flexible with ferrule 1 x 2.5...10 mm² 6...35 mm² 10…70 mm² (1)
2 x 2.5...10 mm² 6...16 mm² 6…35 mm² (1)
L
l
Bars or lugs L ≤ 30 mm (2)
l > 6 mm
Connection capacity acc. to UL/CSA (solid/stranded) 1 or 2 x AWG 8…4 AWG 8…1 AWG 6…2/0
Tightening torque Recommended 2.30 Nm / 20 lb.in 4.00 Nm / 35 lb.in 8 Nm / 71 lb.in
Max. 2.60 Nm 4.50 Nm 9 Nm
Auxiliary conductors
(built-in auxiliary terminals + coil terminals)
Rigid solid 1 x 1…4 mm² 0.75…2.5 mm²
2 x 1…4 mm² 0.75…2.5 mm²
Flexible with ferrule 1 x 0.75…2.5 mm² 1…2.5 mm² 0.75…2.5 mm²
2 x 0.75…2.5 mm²
L
l
Lugs L ≤ 8 mm
l > 3.7 mm
Connection capacity acc. to UL/CSA (solid/stranded) 1 or 2 x AWG 18...14
Tightening torque
Coil terminals Recommended 1.00 Nm / 9 lb.in
Max. 1.20 Nm
Built-in auxiliary terminals Recommended 1.00 Nm / 9 lb.in
Max. 1.20 Nm
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Main terminals IP20 IP10
Coil terminals IP20
Built-in auxiliary terminals IP20
Screw terminals
Delivered in open position, screws of unused terminals must be tightened
Main terminals M5 M6 M8
Screwdriver type Flat Ø 6.5 / Pozidriv 2 Hexagon socket (s = 4 mm)
Coil terminals M3.5
Screwdriver type Flat Ø 5.5 / Pozidriv 2
Built-in auxiliary terminals M3.5
Screwdriver type Flat Ø 5.5 / Pozidriv 2
(1) A(F)95 / A(F)110: use exible without ferrule.
(2) With LW110 enlargement piece, see “Accessories”.
1.100 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General technical data
A/F145...A/F300, 3-pole
Terminal characteristics
Connecting characteristics
Contactor types
AC operated
A145 A185 A210 A260 A300
AC / DC operated
AF145 AF185 AF210 AF260 AF300
Main terminals
Flat type
17.5
ø 8.5
5
20
ø 10.2
5
Connection capacity (min. ... max.)
Main conductors (poles)
Rigid with
connector
Single for Cu cable 6…185 mm² 16…240 mm²
Single for Al/Cu cable 25…150 mm² 120…240 mm²
Double for Al/Cu cable 2 x 95…120 mm²
L
ø
Bars or lugs L ≤ 24 mm 32 mm
Ø > 8 mm 10 mm
Connection capacity acc. to UL/CSA 6 - 250 MCM x 1 4 - 500 MCM x 1 (1)
Tightening torque Recommended 18 Nm / 160 Ib.in 28 Nm / 247 lb.in
Max. 20 Nm 30 Nm
Auxiliary conductors
(coil terminals)
Rigid solid 1 x 1…4 mm²
2 x 1…4 mm²
Flexible with ferrule 1 x 0.75…2.5 mm²
2 x 0.75…2.5 mm²
L
l
Lugs L ≤ 8 mm
l > 3.7 mm
Connection capacity acc. to UL/CSA (solid/stranded) 1 or 2 x AWG 18…14
Tightening torque Recommended 1.00 Nm / 9 lb.in
Max. 1.20 Nm
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Main terminals IP00
Coil terminals IP20
Screw terminals
Main terminals M8 M10
Screws and bolts
Coil terminals (delivered in open position) M3.5
Screwdriver type Flat Ø 5.5 mm / Pozidriv 2
(1) With LW110 enlargement piece: see "Accessories".
Low Voltage Products & Systems 1.101
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General technical data
AF400...AF2050, 3-pole
Terminal characteristics
Connecting characteristics
Contactor types
AC / DC operated
AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050
Main terminals
Flat type
ø 10.5
25
ø 6.5
22.5
6
50
8
ø 13
27
25 15.5
ø 12.5
40
ø 6.5
22.5
6
AF1250AF580
AF750
AF2050
AF1350
AF1650
80
10
40
40
17
17
10
ø 13
80
10
27
40
30
Connection capacity (min. ... max.)
Main conductors (poles)
Rigid with
connector
Single for Cu cable 240 mm² 300 mm²
Single for Al/Cu cable 240 mm² 300 mm²
Double for Al/Cu cable 2 x 240 mm² 3 x 185 mm²
L
ø
Bars or lugs L ≤ 47 mm 52 mm 100 mm
Ø > 10 mm 12 mm 12 mm
Connection capacity acc. to UL/CSA 250 - 500 MCM x 2 2/0 - 500 MCM x 2 1/0 - 750 MCM x 4
Tightening torque Recommended 35 Nm / 310 Ib.in 45 Nm / 398 lb.in 45 Nm / 398 lb.in
Max. 40 Nm 49 Nm 49 Nm
Auxiliary conductors
(coil terminals)
Rigid solid 1 x 1…4 mm²
2 x 1…4 mm²
Flexible with ferrule 1 x 0.75…2.5 mm²
2 x 0.75…2.5 mm²
L
l
Lugs L ≤ 8 mm
l > 3.7 mm
Connection capacity acc. to UL/CSA (solid/stranded) 1 or 2 x AWG 18…14
Tightening torque Recommended 1.00 Nm / 9 lb.in
Max. 1.20 Nm
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Main terminals IP00
Coil terminals IP20
Screw terminals
Main terminals M10 M12
Screws and bolts
Coil terminals (delivered in open position) M3.5
Screwdriver type Flat Ø 5.5 mm / Pozidriv 2
1.102 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Built-in auxiliary contacts according to IEC
Contactor types
AC / DC operated
AF09 AF12 AF16 AF26 AF30 AF38
Rated operational voltage Ue max.
690 V
Rated frequency (without derating)
50 / 60 Hz
Conventional free air thermal current Ith - θ ≤ 40 °C
16 A
Ie / Rated operational current AC-15
acc. to IEC 60947-5-1 24-127 V 50/60 Hz 6 A
220-240 V 50/60 Hz 4 A
400-440 V 50/60 Hz 3 A
500 V 50/60 Hz 2 A
690 V 50/60 Hz 2 A
Making capacity AC-15
10 x Ie AC-15 acc. to IEC 60947-5-1
Breaking capacity AC-15
10 x Ie AC-15 acc. to IEC 60947-5-1
Ie / Rated operational current DC-13
acc. to IEC 60947-5-1 24 V DC 6 A / 144 W
48 V DC 2.8 A / 134 W
72 V DC 1 A / 72 W
110 V DC 0.55 A / 60 W
125 V DC 0.55 A / 69 W
220 V DC 0.27 A / 60 W
250 V DC 0.27 A / 68 W
400 V DC 0.15 A / 60 W
500 V DC 0.13 A / 65 W
600 V DC 0.1 A / 60 W
Short-circuit protection device gG type fuse
10 A
Rated short-time withstand current Icw
for 1.0 s 100 A
for 0.1 s 140 A
Minimum switching capacity
12 V / 3 mA
with failure rate acc. to IEC 60947-5-4 10
-7
Non-overlapping time between N.O. and N.C. contacts
≥ 2 ms
Power dissipation per pole at 6 A
0.1 W
Max. electrical switching frequency
AC-15 1200 cycles/h
DC-13 900 cycles/h
Mechanically linked contacts
Built-in N.O. or N.C. auxiliary contacts and additional N.O. or N.C. auxiliary contacts (CA4, CAL4, CAT4
aux. contact blocks) are mechanically linked contacts.
acc. to annex L of IEC 60947-5-1
Mirror contacts
Built-in N.C. auxiliary contacts or additional N.C. auxiliary contacts (CA4, CAL4, CAT4 aux. contact blocks)
are mirror contacts.
acc. to annex F of IEC 60947-4-1
Built-in auxiliary contacts according to UL / CSA
Contactor types
AC / DC operated
AF09 AF12 AF16 AF26 AF30 AF38
Max. operational voltage
600 V AC, 600 V DC
Pilot duty
A600, Q600
AC thermal rated current 10 A
AC maximum volt-ampere making 7200 VA
AC maximum volt-ampere breaking 720 VA
DC thermal rated current 2.5 A
DC maximum volt-ampere making-breaking 69 VA
General technical data
AF09(Z)...AF38(Z), 3-pole
Built-in auxiliary contacts
Low Voltage Products & Systems 1.103
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Built-in auxiliary contacts according to IEC
Contactor types
AC operated
A40
DC operated
AL40, TAL40
Rated operational voltage Ue max.
690 V
Rated frequency (without derating)
50/60 Hz
Conventional free air thermal current Ith - θ ≤ 40 °C
16 A
Ie / Rated operational current AC-15
acc. to IEC 60947-5-1 24-127 V 50/60 Hz 6 A
220-240 V 50/60 Hz 4 A
380-440 V 50/60 Hz 3 A
500 V 50/60 Hz 2 A
690 V 50/60 Hz 2 A
Making capacity AC-15
10 x Ie AC-15 acc. to IEC 60947-5-1
Breaking capacity AC-15
10 x Ie AC-15 acc. to IEC 60947-5-1
Ie / Rated operational current DC-13
acc. to IEC 60947-5-1 24 V DC 6 A / 144 W
48 V DC 2.8 A / 134 W
72 V DC 2 A / 144 W
110 V DC 1.1 A / 121 W
125 V DC 1.1 A / 138 W
220 V DC 0.55 A / 121 W
250 V DC 0.55 A / 138 W
Short-circuit protection device gG type fuse
10 A
Rated short-time withstand current Icw
for 1.0 s 100 A
for 0.1 s 140 A
Minimum switching capacity
17 V / 5 mA
with failure rate acc. to IEC 60947-5-4 ≤ 10
-7
for AL40 and TAL40 contactors
Non-overlapping time between N.O. and N.C. contacts
≥ 2 ms
Power dissipation per pole at 6 A
0.1 W
Max. electrical switching frequency
AC-15 1200 cycles/h
DC-13 900 cycles/h
Mechanically linked contacts
Built-in N.O. or N.C. auxiliary contacts and additional N.O. or N.C. auxiliary contacts of 4-pole CA5 are
mechanically linked contacts.
acc. to annex L of IEC 60947-5-1
Mirror contacts
Built-in N.C. auxiliary contacts or additional N.C. auxiliary contacts (CA5, CAL5-11) are mirror contacts.
acc. to annex F of IEC 60947-4-1
Built-in auxiliary contacts according to UL / CSA
Contactor types
AC operated
A40
DC operated
AL40, TAL40
Max. operational voltage
600 V AC, 600 V DC
Pilot duty
A600, P300
AC thermal rated current 10 A
AC maximum volt-ampere making 7200 VA
AC maximum volt-ampere breaking 720 VA
DC thermal rated current 5 A
DC maximum volt-ampere making-breaking 138 VA
General technical data
A/E/L40, 3-pole
Built-in auxiliary contacts
1.104 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Main pole - Utilization characteristics according to IEC
Contactor types
AC operated
AS09 AS12 AS16
DC operated
ASL09 ASL12 ASL16
Standards
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage Ue max.
690 V
Rated frequency (without derating)
50 / 60 Hz
Conventional free-air thermal current Ith
acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C 22 A 25 A 25 A
With conductor cross-sectional area 2.5 mm² 4 mm² 4 mm²
AC-1 Utilization category
For air temperature close to contactor
Ie / Rated operational current AC-1
θ ≤ 40 °C 22 A 24 A 24 A
Ue max. ≤ 690 V, 50/60 Hz θ ≤ 60 °C 18 A 20 A 20 A
θ ≤ 70 °C 15 A 16 A 16 A
With conductor cross-sectional area 2.5 mm²
AC-3 Utilization category
For air temperature close to contactor θ ≤ 60 °C
Ie / Max. rated operational current AC-3 (1)
3-phase motors
220-230-240 V 9 A 12 A 15.7 A
400 V 9 A 12 A 15.5 A
415 V 9 A 12 A 15.5 A
440 V 8 A 11 A 13.6 A
500 V 8 A 11 A 12.5 A
690 V 5 A 7 A 9 A
Rated operational power AC-3 (1)
220-230-240 V
2.2 kW 3 kW 4 kW
400 V 4 kW 5.5 kW 7.5 kW
1500 r.p.m. 50 Hz
415 V 4 kW 5.5 kW 7.5 kW
1800 r.p.m. 60 Hz
440 V 4 kW 5.5 kW 7.5 kW
3-phase motors
500 V 4 kW 5.5 kW 7.5 kW
690 V 4 kW 5.5 kW 7.5 kW
Rated making capacity AC-3
10 x Ie AC-3 acc. to IEC 60947-4-1
Rated breaking capacity AC-3
8 x Ie AC-3 acc. to IEC 60947-4-1
AC-8a Utilization category
(without thermal overload relay - Ue 400 V 50/60 Hz - θ ≤ 40 °C)
Ie / Rated operational current AC-8a
12 A 16 A 22 A
Rated operational power AC-8a
5.5 kW 7.5 kW 11 kW
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded
(2)
Ue ≤ 500 V AC - gG type fuse 25 A
Rated short-time withstand current Icw
1 s 230 A 250 A 250 A
at 40 °C ambient temperature, 10 s 100 A 124 A 124 A
in free air from a cold state 30 s 65 A 75 A 75 A
1 min 50 A 55 A 55 A
15 min 22 A 24 A 24 A
Maximum breaking capacity
cos φ = 0.45 at 440 V 155 A
at 690 V 90 A
Power dissipation per pole
Ie / AC-1 1 W 1.2 W 1.2 W
Ie / AC-3 0.16 W 0.3 W 0.5 W
Max. electrical switching frequency
AC-1 600 cycles/h
AC-3 1200 cycles/h
AC-4 300 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
(2) For the protection of motor starters against short circuits, see "Coordination with short-circuit protection devices".
M
3
M
3
IEC technical data
AS/L09...AS/L16, 3-pole, screw terminated
Utilization characteristics
Low Voltage Products & Systems 1.105
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Main pole - Utilization characteristics according to UL / CSA
Contactor types
AC operated
AS09 AS12 AS16
DC operated
ASL09 ASL12 ASL16
Standards
UL 508, CSA C22.2 N°14
Max. operational voltage
690 V
UL / CSA general use rating
600 V AC 20 A 20 A 20 A
With conductor cross-sectional area AWG 12 AWG 12 AWG 12
UL / CSA maximum 1-phase motor rating
Full load current 120 V AC 7.2 A 9.8 A 13.8 A
240 V AC 8 A 10 A 12 A
Horse power rating 120 V AC 1/3 hp 1/2 hp 3/4 hp
240 V AC 1 hp 1-1/2 hp 2 hp
UL / CSA maximum 3-phase motor rating
Full load current (1) 200-208 V AC 7.8 A 7.8 A 11 A
220-240 V AC 6.8 A 9.6 A 15.2 A
440-480 V AC 7.6 A 11 A 14 A
550-600 V AC 9 A 11 A 11 A
Horse power rating (1) 200-208 V AC 2 hp 2 hp 3 hp
220-240 V AC 2 hp 3 hp 5 hp
440-480 V AC 5 hp 7-1/2 hp 10 hp
550-600 V AC 7-1/2 hp 10 hp 10 hp
Max. electrical switching frequency
For general use 600 cycles/h
For motor use 1200 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
General technical data
Contactor types
AC operated
AS09 AS12 AS16
DC operated
ASL09 ASL12 ASL16
Rated insulation voltage Ui
acc. to IEC 60947-4-1 690 V
acc. to UL / CSA 600 V
Rated impulse withstand voltage Uimp.
6 kV
Ambient air temperature
close to contactor
Operation Fitted with thermal overload relay -25...+60 °C
Without thermal overload relay -40...+70 °C
Storage -60...+80 °C
Climatic withstand
Category B according to IEC 60947-1 Annex Q
Maximum operating altitude (without derating)
3000 m
Mechanical durability
Number of operating cycles 10 millions operating cycles
Max. switching frequency 3600 cycles/h
Shock withstand
1/2 sinusoidal shock for 11 ms: no change in contact position, closed or open position
acc. to IEC 60068-2-27 and EN 60068-2-27
Shock direction AS contactors - AC operated ASL contactors - DC operated
Mounting position 1 A20 g 20 g closed position / 10 g open position
B1 10 g closed position / 5 g open position 15 g closed position / 5 g open position
B2 15 g 10 g
C1 20 g closed position / 9 g open position 15 g closed position / 8 g open position
C2 20 g closed position / 14 g open position 14 g closed position / 8 g open position
Vibration withstand
acc. to IEC 60068-2-6
5...300 Hz / 3 g closed position / 2 g open position
B2
AAB1
C2
C1
UL/CSA Technical data
AS/L09...AS/L16, 3-pole, screw terminated
Utilization characteristics
1.106 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Magnet system characteristics for AS09…AS16 contactors
Contactor types AC operated
AS09 AS12 AS16
Coil operating limits AC supply
acc. to IEC 60947-4-1 0.85...1.1 x Uc (at θ ≤ 60 °C); Uc (at θ ≤ 70 °C)
AC control voltage Rated control circuit voltage Uc at 50 Hz 24...415 V
at 60 Hz 24...415 V
Coil consumption Average pull-in value 50 Hz 33 VA
60 Hz 33 VA
50/60 Hz 33 VA
Average holding value 50 Hz 6.5 VA / 1.5 W
60 Hz 5 VA / 1.2 W
50/60 Hz 6.5 VA / 1.5 W
Drop-out voltage Approx. 30...50 % of Uc
Operating time
Between coil energization and: N.O. contact closing 9...24 ms
N.C. contact opening 6...18 ms
Between coil de-energization and: N.O. contact opening (1) 5...19 ms
N.C. contact closing (1) 7...22 ms
(1) The use of RC5-1 surge suppressor increases opening time by a factor of 2 to 3
Magnet system characteristics for ASL09…ASL16 contactors
Contactor types DC operated
ASL09 ASL12 ASL16
Coil operating limits DC supply
acc. to IEC 60947-4-1 0.85...1.1 x Uc (at θ 60 °C); Uc (at θ ≤ 70 °C)
DC control voltage Rated control circuit voltage Uc 12...240 V DC
Coil consumption Average pull-in value 3 W
Average holding value 3 W
Drop-out voltage Approx. 10...40 % of Uc
Coil time constant Open L/R 12 ms
Closed L/R 40 ms
Operating time
Between coil energization and: N.O. contact closing 36...59 ms
N.C. contact opening 31...53 ms
Between coil de-energization and: N.O. contact opening (1) 13...17 ms
N.C. contact closing (1) 15...20 ms
(1) The use of RT5 surge suppressor increases opening time by a factor of 1.1 to 1.2
Mounting characteristics and conditions for use
Contactor types AC operated
AS09 AS12 AS16
DC operated
ASL09 ASL12 ASL16
Mounting positions
Pos. 1 ± 30°
+30° -30°
Pos. 3
Pos
. 2
Pos. 1
Pos. 4
Pos. 5
Mounting distances The contactors can be assembled side by side.
Fixing On rail according to IEC 60715, EN 60715 35 x 7.5 mm or 35 x 15 mm
By screws (not supplied) 2 x M4 screws placed diagonally
General technical data
AS/L09...AS/L16, 3-pole, screw terminated
Coil & mounting characteristics
Low Voltage Products & Systems 1.107
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Connecting characteristics
Contactor types
AC operated
AS09 AS12 AS16
DC operated
ASL09 ASL12 ASL16
Main terminals
Screw terminals with cable clamp
Connection capacity (min. ... max.)
Main conductors (poles)
Rigid solid 1 x 0.75...4 mm²
2 x 0.75...4 mm²
Flexible with non insulated ferrule 1 x 0.75...2.5 mm²
2 x 0.75...2.5 mm²
Flexible with insulated ferrule 1 x 0.75...2.5 mm²
2 x 0.75...1.5 mm²
L
l
Bars or lugs L ≤ 7.7 mm
l > 3.2 mm
Connection capacity acc. to UL / CSA (Sol/Str) 1 or 2 x AWG 18...12
Stripping length 9 mm
Tightening torque Recommended 1.00 Nm / 9 lb.in
Max. 1.20 Nm
Auxiliary conductors
(built-in auxiliary terminals + coil terminals)
Rigid solid 1 x 0.75...2.5 mm²
2 x 0.75...2.5 mm²
Flexible with non insulated ferrule 1 x 0.75...2.5 mm²
2 x 0.75...2.5 mm²
Flexible with insulated ferrule 1 x 0.75...2.5 mm²
2 x 0.75...1.5 mm²
L
l
Lugs L ≤ 7.7 mm
l > 3.2 mm
Connection capacity acc. to UL / CSA (Sol/Str) 1 or 2 x
AWG 18...14
Stripping length
Tightening torque
Coil terminals Recommended 1.00 Nm / 9 lb.in
Max. 1.20 Nm
Built-in auxiliary terminals Recommended 1.00 Nm / 9 lb.in
Max. 1.20 Nm
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
All terminals IP20
Screw terminals
Delivered in open position, screws of unused terminals must be tightened
All terminals M3
Screwdriver type Flat Ø 5.5 / Pozidriv 2
General technical data
ASL09...ASL16 3-pole, screw terminated
Terminal characteristics
1.108 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Built-in auxiliary contacts according to IEC
Contactor types
AC operated
AS09 AS12 AS16
DC operated
ASL09 ASL12 ASL16
Rated operational voltage Ue max.
690 V
Rated frequency (without derating)
50 / 60 Hz
Conventional free-air thermal current Ith - θ ≤ 40 °C
10 A
Ie / Rated operational current AC-15
acc. to IEC 60947-5-1 24-127 V 50/60 Hz 6 A
220-240 V 50/60 Hz 4 A
400-440 V 50/60 Hz 3 A
500 V 50/60 Hz 2 A
690 V 50/60 Hz 2 A
Making capacity AC-15
10 x Ie AC-15 acc. to IEC 60947-5-1
Breaking capacity AC-15
10 x Ie AC-15 acc. to IEC 60947-5-1
Ie / Rated operational current DC-13
acc. to IEC 60947-5-1 24 V DC 6 A / 144 W
48 V DC 2.8 A / 134 W
72 V DC 1 A / 72 W
110 V DC 0.55 A / 60 W
125 V DC 0.55 A / 69 W
220 V DC 0.27 A / 60 W
250 V DC 0.27 A / 68 W
Short-circuit protection device gG type fuse
10 A
Rated short-time withstand current Icw
for 1.0 s 100 A
for 0.1 s 140 A
Minimum switching capacity
12 V / 3 mA
with failure rate acc. to IEC 60947-5-4 10
-7
Non-overlapping time between N.O. and N.C. contacts
1.5 ms
Power dissipation per pole at 6 A
0.1 W
Max. electrical switching frequency
AC-15 1200 cycles/h
DC-13 900 cycles/h
Mechanically linked contacts
Built-in N.O. or N.C. auxiliary contacts and additional N.O. or N.C. auxiliary contacts (CA3 aux.
contact blocks) are mechanically linked contacts.
acc. to annex L of IEC 60947-5-1
Mirror contacts
Built-in N.C. auxiliary contacts or additional N.C. auxiliary contacts (CA3 aux. contact blocks) are
mirror contacts.
acc. to annex F of IEC 60947-4-1
Built-in auxiliary contacts according to UL / CSA
Contactor types
AC operated
AS09 AS12 AS16
DC operated
ASL09 ASL12 ASL16
Max. operational voltage
600 V AC, 250 V DC
Pilot duty
A600, Q300
AC thermal rated current
10 A
AC maximum volt-ampere making
7200 VA
AC maximum volt-ampere breaking
720 VA
DC thermal rated current
2.5 A
DC maximum volt-ampere making-breaking
69 VA
General technical data
ASL09...ASL16, 3-pole, screw terminated
Built-in auxiliary contacts
Low Voltage Products & Systems 1.109
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Main pole - Utilization characteristics according to IEC
Contactor types
AC operated
AS09..S AS12..S AS16..S
DC operated
ASL09..S ASL12..S ASL16..S
Standards
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage Ue max.
690V
Rated frequency (without derating)
50 / 60Hz
Conventional free-air thermal current Ith
acc. to IEC 60947-4-1, open contactors, θ40°C 20A 22A 22A
With conductor cross-sectional area 2.5mm² 2.5mm² 2.5mm²
AC-1 Utilization category
For air temperature close to contactor
Ie / Rated operational current AC-1
θ ≤ 40°C 20A 22A 22A
Ue max. ≤ 690V, 50/60Hz θ ≤ 60°C 15A 17A 17A
θ ≤ 70°C 12A 14A 14A
With conductor cross-sectional area 2.5mm²
AC-3 Utilization category
For air temperature close to contactor θ ≤ 60°C
Ie / Max. rated operational current AC-3 (1)
3-phase motors
220-230-240V 9A 12A 15.7A
400V 9A 12A 15.5A
415V 9A 12A 15.5A
440V 8A 11A 13.6A
500V 8A 11A 12.5A
690V 5A 7A 9A
Rated operational power AC-3 (1)
220-230-240V
2.2kW 3kW 4kW
400V 4kW 5.5kW 7.5kW
1500 r.p.m. 50Hz
415V 4kW 5.5kW 7.5kW
1800 r.p.m. 60Hz
440V 4kW 5.5kW 7.5kW
3-phase motors
500V 4kW 5.5kW 7.5kW
690V 4kW 5.5kW 7.5kW
Rated making capacity AC-3
10 x Ie AC-3 acc. to IEC 60947-4-1
Rated breaking capacity AC-3
8 x Ie AC-3 acc. to IEC 60947-4-1
AC-8a Utilization category
(without thermal overload relay - Ue 400V 50/60Hz - θ ≤ 40°C)
Ie / Rated operational current AC-8a
12A 16A 22A
Rated operational power AC-8a
5.5kW 7.5kW 11kW
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded
(2)
Ue ≤ 500V AC - gG type fuse 25A
Rated short-time withstand current Icw
1s 230A 250A 250A
at 40°C ambient temperature, 10s 100A 124A 124A
in free air from a cold state 30s 65A 75A 75A
1 min 50A 55A 55A
15 min 20A 22A 22A
Maximum breaking capacity
cos φ = 0.45 at 440V 155A
at 690V 90A
Power dissipation per pole
Ie / AC-1 0.9W 1.1W 1.1W
Ie / AC-3 0.18W 0.33W 0.55W
Max. electrical switching frequency
AC-1 600 cycles/h
AC-3 1200 cycles/h
AC-4 300 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50Hz or 1800 r.p.m, 60Hz, 3-phase motors, see "Motor rated operational powers and currents".
(2) For the protection of motor starters against short circuits, see "Coordination with short-circuit protection devices".
M
3
M
3
IEC Technical data
AS/L09...AS/L16, 3-pole, spring terminated
Utilization characteristics
1.110 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Main pole - Utilization characteristics according to UL /CSA
Contactor types
AC operated
AS09..S AS12..S AS16..S
DC operated
ASL09..S ASL12..S ASL16..S
Standards
UL 508, CSA C22.2N°14
Max. operational voltage
690V
UL / CSA General use rating
600V AC 12A 12A 15.2A
With conductor cross-sectional area AWG 14 AWG 14 AWG 12
UL / CSA maximum 1-phase motor rating
Full load current 120V AC 7.2A 9.8A 13.8A
240V AC 8A 10A 12A
Horse power rating 120V AC 1/3 hp 1/2 hp 3/4 hp
240V AC 1 hp 1-1/2 hp 2 hp
UL / CSA maximum 3-phase motor rating
Full load current (1) 200-208V AC 7.8A 7.8A 11A
220-240V AC 6.8A 9.6A 15.2A
440-480V AC 7.6A 11A 14A
550-600V AC 9A 11A 11A
Horse power rating (1) 200-208V AC 2 hp 2 hp 3 hp
220-240V AC 2 hp 3 hp 5 hp
440-480V AC 5 hp 7-1/2 hp 10 hp
550-600V AC 7-1/2 hp 10 hp 10 hp
Max. electrical switching frequency
For general use 600 cycles/h
For motor use 1200 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50Hz or 1800 r.p.m, 60Hz, 3-phase motors, see "Motor rated operational powers and currents".
General technical data
Contactor types
AC operated
AS09..S AS12..S AS16..S
DC operated
ASL09..S ASL12..S ASL16..S
Rated insulation voltage Ui
acc. to IEC 60947-4-1 690V
acc. to UL / CSA 600V
Rated impulse withstand voltage Uimp.
6kV
Ambient air temperature close to contactor
Operation -40...+70°C
Storage -60...+80°C
Climatic withstand
Category B according to IEC 60947-1 Annex Q
Maximum operating altitude (without derating)
3000m
Mechanical durability
Number of operating cycles 10 millions operating cycles
Max. switching frequency 3600 cycles/h
Shock withstand
1/2 sinusoidal shock for 11 ms: no change in contact position, closed or open position
acc. to IEC 60068-2-27 and EN 60068-2-27 Shock direction AS contactors - AC operated ASL contactors - DC operated
Mounting position 1 A20g 20g closed position / 10g open position
B1 10g closed position / 5g open position 15g closed position / 5g open position
B2 15g 10g
C1 20g closed position / 9g open position 15g closed position / 8g open position
C2 20g closed position / 14g open position 14g closed position / 8g open position
Vibration withstand
acc. to IEC 60068-2-6 5...300Hz / 3g closed position / 2g open position
UL/CSA Technical data
AS/L09...AS/L16, 3-pole, spring terminated
Utilization characteristics
B2
AAB1
C2
C1
Low Voltage Products & Systems 1.111
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Magnet system characteristics for AS09..S … AS16..S contactors
Contactor types AC operated
AS09..S AS12..S AS16..S
Coil operating limits AC supply
acc. to IEC 60947-4-1 0.85...1.1 x Uc (at θ60°C); Uc (at θ70°C)
AC control voltage Rated control circuit voltage Uc at 50Hz 24...415V
at 60Hz 24...415V
Coil consumption Average pull-in value 50Hz 33VA
60Hz 33VA
50/60Hz 33VA
Average holding value 50Hz 6.5VA / 1.5W
60Hz 5VA / 1.2W
50/60Hz 6.5VA / 1.5W
Drop-out voltage Approx. 30...50% of Uc
Operating time
Between coil energization and: N.O. contact closing 9...24 ms
N.C. contact opening 6...18 ms
Between coil de-energization and: N.O. contact opening (1) 5...19 ms
N.C. contact closing (1) 7...22 ms
(1) The use of RC5-1 surge suppressor increases opening time by a factor of 2 to 3.
Magnet system characteristics for ASL09..S … ASL16..S contactors
Contactor types DC operated
ASL09..S ASL12..S ASL16..S
Coil operating limits DC supply
acc. to IEC 60947-4-1 0.85...1.1 x Uc (at θ 60°C); Uc (at θ70°C)
DC control voltage Rated control circuit voltage Uc 12...240V DC
Coil consumption Average pull-in value 3W
Average holding value 3W
Drop-out voltage Approx. 10...40% of Uc
Coil time constant Open L/R 12 ms
Closed L/R 40 ms
Operating time
Between coil energization and: N.O. contact closing 36...59 ms
N.C. contact opening 31...53 ms
Between coil de-energization and: N.O. contact opening (1) 13...17 ms
N.C. contact closing (1) 15...20 ms
(1) The use of RT5 surge suppressor increases opening time by a factor of 1.1 to 1.2
Mounting characteristics and conditions for use
Contactor types
AC operated
AS09..S AS12..S AS16..S
DC operated
ASL09..S ASL12..S ASL16..S
Mounting positions
Pos. 1 ± 30°
+30° -30°
Pos. 3
Pos. 2
Pos. 1
Pos. 4
Pos. 5
Mounting distances
The contactors can be assembled side by side.
Fixing
On rail according to IEC 60715, EN 60715 35 x 7.5mm or 35 x 15mm
By screws (not supplied) 2 x M4 screws placed diagonally
General technical data
AS/L09...AS/L16, 3-pole, spring terminated
Coil & mounting characteristics
1.112 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Connecting characteristics
Contactor types
AC operated
AS09..S AS12..S AS16..S
DC operated
ASL09..S ASL12..S ASL16..S
Main terminals
Spring terminals
Connection capacity (min. ... max.)
Main conductors (poles)
Rigid 1 x 0.75...2.5mm²
2 x 0.75...2.5mm²
Flexible with non insulated ferrule 1 x 0.75...2.5mm²
2 x 0.75...2.5mm²
Flexible with insulated ferrule 1 x 0.75...1.5mm²
2 x 0.75...1.5mm²
Connection capacity acc. to UL / CSA (Sol/Str) 1 or 2 x AWG 18...12
Stripping length 10mm
Auxiliary conductors
(built-in auxiliary terminals + coil terminals)
Rigid solid 1 x 0.75...2.5mm²
2 x 0.75...2.5mm²
Flexible with non insulated ferrule 1 x 0.75...2.5mm²
2 x 0.75...2.5mm²
Flexible with insulated ferrule 1 x 0.75...1.5mm²
2 x 0.75...1.5mm²
Connection capacity acc. to UL / CSA (Sol/Str) 1 or 2 x AWG 18...14
Stripping length 10mm
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
All terminals IP20
Screwdriver type Flat Ø 3.5
General technical data
AS/L09...AS/L16, 3-pole, spring terminated
Terminal characteristics
Low Voltage Products & Systems 1.113
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Built-in auxiliary contacts according to IEC
Contactor types
AC operated
AS09..S AS12..S AS16..S
DC operated
ASL09..S ASL12..S ASL16..S
Rated operational voltage Ue max.
690V
Rated frequency (without derating)
50 / 60Hz
Conventional free air thermal current Ith - θ ≤ 40°C
10A
Ie / Rated operational current AC-15
acc. to IEC 60947-5-1 24-127V 50/60Hz 6A
220-240V 50/60Hz 4A
400-440V 50/60Hz 3A
500V 50/60Hz 2A
690V 50/60Hz 2A
Making capacity AC-15
10 x Ie AC-15 acc. to IEC 60947-5-1
Breaking capacity AC-15
10 x Ie AC-15 acc. to IEC 60947-5-1
Ie / Rated operational current DC-13
acc. to IEC 60947-5-1 24V DC 6A / 144W
48V DC 2.8A / 134W
72V DC 1A / 72W
110V DC 0.55A / 60W
125V DC 0.55A / 69W
220V DC 0.27A / 60W
250V DC 0.27A / 68W
Short-circuit protection device gG type fuse
10A
Rated short-time withstand current Icw
for 1.0s 100A
for 0.1s 140A
Minimum switching capacity
12V / 3m
with failure rate acc. to IEC 60947-5-4 10
-7
Non-overlapping time between N.O. and N.C. contacts
1.5 ms
Power dissipation per pole at 6A
0.1W
Max. electrical switching frequency
AC-15 1200 cycles/h
DC-13 900 cycles/h
Mechanically linked contacts
Built-in N.O. or N.C. auxiliary contacts and additional N.O. or N.C. auxiliary contacts (CA3 aux.
contact blocks) are mechanically linked contacts.
acc. to annex L of IEC 60947-5-1
Mirror contacts
Built-in N.C. auxiliary contacts or additional N.C. auxiliary contacts (CA3 aux. contact blocks) are
mirror contacts.
acc. to annex F of IEC 60947-4-1
Built-in auxiliary contacts according to UL / CSA
Contactor types
AC operated
AS09..S AS12..S AS16..S
DC operated
ASL09..S ASL12..S ASL16..S
Max. operational voltage
600V AC, 250V DC
Pilot duty
A600, Q300
AC thermal rated current
10A
AC maximum volt-ampere making
7200VA
AC maximum volt-ampere breaking
720VA
DC thermal rated current
2.5A
DC maximum volt-ampere making-breaking
69VA
General technical data
AS/L09...AS/L16, 3-pole, spring terminated
Built-in auxiliary contacts
1.114 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
M
3
M
3
Main pole - Utilization characteristics according to IEC
Contactor types
AC operated
VAS09 VAS12 VAS16
DC operated
VASL09 VASL12 VASL16
Standards
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage Ue max.
690 V
Rated frequency (without derating)
50 / 60 Hz
Conventional free-air thermal current Ith
acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C 22 A 25 A 25 A
With conductor cross-sectional area 2.5 mm² 4 mm² 4 mm²
AC-3 Utilization category
For air temperature close to contactor θ ≤ 60 °C
Ie / Max. rated operational current AC-3 (1)
3-phase motors
220-230-240 V 9 A 12 A 15.7 A
400 V 9 A 12 A 15.5 A
415 V 9 A 12 A 15.5 A
440 V 8 A 11 A 13.6 A
500 V 8 A 11 A 12.5 A
690 V 5 A 7 A 9 A
Rated operational power AC-3 (1)
220-230-240 V 2.2 kW 3 kW 4 kW
400 V 4 kW 5.5 kW 7.5 kW
1500 r.p.m. 50 Hz
415 V 4 kW 5.5 kW 7.5 kW
1800 r.p.m. 60 Hz
440 V 4 kW 5.5 kW 7.5 kW
3-phase motors
500 V 4 kW 5.5 kW 7.5 kW
690 V 4 kW 5.5 kW 7.5 kW
Rated making capacity AC-3
10 x Ie AC-3 acc. to IEC 60947-4-1
Rated breaking capacity AC-3
8 x Ie AC-3 acc. to IEC 60947-4-1
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded
(2)
Ue ≤ 500 V AC - gG type fuse 25 A
Rated short-time withstand current Icw
1 s 230 A 250 A 250 A
at 40 °C ambient temperature, 10 s 100 A 124 A 124 A
in free air from a cold state 30 s 65 A 75 A 75 A
1 min 50 A 55 A 55 A
15 min 22 A 24 A 24 A
Maximum breaking capacity
cos φ = 0.45 at 440 V 155 A
at 690 V 90 A
Power dissipation per pole
Ie / AC-3 0.16 W 0.3 W 0.5 W
Max. electrical switching frequency
AC-3 600 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
(2) For the protection of motor starters against short circuits, see "Coordination with short-circuit protection devices".
IEC Technical data
VASL09...VASL16, 3-pole, reversing
Utilization characteristics
Low Voltage Products & Systems 1.115
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Main pole - Utilization characteristics according to UL / CSA
Contactor types
AC operated
VAS09 VAS12 VAS16
DC operated
VASL09 VASL12 VASL16
Standards
UL 508, CSA C22.2 N°14
Max. operational voltage
690 V
UL / CSA maximum 1-phase motor rating
Full load current 120 V AC 7.2 A 9.8 A 13.8 A
240 V AC 8 A 10 A 12 A
Horse power rating 120 V AC 1/3 hp 1/2 hp 3/4 hp
240 V AC 1 hp 1-1/2 hp 2 hp
UL / CSA maximum 3-phase motor rating
Full load current (1) 200-208 V AC 7.8 A 7.8 A 11 A
220-240 V AC 6.8 A 9.6 A 15.2 A
440-480 V AC 7.6 A 11 A 14 A
550-600 V AC 9 A 11 A 11 A
Horse power rating (1) 200-208 V AC 2 hp 2 hp 3 hp
220-240 V AC 2 hp 3 hp 5 hp
440-480 V AC 5 hp 7-1/2 hp 10 hp
550-600 V AC 7-1/2 hp 10 hp 10 hp
Max. electrical switching frequency
For motor use 600 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
General technical data
Contactor types
AC operated
VAS09 VAS12 VAS16
DC operated
VASL09 VASL12 VASL16
Rated insulation voltage Ui
acc. to IEC 60947-4-1 690 V
acc. to UL / CSA 600 V
Rated impulse withstand voltage Uimp.
6 kV
Ambient air temperature close to contactor
Operation Fitted with thermal overload relay -25...+60 °C
Without thermal overload relay -40...+70 °C
Storage -60...+80 °C
Climatic withstand
Category B according to IEC 60947-1 Annex Q
Maximum operating altitude (without derating)
3000 m
Mechanical durability
Number of operating cycles 5 millions operating cycles
Max. switching frequency 1800 cycles/h
UL/CSA Technical data
VAS/L09...VAS/L16, 3-pole, reversing
Utilization characteristics
1.116 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Magnet system characteristics for VAS09…VAS16 contactors
Contactor types AC operated
VAS09 VAS12 VAS16
Coil operating limits AC supply
acc. to IEC 60947-4-1 0.85...1.1 x Uc (at θ60 °C); Uc (at θ ≤ 70 °C)
AC control voltage Rated control circuit voltage Uc at 50 Hz 24...415 V
at 60 Hz 24...415 V
Coil consumption Average pull-in value 50 Hz 33 VA
60 Hz 33 VA
50/60 Hz 33 VA
Average holding value 50 Hz 6.5 VA / 1.5 W
60 Hz 5 VA / 1.2 W
50/60 Hz 6.5 VA / 1.5 W
Drop-out voltage Approx. 30...50 % of Uc
Operating time
Between coil energization and: N.O. contact closing 9...24 ms
N.C. contact opening 6...18 ms
Between coil de-energization and: N.O. contact opening (1) 5...19 ms
N.C. contact closing (1) 7...22 ms
(1) The use of RC5-1 surge suppressor increases opening time by a factor of 2 to 3.
Magnet system characteristics for VASL09…VASL16 contactors
Contactor types DC operated
VASL09 VASL12 VASL16
Coil operating limits DC supply
acc. to IEC 60947-4-1 0.85...1.1 x Uc (at θ ≤ 60 °C); Uc (at θ ≤ 70 °C)
DC control voltage Rated control circuit voltage Uc 12...240 V DC
Coil consumption Average pull-in value 3 W
Average holding value 3 W
Drop-out voltage Approx. 10...40 % of Uc
Coil time constant Open L/R 12 ms
Closed L/R 40 ms
Operating time
Between coil energization and: N.O. contact closing 36...59 ms
N.C. contact opening 31...53 ms
Between coil de-energization and: N.O. contact opening (1) 13...17 ms
N.C. contact closing (1) 15...20 ms
(1) The use of RT5 surge suppressor increases opening time by a factor of 1.1 to 1.2
Mounting characteristics and conditions for use
Contactor types
AC operated
VAS09 VAS12 VAS16
DC operated
VASL09 VASL12 VASL16
Mounting positions
Pos. 1 ± 30°
+30° -30°
Pos. 3
Pos. 2
Pos. 1
Pos. 4
Pos. 5
Mounting distances
The reversing contactors can be assembled side by side.
Fixing
On rail according to IEC 60715, EN 60715 35 x 7.5 mm or 35 x 15 mm
By screws (not supplied) 2 x M4 screws placed diagonally
General technical data
VAS/L09...VAS/L16, 3-pole, reversing
Coil & mounting characteristics
Low Voltage Products & Systems 1.117
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Connecting characteristics
Contactor types
AC operated
VAS09 VAS12 VAS16
DC operated
VASL09 VASL12 VASL16
Main terminals
Screw terminals with cable clamp
Connection capacity (min. ... max.)
Main conductors (poles)
Rigid solid 1 x 0.75...4 mm²
Flexible with non insulated ferrule 1 x 0.75...2.5 mm²
Flexible with insulated ferrule 1 x 0.75...1.5 mm²
Connection capacity acc. to UL / CSA (Sol/Str) 1 x AWG 18...12
Stripping length 9 mm
Tightening torque Recommended 1.00 Nm / 9 lb.in
Max. 1.20 Nm
Auxiliary conductors
(built-in auxiliary terminals + coil terminals)
Rigid solid 1 x 0.75...2.5 mm²
Flexible with non insulated ferrule 1 x 0.75...2.5 mm²
Flexible with insulated ferrule 1 x 0.75...1.5 mm²
Connection capacity acc. to UL / CSA (Sol/Str) 1 x AWG 18...14
Stripping length 9 mm
Tightening torque
Coil terminals Recommended 1.00 Nm / 9 lb.in
Max. 1.20 Nm
Built-in auxiliary terminals Recommended 1.00 Nm / 9 lb.in
Max. 1.20 Nm
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
All terminals IP20
Screw terminals
Delivered in open position, screws of unused terminals must be tightened
All terminals M3
Screwdriver type Flat Ø 5.5 / Pozidriv 2
General technical data
VAS/L09...VAS/L16, 3-pole, reversing
Terminal characteristics
1.118 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
IEC Technical data
(V)B/C6...(V)B/C7, 3 & 4-pole
Utilization characteristics
Main pole – Utilization characteristics according to IEC
Contactor types
AC operated
B6, VB6, VB6A B7, VB7, VB7A
DC operated
BC6, VBC6, VBC6A BC7, TBC7, VBC7, VBC7A
Standards
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage U
e max
690 V AC
Rated frequency (without derating)
DC or 50 / 60 Hz
Conventional free-air thermal current l
th
acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C,
with conductor cross-sectional area
20 A
AC-1 Utilization category for air temperature close to contactor θ ≤ 40 °C
I
e
/ Rated operational current AC-1
U
e max
690 V, 50/60 Hz
220-230-240 V Screw terminal types: 20 A
Soldering pin types: 12 A
Flat pin types: 16 A
380-400 V Screw terminal types: 20 A
Soldering pin types: 12 A
Flat pin types: 16 A
440 V Screw terminal types: 20 A
Soldering pin types: 12 A
Flat pin types: 16 A
500 V 12 A
690 V 6 A
AC-1 Utilization category for air temperature close to contactor θ ≤ 55 °C
I
e
/ Rated operational current AC-1
U
e max
690 V, 50/60 Hz
220-230-240 V Screw terminal types: 16 A
Soldering pin types: 12 A
Flat pin types: 16 A
Screw terminal types: 20 A
Soldering pin types: 12 A
Flat pin types: 16 A
380-400 V Screw terminal types: 16 A
Soldering pin types: 12 A
Flat pin types: 16 A
Screw terminal types: 20 A
Soldering pin types: 12 A
Flat pin types: 16 A
440 V Screw terminal types: 16 A
Soldering pin types: 12 A
Flat pin types: 16 A
Screw terminal types: 20 A
Soldering pin types: 12 A
Flat pin types: 16 A
500 V 12 A
690 V 6 A
AC-3 Utilization category for air temperature close to contactor θ ≤ 55 °C
Ie / Rated operational current AC-3 220-230-240 V 9 A 12 A
3-phase motors
380-400 V 8 A 12 A
440 V 8 A 12 A
500 V 6.5 A 9 A
690 V 3.5 A 3.5 A
Rated operational power AC-3
220-230-240 V 2.2 kW 3 kW
1500 r.p.m. 50 Hz
1800 r.p.m. 60 Hz
3-phase motors
380-400 V 4 kW 5.5 kW
440 V 4 kW 5.5 kW
500 V 3 kW 4 kW
690 V 3 kW 3 kW
DC-1 Utilization category for air temperature close to contactor θ ≤ 55 °C
I
e
/ Rated operational current DC-1 110 V
-4 A
220 V
-0.6 A
DC-3 Utilization category for air temperature close to contactor θ ≤ 55 °C
I
e
/ Rated operational current DC-3 110 V
-1.5 A
220 V
-0.25 A
DC-5 Utilization category for air temperature close to contactor θ ≤ 55 °C
I
e
/ Rated operational current DC-5 110 V
-0.4 A
220 V
-0.2 A
Rated making capacity AC-3
10 x I
e
AC-3 acc. to IEC 60947-4-1
Rated breaking capacity AC-3
8 x I
e
AC-3 acc. to IEC 60947-4-1
Short-circuit protection device for contactors
without thermal O/L relay - motor protection excluded
U
e
500 V AC - gG type fuse Coordination type 1: 25 A / Coordination type 2: 20 A
Rated short-time withstand current I
CW
at 40 °C ambient temperature, in free air from a cold state 10 s 64 A 96 A
Maximum breaking capacity cos ϕ = 0.45
at 400 V 64 A 96 A
Maximum electrical switching frequency
AC-1 300 cycles/h
AC-3 600 cycles/h
DC-1, DC-3, DC-5 600 cycles/h
M
3
M
3
M
3
M
3
Low Voltage Products & Systems 1.119
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
UL/CSA Technical data
(V)B/C6...(V)B/C7, 3 & 4-pole
Utilization characteristics
Main pole – Utilization characteristics according to UL/CSA
Contactor types
AC operated
B6, VB6, VB6A B7, VB7, VB7A
DC operated
BC6, VBC6, VBC6A BC7, TBC7, VBC7, VBC7A
Standards
UL 508, CSA C22.2 N°14
Maximum operational voltage
600 V
UL/CSA general use rating
12 A 16 A
UL/CSA maximum 1-phase motor rating
Full load current 120 V AC 8.4 A 13.8 A
240 V AC 6.8 A 10.0 A
Horse power rating 120 V AC 1 hp (screw termination only) 0.75 hp
240 V AC 2 hp (screw termination only) 1.5 hp
UL/CSA maximum 3-phase motor rating
Full load current
1)
200-208 V AC 4.6 A 7.5 A
220-240 V AC 6.8 A 9.6 A
440-480 V AC 3.4 A 7.6 A
550-600 V AC 1.7 A 6.1 A
Horse power rating
1)
200-208 V AC 1 hp 2 hp
220-240 V AC 2 hp 3 hp
440-480 V AC 3 hp 5 hp
550-600 V AC 1 hp 5 hp
Maximum electrical switching frequency
For resitive loads AC-1 300 cycles/h
For motor loads AC-3 600 cycles/h
1)
For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
General technical data
Contactor types
AC operated
B6, VB6, VB6A B7, VB7, VB7A
DC operated
BC6, VBC6, VBC6A BC7, TBC7, VBC7, VBC7A
Rated insulation voltage U
i
acc. to IEC 60947-4-1 690 V
acc. to UL/CSA 600 V
Rated impulse withstand voltage U
imp
6 kV
Ambient air temperature, close to contactor
Operation Fitted with thermal overload relay -25 ... +55 °C
Without thermal overload relay -25 ... +55 °C
Storage -40 ... +80 °C
Climatic withstand
acc. to IEC 60947-1 Annex Q
Maximum operating altitude (without derating)
2000 m
Mechanical durability
10
7
operating cycles
Resistance to shock
Half-sine
acc. to IEC 60068-2-27 and EN 60068-2-27 15 g / 11 ms
acc. to IEC/EN 60947-1 Annex. Q Category E
Resistance to vibrations
Sinusoidal
acc. to IEC 60068-2-27 and EN 60068-2-27 5 g / 3 ... 150 Hz
acc. to IEC/EN 60947-1 Annex. Q Category E
1.120 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General technical data
(V)B/C6...(V)B/C7, 3 & 4-pole
Coil & mounting characteristics
Magnet system characteristics for B6, B7 contactors
Contactor types
AC operated
B6, VB6 B7, VB7
Coil operating limits acc. to IEC 60947-4-1
AC supply 0.85 ... 1.1 x U
c
AC control voltage
Rated control circuit voltage U
C
See ordering tables
Coil consumption Average pull-in value 3.5 VA / 3.5 W
Average holding value 3.5 VA / 3.5 W
Drop-out voltage
0.20 ... 0.75 % of U
c
Magnet system characteristics for BC6, BC7 contactors
Contactor types
DC operated
BC6, VBC6 BC7, VBC7
Coil operating limits acc. to IEC 60947-4-1
DC supply 0.85 ... 1.1 x U
c
DC control voltage
Rated control circuit voltage U
C
See ordering tables
Coil consumption
1)
Average pull-in value 3.5 VA / 3.5 W
Average holding value 3.5 VA / 3.5 W
Drop-out voltage in % of U
C min
0.10 ... 0.75 x U
C
1) Interface mini-contactors: see coil consumption on ordering details pages
Magnet system characteristics for TBC7 contactors
Contactor types
DC operated
TBC7
Coil operating limits acc. to IEC 60947-4-1
DC supply Wide range voltage supply see ordering tables, U
Cmin
... U
Cmax
AC control voltage
Rated control circuit voltage U
C
See ordering tables
Coil consumption Average pull-in value 5 VA / 5 W
Average holding value 5 VA / 5 W
Drop-out voltage in % of U
C min
0.20 % of U
Cmin
Mounting characteristics and conditions for use
Contactor types
AC operated
B6, VB6, VB6A B7, VB7, VB7A
DC operated
BC6, VBC6, VBC6A BC7, TBC7, VBC7, VBC7A
Mounting positions
Pos. 1
Pos. 2
Pos. 4
Pos. 1 ± 30°
- 30°+ 30°
Pos. 5 Pos. 6
Pos. 3
Mounting distances
The contactors can be assembled side by side
Fixing
On rail acc. to IEC 60715, EN 60715 35 x 7.5 mm or 35 x 15 mm
By screws (not supplied) 2 x M4 screws placed diagonally
Low Voltage Products & Systems 1.121
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General technical data
(V)B/C6...(V)B/C7, 3 & 4-pole
Built-in auxiliary contacts
Built-in auxiliary contacts according to IEC
Contactor types
AC operated
B6, VB6, VB6A B7, VB7, VB7A
DC operated
BC6, VBC6, VBC6A BC7, TBC7, VBC7, VBC7A
Standards
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage Ue max
690 V
Rated frequency (without derating)
DC or 50 / 60 Hz
Conventional free-air thermal current l
th
θ ≤ 40 °C
6 A
I
e
/ Rated operational current AC-15
acc. to IEC 60947-5-1
24 V 50/60 Hz
4 A
110-120 V 50/60 Hz
4 A
220-230-240 V 50/60 Hz
4 A
380-400 V 50/60 Hz
3 A
440 V 50/60 Hz
3 A
I
e
/ Rated operational current DC-13
acc. to IEC 60947-5-1
24 V DC 2.5 A
110 V DC
0.7 A
220 - 240 V DC 0.4 A
Short-circuit protection device
6 A, Type gG
Minimum switching capacity with failure rate acc. to IEC 60947-5-4
17 V / 5 mA
Maximum electrical switching frequency
AC-15 600 cycles/h
DC-13 600 cycles/h
Built-in auxiliary contacts according to UL/CSA
Contactor types
AC operated
B6, VB6, VB6A B7, VB7, VB7A
DC operated
BC6, VBC6, VBC6A BC7, VBC7, VBC7A
Max. operational voltage
600 V AC
Pilot duty
A600
AC thermal rated current 5 A
1.122 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General technical data
(V)B/C6...(V)B/C7, 3 & 4 pole
Terminal characteristics
Connection characteristics
Contactor types
AC operated
B6, VB6, VB6A B7, VB7, VB7A
DC operated
BC6, VBC6, VBC6A BC7, TBC7, VBC7, VBC7A
Main terminals
1)
Screw terminals with cable clamp
Connection capacity
Main conductors (poles)
Rigid: solid
1 or 2 x
1 ... 4 mm²
Flexible without ferrule
1 or 2 x
1 ... 2.5 mm²
Connection capacity acc. to UL/CSA
(Sol/Str)
1 or 2 x
AWG 22 ... 10
Stripping length
9 mm
Tightening torques
0.8 ... 1.1 Nm / 7 lb.in
Connection capacity – auxiliary conductors
(built-in auxiliary terminals + coil terminals)
Rigid: solid
1 or 2 x
1 ... 4 mm²
Flexible without ferrule
1 or 2 x
1 ... 2.5 mm²
Connection capacity acc. to UL/CSA
(Sol/Str)
1 or 2 x
AWG 22 ... 10
Stripping length
9 mm
Tightening torques
Coil terminals
0.8 ... 1.1 Nm / 7 lb.in
Built-in auxiliary terminals
0.8 ... 1.1 Nm / 7 lb.in
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Main terminals
IP20
Coil terminals
IP20
Built-in auxiliary terminals
IP20
Screw terminals
(Delivered in open position, screws of unused terminals must be tightened)
All terminals
M3
Screwdriver type
Flat Ø 5.5 mm / Pozidriv 1
1) Soldering pin connection acc. to DIN 40801: 0.8 x 1 mm / 0.8 x 2.54 mm
Flat pin connection acc. to DIN 46248: 1 x 6.3 mm / 1 x 2.8 mm
Low Voltage Products & Systems 1.123
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
IEC/UL/CSA Technical data
AF09(Z)...AF38(Z), 4-pole
Utilization characteristics
Main pole - Utilization characteristics according to IEC
Contactor types
AC / DC operated
AF09(Z) AF16(Z) AF26(Z) AF38(Z)
Standards
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage Ue max.
690 V
Rated frequency (without derating)
50 / 60 Hz
Conventional free-air thermal current Ith
acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C 35 A 35 A 55 A 55 A
With conductor cross-sectional area 6 mm² 6 mm² 16 mm² 16 mm²
AC-1 Utilization category
For air temperature close to contactor
Ie / Rated operational current AC-1
θ ≤ 40 °C 25 A 30 A 45 A 55 A
Ue max. ≤ 690 V, 50/60 Hz θ ≤ 60 °C 25 A 30 A 40 A 45 A
θ ≤ 70 °C 22 A 26 A 32 A 37 A
With conductor cross-sectional area 4 mm² 6 mm² 10 mm² 16 mm²
Short-circuit protection device for contactors
Without thermal overload relay - Motor protection excluded
Ue ≤ 500 V AC - gG type fuse 25 A 32 A 50 A 63 A
Rated short-time withstand current Icw
1 s 300 A 300 A 450 A 450 A
At 40 °C ambient temperature,
in free air from a cold state
10 s 150 A 150 A 300 A 300 A
30 s 80 A 80 A 225 A 225 A
1 min 60 A 60 A 150 A 150 A
15 min 35 A 35 A 55 A 55 A
Power dissipation per pole
Ie / AC-1 0.8 W 1.2 W 1.6 W 2.3 W
Max. electrical switching frequency
AC-1 600 cycles/h
Main pole - Utilization characteristics according to UL / CSA
Contactor types AF09(Z) AF16(Z) AF26(Z) AF38(Z)
Standards
UL 508, CSA C22.2 N°14
Max. operational voltage
600 V
UL / CSA general use rating
600 V AC 25 A 30 A 45 A 55 A
With conductor cross-sectional area AWG 10 AWG 10 AWG 8 AWG 6
Max. electrical switching frequency
For general use 600 cycles/h
Remark for 4-pole contactors fitted with 2 N.O. + 2 N.C. main poles
These contactors are suitable for controlling 2 separate circuits, i.e. 2 loads with 2 separate supplies, or 1 circuit comprising 2 separate loads with a sin-
gle supply (see diagrams below). When the contactor operates there is no mechanical overlapping between the N.O. poles and the N.C. poles: BREAK
before MAKE.
!
These contactors are not suitable for a reversing starter or for controlling a single load from 2 separate supplies.
Block diagrams
– Single supply and 2 separate loads – 2 separate supplies and 2 separate loads
1
2
R5
R6
R3
R4
7
8
A1
A2
1
2
R5
R6
R3
R4
7
8
Load
Load
Back-up
supply
Main
supply
A1
A2
1
2
R5
R6
R3
R4
7
8
Load
Load
Supply
1.124 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
IEC/UL/CSA Technical data
A/E/F45...A/E/F75, 4-pole
Utilization characteristics
Main pole - Utilization characteristics according to IEC
Contactor types
AC operated
A45 A50 A75
DC operated
AE45 AE50 AE75
TAE45 TAE50 TAE75
AC / DC operated
AF45 AF50 AF75
Standards
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage Ue max.
1000 V (690 V for AF.. contactors)
Rated frequency (without derating)
50 / 60 Hz
Conventional free-air thermal current Ith
acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C 100 A 100 A 125 A
With conductor cross-sectional area 35 mm² 35 mm² 50 mm²
AC-1 Utilization category
For air temperature close to contactor
Ie / Rated operational current AC-1
θ ≤ 40 °C 70 A 100 A 125 A
Ue max. ≤ 690 V, 50/60 Hz θ ≤ 55 °C 60 A 85 A 105 A
θ ≤ 70 °C (1) 50 A 70 A 85 A
With conductor cross-sectional area 25 mm² 35 mm² 50 mm²
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded
Ue ≤ 500 V AC - gG type fuse 80 A 100 A 160 A
Rated short-time withstand current Icw
1 s 1000 A
At 40 °C ambient temperature,
in free air from a cold state
10 s 650 A
30 s 370 A
1 min 250 A
15 min 110 A 110 A 135 A
Power dissipation per pole
Ie / AC-1 2.5 W 5 W 7 W
Max. electrical switching frequency
AC-1 600 cycles/h (300 for AF.., AE.., TAE..)
(1) Unauthorized for TAE.. contactors
Main pole - Utilization characteristics according to UL / CSA
Contactor types
AC operated
A45 A50 A75
DC operated
AE45 AE50 AE75
TAE45 TAE50 TAE75
AC / DC operated
AF45 AF50 AF75
Standards
UL 508, CSA C22.2 N°14
Max. operational voltage
600 V
UL / CSA general use rating
600 V AC 65 A 80 A 105 A
With conductor cross-sectional area AWG 6 AWG 4 AWG 2
Max. electrical switching frequency
For general use 600 cycles/h (300 for AF.., AE.. TAE..)
Remark for 4-pole contactors fitted with 2 N.O. + 2 N.C. main poles
These contactors are suitable for controlling 2 separate circuits, i.e. 2 loads with 2 separate supplies, or 1 circuit comprising
2 separate loads with a single supply (see diagrams below). When the contactor operates there is no mechanical overlapping
between the N.O. poles and the N.C. poles: BREAK before MAKE.
!
These contactors are not suitable for a reversing starter or for controlling a single load from 2 separate supplies.
Block diagrams
– Single supply and 2 separate loads – 2 separate supplies and 2 separate loads
1
2
R5
R6
R3
R4
7
8
A1
A2
1
2
R5
R6
R3
R4
7
8
Load
Load
Back-up
supply
Main
supply
A1
A2
1
2
R5
R6
R3
R4
7
8
Load
Load
Supply
Low Voltage Products & Systems 1.125
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Main pole - Utilization characteristics according to IEC
Contactor types AC or DC operated EK110 EK150 EK175 EK210 EK370 EK550 EK1000
Standards
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage Ue max.
1000 V
Rated frequency (without derating)
50 / 60 Hz
Conventional free-air thermal current Ith
acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C 200 A 250 A 300 A 350 A 550 A 800 A 1000 A
With conductor cross-sectional area 95 mm² 150 mm² 185 mm² 240 mm² 2x 185 mm² 2x 240 mm² 2x 300 mm²
AC-1 Utilization category
For air temperature close to contactor
Ie / Rated operational current AC-1
θ ≤ 40 °C 200 A 250 A 300 A 350 A 550 A 800 A 1000 A
Ue max. 1000 V, 50/60 Hz θ ≤ 55 °C 180 A 230 A 270 A 310 A 470 A 650 A 800 A
θ ≤ 70 °C 155 A 200 A 215 A 250 A 400 A 575 A 720 A
With conductor cross-sectional area 95 mm² 150 mm² 185 mm² 240 mm² 2x 185 mm² 2x 240 mm² 2x 300 mm²
AC-3 Utilization category
For air temperature close to contactor θ ≤ 55 °C
Ie / Max. rated operational current AC-3 (1)
M
3
3-phase motors
220-230-240 V 120 A 145 A 210 A 210 A 400 A 550 A -
380-400 V 120 A 145 A 210 A 210 A 400 A 550 A -
415 V 120 A 145 A 210 A 210 A 400 A 550 A -
440 V 120 A 145 A 210 A 210 A 370 A 550 A -
500 V 120 A 145 A 210 A 210 A 370 A 550 A -
690 V 120 A 120 A 210 A 210 A 370 A 550 A -
1000 V 64 A 80 A 113 A 113 A 155 A 175 A -
Rated operational power AC-3 (1)
M
3
1500 r.p.m. 50 Hz
1800 r.p.m. 60 Hz
3-phase motors
220-230-240 V 30 kW 45 kW 59 kW 59 kW 110 kW 160 kW -
380-400 V 55 kW 75 kW 110 kW 110 kW 200 kW 280 kW -
415 V 55 kW 75 kW 110 kW 110 kW 220 kW 315 kW -
440 V 59 kW 75 kW 110 kW 110 kW 220 kW 315 kW -
500 V 75 kW 90 kW 132 kW 132 kW 250 kW 400 kW -
690 V 110 kW 110 kW 160 kW 160 kW 355 kW 500 kW -
1000 V 90 kW 110 kW 160 kW 160 kW 220 kW 250 A -
Rated making capacity AC-3
10 x Ie AC-3 acc. to IEC 60947-4-1
Rated breaking capacity AC-3
8 x Ie AC-3 acc. to IEC 60947-4-1
Short-circuit protection device for contactors
without thermal overload relay - Motor protection excluded
Ue ≤ 500 V AC - gG type fuse 250 A 250 A 355 A 355 A 630 A 800 A 1000 A
Rated short-time withstand current Icw
1 s 1700 A 1800 A 2300 A 2300 A 5500 A 5500 A 6800 A
at 40 °C ambient temperature,
in free air from a cold state
10 s 900 A 1200 A 1680 A 1680 A 5300 A 5300 A 6400 A
30 s 600 A 700 A 1000 A 1000 A 3700 A 3700 A 4400 A
1 min 450 A 550 A 800 A 800 A 3000 A 3000 A 3400 A
15 min 210 A 250 A 320 A 320 A 1000 A 1000 A 1200 A
Maximum breaking capacity
cos ϕ = 0.45 at 440 V 1400 A 1500 A 2000 A 2000 A 5000 A 5400 A -
(cos ϕ = 0.35 for Ie > 100 A) at 690 V 1100 A 1200 A 1700 A 1700 A 5000 A 5400 A -
Power dissipation per pole
Ie / AC-1 10 W 13 W 18 W 18 W 40 W 60 W 80 W
Ie / AC-3 3 W 5 W 9 W 9 W 15 W 25 W -
Max. electrical switching frequency
AC-1 300 cycles/h
AC-3 300 cycles/h -
AC-2, AC-4 150 cycles/h 120 cycles/h -
Main pole - Utilization characteristics according to UL / CSA
Contactor types AC or DC operated EK110 EK150 EK175 EK210 EK370 EK550 EK1000
Standards
UL 508, CSA C22.2 N°14 -
Max. operational voltage
600 V -
UL / CSA general use rating
600 V AC
170 A 200 A 250 A 300 A 420 A 540 A -
Max. electrical switching frequency
For general use
300 cycles/h
(1) For the corresponding kW/A or hp/A values of 1500 r.p.m, 50 Hz or 1800 r.p.m, 60 Hz, 3-phase motors, see "Motor rated operational powers and currents".
IEC/UL/CSA Technical data
EK110...EK1000, 4-pole
Utilization characteristics
1.126 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General technical data
AF09(Z)...AF38(Z)
Coil & mounting characteristics
Magnet system characteristics
Contactor types
AC / DC operated
AF09(Z) AF16(Z) AF26(Z) AF38(Z)
Coil operating limits
AC supply At θ60 °C 0.85 x Uc min...1.1 x Uc max.
At θ 70 °C 0.85 x Uc min...Uc max.
acc. to IEC 60947-4-1
DC supply At θ60 °C 0.85 x Uc min...1.1 x Uc max.
At θ 70 °C (AF) 0.85 x Uc min...Uc max. - (AF..Z) 0.85 x Uc min...1.1 x Uc max.
AC control voltage
Rated control circuit voltage Uc 24...500 V AC
50/60 Hz
Coil consumption Average pull-in value (AF) 50 VA - (AF..Z) 16 VA
Average holding value (AF) 2.2 VA / 2 W - (AF..Z) 1.7 VA / 1.5 W
DC control voltage
Rated control circuit voltage Uc 12...500 V DC
Coil consumption Average pull-in value (AF) 50 W - (AF..Z) 12...16 W
Average holding value (AF) 2 W - (AF..Z) 1.7 W
PLC-output control
(AF..Z) ≥ 500 mA 24 V DC
Drop-out voltage
≤ 60 % of Uc min.
Voltage sag immunity acc. to SEMI F47-0706
(AF..Z) conditions of use on request
Dips withstand
(AF..Z) 22 ms average
-20 °C θ ≤ +60°C
Operating time
Between coil energization and: N.O. contact closing 40...95 ms
N.C. contact opening 38...90 ms
Between coil de-energization and: N.O. contact opening 11...95 ms
N.C. contact closing 13...98 ms
Mounting characteristics and conditions for use
Contactor types AF09(Z) AF16(Z) AF26(Z) AF38(Z)
Mounting positions
Max. add-on N.C. auxiliary contacts:
see accessory fitting details for a 4-pole contactor AF09 ... AF38
Mounting distances
The contactors can be assembled side by side
Fixing
On rail according to IEC 60715, EN 60715 35 x 7.5 mm or 35 x 15 mm
By screws (not supplied) 2 x M4 screws placed diagonally
Low Voltage Products & Systems 1.127
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General technical data
A45...A75
Coil & mounting characteristics
Magnet system characteristics
Contactor types
AC operated
A45 A50 A75
Coil operating limits
AC supply At θ55 °C 0.85...1.1 x Uc
acc. to IEC 60947-4-1 Please also refer to "Mounting characteristics and conditions for use"
AC control voltage
Rated control circuit voltage Uc at 50 Hz 24…690 V
at 60 Hz 24…690 V
Coil consumption Average pull-in value 50 Hz 180 VA
60 Hz 210 VA
50/60 Hz (1) 190 VA / 180 VA
Average holding value 50 Hz 18 VA / 5.5 W
60 Hz 18 VA / 5.5 W
50/60 Hz (1) 18 VA / 5.5 W
Drop-out voltage
approx. 40...65 % of Uc
Operating time
Between coil energization and: N.O. contact closing 8…27 ms
N.C. contact opening 7…22 ms
Between coil de-energization and: N.O. contact opening 4…11 ms
N.C. contact closing 7…14 ms
(1) 50/60 Hz coils: see "Coil voltage code table".
Mounting characteristics and conditions for use
Contactor types
AC operated
A45 A50 A75
Mounting positions
Pos. 5Pos. 6
Pos. 3
Pos
. 2
Pos. 1Pos. 1 ± 30°
+30° -30°
Pos. 4
Pos. 5 unauthorized for A45-22-00, A75-22-00
Max. add-on N.O. or N.C. auxiliary contacts: see accessory fitting details for 4-pole contactor
A45 ... A75
Control voltage / Ambient temperature
Mounting
positions (1)
1, 1±30°, 2, 3, 4, 5 at θ ≤ 55 °C 0.85…1.1 x Uc
at θ ≤ 70 °C Uc
6at θ ≤ 55 °C 0.95…1.1 x Uc
at θ ≤ 70 °C Unauthorized
Mounting distances
The contactors can be assembled side by side
Fixing
On rail according to IEC 60715, EN 60715 35 x 15 mm or 75 x 25 mm
By screws (not supplied) 2 x M6 screws placed diagonally
(1) For 60 Hz coil voltage: (only for devices tted with CA 5-.. and CAL 5-11 auxiliary contacts or TP timer).
A45-40-00, A50-40-00 and A75-40-00 contactors.
Mounting positions 1 to 5 and ambient temperature ≤ 55 °C: tolerance reduced to 0.9...1.1 Uc (instead of 0.85...1.1 Uc) for coil voltage codes 70 to 79 and 80 to 89.
A45-22-00 and A75-22-00 contactors.
Mounting positions 1 to 4 and ambient temperature ≤ 55 °C: tolerance reduced to 0.9...1.1 Uc (instead of 0.85...1.1 Uc) for coil voltage codes 70 to 79 and 80 to 89.
For mounting position 6 or ambient temperature of 55 to 70 °C the information given on this page remains applicable.
1.128 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General technical data
AE45...AE75
Coil & mounting characteristics
Magnet system characteristics
Contactor types
DC operated
AE45 AE50 AE75
Coil operating limits
DC supply At θ55 °C 0.85...1.1 x Uc
acc. to IEC 60947-4-1 Please also refer to "Mounting characteristics and conditions for use"
DC control voltage
Rated control circuit voltage Uc 12…250 V DC
Coil consumption Average pull-in value 200 W
Average holding value 4 W
Drop-out voltage
approx. 15...40 % of Uc
Coil time constant
Open L/R 3 ms
Closed L/R 15 ms
Operating time
Between coil energization and: N.O. contact closing 13…30 ms
N.C. contact opening 10…27 ms
Between coil de-energization and: N.O. contact opening (1) 5…15 ms
N.C. contact closing (1) 8…18 ms
(1) The use of surge suppressors increases the opening time with a factor of 1.1 to 1.5 for RV5 surge suppressor and a factor of 1.5 to 3 for RT5 surge suppressor.
Mounting characteristics and conditions for use
Contactor types
DC operated
AE45 AE50 AE75
Mounting positions
Pos. 5Pos. 6
Pos. 3
Pos
. 2
Pos. 1Pos. 1 ± 30°
+30° -30°
Pos. 4
Pos. 5 unauthorized for AE45-22-00, AE75-22-00
Max. add-on N.O. or N.C. auxiliary contacts: see accessory fitting details for 4-pole contactor
AE45 … AE75 (1)(2)
Control voltage / Ambient temperature
Mounting
positions
1, 1±30°, 2, 3, 4, 5 at θ ≤ 55 °C 0.85…1.1 x Uc
at θ ≤ 70 °C Uc
6at θ ≤ 55 °C 0.95…1.1 x Uc
at θ ≤ 70 °C Unauthorized
Mounting distances
The contactors can be assembled side by side
Fixing
On rail according to IEC 60715, EN 60715 35 x 15 mm or 75 x 25 mm
By screws (not supplied) 2 x M6 screws placed diagonally
Low Voltage Products & Systems 1.129
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General technical data
AF45...AF75
Coil & mounting characteristics
Magnet system characteristics
Contactor types
AC / DC operated
AF45 AF50 AF75
Coil operating limits
AC or DC supply At θ70 °C 0.85 x Uc min...1.1 x Uc max.
Please also refer to "Mounting characteristics and conditions for use"
acc. to IEC 60947-4-1
AC control voltage
Rated control circuit voltage Uc 48…250 V
50/60 Hz
Coil consumption Average pull-in value 210 VA
Average holding value 7 VA / 2.8 W
DC control voltage
Rated control circuit voltage Uc 20…250 V DC
Coil consumption Average pull-in value 190 W
Average holding value 2.8 W
Drop-out voltage
55 % of Uc min.
Voltage sag immunity
Conditions of use on request
acc. to SEMI F47
Dips withstand
≥ 20 ms
Operating time
Between coil energization and: N.O. contact closing 30…100 ms
N.C. contact opening 27…95 ms
Between coil de-energization and: N.O. contact opening 30…110 ms
N.C. contact closing 35…115 ms
Mounting characteristics and conditions for use
Contactor types
AC / DC operated
AF45 AF50 AF75
Mounting positions
Pos. 5 unauthorized for AF45-22-00, AF75-22-00 contactors
Max. and add-on N.O. or N.C. auxiliary contacts: see accessory fitting details for 4-pole con-
tactor AF45 ... AF110
Control voltage / Ambient temperature
Mounting 1, 1±30°, 2, 3, 4, 5 at θ ≤ 70 °C 0.85 x Uc min…1.1 x Uc max.
positions 6Unauthorized
Mounting distances
The contactors can be assembled side by side
Fixing
On rail according to IEC 60715, EN 60715 35 x 15 mm or 75 x 25 mm
By screws (not supplied) 2 x M6 screws placed diagonally
Pos. 5Pos. 6
Pos. 3
Pos
. 2
Pos. 1Pos. 1 ± 30°
+30° -30°
Pos. 4
1.130 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General technical data
EK110...EK1000
Coil & mounting characteristics
Magnet system characteristics
Contactor types
AC operated
EK110 EK150 EK175 EK210 EK370 EK550 EK1000
Coil operating limits
AC supply At θ70 °C 0.85 x Uc min...1.1 x Uc max.
Please also refer to "Mounting characteristics and conditions for use"
acc. to IEC 60947-4-1
AC control voltage
Rated control circuit voltage 50 Hz 24...500 V 48...500 V
60 Hz 24...600 V 110...600 V
Coil consumption Average pull-in value 50 Hz 800 VA 1100 VA 3500 VA
60 Hz 900 VA 1200 VA 4000 VA
50/60 Hz (1) 500 /500 VA 630 / 630 VA 3800 / 3400 VA
Average holding value 50 Hz 44 VA / 15 W 52 VA / 18 W 125 VA / 50 W
60 Hz 52 VA /18 W 65 VA / 22 W 140 VA / 60 W
50/60 Hz (1) 2.5 VA / 2.5 W 2.5 VA / 2.5 W 140 VA /60 W
Drop-out voltage in % of Uc min.
approx. 45...65 % (20...50 % for "E" coil voltage codes) approx. 45...65 %
Operating time
Between coil energization and: N.O. contact closing 20...40 (1) / 30...50 (2) ms 30...60 ms
N.C. contact opening 15...35 (1)
/ 25...45 (2)
ms 25...55 ms
Between coil de-energization and: N.O. contact opening 7.5...15 (1)
/ 95...120 (2) ms 10...20 ms
N.C. contact closing 10...18 (1) / 100...125 (2)
ms 13...23 ms
(1) "A" coil voltage: see "Coil voltage code table".
(2) 50/60 Hz "E" coil voltage codes, see "Coil voltage code table".
Magnet system characteristics
Contactor types
DC operated
EK110 EK150 EK175 EK210 EK370 EK550 EK1000
Coil operating limits
DC supply At θ70 °C 0.85 x Uc min...1.1 x Uc max.
Please also refer to "Mounting characteristics and conditions for use"
acc. to IEC 60947-4-1
DC control voltage
Rated control circuit voltage 12...220 24...220
Coil consumption Average pull-in value 500 W 630 W 1100 W
Average holding value 2.5 W 2.5 W 20 W
Drop-out voltage
approx. 15...50 % of Uc min.
Coil time constant Open
L/R 8 ms 12 ms
Closed
L/R 50 ms 60 ms
Operating time
Between coil energization and: N.O. contact closing 30...50 ms 60...80 ms
N.C. contact opening 27...47 ms 55...75 ms
Between coil de-energization and: N.O. contact opening 10...35 ms
N.C. contact closing 13...38 ms
Mounting characteristics and conditions for use
Contactor types
AC / DC operated
EK110 EK150 EK175 EK210 EK370 EK550 EK1000
Mounting positions
ABB
ABB
ABB
ABB
Position 1
Position 3
Position 4
Position 2
Position 5
Position 1 30
+30
-30
Position 6
Max. N.O. or N.C. built-in and add-on N.O. or N.C. auxiliary contacts: see accessory fitting
details for 4-pole contactor EK110 ... EK1000
Control voltage / Ambient temperature
Mounting
positions
1, 1±30°, 2, 3, 4, 5 at θ ≤ 70 °C 0.85…1.1 x Uc
2at θ ≤ 70 °C Unauthorized 0.85...1.1 x Uc
6at θ ≤ 70 °C Unauthorized
Mounting distances
The contactors can be assembled side by side
Fixing
On rail according to IEC 60715, EN 60715
By screws (supplied) 4 x M6 4 x M6 (1)
(1) Damping elements are supplied.
Low Voltage Products & Systems 1.131
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General technical data
AF09(Z)...AF38(Z), 4-pole
General technical data
Contactor types AF09(Z) AF16(Z) AF26(Z) AF38(Z)
Rated insulation voltage Ui
acc. to IEC 60947-4-1 690 V
acc. to UL / CSA 600 V
Rated impulse withstand voltage Uimp.
6 kV
Electromagnetic compatibility
Devices complying with IEC 60947-1 / EN 60947-1 - Environment A
Ambient air temperature close to contactor
Operation -40...+70 °C
Storage -60...+80 °C
Climatic withstand
Category B according to IEC 60947-1 Annex Q
Maximum operating altitude (without derating)
3000 m
Mechanical durability
Number of operating cycles 10 millions operating cycles
Max. switching frequency 3600 cycles/h
Shock withstand
acc. to IEC 60068-2-27 and EN 60068-2-27
Mounting position 1
Shock direction 1/2 sinusoidal shock for 11 ms: no change in contact position, closed or open position
B2
AAB1
C2
C1
4 N.O.
Main poles
A30 g
B1 25 g closed position / 5 g open position
B2 15 g
C1 25 g
C2 25 g
2 N.O. + 2 N.C.
Main poles
A30 g 30 g closed position / 25 g open position
B1 25 g closed position / 5 g open position 25 g closed position / 5 g open position
B2 15 g 15 g closed position / 10 g open position
C1 25 g 25 g closed position / 20 g open position
C2 25 g 25 g closed position / 20 g open position
Vibration withstand
5...300 Hz
acc. to IEC 60068-2-6 4 g closed position / 2 g open position
1.132 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General technical data
A/E/F45...A/E/F75, 4-pole
General technical data
Contactor types
AC operated
A45 A50 A75
DC operated
AE45 AE50 AE75
TAE45 TAE50 TAE75
AC / DC operated
AF45 AF50 AF75
Rated insulation voltage Ui
acc. to IEC 60947-4-1 1000 V
acc. to UL / CSA 600 V
Rated impulse withstand voltage Uimp.
8 kV
Electromagnetic compatibility
AF contactors complying with IEC 60947-1 / EN 60947-1 - Environment A
Ambient air temperature close to contactor
Operation -40...+70 °C (1)
Storage -60...+80 °C
Climatic withstand
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum operating altitude (without derating)
3000 m
Mechanical durability
Number of operating cycles 10 millions operating cycles (5 millions for AE... and TAE... contactors)
Max. switching frequency 3600 cycles/h (300 for AF...)
Shock withstand
acc. to IEC 60068-2-27 and EN 60068-2-27
Mounting position 1
Shock direction 1/2 sinusoidal shock for 11 ms: no change in contact position, closed or open position
B2
AAB1
C2
C1
4 N.O.
Main poles
A20 g
B1 10 g closed position / 5 g open position
B2 15 g
C1 20 g
C2 20 g
2 N.O. + 2 N.C.
Main poles
A20 g
B1 10 g closed position / 5 g open position (2)
B2 15 g (3)
C1 20 g
C2 20 g
(1) 55 °C max. for TAE... contactors.
(2) 3 g in open position for AF 45-22, AE 45-22, AF 75-22 and AE 75-22.
(3) 10 g for AF 45-22, AE 45-22, AF 75-22 and AE 75-22.
Low Voltage Products & Systems 1.133
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General technical data
EK110...EK1000, 4-pole
General technical data
Contactor types
AC or DC operated
EK110 EK150 EK175 EK210 EK370 EK550 EK1000
Rated insulation voltage Ui
acc. to IEC 60947-4-1 1000 V
acc. to UL 600 V
Rated impulse withstand voltage Uimp.
8 kV
Electromagnetic compatibility
EK contactors complying with IEC 60947-1 / EN 60947-1 - Environment A
Ambient air temperature close to contactor
Operation Fitted with thermal overload relay -25 to +55 °C -
Without thermal overload relay -40 to +70 °C -
Storage -50 to +70 °C -
Climatic withstand
Category B acc. to IEC 60068-2-30
Maximum operating altitude (without derating)
≤ 3000 m
Mechanical durability
Number of operating cycles 10 millions operating cycles 5 millions operating cycles 3 millions operating cycles
Max. switching frequency 3600 cycles/h 60 cycles/h
Shock withstand
acc. to IEC 60068-2-27 and EN 60068-2-27
Mounting position 1
B2
AAB1
C2
C1
ABB
Closed
or open
position
Shock direction 1/2 sinusoidal shock for 15 ms: no change in contact position, closed or open position
A10 g
B1 10 g
B2 10 g
C1 10 g
C2 10 g
1.134 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General technical data
AF09(Z)...AF38(Z), 4-pole
Terminal characteristics
Connecting characteristics
Contactor types AF09(Z) AF16(Z) AF26(Z) AF38(Z)
Main terminals
Screw terminals with cable clamp Screw terminals with double connector
2 x (5.5 width x 6.8 depth)
Connection capacity (min. ... max.)
Main conductors (poles)
Rigid Solid (≤ 4 mm²) 1 x 1...6 mm² 1.5...16 mm²
Stranded (≥ 6 mm²) 2 x 1...6 mm² 1.5...16 mm²
Flexible with non insulated ferrule 1 x 0.75...6 mm² 1.5...16 mm²
2 x 0.75...6 mm² 1.5...16 mm²
Flexible with insulated ferrule 1 x 0.75...4 mm² 1.5...16 mm²
2 x 0.75...2.5 mm² 1.5...16 mm²
L
6
Bars or lugs L < 9.6 mm -
Connection capacity acc. to UL/CSA (Sol/Str) 1 or 2 x AWG 16...10 AWG 16...6
Stripping length 10 mm 12 mm
Tightening torque 1.5 Nm / 13 lb.in 2.5 Nm / 22 lb.in
Auxiliary conductors
(coil terminals)
Rigid solid 1 x 1...2.5 mm²
2 x 1...2.5 mm²
Flexible with non insulated ferrule 1 x 0.75...2.5 mm²
2 x 0.75...2.5 mm²
Flexible with insulated ferrule 1 x 0.75...2.5 mm²
2 x 0.75...1.5 mm²
L
6
Lugs L < 8 mm
Connection capacity acc. to UL/CSA (Sol/Str) 1 or 2 x AWG 18...14
Stripping length 10 mm
Tightening torque 1.2 Nm / 11 lb.in
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Main terminals IP20
Coil terminals IP20
Screw terminals
Delivered in open position, screws of unused terminals must be tightened
Main terminals M3.5 M4.5
Screwdriver type Flat Ø 5.5 / Pozidriv 2
Coil terminals M3.5
Screwdriver type Flat Ø 5.5 / Pozidriv 2
Low Voltage Products & Systems 1.135
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General technical data
A/E/F45...A/E/F75
Terminal characteristics
Connecting characteristics
Contactor types
AC operated
A45 A50 A75
DC operated
AE45 AE50 AE75
TAE45 TAE50 TAE75
AC / DC operated
AF45 AF50 AF75
Main terminals
Screw terminals with single connector
(13 x 10 mm)
Connection capacity (min. ... max.)
Main conductors (poles)
Rigid Solid (≤ 4 mm²) 1 x 6…50 mm²
Stranded (≥ 6 mm²) 2 x 6…25 mm²
Flexible with ferrule 1 x 6…35 mm²
2 x 6…16 mm²
L
l
Bars or lugs L ≤ -
l > -
Connection capacity acc. to UL/CSA (Sol/Str) 1 or 2 x AWG 8…1
Tightening torque Recommended 4.00 Nm / 35 lb.in
Max. 4.50 Nm
Auxiliary conductors
(built-in auxiliary terminals + coil terminals)
Rigid solid 1 x 1…4 mm²
2 x 1…4 mm²
Flexible with ferrule 1 x 1…2.5 mm²
2 x 0.75…2.5 mm²
L
l
Lugs L ≤ 8 mm
l > 3.7 mm
Connection capacity acc. to UL/CSA (Sol/Str) 1 or 2 x AWG 18…14
Tightening torque Recommended 1.00 Nm / 9 lb.in
Max. 1.20 Nm
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Main terminals IP10
Coil terminals IP20
Screw terminals
Delivered in open position, screws of unused terminals must be tightened
Main terminals M6
Screwdriver type Flat Ø 6.5 / Pozidriv 2
Coil terminals M3.5
Screwdriver type Flat Ø 5.5 / Pozidriv 2
1.136 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General technical data
EK110...EK1000
Terminal characteristics
Connecting characteristics
Contactor types
AC or DC operated
EK110 EK150 EK175 EK210 EK370 EK550 EK1000
Main terminals
Flat type
15
ø 6.6
4.5
20
ø 11
4
20
ø 11
5
25
ø 11
640
ø 11
8
Connection capacity (min. ... max.)
Main conductors (poles)
Rigid with
connector
Single for Cu cable
25...120 mm² 25...185 mm² 25...185 mm² 70...300 mm² -
Single for Al/Cu cable
10...70 mm² 35...120 mm² 35...120 mm² 70...300 mm² 95...300 mm²
Double for Al/Cu cable
- - - 2 x 35...185 2 x 95...300
L
ø
Bars or lugs L ≤
30 mm 30 mm 33 mm 33 mm 55 mm 55 mm 55 mm
Ø >
6 mm 10 mm 10 mm 10 mm 10 mm 10 mm 10 mm
Connection capacity acc. to UL/CSA 1 or 2 x
8 -3 /0 AWG 6 - 250 MCM
2 x 4 - 500 MCM 3 x 4 - 500 MCM
-
Tightening torque Recommended
5 Nm/44 Ib.in
18 Nm / 160 Ib.in
Max. 6 Nm 22 Nm
Auxiliary conductors
(coil terminals)
Rigid solid 1 x 0.5…2.5 mm²
2 x 0.5…2.5 mm²
Flexible with ferrule 1 x 0.5…2.5 mm²
2 x 0.5…2.5 mm²
L
l
Bars or lugs L ≤ 8 mm
l > 3.7 mm
Connection capacity acc. to UL/CSA (Sol/Str) 1 or 2 x 18…14 AWG
Tightening torque Recommended 1.00 Nm / 9 lb.in
Max. 1.20 Nm
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Main terminals IP00
Coil terminals IP20
Screw terminals
Main terminals M6 M10
Screws and bolts
Coil terminals (delivered in open positions) M3.5
Screwdriver type Flat Ø 5.5 mm / Pozidriv 2
Low Voltage Products & Systems 1.137
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General
The arc switching on DC is more difcult than on AC.
For selecting a contactor it is essential to determine the current, the voltage and the L/R time constant of the controlled load.
For information, typical time constant values are quoted hereafter: non inductive loads such as resistance furnaces (L/R ≈ 1 ms), inductive loads such as shunt
motors (L/R ≈ 2 ms) or series motors (L/R ≈ 7.5 ms).
The addition of a resistor in parallel with an inductive winding helps in the elimination of the arcs.
All the poles required for breaking must be connected in series between the load and the source polarity not linked to earth (or chassis).
Technical Data
The tables indicate for the standard contactors the Ie max. operating currents depending on: the utilization category (i.e. L/R) DC-1, DC-3, DC-5 as dened
in the IEC 60947-4-1 publication, the operating voltage Ue and the pole coupling details.
Ampere values quoted in these tables are valid for a -25 … +70 °C temperature close to the contactors, as long as these values do not exceed the AC-1
Ampere values for the corresponding ambient temperature.
Max. switching frequency: 300 cycles/h.
IEC Technical data
AF09(Z)...AF38(Z), 3 & 4-pole
DC circuit switching
Selection table
Contactor types AF09 AF12 AF16 AF26 AF30 AF38
3 or 4-pole 3-pole 4-pole 3-pole 3-pole 4-pole
Utilization category DC-1, L/R ≤ 1 ms
≤ 72 V 25 A 27 A 30 A 45 A 45 A 50 A 50 A 55 A
110 V 10 A 15 A 20 A —————
220 V ————————
≤ 72 V 25 A 27 A 30 A 45 A 45 A 50 A 50 A 55 A
110 V 25 A 27 A 30 A 45 A 45 A 50 A 50 A 55 A
220 V 10 A 15 A 20 A —————
≤ 72 V 25 A 27 A 30 A 45 A 45 A 50 A 50 A 55 A
110 V 25 A 27 A 30 A 45 A 45 A 50 A 50 A 55 A
220 V 25 A 27 A 30 A 45 A 45 A 50 A 50 A 55 A
≤ 72 V 25 A 30 A 45 A ——55 A
110 V 25 A 30 A 45 A ——55 A
220 V 25 A 30 A 45 A ——55 A
440 V 10 A 20 A —————
Utilization category DC-3, L/R ≤ 2 ms
≤ 72 V 25 A 27 A 30 A 45 A 50 A 50 A
110 V 6 A 7 A 8 A —————
220 V ————————
≤ 72 V 25 A 27 A 30 A 45 A 50 A 50 A
110 V 25 A 27 A 30 A 45 A 50 A 50 A
220 V 6 A 7 A 8 A —————
≤ 72 V 25 A 27 A 30 A 45 A 50 A 50 A
110 V 25 A 27 A 30 A 45 A 50 A 50 A
220 V 25 A 27 A 30 A 45 A 50 A 50 A
≤ 72 V 25 A 30 A —————
110 V 25 A 30 A —————
220 V 25 A 30 A —————
440 V 6 A 8 A —————
Utilization category DC-5, L/R ≤ 7.5 ms
≤ 72 V 9 A 12 A 16 A 20 A 25 A 25 A
110 V 4 A 4 A 4 A
220 V ————————
≤ 72 V 25 A 27 A 30 A 45 A 50 A 50 A
110 V 10 A 15 A 20 A 45 A 50 A 50 A
220 V 4 A 4 A 4 A
≤ 72 V 25 A 27 A 30 A 45 A 50 A 50 A
110 V 25 A 27 A 30 A 45 A 50 A 50 A
220 V 9 A 12 A 16 A 20 A 25 A 25 A
≤ 72 V 25 A 30 A —————
110 V 25 A 30 A —————
220 V 10 A 20 A —————
440 V 4 A 4 A
1.138 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General
The arc switching on d.c. is more difcult than on a.c.
For selecting a contactor it is essential to determine the current, the voltage and the L/R time constant of the controlled load.
For information, typical time constant values are quoted hereafter: non-inductive loads such as resistance furnaces (L/R ~ 1 ms), inductive loads such as shunt motors
(L/R ~ 2 ms) or series motors (L/R ~ 7.5 ms).
The addition of a resistor in parallel with an inductive winding helps in the elimination of the arcs.
All the poles required for breaking must be connected in series between the load and the source polarity not linked to earth (or chassis).
a.c. operated contactors A9 A12 A16 A26 A30 A40 A45 A50 A63 A75 GA75
a.c. / d.c. operated (electronic coil interface) AF45 AF50 AF63 AF75
d.c. operated contactors AE9 AE12 AE16 AE26 AE30 AE40 AE45 AE50 AE63 AE75 GAE75
Utilization category DC-1, L/R < 1 ms
≤ 72 V A 25 27 30 45 55 60 70 100 110 120 120
110 V A 10 15 20 120
220 V A 120
440 V A – – – – – – – – 100
600 V A 75
≤ 72 V A 25 27 30 45 55 60 70 100 110 120
110 V A 25 27 30 45 55 60 70 100 110 120
220 V A 10 15 20
≤ 72 V A 25 27 30 45 55 60 70 100 110 120
110 V A 25 27 30 45 55 60 70 100 110 120
220 V A 25 27 30 45 55 60 70 100 110 120
≤ 72 V A 25 27 30 45 70 100 120
110 V A 25 27 30 45 70 100 120
220 V A 25 27 30 45 70 100 120
440 V A 10 15 20
Utilization category DC-3, L/R < 2 ms
≤ 72 V A 25 27 30 45 55 60 70 100 110 120 120
110 V A 6 7 8 120
220 V A 100
440 V A 85
≤ 72 V A 25 27 30 45 55 60 70 100 110 120
110 V A 25 27 30 45 55 60 70 100 110 120
220 V A 6 7 8
≤ 72 V A 25 27 30 45 55 60 70 100 110 120
110 V A 25 27 30 45 55 60 70 100 110 120
220 V A 25 27 30 45 55 60 70 100 110 120
≤ 72 V A 25 27 30 45 70 100 120
110 V A 25 27 30 45 70 100 120
220 V A 25 27 30 45 70 100 120
440 V A 6 7 8
Utilization category DC-5, L/R < 7.5 ms
≤ 72 V A 9 12 16 25 30 40 50 50 63 75 85
110 V A 4 4 4 85
220 V A 85
440 V A 35
≤ 72 V A 25 27 30 45 55 60 70 100 110 120
110 V A 10 15 20 30 45 50 70 80 90 100
220 V A 4 4 4
≤ 72 V A 25 27 30 45 55 60 70 100 110 120
110 V A 25 27 30 45 55 60 70 100 110 120
220 V A 9 12 16 25 30 40 50 50 63 75
≤ 72 V A 25 27 30 45 70 100 120
110 V A 25 27 30 45 70 100 120
220 V A 10 15 20 30 70 70 100
440 V A 4 4 4 – – – – – – –
IEC technical data
A/E/L9...A/E/F75, GA/E75, 3 & 4-pole
DC Circuit switching
Low Voltage Products & Systems 1.139
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
IEC Technical data
A/F95...AF750, B/C6...B/C7, 3-pole
DC circuit switching
Technical Data
The tables indicate for the standard contactors the Ie max. operating currents depending on: the utilization category (i.e. L/R) DC-1, DC-3, DC-5 as dened in the IEC
60947-4-1 publication, the operating voltage Ue and the pole coupling details. See page 1.81.
Ampere values quoted in the tables below are valid for a -25 … +70 °C temperature close to the contactors, as long as the AC-1 Ampere values (see pages 1.45 - 146)
for the corresponding ambient temperature are not exceeded.
Max. switching frequency: 300 ops/h.
For switching higher d.c. ratings, we recommend the use of bar mounted contactors, R series (63 … 2000 A).
The selection table for AE 50 ... AE 110 contactors can be used for the TAE 50 ... TAE 110 types.
a.c. operated contactors A95 A110 A145 A185 A210 A260 A300 –
a.c. / d.c. operated (electronic coil interface) AF95 AF110 AF145 AF185 AF210 AF260 AF300 AF400 AF460 AF580 AF750
d.c. operated contactors – – – – – – – – –
Utilization category DC-1, L/R < 1 ms
<110 V A 600 700 800 1050
<110 V A 145 160 250 275 350 400 450 600 700 800 1050
220 V A 600 700 800 1050
<110 V A 145 160 250 275 350 400 450 600 700 800 1050
220 V A 145 160 250 275 350 400 450 600 700 800 1050
440 V A 600 700 800 1050
600 V A 600 700 800 1050
Utilization category DC-3, L/R ≤ 2.5 ms
<110 V A 600 700 800 1050
<110 V A 145 160 250 275 350 400 450 600 700 800 1050
220 V A 600 700 800 1050
<110 V A 145 160 250 275 350 400 450 600 700 800 1050
220 V A 145 160 250 275 350 400 450 600 700 800 1050
440 V A 600 700 800 1050
600 V A 600 700 800 1050
Utilization category DC-5, L/R ≤ 15 ms
<110 V A 600 700 800 1050
<110 V A 145 160 250 275 350 400 450 600 700 800 1050
220 V A 600 700 800 1050
<110 V A 145 160 250 275 350 400 450 600 700 800 1050
220 V A 145 160 250 275 350 400 450 600 700 800 1050
440 V A 600 700 800 1050
600 V A 600 700 800 1050
D.C. Power circuit switching
Utilization category DC-1 DC-3 DC-5
L/R ≤ 1 ms L/R ≤ 2 ms L/R ≤ 7.5 ms
24 V A 16.0 16.0 16.0
48 V A 16.0 8.0 2.0
60 V A 16.0 4.0 1.25
110 V A 7.0 1.5 0.4
220 V A 0.8 0.25 0.2
24 V A 16.0 16.0 16.0
48 V A 16.0 16.0 16.0
60 V A 16.0 15.0 12.0
110 V A 16.0 7.0 2.0
220 V A 5.0 1.5 0.5
24 V A 16.0 16.0 16.0
48 V A 16.0 16.0 16.0
60 V A 16.0 16.0 16.0
110 V A 16.0 15.0 8.0
220 V A 14.0 4.0 2.0
1.140 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
General
The arc switching on d.c. is more difcult than on a.c.
For selecting a contactor it is essential to determine the current, the voltage and the L/R time constant of the controlled load.
For information, typical time constant values are quoted hereafter: non inductive loads such as resistance furnaces (L/R ~ 1 ms), inductive loads such as shunt motors
(L/R ~ 2 ms) or series motors (L/R ~ 7.5 ms).
The addition of a resistor in parallel with an inductive winding helps in the elimination of the arcs.
All the poles required for breaking must be connected in series between the load and the source polarity not linked to earth (or chassis).
A.C. operated contactors AL9 AL12 AL16 AL26 AL30 AL40
Utilization category DC-1, L/R < 1 ms
≤ 72 V A 25 27 30 45 55 60
110 V A 10 15 20
220 V A
440 V A – – – – – –
600 V A – – – – – –
≤ 72 V A 25 27 30 45 55 60
110 V A 25 27 30 45 55 60
220 V A 10 15 20
≤ 72 V A 25 27 30 45 55 60
110 V A 25 27 30 45 55 60
220 V A 25 27 30 45 55 60
≤ 72 V A 25 27 30 45
110 V A 25 27 30 45
220 V A 25 27 30 45
440 V A 10 15 20
Utilization category DC-3, L/R < 2 ms
≤ 72 V A 25 27 30 45 55 60
110 V A 6 7 8
220 V A
440 V A – – – – – –
≤ 72 V A 25 27 30 45 55 60
110 V A 25 27 30 45 55 60
220 V A 6 7 8
≤ 72 V A 25 27 30 45 55 60
110 V A 25 27 30 45 55 60
220 V A 25 27 30 45 55 60
≤ 72 V A 25 27 30 45
110 V A 25 27 30 45
220 V A 25 27 30 45
440 V A 6 7 8
Utilization category DC-5, L/R < 7.5 ms
≤ 72 V A 9 12 16 25 30 40
110 V A 4 4 4
220 V A
440 V A – – – – – –
≤ 72 V A 25 27 30 45 55 60
110 V A 10 15 20 30 45 50
220 V A 4 4 4
≤ 72 V A 25 27 30 45 55 60
110 V A 25 27 30 45 55 60
220 V A 9 12 16 25 30 40
≤ 72 V A 25 27 30 45
110 V A 25 27 30 45
220 V A 10 15 20 30
440 V A 4 4 4
IEC Technical data
AL9 – AL40
DC circuit switching
Low Voltage Products & Systems 1.141
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
General
The arc switching on d.c. is more difcult than on a.c.
For selecting a contactor it is essential to determine the current, the voltage and the L/R time constant of the controlled load.
For information, typical time constant values are quoted hereafter: non inductive loads such as resistance furnaces (L/R ~ 1 ms), inductive loads such as shunt
motors (L/R ~ 2 ms) or series motors (L/R ~ 7.5 ms).
The addition of a resistor in parallel with an inductive winding helps in the elimination of the arcs.
All the poles required for breaking must be connected in series between the load and the source polarity not linked to earth (or chassis).
Technical Data
The tables indicate for the standard contactors the Ie max. operating currents depending on: the utilization category (i.e. L/R) DC-1, DC-3, DC-5 as dened in the
IEC 60947-4-1 publication (see page 1.75 for more details), the operating voltage Ue and the pole coupling details.
Ampere values quoted in the tables below are valid for a -25 … +70 °C temperature close to the contactors, as long as the AC-1 Ampere values (see page 1.61)
for the corresponding ambient temperature are not exceeded.
Max. switching frequency: 300 ops/h.
For switching higher d.c. ratings, we recommend the use of bar mounted contactors, R series (63 … 2000 A).
Selection Table
a.c. / d.c. operated contactors EK110 EK150 EK175 EK210 EK370 EK550 EK1000
Utilization category DC-1, L/R < 1 ms
≤ 72 V A 120 145 210 210 370 550
110 V A 120 145 210 210 370 550
≤ 72 V A 200 200 300 300 550 800
110 V A 200 200 300 300 550 800
220 V A 200 200 300 300 550 800
≤ 72 V A 200 200 300 300 550 800
110 V A 200 200 300 300 550 800
220 V A 200 200 300 300 550 800
440 V A 210 210 450 650
600 V A 450 650
≤ 72 V A 200 200 300 300 550 800
110 V A 200 200 300 300 550 800
220 V A 200 200 300 300 550 800
440 V A 200 200 260 300 450 650
600 V A 260 300 450 650
Utilization category DC-3, L/R < 2 ms
≤ 72 V A 120 145 210 210 370 550
≤ 72 V A 135 145 210 210 450 650
110 V A 135 135 210 210 450 650
220 V A 135 135 210 210 450 650
≤ 72 V A 135 145 210 210 450 650
110 V A 135 135 210 210 450 650
220 V A 135 135 210 210 450 650
440 V A 210 210 450 650
600 V A 450 650
≤ 72 V A 135 145 210 210 450 650
110 V A 135 135 210 210 450 650
220 V A 135 135 210 210 450 650
440 V A 135 135 210 210 450 650
600 V A 170 210 450 650
Utilization category DC-5, L/R < 7.5 ms
≤ 72 V A 135 145 210 210 450 650
110 V A 135 135 210 210 450 650
220 V A 135 135 210 210 450 650
≤ 72 V A 135 145 210 210 450 650
110 V A 135 135 210 210 450 650
220 V A 135 135 210 210 450 650
440 V A 210 210 450 650
600 V A 450 650
≤ 72 V A 135 145 210 210 450 650
110 V A 135 135 210 210 450 650
220 V A 135 135 210 210 450 650
440 V A 135 135 210 210 450 650
600 V A 170 210 450 650
IEC Technical data
EK110 – EK1000
DC circuit switching
1.142 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
IEC Technical data
3-pole contactors
Electrical durability and utilization categories
General
Utilization categories determine the current making and breaking conditions relating to the characteristics of the loads to be
controlled by the contactors. International standard IEC 60947-4-1 and European standard EN 60947-4-1 are the standards to
be referred to.
If Ic is the current to be broken by the contactor and Ie the rated operational current normally drawn by the load, then:
Categories AC-1 and AC-3: Ic = Ie
Category AC-2: Ic = 2.5 x Ie
Category AC-4: Ic = 6 x Ie
Generally speaking Ic = m x Ie where m is a multiple of the load operational current.
On next pages, the curves corresponding to categories AC-1, AC-3 and AC-4 represent the electrical durability variation of
standard contactors in relation to the breaking current Ic.
Electrical durability is expressed in millions of operating cycles.
Curve utilization mode
Electrical durability forecast and contactor selection for categories AC-1, AC-2, AC-3 or AC-4
Note the characteristics of the load to be controlled:
Operational voltage .......................................... Ue
Current normally drawn .................................... Ie (Ue / Ie / kW relation for motors, see "Motor rated operational powers and currents").
Utilization category .......................................... AC-1, AC-2, AC-3 or AC-4
Breaking current .............................................. Ic = Ie for AC-1 and for AC-3 ; Ic = 2.5 x Ie for AC-2 ; Ic = 6 x Ie for AC-4
Define the number of operating cycles N required.
On the diagram corresponding to the operational category, select the contactor with the curve immediately above the inter-
section point (Ic ; N).
Electrical durability forecast and contactor selection for mixed duty motor control: AC-3 (Ic = Ie) type switching off while
"motor running" and, occasionally, AC-4 (Ic = 6 x Ie) type switching off while "motor accelerating"
Note the characteristics of the motor to be controlled:
Operational voltage ...................................................... Ue
Current normally drawn while "motor running" ............... Ie
(Ue / Ie / kW relation for motors, see "Motor rated operational powers and currents")
Breaking current for AC-3 ............................................ Ic = Ie
Breaking current for AC-4 while "motor accelerating" ..... Ic = 6 x Ie
Percentage of AC-4 operating cycles ............................ K (on the basis of the total number of operating cycles)
Define the total number of operating cycles N required.
Note the smallest contactor rating compatible for AC-3 (Ue / Ie) on Main pole utilization characteristic table (see “Technical data”).
For the selected contactor make a note of the following in relation to the voltage using diagram AC-3 in next pages:
The number of operating cycles A for Ic = Ie (AC-3)
The number of operating cycles B for Ic = 6 x Ie (AC-4)
Calculate the estimated number of cycles N’ (N’ is always below A)
N'= A
1 + 0.01 K (A/B - 1)
If N' is too low in relation to the target N, calculate the estimated number of cycles for a higher contactor rating.
Case of uninterrupted duty
For uninterrupted duty, some verifications of preventing maintenance are necessary to check the functionality of the concerned
product (consult us).
The combinated effect of environmental conditions and the proper temperature of the product may require some disposals. As
a matter of fact, for this duty, the use duration prevails over the number of operating cycles.
Low Voltage Products & Systems 1.143
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
IEC Technical data
3-pole contactors
Electrical durability (AC-1)
Electrical durability for AC-1 utilization category - Ue ≤ 690 V
Ambient temperature ≤ 60 °C for AF09(Z)...AF38(Z), ≤ 55 °C for A40 ... AF2050
Switching non-inductive or slightly inductive loads. The breaking current Ic for AC-1 is equal to the rated operational current of
the load.
Maximum electrical switching frequency: see "Technical data".
13579
13579
1
3
5
7
9
1
3
5
7
9
13579
13579
1
3
5
7
9
10
1
0.1
0.2
0.3
0.5
3
5
10 100 100023 5203050 200 300 500
A145
A40
A50
A63
A75
A95
A110
A185
A210
A300
A260
AF400
AF460
AF580
AF750
2
26.5
AF09
AF12
AF16
AF26
AF30, AF38
The curves provided for the A50 ... A300 contactors
can be used for the AE, TAE and AF equivalent types
Millions of
operating
cycles
Breaking current Ic (A)
AF1250, AF1350,
AF1650, AF2050:
The electrical durability at
the rated current is 50000
operating cycles.
Endurance curves – B 6, BC 6, B 6S
1013 0201. 234568
Rated operating current [A]
15
Millions of operations
0.01
0.1
1
2
0.02
0.03
0.04
0.05
0.06
0.08
0.2
0.3
0.4
0.5
0.6
0.8
3
4
5
6
8
10
AC3 AC1
Example:
Ic / AC-1 = 26.5 A – Electrical durability required = 2 millions operating cycles.
Using the AC-1 curves above select the AF26 contactor at intersection " " (26.5 A / 2 millions operating cycles).
Endurance curves – B 7, BC 7, B 7S
Rated operating current
Millions of operations
0.01
0.1
1
2
0.02
0.03
0.04
0.05
0.06
0.08
0.2
0.3
0.4
0.5
0.6
0.8
3
4
5
6
8
10
AC1
AC3
1 1.5 2 3 4 5 6 8 10 15 20 30
1.144 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
IEC Technical data
3-pole contactors
Electrical durability (AC-3)
Electrical durability for AC-3 utilization category - Ue ≤ 440 V
Ambient temperature ≤ 60 °C for AF09(Z)...AF38(Z), ≤ 55 °C for A40 ... AF1650
Switching cage motors: starting and switching off running motors. The breaking current Ic for AC-3 is equal to the rated opera-
tional current Ie (Ie = motor full load current). Maximum electrical switching frequency: see "Technical data".
10
1
10 100 100023 5203050 200 300 500
0.2
0.3
0.5
2
3
5
13579
1
3
5
7
9
1
3
5
7
9
1357913579
1357913579
A50
A63
A75
A95
A110
A145
A185
A210
A260
A300
AF400
AF460
AF580
AF750
1.5
79
AF09
AF12
AF16
AF26
A40
AF30, AF38
The curves provided for the A50 ... A300 contactors can be used for the AE, TAE and AF equivalent types
Millions of
operating
cycles
Breaking current Ic (A)
AF1350, AF1650:
The electrical durability at
the rated current is 50000
operating cycles.
Example:
Motor power 40 kW for AC-3 - Ue = 400 V and Ie = 79 A utilization Electrical durability required = 1.5 million operating cycles.
For AC-3: Ic = Ie. Select the A110 contactor at intersection " " (79 A / 1.5 million operating cycles) on the curves (AC-3 - Ue ≤ 440 V).
Endurance curves – B 6, BC 6, B 6S
1013 0201. 234568
Rated operating current [A]
15
Millions of operations
0.01
0.1
1
2
0.02
0.03
0.04
0.05
0.06
0.08
0.2
0.3
0.4
0.5
0.6
0.8
3
4
5
6
8
10
AC3 AC1
Endurance curves – B 7, BC 7, B 7S
Rated operating current
Millions of operations
0.01
0.1
1
2
0.02
0.03
0.04
0.05
0.06
0.08
0.2
0.3
0.4
0.5
0.6
0.8
3
4
5
6
8
10
AC1
AC3
1 1.5 2 3 4 5 6 8 10 15 20 30
Low Voltage Products & Systems 1.145
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
IEC Technical data
3-pole contactors
Electrical durability (AC-2, AC-4)
Electrical durability for AC-2 or AC-4 utilization category - Ue < 440 V
Ambient temperature ≤ 60 °C for AF09(Z)...AF38(Z), ≤ 55 °C for A40 ... AF1650
Switching cage motors: starting, reverse operation and step-by-step operation. The breaking current Ic is equal to 2.5 x Ie for
AC-2 and 6 x Ie for AC-4, keeping in mind that Ie is the motor rated operational current (Ie = motor full-load current).
Maximum electrical switching frequency: see "Technical data".
Example:
Motor power 45 kW for AC-4 - Ue = 400 V and Ie = 85 A utilization Electrical durability required = 0.2 million operating cycles.
For AC-4: Ic = 6 x Ie = 510 A - Select the A260 contactor at intersection " " (510 A / 0.2 million operating cycles) on the
curves (AC-4 - Ue 440 V).
1013 0201.5 234568
Switch off current [A]
15
Millions of operations
0.01
0.1
1
2
0.02
0.03
0.04
0.05
0.06
0.08
0.2
0.3
0.4
0.5
0.6
0.8
3
4
5
6
8
10
AC4
Endurance curves – B 6, BC 6, B 6S Endurance curves – B 7, BC 7, B 7S
10
10201.5 23
45
68
Switch off current [A]
15
Millions of operations
0.01
0.1
1
2
0.02
0.03
0.04
0.05
0.06
0.08
0.2
0.3
0.4
0.5
0.6
0.8
3
4
5
6
8
10
AC4
300010001001023 5203050 200 300 500 2000 5000
10
1
0.1
0.005
0.01
0.02
0.03
0.05
0.3
0.5
2
3
5
13579
13579
13579
13579
13579
13579
1
3
5
7
9
1
3
5
7
9
1
3
5
7
9
1
3
5
7
9
1
3
5
7
9
1
3
5
7
9
A40
A50
A63
A75
A95
A110
A260
A300
A145
A185
A210
0.2
510
AF400
AF460
AF580
AF750
AF1350
AF1650
0.2
510
AF12
AF16
AF09
AF26
AF30, AF38
The curves provided for the A50 ... A300 contactors can be used for the AE,
TAE and AF equivalent types
Millions of
operating
cycles
Breaking current Ic (A)
1.146 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
IEC Technical data
4-pole contactors
Electrical durability (AC-1)
Electrical durability for AC-1 utilization category - Ue ≤ 690 V
Ambient temperature ≤ 60 °C for AF09 ... AF38, ≤ 55 °C for A45 ... EK1000
Switching non-inductive or slightly inductive loads. The breaking current Ic for AC-1 is equal to the rated operational current of
the load.
Maximum electrical switching frequency: see "Technical data".
Example:
13579
13579
1
3
5
7
9
1
3
5
7
9
13579
13579
1
3
5
7
9
10
1
0.1
0.2
0.3
0.5
3
5
10 100 100023 5203050 200 300 500
A45
A50
A75
13.5
2
EK1000
EK110
EK150
EK175
EK210
EK370
EK550
AF09
AF16
AF26
AF38
The curves provided for the A45 ... A75 contactors
can be used for the AE, TAE and AF equivalent types
Millions of
operating
cycles
Breaking current Ic (A)
Ic / AC-1 = 13.5 A – Electrical durability required = 2 millions operating cycles.
Using the AC-1 curves above select the AF16 contactor at intersection " " (13.5 A / 2 millions operating cycles).
Endurance curves – B 6, BC 6, B 6S
1013 0201. 234568
Rated operating current [A]
15
Millions of operations
0.01
0.1
1
2
0.02
0.03
0.04
0.05
0.06
0.08
0.2
0.3
0.4
0.5
0.6
0.8
3
4
5
6
8
10
AC3 AC1
Endurance curves – B 7, BC 7, B 7S
Rated operating current
Millions of operations
0.01
0.1
1
2
0.02
0.03
0.04
0.05
0.06
0.08
0.2
0.3
0.4
0.5
0.6
0.8
3
4
5
6
8
10
AC1
AC3
1 1.5 2 3 4 5 6 8 10 15 20 30
Low Voltage Products & Systems 1.147
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Dimensions mm, inches
Note: contactor lateral distance to grounded component 2 mm 0.08" min.
AF09, AF12, AF16 AF09, AF12, AF16
45 1.77"
80 3.15"
6 0.24"
77 3.03"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
35 1.38"
70 2.76"
60 2.36"
5 0.20"
5 0.20"
ø 4.2 0.17"
2 x
M4 8-32 UNC
45 1.77"
80 3.15"
6 0.24"
77 3.03"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
35 1.38"
70 2.76"
60 2.36"
5 0.20"
5 0.20"
ø 4.2 0.17"
2 x
M4 8-32 UNC
AF09, AF12, AF16
+ CA4, CC4 1-pole auxiliary contact block
45 1.77"
80 3.15"
6 0.24"
43 1.69"
110.5 4.35"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
5.5 0.22"
10 0.39"
AF09, AF12, AF16
+ CAL4-11 2-pole auxiliary contact block
45 1.77"12 0.47"
80 3.15"
6 0.24"
77 3.03"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
AF09, AF12, AF16
+ CA4 4-pole auxiliary contact block
45 1.77"
80 3.15"
6 0.24"
110.5 4.35"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
43 1.69"
AF09, AF12, AF16
+ CAT4 2-pole auxiliary contact and coil terminal block
45 1.77"
80 3.15"
102.5 4.04"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
43 1.69"
AF09, AF12, AF16
+ VEM4 mechanical and electrical interlock set
AF09, AF12, AF16
+ VEM4 mechanical and electrical interlock set
90 3.54"
91.5 3.60"
102.5 4.04"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
43 1.69"
60 2.36"
ø 4.2 0.17"
80 3.15"
70 2.76"
5 0.20"
5 0.20"
2 x
M4 8-32 UNC
90 3.54"
91.5 3.60"
102.5 4.04"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
43 1.69"
60 2.36"
ø 4.2 0.17"
80 3.15"
70 2.76"
5 0.20"
5 0.20"
2 x
M4 8-32 UNC
Approximate dimensions
AF09/Z...AF16/Z, AF09N00/Z...AF16N0/Z, 3-pole contactors
Note: Approximate dimensions for AF09 & AF16 apply to AF NEMA Sz. 00 & 0. AF09...AF16 dimensions apply to AF..Z type.
1.148 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Approximate dimensions
AF09/Z...AF16/Z, AF09N00/Z...AF16N0/Z, 3-pole contactors
Dimensions mm, inches
Note: contactor lateral distance to grounded component 2 mm 0.08" min.
AF26, AF30, AF38
45 1.77"
80 3.15"
6 0.24"
77 3.03"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
35 1.38"
70 2.76"
60 2.36"
5 0.20"
5 0.20"
ø 4.2 0.17"
2 x
M4 8-32 UNC
AF26, AF30, AF38
35 1.38"
70 2.76"
60 2.36"
5 0.20"
5 0.20"
ø 4.2 0.17"
2 x
M4 8-32 UNC
45 1.77"
80 3.15"
6 0.24"
86 3.39"
80 3.15"
10 0.39"
35 mm
EN/IEC 60715
5.5 0.22"
5.5 0.22"
AF26, AF30, AF38
+ CA4, CC4 1-pole auxiliary contact block
45 1.77"
80 3.15"
6 0.24"
119.5 4.70"
80 3.15" 10 0.39"
35 mm
EN/IEC 60715
5.5 0.22"
5.5 0.22"
43 1.69"
AF26, AF30, AF38
+ CAL4-11 2-pole auxiliary contact block
80 3.15"
6 0.24"
12 0.47" 45 1.77"
86 3.39"
80 3.15"
10 0.39"
35 mm
EN/IEC 60715
5.5 0.22"
5.5 0.22"
AF26, AF30, AF380
+ CA4 4-pole auxiliary contact block
45 1.77"
80 3.15"
6 0.24"
119.5 4.70"
80 3.15" 10 0.39"
35 mm
EN/IEC 60715
5.5 0.22"
5.5 0.22"
43 1.69"
111.5 4.39"
80 3.15" 10 0.39"
35 mm
EN/IEC 60715
5.5 0.22"
5.5 0.22"
43 1.69"
45 1.77"
80 3.15"
AF26, AF30, AF38
+ VEM4 mechanical and electrical interlock set
AF26, AF30, AF38
+ VEM4 mechanical and electrical interlock set
60 2.36"
ø 4.2 0.17"
80 3.15"
70 2.76"
5 0.20"
5 0.20"
2 x
M4 8-32 UNC
90 3.54"
91.5 3.60"
111.5 4.39"
80 3.15" 10 0.39"
35 mm
EN/IEC 60715
5.5 0.22"
5.5 0.22"
43 1.69"
60 2.36"
ø 4.2 0.17"
80 3.15"
70 2.76"
5 0.20"
5 0.20"
2 x
M4 8-32 UNC
90 3.54"
91.5 3.60"
111.5 4.39"
80 3.15" 10 0.39"
35 mm
EN/IEC 60715
5.5 0.22"
5.5 0.22"
43 1.69"
Note: Approximate dimensions for AF26 apply to AF NEMA Sz. 1. AF26...AF38 dimensions apply to AF..Z type.
AF26, AF30, AF38
+ CAT4 2-pole auxiliary contact and coil terminal block
Low Voltage Products & Systems 1.149
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Dimensions mm, inches
Note: contactor lateral distance to grounded component 2 mm 0.08" min.
AF09, AF16 AF09, AF16
45 1.77"
80 3.15"
6 0.24"
77 3.03"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
35 1.38"
70 2.76"
60 2.36"
5 0.20"
5 0.20"
ø 4.2 0.17"
2 x
M4 8-32 UNC
45 1.77"
80 3.15"
6 0.24"
77 3.03"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
35 1.38"
70 2.76"
60 2.36"
5 0.20"
5 0.20"
ø 4.2 0.17"
2 x
M4 8-32 UNC
AF09, AF16
+ CA4, CC4 1-pole auxiliary contact block
45 1.77"
80 3.15"
6 0.24"
43 1.69"
110.5 4.35"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
5.5 0.22"
10 0.39"
AF09, AF16
+ CAL4-11 2-pole auxiliary contact block
45 1.77"12 0.47"
80 3.15"
6 0.24"
77 3.03"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
AF09, AF16
+ CA4 4-pole auxiliary contact block
45 1.77"
80 3.15"
6 0.24"
110.5 4.35"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
43 1.69"
AF09, AF16
+ CAT4 2-pole auxiliary contact and coil terminal block
45 1.77"
80 3.15"
102.5 4.04"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
43 1.69"
AF09..-40-00, AF16..-40-00
+ VEM4 mechanical and electrical interlock set
AF09..-40-00, AF16..-40-00
+ VEM4 mechanical and electrical interlock set
90 3.54"
91.5 3.60"
102.5 4.04"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
43 1.69"
60 2.36"
ø 4.2 0.17"
80 3.15"
70 2.76"
5 0.20"
5 0.20"
2 x
M4 8-32 UNC
90 3.54"
91.5 3.60"
102.5 4.04"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
43 1.69"
60 2.36"
ø 4.2 0.17"
80 3.15"
70 2.76"
5 0.20"
5 0.20"
2 x
M4 8-32 UNC
Approximate dimensions
AF09/Z & AF16/Z 4-pole contactors
Note: AF09 & AF16 dimensions apply to AF..Z type.
1.150 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Dimensions mm, inches
Note: contactor lateral distance to grounded component 2 mm 0.08" min.
AF26, AF38 AF26, AF38
35 mm
EN/IEC 60715
5.5 0.22"
95 3.74"
101 3.98"
10 0.39"
5.5 0.22"
45 1.77"
80 3.15"
6 0.24"
35 1.38"
70 2.76"
60 2.36"
5 0.20"
5 0.20"
ø 4.2 0.17"
2 x
M4 8-32 UNC
45 1.77"
80 3.15"
6 0.24"
77 3.03"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
35 1.38"
70 2.76"
60 2.36"
5 0.20"
5 0.20"
ø 4.2 0.17"
2 x
M4 8-32 UNC
AF26, AF38
+ CA4, CC4 1-pole auxiliary contact block
45 1.77"
80 3.15"
6 0.24"
35 mm
EN/IEC 60715
5.5 0.22"
95 3.74"
134.5 5.30"
10 0.39"
43 1.69"
5.5 0.22"
AF26, AF38
+ CAL4-11 2-pole auxiliary contact block
45 1.77"12 0.47"
80 3.15"
6 0.24"
35 mm
EN/IEC 60715
5.5 0.22"
95 3.74"
101 3.98"
10 0.39"
5.5 0.22"
AF26, AF38
+ CA4 4-pole auxiliary contact block
45 1.77"
80 3.15"
6 0.24"
35 mm
EN/IEC 60715
5.5 0.22"
95 3.74"
134.5 5.30"
10 0.39"
43 1.69"
5.5 0.22"
AF26, AF38
+ CAT4 2-pole auxiliary contact and coil terminal block
45 1.77"
80 3.15"
35 mm
EN/IEC 60715
5.5 0.22"
95 3.74"
126.5 4.98"
10 0.39"
5.5 0.22"
43 1.69"
AF26..-40-00, AF38..-40-00
+ VEM4 mechanical and electrical interlock set
AF26..-40-00, AF38..-40-00
+ VEM4 mechanical and electrical interlock set
90 3.54"
91.5 3.60"
60 2.36"
ø 4.2 0.17"
80 3.15"
70 2.76"
5 0.20"
5 0.20"
2 x
M4 8-32 UNC
35 mm
EN/IEC 60715
5.5 0.22"
95 3.74"
126.5 4.98"
10 0.39"
5.5 0.22"
43 1.69"
90 3.54"
91.5 3.60"
102.5 4.04"
71 2.80"
5.5 0.22"
35 mm
EN/IEC 60715
10 0.39"
5.5 0.22"
43 1.69"
60 2.36"
ø 4.2 0.17"
80 3.15"
70 2.76"
5 0.20"
5 0.20"
2 x
M4 8-32 UNC
Approximate dimensions
AF26/Z & AF38/Z 4-pole contactors
Note: AF26 & AF38 dimensions apply to AF..Z type.
Low Voltage Products & Systems 1.151
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Approximate dimensions
AS09..S ... AS16..S 3-pole contactors w/spring terminals
AC/DC operated, with screw terminals
Main dimensions mm, inches
68 2.68"
90 3.54"
72.5 2.85"
5.5 0.22"
7 0.28"
35 mm
EN/IEC 60715
50 1.97"
60 2.36"
80 3.15"
ø 4.2 0.17"
4 x
M4 8-32 UNC
10 0.39"
AS/L09..S, AS/L12..S, AS/L16..S
+ VM3 mechanical interlock unit including two BB3 fixing clips
50 1.97"
60 2.36"
35 1.38"
72.5 2.85"
45 1.77"
68 2.68"
5.5 0.22"
7 0.28"
35 mm
EN/IEC 60715
ø 4.2 0.17"
2 x
M4 8-32 UNC
10 0.39"
AS/L09..S, AS/L12..S, AS/L16..S
10 0.39"
50 1.97"
60 2.36"
35 1.38"
45 1.77"
68 2.68"
72.5 2.85"
5.5 0.22"
7 0.28"
35 mm
EN/IEC 60715
35.4 1.39"
110.8 4.36"
ø 4.2 0.17"
2 x
M4 8-32 UNC
AS/L09..S, AS/L12..S, AS/L16..S
+ CA3..S front-mounted 1-pole auxiliary contact block
AS/L09...16-30-32S
10 0.39"
50 1.97"
60 2.36"
35 1.38"
45 1.77"
68 2.68"
72.5 2.85"
5.5 0.22"
7 0.28"
35 mm
EN/IEC 60715
110.8 4.36"
35.4 1.39"
ø 4.2 0.17"
2 x
M4 8-32 UNC
72.5 2.85"
45 1.77"
68 2.68"
5.5 0.22"
7 0.28"
50 1.97"
60 2.36"
35 1.38"
35 mm
EN/IEC 60715
ø 4.2 0.17"
2 x
M4 8-32 UNC
10 0.39"
AS/L09, AS/L12, AS/L16
10
0.39"
45 1.77"
68 2.68"
72.5 2.85"
5.5 0.22"
7 0.28"
35 mm
EN/IEC 60715
100.2 3.94"
44.2 1.74"
AS/L09...16-30-32
50 1.97"
60 2.36"
80 3.15"
ø 4.2 0.17"
2 x
M4 8-32 UNC
5.5 0.22"
7 0.28"
35 mm
EN/IEC 60715
72.5 2.85"
68 2.68"
78.5 3.09"
90 3.54"
10 0.39"
AS/L09, AS/L12, AS/L16
1.152 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
2.26
1.77
1.65
1.00
57.5
45.0
42.0
25.4
1.32
33.5
1.71
43.5
1.83
46.5
0.18
4. 5
CAF6
A1
A2
1.10
28
2.36
1.71
1.02
60
43.5
26
2.79
71
1.83
46.5
1.71
43.5
1.32
33.5
0.18
4. 5
1.00
25.4
1.65
42.0
1.77
45.0
2.26
57.5
1.87
47.5
2.07
52.5
1.97
50.0
0.18
4. 5
1.77
45.0
1.57
40.0
1.38
35.0
0.18
4. 5
1.83
46.5
1.71
43.5
1.32
33.5
2.26
1.77
1.65
1.00
57.5
45.0
42.0
25.4
3.80
96.5
1.97
50.0
3.54
90.0
0.18
4. 5
B/C6...B/C7
B/C6...B/C7 + CA6
B/C6...B/C7 + CAF6
VB/C6...VB/C7
Approximate dimensions
B/C6...B/C7
00.00
00.00
Inches
[Millimeters]
Low Voltage Products & Systems 1.153
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
A26
3.54
90
2.13
54
3.15
80
1.77
45
0.17
4.2
70
2.76
3.69
93.6
3.44
87.3
0.35
9
A26+VM5
3.54
90
4.84
123.0
5.25
133.4
5.25
133.4
3.69
93.6
3.44
87.3
0.35
9
4.03
102
70
2.76 3.15
80
4.64
117.9
0.17
4.2
1.77
45
2.72
69
2.32
59
4.64
117.9
0.22
5.5
A9-16,N
2.91
74
1.73
44
1.972.36
60 50
1.38
35
0.18
4.5
2.91
74
2.68
68
0.22
5.5
A9-16+VM5
5.50
139.7
2.91
74
4.06
103
1.38
35
2.36
60
1.97
50
2.32
59
0.18
4.5
2.91
74
2.68
68
0.22
5.5
A/AE26 — Contactor, 3 pole
A/AE26 + VM5 or VE5 — Mechanically interlocked contactor, 3 pole
Approximate dimensions
A/AE9 – A/AE26, 3 pole
A/AE9 – A/AE16 — Contactor, 3 pole
A/AE9 – A/AE16 + VM5 or VE5 — Mechanically interlocked contactor, 3 pole
00.00
00.00
Inches
[Millimeters]
1.154 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
A30,40
4.26
108.3
4.02
102
0.35
9
3.15
80
1.77
0.17
4.2
70
2.13
54
3.54
90
45
2.76
A30,40+VM5
2.32
59
90
4.84
123.0
5.25
133.4
5.25
133.4
3.54
70 3.15
80
4.64
117.9
0.17
4.2
1.77
45 2.72
69
4.64
117.9
0.22
5.5
4.02
102
0.35
9
4.26
108.3
4.60
117
2.76
A( E ) 50-75
2.76
70
4.25
108
4.00
101.5
0.39
10
0.24
6.2
2.36
60
3.54
90
3.94
100
3.22
82
4.33
110
A50-75+VM5
6.10
155
6.62
168.2
6.50
165
110
4.33
4.25
108
4.00
101.5
0.39
10
4.54
115.3
5.87
149
6.00
152.5
0.22
5.5
3.00
76.3
0.24
6.2
90
3.94
100
3.54
2.36
60
3.35
85
A/AE30 & A/AE40 — Contactor, 3 pole
A/AE30 & A/AE40 + VM5 or VE5 — Mechanically interlocked contactor, 3 pole
Approximate dimensions
A/AE30 – A/AE/AF75, 3 pole
A/AE/AF50 – A/AE/AF75 — Contactor, 3 pole
A/AE/AF50 – A/AE/AF75 + VM5 or VE5 — Mechanically interlocked contactor, 3 pole
00.00
00.00
Inches
[Millimeters]
Low Voltage Products & Systems 1.155
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
5-20-98
ABB Control Inc. FILE NAME
A95-110C.DXF
3.07
78.0
0.45
11.5
126.0
4.96
136.0
5.35
148.0
5.83
3.54
90.0
4.01
102.0
5.90
150.0 0.24
6.2
A95-110+VM5
7.68
195
8.10
205.7
148
4.33
8.70
221
4.86
123.5
0.39
10
5.17
131
7.28
185
7.91
200.1
3.90
99
0.31
8
126
5.35
136
3.07
78
4.13
105
0.24
6.2
4.96
Approximate dimensions
A/AE/AF95 & A/AE/AF110, 3 pole
A/AE/AF95 & A/AE/AF110 — Contactor, 3 pole
A/AE/AF95 & A/AE/AF110 + VE5 — Mechanically interlocked contactor, 3 pole
00.00
00.00
Inches
[Millimeters]
1.156 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
A9-16,N
2.91
74
1.73
44
1.972.36
60 50
1.38
35
0.18
4.5
2.91
74
2.68
68
0.22
5.5
A26
3.54
90
2.13
54
3.15
80
1.77
45
0.17
4.2
70
2.76
3.69
93.6
3.44
87.3
0.35
9
A45
0.24
6.2
3.62
92
4.33
110
3.23
82
3.54
90
3.94
100
4.71
119.5
4.45
113
0.39
10
Approximate dimensions
A/AE9 – A/AE/AF75, 4 pole
A/AE9 – A/AE16 — Contactor, 4 pole
A/AE26 — Contactor, 4 pole
A/AE/AF45 – A/AE/AF75 — Contactor, 4 pole
00.00
00.00
Inches
[Millimeters]
Low Voltage Products & Systems 1.157
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Approximate dimensions
AL9 – AL40, 3 & 4 pole
AL9, AL12,, AL16 — Contactor, 3 & 4 pole
AL26 — Contactor, 3 & 4 pole
AL30, AL40 — Contactor, 3 pole
00.00
00.00
Inches
[Millimeters]
1.158 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
MECH INTERLOCK D.C.
OPERATED
SIDE MOUNTED
AUXILIARY
A
SINGLE POLE
TOP MOUNTED
AUXILIARY
B C
FOUR POLE
TOP MOUNTED
AUXILIARY
ON-POSITION
LATCH
E
D
PNEUMATIC
TIMER
F
TYPE
A/AE9-16 IN
MM
A
2.20
56
B
3.96
100.5
C
4.21
107
D
5.71
145
E
5.00
127
F
A/AE26 IN
MM
2.20
56
4.72
119.8
4.97
126.3
6.47
164.3
5.76
146.3
A/AE30-40 IN
MM
2.20
56
5.30
134.5
5.55
141
7.05
179
6.34
161
A/AE/AF50-75 IN
MM
3.23
82
5.27
133.9
5.52
140.3
7.03
178.5
6.32
160.4
A/AE/AF45 IN
MM
4.09
104
5.73
145.5
5.98
152
7.48
190
6.77
172
A/AE/AF95-110 IN
MM
4.02
102
5.91
150
6.16
156.5
Approximate dimensions
Accessories for A/AE9 – A/AE/AF110
A/AE9 – A/AE40
A/AE/AF50 – A/AE/AF110
00.00
00.00
Inches
[Millimeters]
Low Voltage Products & Systems 1.159
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Approximate dimensions
A/AF145 – A/AF185
A/AF145 & A/AF185
A/AF145, A/AF185 with mechanical interlock
A/AF145, A/AF185 reversing
00.00
00.00
Inches
[Millimeters]
1.160 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Approximate dimensions
A/AF145 – A/AF300
A/AF145 – A/AE/AF95-110 mechanically interlocked
A/AF210, A/AF260, A/AF300
00.00
00.00
Inches
[Millimeters]
Low Voltage Products & Systems 1.161
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Approximate dimensions
A/AF210 – A/AF300
A/AF210, A/AF260, A/AF300 with mechanical interlock
A/AF210, A/AF145 with mechanical interlock
A/AF210, A/AF260, A/AF300 reversing +TA450
00.00
00.00
Inches
[Millimeters]
1.162 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
Approximate dimensions
AF400 – AF460
AF400, AF460
AF400, AF460 with mechanical interlock
00.00
00.00
Inches
[Millimeters]
Low Voltage Products & Systems 1.163
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Approximate dimensions
AF400 – AF750
AF580 – AF750
AF400, AF460 reversing
00.00
00.00
Inches
[Millimeters]
1.164 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
AF580 – AF750 with mechanical interlock
Approximate dimensions
AF580 – AF750
AF580 – AF750 reversing
00.00
00.00
Inches
[Millimeters]
Low Voltage Products & Systems 1.165
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Across the line
Contactors
Approximate dimensions
AF1250 – AF2050
AF1250 – AF2050
50 1.97"
72 2.83"
72 2.83"
210 8.27"
344 13.54"
313 12.32"
263 10.35"
72 2.83"
ø 7 0.28"
ø 7 0.28"
27 1.06" 210 8.27"
46.5
1.83"
8
0.31"
136 5.35"136 5.35"
80 136 5.35" ø9 0.35"
104
438 17.24"
132 5.2"
132 5.2"
3
0.12"
47
1.85"
10 0.39"
244 9.61"
3.15"
4.09"
40 1.57"
27
13 0.51"
30 1.18"
17 0.67"
10 0.39"
1.06"
AF1350, AF1650 AF2050
40
1.57"
ø13
0.51"
40 1.57"
17 0.67"
AF1250 AF1350 ... AF2050
00.00
00.00
Inches
[Millimeters]
1.166 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Across the line
Contactors
EK110-550
C
C2
C1
F1
E
T
T1
P
P1
PE
H
DG
H1
K1
F
B1
B
M6 M4
B
6.50
165
6.50
165
EK 110
EK 150
in
mm
in
mm
B1
5.35
136
5.35
136
C1
5.51
140
5.51
140
E
1,57
40
1.57
40
C
4.72
120
4.72
120
D
0.26
6.6
0.43
11
K1H1
6.14
156
6.77
172
F1
1.69
43
1.65
42
H
6.14
156
6.14
156
F
1.61
41
1.65
42
G
0.59
15
0.79
20
P P1 T
0.39
10
0.39
10
T1
0.16
4
0.16
4
0.30
7.5
0.39
10
6.08
154.5
6.08
154.5
4.03
102.3
4.03
102.3
7.91
201
7.91
201
EK 175
EK 210
in
mm
in
mm
6.93
176
6.93
176
5.51
140
5.51
140
0.59
15
0.59
15
6.30
160
6.30
160
0.43
11
0.43
11
7.80
198
7.80
198
2.64
67
2.64
67
6.14
156
6.14
156
1.77
45
1.77
45
0.79
20
0.79
20
0.39
10
0.39
10
0.20
5
0.20
5
0.39
10
0.39
10
6.77
172
6.77
172
4.20
106.7
4.20
106.7
10.63
270
10.63
270
EK 370
EK 550
in
mm
in
mm
9.61
244
9.61
244
7.87
200
7.87
200
1.57
40
1.57
40
8.66
220
8.66
220
0.43
11
0.43
11
10.71
272
10.71
272
2.76
70
2.76
70
8.78
223
8.78
223
2.64
67
2.64
67
0.98
25
0.98
25
0.91
23
0.91
23
0.24
6
0.24
6
0.49
12.5
0.49
12.5
8.88
225.5
8.88
225.5
5.49
139.5
5.49
139.5
EK 1000
Approximate dimensions
EK110 – EK550, 4 pole
1
Capacitive
switching
Low Voltage Products & Systems 1.167
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Capacitive switching
For applications up to 130 kVar
Capacitive switching
ABB offers 3 contactor types for capacitive switching:
UA…RA contactors for capacitor switching (UA16…RA to UA110…RA) with preinstalled damping resistors.
The insertion of damping resistors protects the contactor and the capacitor from the highest inrush currents.
UA contactors for capacitor switching (UA16 to UA110) Maximum permissible peak current î ≤ 100 times the
nominal rms current of the switched capacitor.
A and AF standard contactors Maximum permissible peak current î ≤ 30 times the nominal rms current of the
switched capacitor.
Please contact Technical Support for more information.
UA…RA description
These devices intended for capacitor switching can be used for installations in which the peak current far
exceeds 100 times nominal rms current. The contactors are delivered complete with their damping
resistors and must be used without additional inductances. The capacitors must be discharged
(maximum residual voltage at terminals ≤ 50 V) before being re-energized when the contactors are
making.
The UA…RA contactors are tted with a special front-mounted block, which ensures the serial insertion of 3
damping resistors into the circuit to limit the current peak on energization of the capacitor bank
Their connection also ensures capacitor precharging in order to limit the second current peak occurring upon
making of the main poles
The insertion of resistors allows to damp the highest current peak of the capacitor when switching on, whatever
its level.
Control circuit: AC operated
Add-on auxiliary contact blocks for side mounting and a wide range of accessories.
CE mark
UL le #E312527 (16…75), #E36588 (95…110)
CSA le #LR56745 (16…75), cULus (95…110)
UA description
UA contactors can be used for the switching of capacitor banks whose inrush current peaks are less
than or equal to 100 times nominal rms current. The capacitors must be discharged (maximum residual
voltage at terminals ≤ 50 V) before being re-energized when the contactors are making. These
contactors are of the block type design with:
Control circuit: AC operated
Add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
CE mark
UL le #E312527 (26…75), #E36588 (95…110)
CSA le #LR56745 (26…75), cULus (95…110)
1
Capacitive
switching
1.168 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Contactors for capacitive switching
AC-6b utilization category according to IEC 60947-4-1
Capacitor transient conditions
In Low Voltage industrial installations, capacitors are mainly used for reactive energy correction (raising the power factor). When these capacitors
are energized, overcurrents of high amplitude and high frequencies (3 to 15 kHz) occur during the transient period (1 to 2 ms).
The amplitude of these current peaks, also known as "inrush current peaks", depends on the following factors:
The network inductances.
The transformer power and short-circuit voltage.
The type of power factor correction.
There are 2 types of power factor correction: fixed or automatic.
Fixed power factor correction consists of inserting, in parallel on
the network, a capacitor bank whose total power is provided by the
assembly of capacitors of identical or different ratings.
The bank is energized by a contactor that simultaneously supplies all
the capacitors (a single step).
The inrush current peak, in the case of xed correction, can reach 30
times the nominal current of the capacitor bank.
Single-step capacitor bank scheme
Use the A/AF... contactor ranges.
An automatic power factor correction system, on the other hand,
consists of several capacitor banks of identical or different ratings
(several steps), energized separately according to the value of the
power factor to be corrected.
An electronic device automatically determines the power of the
steps to be energized and activates the relevant contactors.
The inrush current peak, in the case of automatic correction, de-
pends on the power of the steps already on duty, and can reach 100
times the nominal current of the step to be energized.
Multi-step capacitor bank scheme
Use the UA... or UA..RA contactor ranges.
Steady state condition data
The presence of harmonics and the network's voltage tolerance lead to a current, estimated to be 1.3 times the nominal current In of the capaci-
tor, permanently circulating in the circuit.
Taking into account the manufacturing tolerances, the exact power of a capacitor can reach 1.15 times its nominal power.
Standard IEC 60831-1 Edition 2002 species that the capacitor must therefore have a maximum thermal current IT of:
IT = 1.3 x 1.15 x In = 1.5 x In
Consequences for the contactors
To avoid malfunctions (welding of main poles, abnormal temperature rise, etc.), contactors for capacitor bank switching must be sized to with-
stand:
A permanent current that can reach 1.5 times the nominal current of the capacitor bank.
The short but high peak current on pole closing (maximum permissible peak current Î ).
Contactor selection tool for capacitor switching
In a given application, if the user does not know the value of the inrush current peak,
this value can be approximately calculated using the formulas given on the pages
"Calculation and dimensioning".
Alternatively by the CAPCAL selection tool, available on the ABB Website:
www.abb.com/lowvoltage
right hand side menu
search: "Online product selection tools"
select: "Contactors: AC-6b capacitor switching"
This program allows the calculation of these peaks and gives the references of the
ABB contactors according to the installation specications. This calculation is valid for
one or several capacitor banks.
1
Capacitive
switching
Low Voltage Products & Systems 1.169
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
UA, UA...RA 3 pole
For capacitive switching applications up to 130 kVar
AC operated coils
Electrical ratings Capacitive switching
IEC/EN 60947-1
IEC/EN 60947-4-1
UL 508/60947-4-1A
CSA C22.2 No.14, 60947-4-1-07 Standard
auxiliary
contacts
Catalog
number
Rated operational power AC-6b,
three phase, 50 Hz, 40°C (kVar) AC capacitive switching ratings
230…
240V
400…
415V 440V 500…
550V 690V
Power, three phase, 60 Hz (kVar)
220…
240V
440…
480V
550…
600V NO NC
UA…RA – rated for capacitors with peak (inrush) current î > 100 times the rms current (unlimited peak current)
8 12.5 15 18 22 8 16 20 1- UA16-30-10-RAΔ
12.5 22 24 30 35 11 22 27 1- UA26-30-10-RAΔ
16 30 32 34 45 14 28 35 1- UA30-30-10-RAΔ
25 40 50 55 72 25 50 62 - - UA50-30-00-RAΔ
1 1 UA50-30-11-RAΔ
30 50 55 65 80 27.5 55 70 - - UA63-30-00-RAΔ
1 1 UA63-30-11-RAΔ
35 60 65 75 100 32 64 80 - - UA75-30-00-RAΔ
1 1 UA75-30-11-RAΔ
40 70 75 85 120 40 80 100 - - UA95-30-00-RAΔ
1 1 UA95-30-11-RAΔ
45 80 85 95 130 45 95 120 - - UA110-30-00-RAΔ
1UA110-30-11-RAΔ
UA – rated for capacitors with peak (inrush) current î ≤ 100 times the rms current (see technical data for values)
7.5 12.5 13.7 15.5 21.5 IEC/EN applications only – use UA…RA type 1- UA16-30-10-Δ
12 20 22 22 30 12.5 25 30 1- UA26-30-10-Δ
16 27.5 30 34 45 16 32 40 1- UA30-30-10-Δ
20 33 36 40 55 20 40 50 - - UA50-30-00-Δ
1 1 UA50-30-11-Δ
25 45 50 50 70 IEC/EN applications only – use UA…RA type - - UA63-30-00-Δ
1 1 UA63-30-11-Δ
30 50 55 62 75 27.5 55 70 - - UA75-30-00-Δ
1 1 UA75-30-11-Δ
35 65 65 70 80 35 70 75 - - UA95-30-00-Δ
1 1 UA95-30-11-Δ
40 75 75 80 90 40 80 85 - - UA110-30-00-Δ
1UA110-30-11-Δ
UA30...40/..RA UA50...75 UA95...110/..RA
Coil voltage selection chart (Δ)
Rated control circuit
voltage Uc
UA16…
UA110
UA16RA…
UA110RA
24V 50/60 81 81
48V 50/60 83 83
110V/50, 110…120V/60 84 84
230…240V/60 80 80
400…415V/50, 480V/60 51 51
500V/50, 600V/60 55 55
R
1
Capacitive
switching
1.170 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Main pole - Utilization characteristics according to IEC
Contactor types AC operated UA16..RA UA26..RA UA30..RA UA50..RA UA63..RA UA75..RA UA95..RA UA110..RA
Standards
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage Ue max.
690 V
Rated frequency (without derating)
50 / 60 Hz
AC-6b Utilization category
Rated operational power AC-6b
For air temperature close
to contactor
θ ≤ 40 °C
230-240 V 8 kvar 12.5 kvar 16 kvar 25 kvar 30 kvar 35 kvar 40 kvar 45 kvar
400-415 V 12.5 kvar 22 kvar 30 kvar 40 kvar 50 kvar 60 kvar 70 kvar 80 kvar
440 V 15 kvar 24 kvar 32 kvar 50 kvar 55 kvar 65 kvar 75 kvar 85 kvar
500-550 V 18 kvar 30 kvar 34 kvar 55 kvar 65 kvar 75 kvar 85 kvar 95 kvar
690 V 22 kvar 35 kvar 45 kvar 72 kvar 80 kvar 100 kvar 120 kvar 130 kvar
θ ≤ 55 °C
230-240 V 7.5 kvar 11.5 kvar 16 kvar 24 kvar 27 kvar 30 kvar 35 kvar 40 kvar
400-415 V 12.5 kvar 20 kvar 27.5 kvar 40 kvar 45 kvar 50 kvar 60 kvar 70 kvar
440 V 13 kvar 20 kvar 30 kvar 43 kvar 48 kvar 53 kvar 65 kvar 75 kvar
Multi-step capacitor
bank scheme
500-550 V 16 kvar 25 kvar 34 kvar 50 kvar 60 kvar 65 kvar 75 kvar 82 kvar
690 V 21 kvar 31 kvar 45 kvar 65 kvar 75 kvar 80 kvar 105 kvar 110 kvar
θ ≤ 70 °C
230-240 V 6 kvar 9 kvar 11 kvar 20 kvar 23 kvar 25 kvar 30 kvar 35 kvar
400-415 V 10 kvar 15.5 kvar 19.5 kvar 35 kvar 39 kvar 41 kvar 53 kvar 60 kvar
440 V 11 kvar 17 kvar 20.5 kvar 37 kvar 42.5 kvar 45 kvar 58 kvar 70 kvar
500-550 V 12.5 kvar 20 kvar 25 kvar 46 kvar 50 kvar 55 kvar 70 kvar 78 kvar
690 V 17 kvar 26 kvar 32 kvar 60 kvar 65 kvar 70 kvar 85 kvar 100 kvar
Max. permissible peak current Î
Unlimited
Short-circuit protection device for contactors
gG type fuse (1) 80 A 125 A 200 A 250 A
Max. electrical switching frequency
240 cycles/h
Electrical durability AC-6b
Ue ≤ 440V 250 000 operating cycles
500 V ≤ Ue ≤ 690V 100 000 operating cycles
(1) The fuse ratings given represent the maximum ratings ensuring type 1 coordination according to the denition of standard IEC 60947-4-1.
Main pole - Utilization characteristics according to UL / CSA
Contactor types
AC operated
UA16..RA UA26..RA UA30..RA UA50..RA UA63..RA UA75..RA UA95..RA UA110..RA
Power - 60Hz
For air temperature close
to contactor
θ ≤ 40 °C
240 V 8 kvar 11 kvar 14 kvar 25 kvar 27.5 kvar 32 kvar 40 kvar 45 kvar
480 V 16 kvar 22 kvar 28 kvar 50 kvar 55 kvar 64 kvar 80 kvar 95 kvar
600 V 20 kvar 27 kvar 35 kvar 62 kvar 70 kvar 80 kvar 100 kvar 120 kvar
Max. permissible peak Current Î
Unlimited
Operating principle
The front-mounted block mechanism of the UA..RA contactors ensures:
early making of the auxiliary "PA" poles with respect to the main "PP" poles
automatic return to the open position of the auxiliary "PA" poles after the main poles are closed.
When the coil is energized, the early making auxiliary poles connect the capacitor to the network via the set of 3 resistors. The damping resistors
attenuate the rst current peak and the second inrush current when the main contacts begin to make. Once the main poles are in the closed posi-
tion, the auxiliary poles automatically break.
When the coil is de-energized, the main poles break ensuring the breaking of the capacitor bank.
The contactor can then begin a new cycle.
The insertion of resistors allows to damp the high-
est current peak of the capacitor when switching
on, whatever its level.
A1
A2
PA
R
PP
R
C
Coil voltage
Uc
Aux. poles
PA
Main poles
PP
Total
closing time
UA16/RA...UA110/RA 3-pole contactors
Unlimited peak current Î
IEC & UL/CSA Technical data
1
Capacitive
switching
Low Voltage Products & Systems 1.171
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Connecting characteristics
Contactor types AC operated UA16..RA UA26..RA UA30..RA
UA50..RA UA95..RA
UA63..RA UA110..RA
UA75..RA
Connection capacity (min. ... max.)
Main conductors (poles)
Rigid Solid (≤ 4 mm²) 1 x 1...4 mm² 1.5...6 mm² 2.5...16 mm² 6...50 mm² 10...95 mm²
Stranded (≥ 6 mm²) 2 x - -
2.5...16 + 2.5...6 mm² 6…25 + 6…16 mm²
6...35 mm²
Flexible with ferrule 1 x 0.75...2.5 mm² 1.5...4 mm² 2.5...10 mm² 6...35 mm² 10...70 mm²
2 x - -
2.5...10 + 2.5...4 mm² 6...16 + 6...10 mm²
6...35 mm²
L
l
Bars or lugs L ≤ 7.7mm 10 mm ---
l > 3.7 mm 4.2 mm ---
Connection capacity acc. to UL/CSA 1 or 2 x AWG 18...10 AWG 12...8 AWG 8...4 AWG 8...1 AWG 6...2/0
Tightening torque Recommended 1 Nm / 9 Ib.in 1.7 Nm / 15 Ib.in 2.3 Nm / 20 Ib.in 4 Nm / 35 Ib.in 8 Nm / 53 Ib.in
Max. 1.2 Nm 2.2 Nm 2.6 Nm 4.5 Nm 9 Nm
Auxiliary conductors
(built-in auxiliary terminals + coil terminals)
Rigid solid 1 x 1...4 mm² 0.75…2.5 mm²
2 x 1...4 mm² 0.75…2.5 mm²
Flexible with ferrule 1 x 0.75...2.5 mm² 1…2.5 mm² 0.75…2.5 mm²
2 x 0.75...2.5 mm²
L
l
Lugs Coil terminals L ≤ 8 mm
l > 3.7 mm
Built-in auxiliary L ≤ 7.7 mm 10 mm 8 mm - -
terminals l > 3.7 mm 4.2 mm 3.7 mm - -
Connection capacity acc. to UL/CSA 1 or 2 x AWG 18...14
Tightening torque
Coil terminals Recommended 1 Nm / 9 Ib.in
Max. 1.2 Nm
Built-in auxiliary terminals Recommended 1 Nm / 9 Ib.in
Max. 1.2 Nm
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Main terminals IP20 IP10
Coil terminals IP20
Built-in auxiliary terminals IP20 - -
Screw terminals
Delivered in open position, screws of unused terminals must be tightened
Main terminals M 3.5 M 4 M 5 M6 M8
Screwdriver type Flat Ø 5.5 / Pozidriv 2 Flat Ø 6.5 / Pozidriv 2 Hexagon socket
(s = 4 mm)
Coil terminals M 3.5
Screwdriver type Flat Ø 5.5 / Pozidriv 2
Built-in auxiliary terminals
M 3.5 M 4 M 3.5 - -
Screwdriver type Flat Ø 5.5 / Pozidriv 2 - -
Other technical characteristics are the same as those of standard A contactors.
UA16/RA...UA110/RA 3-pole contactors
Unlimited peak current Î
General technical data
1
Capacitive
switching
1.172 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Main pole - Utilization characteristics according to IEC
Contactor types AC operated UA16 UA26 UA30 UA50 UA63 UA75 UA95 UA110
Standards
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1
Rated operational voltage Ue max.
690 V
Rated frequency (without derating)
50 / 60 Hz
AC-6b Utilization category
Rated operational power AC-6b (1)
For air temperature close
to contactor
θ ≤ 40 °C
230-240 V 7.5 kvar 12 kvar 16 kvar 20 kvar 25 kvar 30 kvar 35 kvar 40 kvar
400-415 V 12.5 kvar 20 kvar 27.5 kvar 33 kvar 45 kvar 50 kvar 65 kvar 75 kvar
440 V 13.7 kvar 22 kvar 30 kvar 36 kvar 50 kvar 55 kvar 65 kvar 75 kvar
500-550 V 15.5 kvar 22 kvar 34 kvar 40 kvar 50 kvar 62 kvar 70 kvar 80 kvar
690 V 21.5 kvar 30 kvar 45 kvar 55 kvar 70 kvar 75 kvar 80 kvar 90 kvar
θ ≤ 55 °C
230-240 V 6.7 kvar 11 kvar 16 kvar 20 kvar 25 kvar 30 kvar 35 kvar 40 kvar
400-415 V 11.7 kvar 18.5 kvar 27.5 kvar 33 kvar 43 kvar 50 kvar 65 kvar 70 kvar
440 V 13 kvar 20 kvar 30 kvar 36 kvar 48 kvar 53 kvar 65 kvar 75 kvar
Multi-step capacitor
bank scheme
500-550 V 14.7 kvar 22 kvar 34 kvar 40 kvar 50 kvar 62 kvar 70 kvar 80 kvar
690 V 20 kvar 30 kvar 45 kvar 55 kvar 70 kvar 75 kvar 80 kvar 90 kvar
θ ≤ 70 °C
230-240 V 6 kvar 8.5 kvar 11 kvar 19 kvar 21 kvar 22 kvar 30 kvar 35 kvar
400-415 V 10 kvar 14.5 kvar 19 kvar 32 kvar 37 kvar 39 kvar 55 kvar 65 kvar
440 V 11 kvar 16 kvar 20 kvar 35 kvar 41 kvar 43 kvar 55 kvar 70 kvar
500-550 V 12.5 kvar 19.5 kvar 23.5 kvar 40 kvar 45 kvar 47.5 kvar 60 kvar 75 kvar
690 V 17 kvar 25 kvar 32 kvar 52 kvar 60 kvar 65 kvar 70 kvar 85 kvar
Max. permissible peak current Î
Ue ≤ 500 V 1.8 kA 3 kA 3.5 kA 5 kA 6.5 kA 7.5 kA 9.3 kA 10.5 kA
Ue > 500 V 1.6 kA 2.7 kA 3.1 kA 4.5 kA 5.8 kA 6.75 kA 8 kA 9 kA
Short-circuit protection device for contactors
gG type fuse sized 1.5…1.8 In of the capacitor
Max. electrical switching frequency
240 cycles/h
Electrical durability AC-6b
Ue ≤ 690V 100 000 operating cycles
(1) For 220 V and 380 V, multiply by 0.9 the rated values at 230 V and 400 V respectively.
Example: 50 kvar / 400 V corresponding to 0.9 x 50 = 45 kvar/380 V.
If, in an application, the current peak is greater than the maximum peak current Î specied in the tables above, select a higher rating, refer to the UA..RA contactors, or add induct-
ances. (see application guide "Contactors for capacitor switching").
Main pole - Utilization characteristics according to UL / CSA
Contactor types
AC operated
UA16 UA26 UA30 UA50 UA63 UA75 UA95 UA110
Power - 60Hz
For air temperature close
to contactor
θ ≤ 40 °C
240 V -12.5 kvar 16 kvar 20 kvar -27.5 kvar 35 kvar 40 kvar
480 V -25 kvar 32 kvar 40 kvar -55 kvar 70 kvar 80 kvar
600 V -30 kvar 40 kvar 50 kvar -70 kvar 75 kvar 85 kvar
If, in an application, the current peak is greater than the maximum peak current Î specied in the tables above, select a higher rating, refer to the UA..RA contactors, or add induct-
ances. (see application guide "Contactors for capacitor switching").
UA16...UA110 3-pole contactors
Peak current Î 100 times the rms current
IEC & UL/CSA technical data
1
Capacitive
switching
Low Voltage Products & Systems 1.173
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Connecting characteristics
Contactor types AC operated UA16 UA26 UA30
UA50 UA95
UA63 UA110
UA75
Connection capacity (min. ... max.)
Main conductors (poles)
Rigid Solid (≤ 4 mm²) 1 x 1...4 mm² 1.5...6 mm² 2.5...16 mm² 6...50 mm² 10...95 mm²
Stranded (≥ 6 mm²) 2 x 1...4 mm² 1.5...6 mm² 2.5...16 mm² 6...25 mm² 6...35 mm²
Flexible with ferrule 1 x 0.75...2.5 mm² 0.75...4 mm² 2.5...10 mm² 6...35 mm² 10...70 mm²
2 x 0.75...2.5 mm² 0.75...4 mm² 2.5...10 mm² 6...16 mm² 6...35 mm²
L
l
Bars or lugs L ≤ 7.7mm 10 mm ---
l > 3.7 mm 4.2 mm ---
Connection capacity acc. to UL/CSA 1 or 2 x AWG 18...10 AWG 12...8 AWG 8...4 AWG 8...1 AWG 6...2/0
Tightening torque Recommended 1 Nm / 9 Ib.in 1.7 Nm / 15 Ib.in 2.3 Nm / 20 Ib.in 4 Nm / 35 Ib.in 8 Nm / 71 Ib.in
Max. 1.2 Nm 2.2 Nm 2.6 Nm 4.5 Nm 9 Nm
Auxiliary conductors
(built-in auxiliary terminals + coil terminals)
Rigid solid 1 x 1...4 mm² 0.75…2.5 mm²
2 x 1...4 mm² 0.75…2.5 mm²
Flexible with ferrule 1 x 0.75...2.5 mm² 1…2.5 mm² 0.75…2.5 mm²
2 x 0.75...2.5 mm²
L
l
Lugs Coil terminals L ≤ 8 mm
l > 3.7 mm
Built-in auxiliary L ≤ 7.7 mm 10 mm 8 mm - -
terminals l > 3.7 mm 4.2 mm 3.7 mm - -
Connection capacity acc. to UL/CSA AWG 18...14
Tightening torque
Coil terminals Recommended 1 Nm / 9 Ib.in
Max. 1.2 Nm
Built-in auxiliary terminals Recommended 1 Nm / 9 Ib.in
Max. 1.2 Nm
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Main terminals IP20 IP10
Coil terminals IP20
Built-in auxiliary terminals IP20 - -
Screw terminals
Delivered in open position, screws of unused terminals must be tightened
Main terminals M3.5 M4 M5 M6 M8
Screwdriver type Flat Ø 5.5 / Pozidriv 2 Flat Ø 6.5 / Pozidriv 2 Hexagon socket
(s = 4mm)
Coil terminals M3.5
Screwdriver type Flat Ø 5.5 / Pozidriv 2
Built-in auxiliary terminals
M3.5 M4 M3.5 - -
Screwdriver type Flat Ø 5.5 / Pozidriv 2 - -
Other technical characteristics are the same as those of standard A contactors.
UA16 … UA110 3-pole contactors
Peak current Î 100 times the rms current
General technical data
1
Capacitive
switching
1.174 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Approximate dimensions
Main dimensions mm, inches
68 2.68"
47 1.85"
107 4.21"
5.5 0.22"
4 0.16"
35 mm
EN/IEC 60715
+10 +.394"
120 4.72"
44 1.73"
74 2.91"
UA16..RA
47 1.85"
87.3 3.44"
126.3 4.97"
9 0.35"
4 0.16"
35 mm
EN/IEC 60715
+10
120 4.72" +.394"
54 2.13"
90 3.54"
UA26..RA
102 4.02"
9 0.35"
4 0.16"
47 1.85"
130 5.12"
+10 +.394"
141 5.55"
35 mm
EN/IEC 60715
54 2.13"
90 3.54"
UA30/40..RA
6 0.24"
10 0.39"
4 0.16"
75 mm
EN/IEC 60715
35 mm x 15
EN/IEC 60715
140.4 5.53"
47 1.85"
+10 +10"
150 5.91"
101.5 4"
70 2.76"
110 4.33"
114 4.49"
UA50..RA, UA63..RA, UA75..RA
UA50/75...RA
47 1.85"
+10 +10"
170 6.69"
114.4 4.5"
6 0.24"
75 mm
EN/IEC 60715
10 0.39"
155.6 6.13"
155.3 6.11"
90 3.54"
148 5.83"
UA95/110...RA
Note: dimensions for UA... contactor identical to UA...RA types less front-mount dampening resistors.
1
Definite purpose
contactors
Low Voltage Products & Systems 1.175
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Definite purpose contactors
For applications up to 90 FLA
Applications
Type DP contactors provide high performance with
exibility and reliability, designed to match numerous
applications including:
Motors
Power supplies
Food service equipment
Compressors
Business machines
Resistive heating
Air conditioning
Refrigeration equipment
Welding
Agency approvals
• UL 508 Guide No. NLDX2, File # E224401
• CSA C22.2 No. 221260 (1456104)
Class 3211 04 / 3211 84
• CE/Semko Certied, EN60947-4-1:2001
Features
• Available as:
– 20A, 25A,1, 2 or 3 pole
– 30A, 1, 2, 3 or 4 pole
– 40A, 2, 3 or 4 pole
– 50-90A, 3 pole
• Industry standard mounting plate provides easily
accessible mounting holes
• Coil terminals are provided with #6-32 screws and
(1) .250 quick connect or dual .250 quickconnect
terminals
• Exclusive hex, slotted, phillips #10-32 terminal
screws for main terminals
• Coil is class B (130° C) insulation system with a wide
range of voltages and 50/60 Hz ratings
• Double E magnet assembly provides optimal
performance with reduced power consumption
• Snap-in auxiliary switch with 1 SPDT or 2 SPDT
contacts available as an option
• 1 N.O. & 1 N.C. auxiliary contact block with 600 VAC
rating available as an option
• Base assembly is made from high arc-resistant
polyesterplastic
Catalog number explanation
DP 30 C 3P - 1
Definite purpose
Frame size
20 = 20A
25 = 25A
30 = 30A
40 = 40A
50 = 50A
60 = 60A
75 = 75A
90 = 90A
Coil voltage
(See coil voltage selection chart)
Power poles
1P = 1 N.O.
2P = 2 N.O.
3P = 3 N.O.
4P = 4 N.O.
Contactor type
C = Non-reversing
Definite purpose
Contactors
1
Definite purpose
contactors
1.176 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
DP non-reversing 1, 2, 3 & 4 pole
For denite purpose applications up to 90 FLA
AC operated coils
DP20C1P… DP20C3P… DP40C4P
DP40C1P DP30C3P
1 1- & 2-pole devices rated per pole
2 DP20…DP30 intended for single phase resistive applications only above 277V
3 220…240V only
4 Max. 277V
5 Breaking all lines
6 Suitable at 208V
Electrical ratings Electrical ratings
AC denite purpose controller ratings AC
resistance
air heating,
per pole
(A)
AC motor ratings, breaking all lines (hp)
N.O.
power
poles
Catalog
number
Catalog
number
(bulk pack)
Bulk
qty.
Full
load
amperes
(FLA)
Locked rotor Amperes,
breaking all lines (LRA) 1Single phase Three phase
220…240 /
277V
440…
480V
550…
600V 600V 2110…
120V
220…
240V
220…
240V
440…
480V
550…
600V
20 120 100 80 30 - - - - -
1
DP20C1P-Δ DP20C1P-Δ/B
50
25 150 125 100 35 - - - - - DP25C1P-Δ DP25C1P-Δ/B
30 180 125 100 40 - - - - - DP30C1P-Δ DP30C1P-Δ/B
40 240 160 120 50 4- - - - - DP40C1P-Δ DP40C1P-Δ/B
20 120 100 80 30 - - - - -
2
DP20C2P-Δ DP20C2P-Δ/B
50
25 150 125 100 35 - - - - - DP25C2P-Δ DP25C2P-Δ/B
30 180 125 100 40 - - - - - DP30C2P-Δ DP30C2P-Δ/B
40 240 160 120 50 4- - - - - DP40C2P-Δ DP40C2P-Δ/B
20 120 100 80 30 1.5 37.5 7.5 7.5
3
DP20C3P-Δ DP20C3P-Δ/B
25
25 150 125 100 35 2 5 7.5 15 20 DP25C3P-Δ DP25C3P-Δ/B
30 180 150 120 40 2 5 10 15 20 DP30C3P-Δ DP30C3P-Δ/B
40 240 200 160 50 537.5 10 20 25 DP40C3P-Δ DP40C3P-Δ/B
50 300 3250 200 65 3 7.5 6 15 625 25 DP50C3P-Δ - -
60 360 3300 240 75 5 10 6 25 630 30 DP60C3P-Δ - -
75 450 3375 300 90 5 15 25 640 40 DP75C3P-Δ - -
90 540 3450 360 120 7.5 20 30 650 50 DP90C3P-Δ - -
20 120 100 80 30 1.5 37.5 7.5 7.5
4
DP20C4P-Δ DP20C4P-Δ/B
25
25 150 125 100 35 2 5 7.5 15 20 DP25C4P-Δ DP25C4P-Δ/B
30 180 150 120 40 2 5 10 15 20 DP30C4P-Δ DP30C4P-Δ/B
40 240 200 160 50 537.5 10 20 25 DP40C4P-Δ DP40C4P-Δ/B
Note: 1-pole devices in 2-pole frame with shunt included.
Coil voltage selection chart (Δ)
Control circuit
voltage
Control circuit
voltage
24V 60 Hz F
120V/60 1
208/240V AC 2
277V AC C
480V AC 4
575/600V 60 Hz 6
DP ratings for AF & AS/ASL
ABB has additionally performed denite purpose testing for air conditioning
(h.r.c.) applications with AF and AS/ASL series contactors. Please contact
Technical Support regarding the use of these devices for applications
20…900 FLA, 80…5600 LRA.
1
Definite purpose
contactors
Low Voltage Products & Systems 1.177
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Accessories
Auxiliary contact blocks
Description DP20 to DP40, 3 pole and 4 pole
congurations DP50 to DP60 DP75 to DP90"
Form C SPDT CADP40-10 CADP40-10 -
Double Form C SPDT CADP40-20 CADP40-20 -
Form Z SPDT (1NO & 1NC)** CADP40-11 CADP40-11 CADP90-11
** Must be the same polarity on both poles. For a complete description on contact types, please refer to page 1.78.
Mechanical interlock
Application Catalog number
DP30C3P-* VMDP-1
DP40C3P-* VMDP-1
Protective cover
Application Catalog number
DP20C2P-* DP-2-AC
DP25C2P-* DP-2-AC
DP30C2P-* DP-2-AC
Din-rail mounting bracket
Application Catalog number
DP20C1P-* DP/DIN1-2
DP25C1P-* DP/DIN1-2
DP30C1P-* DP/DIN1-2
DP20C2P-* DP/DIN1-2
DP25C2P-* DP/DIN1-2
DP30C2P-* DP/DIN1-2
Note: Replace “*” with appropriate coil voltage as per
previous page
1
Definite purpose
contactors
1.178 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Technical data
DP20 to DP40, 1 & 2 poles
Coil technical data DP20 to DP30, 1 pole DP20 to DP40, 2 poles
Nominal coil voltage 24 120 208/240 277 24 120 208/240 277
Maximum pickup volts 18 88 177 221 18 88 177 221
Drop out volts range 6 - 15 20 - 70 40 - 140 50 - 165 6 - 15 20 - 70 40 - 170 50 - 165
Nominal inrush VA 50 Hz 31 31 31 31 33 33 33 33
Nominal inrush VA 60 Hz 28 28 28 28 30 30 30 30
Nominal closed VA 50 Hz 6 6 6 6 8 8 8 8
Nominal closed VA 60 Hz 55556.5 6.5 6.5 6.5
Nominal coil resistance Ohms 18 420 1800 2500 11 237 1000 1600
Other specifications
Specications DP20 to DP30, 1 and 2 poles DP40, 2 poles
Line and load terminals # 10 - 32 screw Box lug
Wire size AWG (min - max) 16 - 8 14 - 4 Cu/Al
Tightening torque (recommended) 25 in. lbs. 40 in. lbs.
Coil terminals Dual .250” QC Dual .250” QC
Power Terminals 1 Pole: Quad .250” QC Quad
2 Pole: Dual or Quad .250” QC Dual or quad
Covers Optional Standard
Insulation System 130o C class B 130o C class B
DP20 to DP60, 3 poles
Coil technical data DP20 to DP40, 3 poles DP50 to DP60, 3 poles
Nominal coil voltage 24 120 208/240 277 480 24 120 208/240 277 480
Maximum pickup volts 18 88 177 220 384 18 88 177 220 374
Drop out volts range 6 - 15 20 - 70 40 - 140 50 - 140 150 - 270 6 - 15 20 - 70 40 - 140 50 - 185 150 - 286
Nominal inrush VA 50 Hz 65 65 65 65 65 62 62 62 62 62
Nominal inrush VA 60 Hz 60 60 60 60 60 59 59 59 59 59
Nominal closed VA 50 Hz 7.5 7.5 7.5 7.5 7.5 9 9 9 9 9
Nominal closed VA 60 Hz 6 6 6 6 6 7767 7
Nominal coil resistance Ohms 7180 720 900 1320 2.4 150 600 750 1452
Other specifications
Specications DP20 to DP30, 3 poles DP40, 3 poles DP50 to DP60, 3 poles
Line and load terminals # 10 - 32 screw 1Box lug 1Box lug 1
Wire size AWG (min - max) 16 - 8 2 14 - 4 Cu/Al 14 - 2 Cu/Al
Tightening torque (recommended) 22 in. lbs. 40 in. lbs. 50 in. lbs.
Quick connects (power terminals) Dual .250 QC Dual .250 QC Dual .250 QC
Coil terminals Dual .250 QC 2Dual .250 QC 2# 6 - 32 screw & dual .250 QC 2
Covers Standard Standard Standard
Insulation system 130o C class B 130o C class B 130o C class B
Contact rating of SPDT auxiliary contacts
Voltage Current rating
125 VAC 10 A, 1/3 HP
120 VAC 4 A on lamp load
250 VAC 10 A, 1/3 HP
125 VDC 0.5 A
250 VDC 0.25 A
Contact rating of 1 N.O. & 1 N.C. auxiliary contacts
120V 240V 480V 600V
Break (A) 3.0 1.5 0.75 0.6
Make (A) 30 15 7.5 6
Continuous (A) 10 10 10 10
1 See diagram on page 1.183 for approximate dimensions and description.
2 Stranding must be split for # 8 wire.
1
Definite purpose
contactors
Low Voltage Products & Systems 1.179
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Technical data
DP20 to DP40, 4 poles
Coil technical data DP20 to DP40, 4 poles
Nominal coil voltage 24 120 208/240 277 480
Maximum pickup volts 18 88 177 220 384
Drop out volts range 6 - 15 20 - 70 40 - 140 65 - 185 150 - 270
Nominal inrush VA 50 Hz 62 62 62 62 62
Nominal inrush VA 60 Hz 59 59 59 59 59
Nominal closed VA 50 Hz 99999
Nominal closed VA 60 Hz 77676
Nominal coil resistance Ohms 6 148 600 750 2100
Other specifications
Specications DP20 to DP30, 4 poles DP40, 4 poles
Line and load terminals # 10 - 32 screw 1Box lug 1
Wire size AWG (min - max) 16 - 8 2 14 - 4 Cu/Al
Tightening torque (recommended) 22 in. lbs. 40 in. lbs.
Quick connects (power terminals) Dual .250 QC Dual .250 QC
Coil terminals Dual .250 QC 2Dual .250 QC 2
Covers Standard Standard
Insulation system 130o C class B 130o C class B
1 See diagram on page 1.183 for approximate dimensions and description.
2 Stranding must be split for # 8 wire.
DP75 to DP90, 3 poles
Coil technical data DP75 to DP90, 3 poles
Nominal coil voltage 24 120 208/240 277 480
Maximum pickup volts 18 88 177 220 384
Drop out volts range 6-15 20-70 40-10 65-185 150 - 270
Nominal inrush VA 50 Hz 285 285 285 285 62
Nominal inrush VA 60 Hz 240 240 240 240 59
Nominal closed VA 50 Hz 42 42 42 42 9
Nominal closed VA 60 Hz 27 27 27 27 6
Nominal coil resistance Ohms 0.65 16 64 85 2100
Other specifications
Specications DP75 to DP90, 3 poles
Line and load terminals Box lug (1)
Wire size AWG (min-max) 14-1 Cu/Al
Tightening torque (recommended) 50 in. lbs
Quick connects (power terminals) Dual .250" QC
Coil terminals Dual .250" QC
Covers Standard
Insulation system 130°C Class B
1
Definite purpose
contactors
1.180 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
DP20 to DP30, 1 pole
DP20 to DP30, 2 poles
DP20 to DP30, 3 poles
Approximate dimensions
1
Definite purpose
contactors
Low Voltage Products & Systems 1.181
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
DP30, 4 poles
DP40, 2 poles
DP40, 3 poles
2.75
Approximate dimensions
1
Definite purpose
contactors
1.182 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
DP40, 4 poles
DP50 to DP60, 3 poles
Approximate dimensions
4.05
3.75
3.75
.20
2.90
2.50
4.62
5.00
DP75 to DP90, 3 poles
1
Definite purpose
contactors
Low Voltage Products & Systems 1.183
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Standard on DP 20 to DP30 Standard on DP40 Standard on DP 60 Standard on DP 90
Approximate dimensions
Terminals
1
Definite purpose
contactors
1.184 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Notes
Dynamic braking
DC Drive
1
Low Voltage Products & Systems 1.185
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Dynamic braking / DC drive
Up to 960 A, 600V DC
Description
Drive contactors are specically designed for use with solid state D.C. adjustable speed drive systems. In drive
applications, the contactor is not required to make or break the load during normal operation. The N.C. contact
is used for dynamic braking applications. EHDB contactors are provided less terminal lugs. Additionally, EHDB
contactors carry elevator service ratings.
Type DA
60 A continuous
160…300V DC dynamic braking
Double-break contacts
Identical H/W dimensions to standard A-line
DIN rail and panel mount
cULus Recognized – File # E312527
Motor Controllers, Magnetic – Component (NLDX2,
NLDX8)
Dynamic braking / DC drive
Type EHDB
220..960 A continuous
600V DC dynamic braking
Double-break contacts with magnetic arc chutes
Elevator service rated
Replacement parts available
cULus Recognized – File # E36588
Motor Controllers, Magnetic – Component (NLDX2,
NLDX8)
Dynamic braking
DC Drive
1
1.186 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
EHDB, DA75 2- & 3-pole, non-reversing
For DC drive applications up to 960 A
AC or DC operated coils
DA75-21A-11-84 EHDB280C-1L EHDB520C2P-1L
Electrical ratings 2 & 3 pole non-reversing
DC continuous
current (A)
N.O. power
poles
N.C. dynamic
braking pole Standard
auxiliary contacts
Catalog number
2-pole
2 N.O.
Catalog number
3-pole
2 N.O. + 1 N.C.
DC make/break DC make DC break
500V 500V 500V 150V 300V N.O. N.C.
Type DA75, 2 & 3 pole
60 60 ---1 1 DA75-20-11-Δ -
60 60 90 55 - 2 1- DA75-21-21-Δ
60 60 90 -55 1 1 - DA75-21A-11-Δ
Note: DA75 2 & 3 pole contactors are equipped with polarity-dependent N.O. contacts.
DC continuous
current (A)
N.O. power
poles
N.C. dynamic
braking pole Standard
auxiliary contacts
Catalog number
2-pole
2 N.O.
Catalog number
3-pole
2 N.O. + 1 N.C.
DC make/break DC make DC break
600V 600V 600V 300V N.O. N.C.
Type EHDB, 2 & 3 pole
220 333 450 285 1 1 EHDB220C2P-ΔL EHDB220C-ΔL
280 425 565 363 1 1 EHDB280C2P-ΔL EHDB280C-ΔL
360 556 728 472 1 1 EHDB360C2P-ΔL EHDB360C-ΔL
520 780 1040 680 1 1 EHDB520C2P-ΔL EHDB520C-ΔL
650 975 1300 850 1 1 EHDB650C2P-ΔL EHDB650C-ΔL
800 1200 1600 1050 1 1 EHDB800C2P-ΔL EHDB800C-ΔL
960 1440 1920 1250 1 1 EHDB960C2P-ΔL EHDB960C-ΔL
Note: The polarity of the N.C. dynamic braking pole must be respected; 5/L2 (+) – 6/T2 (-).
Coil voltage selection chart (Δ)
Rated control circuit
voltage Uc
DA75 EHDB220...
EHDB360
EHDB520...
EHDB960
24V/50 81 N -
24V/60 81 F -
24V DC - Y Y
48V/60 83 G-
48V DC - W W
110/50, 110…120/60 84 1 1
125V DC - Q Q
208V/60 34 B B
220V DC - R R
240V/60 80 2 2
277V/60 42 C C
480V/60 51 4 4
600V/60 55 6 6
Example:
24V DC input voltage: EHDB280C-YL
120V AC input voltage: DA75-21-21-84
Dynamic braking
DC Drive
1
Low Voltage Products & Systems 1.187
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
EHDB, DA75 2 & 3 pole, mechanically-interlocked
DC drive applications up to 960 A
AC or DC operated coils
EHDB280M-1L
Electrical ratings 2 & 3 pole mechanically interlocked
DC continuous
current (A)
N.O. power
poles
N.C. dynamic
braking pole Standard
auxiliary contacts
Catalog number
2-pole
2 N.O.
Catalog number
3-pole
2 N.O. + 1 N.C.
DC make/break DC make DC break
500V 500V 500V 150V 300V N.O. N.C.
Type DA75, 2 & 3 pole
60 60 ---1 1 DA75M-20-11-Δ -
60 60 90 -55 1 1 - DA75M-21A-11-Δ
Note: DA75 2 & 3 pole contactors are equipped with polarity-dependent N.O. contacts.
DC continuous
current (A)
N.O. power
poles
N.C. dynamic
braking pole Standard
auxiliary contacts
Catalog number
2-pole
2 N.O.
Catalog number
3-pole
2 N.O. + 1 N.C.
DC make/break DC make DC break
600V 600V 600V 300V N.O. N.C.
Type EHDB, 2 & 3 pole
220 333 450 285 1 1 EHDB220M2P-ΔL EHDB220M-ΔL
280 425 565 363 1 1 EHDB280M2P-ΔL EHDB280M-ΔL
360 556 728 472 1 1 EHDB360M2P-ΔL EHDB360M-ΔL
520 780 1040 680 1 1 EHDB520M2P-ΔL EHDB520M-ΔL
650 975 1300 850 1 1 EHDB650M2P-ΔL EHDB650M-ΔL
800 1200 1600 1050 1 1 EHDB800M2P-ΔL EHDB800M-ΔL
960 1440 1920 1250 1 1 EHDB960M2P-ΔL EHDB960M-ΔL
Note: The polarity of the N.C. dynamic braking pole must be respected; 5/L2 (+) – 6/T2 (-).
Coil voltage selection chart (Δ)
Rated control circuit
voltage Uc
DA75 EHDB220...
EHDB360
EHDB520...
EHDB960
24V/50 81 N -
24V/60 81 F -
24V DC - Y Y
48V/60 83 G-
48V DC - W W
110/50, 110…120/60 84 1 1
125V DC - Q Q
208V/60 34 B B
220V DC - R R
240V/60 80 2 2
277V/60 42 C C
480V/60 51 4 4
600V/60 55 6 6
Example:
24V DC input voltage: EHDB280M-YL
120V AC input voltage: DA75M-21A-11-84
Dynamic braking
DC Drive
1
1.188 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Replacement parts
EHDBRC280-1
EHDBAS280
Hz Cntr Volts
type 12 24 48 110 120 125 208 220 240 277 380 415 440 480 500 600
60 A 81 83 84 84 34 36 80 42 86 86 51 53 55
50 A 81 83 84 80 85 86 55
NOTE: DC coils are available for DA75 contactors only.
Coil voltage selection chart – DA contactors 1
Volts
24 48 110 120 125 208 220 240 277 380 415 440 480 500 600
60 F G 1 B 2 2 C 3 4 6
50 N 1 J 3 4 6
DC Y W P Q R
Coil voltage selection chart – EHDB contactors
NOTE: For other voltages, consult factory. • 24VAC coils are not available for sizes EHDB520 –
EHDB960. • 48VAC coils are not available for sizes EHDB520 – EHDB960. For these 24V and
48V applications, use an interposing control relay. • 12VDC coils are not available for EHDB520
– EHDB960.
1 For other voltages, see page 1.26.
Coils
Contactor
type
Catalog
number
DA75 ZA75-Δ 1
EHD220, EHD280 EHDRC280-Δ
EHD350 EHDRC360-Δ
Withdrawable type EHDB220, EHDB280 EHDBRC280-Δ
EHDB360 EHDBRC360-Δ
EHDB520, EHDB650 EHDBRC650-Δ
EHDB800, EHDB960 EHDBRC960-Δ
Δ Substitute the Δ for a coil voltage sufx found in the Coil Voltage Selection Chart. EHDB coils can be used as replacement parts in EHD contactors.
Arc shields
Contactor
size
Catalog
number
3 Pole
EHDB220 EHDBAS220
EHDB280 EHDBAS280
EHDB360 EHDBAS360
EHDB520 EHDBAS520
EHDB650 EHDBAS650
EHDB800 EHDBAS800
EHDB960 EHDBAS960
2 Pole
EHDB220 EHDBAS220-2
EHDB280 EHDBAS280-2
EHDB360 EHDBAS360-2
EHDB520 EHDBAS520-2
EHDB650 EHDBAS650-2
EHDB800 EHDBAS800-2
EHDB960 EHDBAS960-2
Auxiliary contact blocks — EHDB220 to EHDB960
Contactor
size Description Terminal markings Catalog
number
EHDB130
to
EHDB960
Standard 1 N.O. & 1 N.C. 13, 14 21, 22 CAL16-11A L
Standard 1 N.O. & 1 N.C. 43, 44 31, 32 CAL16-11B R
Standard 1 N.O. & 1 N.C. 53, 54 61, 62 CAL16-11C L
Standard 1 N.O. & 1 N.C. 83, 84 71, 72 CAL16-11D R
Late break 1 N.O. & 1 N.C. 47, 48 35, 36 CAL16-11E L,R
EHDB130 to EHDB960 contactors are provided with a 1 N.O. & 1 N.C. auxiliary contact block mounted on each contactor. One
additional 1 N.O. & 1 N.C. auxiliary contact block can be mounted on the left side of the contactor and two additional 1 N.O. & 1
N.C. contact blocks can be mounted on the right side.
Positive driven action auxiliary contact blocks — EHDB220 to EHDB360
Contactor
size Description Terminal markings Catalog
number
EHDB220
to
EHDB360
Standard 1 N.O. & 1 N.C. 13, 14 21, 22 CAL16-11A L
Standard 1 N.O. & 1 N.C. 43, 44 31, 32 CAL16-11B R
Only one of these auxiliary contact blocks can be mounted on each side of the contactor. They ful ll the mirror contacts IEC609
47-1 Annex F, positive driven action IEC609 47-1, Chapter 4. They also ful ll elevator standard ASME A17-1-2000.
Dynamic braking
DC Drive
1
Low Voltage Products & Systems 1.189
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Replacement parts
EHDBCK280-NC
EHDBCK280-2
Contact kits – 2 Pole, N.O.
Contactor
size
Catalog
number
DA75 ZL75
EHDB220 EHDBCK220-2
EHDB280 EHDBCK280-2
EHDB360 EHDBCK360-2
EHDB520 EHDBCK520-2
EHDB650 EHDBCK650-2
EHDB800 EHDBCK800-2
EHDB960 EHDBCK960-2
N.C. DB Kit only
Contactor
size
Contact
rating
Auxiliary
interlocks
Catalog
number
DA75 55A/160V; 28A/300V 1 NO CA5D-11
DA75 300V CA5D-01
EHDB220 300V EHDBCK220-NC
EHDB280 300V EHDBCK280-NC
EHDB360 300V EHDBCK360-NC
EHDB520 300V EHDBCK520-NC
EHDB650 300V EHDBCK650-NC
EHDB800 300V EHDBCK800-NC
EHDB960 300V EHDBCK960-NC
Lug kits – 2 & 3 Pole
Contactor
size
Wire
size
Catalog
number
EHDB220 – EHDB280 6-250 EHTK210
EHDB360 – EHDB650 4-500 EHTK550N
EHDB800 (2) 4-500 EHTK700
EHDB960 (3) 2-600 EHTK800
Dynamic braking
DC Drive
1
1.190 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Technical data
Type DA
Contactor DA75-21 DA75-21A
Center pole
N.C. Pole, 150V Make Max. Amps 90
N.C. Pole, 150V Break Max. Amps 55
N.C. Pole, 300V Make Max. Amps 90
N.C. Pole, 300V Break Max. Amps 55
DC rating
Maximum thermal current A 60 60
Peak interrupting current A 90 90
Connectable wire size
Main poles with lugs 8 – 1 8 – 1
Auxiliary contacts, min/max 18 – 10 18 – 10
Main contacts (contactor life)
Mechanical endurance @ no load mil. 5 5
Electrical endurance, main poles mil. 1.5 1.5
Frequency of operations per hour 600 600
Auxiliary contacts
NEMA rating A600 A600
AC rated voltage V 600 600
AC thermal rated current A 10 10
AC maximum making VA 7200 7200
AC maximum breaking VA 720 720
NEMA rating P600 P600
DC rated voltage V 600 600
DC thermal rated current A 5 5
DC maximum make-break A 0.2 0.2
Min. breakdown AC RMS voltage
between live parts and ground V 2200 2200
Minimum permissable load, 17V A 0.005 0.005
Max. wire size on terminals @ 2/term 10 AWG 10 AWG
Max. operations per hour 600 600
Min. expected mechanical life mil. 10 10
Min. expected electrical life mil. 2 2
Coil operating data
AC power consumption
Inrush 60 Hz VA 200 200
Holding 60 Hz VA 20 20
Holding 60 Hz W 5.5 5.5
AC operating time (in milliseconds)
Closing time ms 20 – 25 20 – 15
Opening time ms 10 – 15 10 – 15
General data
Approximate weight lbs 2.4 2.4
Temperature limits
Maximum operating temperature °C 50 50
Minimum operating temperature °C -25 -25
Minimum storage temperature °C -40 -40
Maximum storage temperature °C 70 70
Min. breakdown AC RMS voltage V 2200 2200
Operating altitude
Maximum operating altitude feet 10,000 10,000
Dynamic braking
DC Drive
1
Low Voltage Products & Systems 1.191
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Technical data
Type EHDB
Contactor model number EHDB220 EHDB280 EHDB360 EHDB520 EHDB650 EHDB800 EHDB960
N.O. poles, Amps 600 VDC 220 280 360 520 650 800 960
N.C. pole, 600V Make Max. amps 456 565 728 1040 1300 1600 1920
N.C. pole, 300V Break Max. amps 285 363 472 680 850 1050 1250
Connectable wire size
Main poles with lugs
8 – 30 5 – 250 kcmils 4 – 500 kcmils (2) 4 – 500 kcmils (2) 4 – 500 kcmils (3) 2 – 600 kcmils (3) 2 – 600 kcmils
Auxiliary contacts min./max. 16/10 16/10 16/10 16/10 16/10 16/10 16/10
DC rating information No. Poles
Peak interrupting current A 330 420 540 780 975 1200 1440
Maximum thermal current A 220 280 360 520 650 800 960
Main contacts (contactor life)
Mechanical endurance @ no load mil. 5 5 5 5 5 5 5
Electrical endurance mil. 1.5 1.5 1.5 1.5 1.5 1.5 1.5
Frequency of operations per hour 300 300 300 300 300 300 300
Auxiliary contacts
NEMA rating A600 A600 A600 A600 A600 A600 A600
AC rated voltage V 600 600 600 600 600 600 600
AC thermal rated current A 10 10 10 10 10 10 10
AC maximum making VA 7200 7200 7200 7200 7200 7200 7200
AC maximum breaking VA 720 720 720 720 720 720 720
NEMA rating
DC rated voltage V 600 600 600 600 600 600 600
DC thermal rated current A 5 5 5 5 5 5 5
DC maximum make-break A 0.2 0.2 0.2 0.2 0.2 0.2 0.2
Min. breakdown AC RMS voltage
between live parts and ground 2200 2200 2200 2200 2200 2200 2200
Min. permissable load, 17V A 0.005 0.005 0.005 0.005 0.005 0.005 0.005
Expected mechanical life mil. 5 5 5 5 5 5 5
Max. operations per hour 300 300 300 300 300 300 300
Coil operating data
AC power consumption
Inrush 60 Hz VA 900 900 1200 2900 2900 400 4000
Holding 60 Hz VA 52 52 65 105 105 140 140
Holding 60 Hz W 18 18 22 44 44 60 60
DC power consumption
Inrush W 500 500 630 800 800 1100 1100
Holding W 3.6 3.6 4 20 20 20 20
AC operating time
Closing time ms 20 – 30 20 – 30 20 – 30 30 – 50 30 – 50 30 – 50 30 – 50
Opening time ms 7 – 15 7 – 15 7 – 15 10 – 20 10 – 20 10 – 20 10 – 20
DC operating time
Closing time ms 30 – 40 30 – 40 30 – 40 60 – 80 60 – 80 60 – 80 60 – 80
Opening time ms 27 – 37 27 – 37 27 – 37 10 – 20 55 – 75 55 – 75 55 – 75
General data
Approximate weight lbs 9.2 9.2 13 27.3 27.3 37 38
Temperature limits
Maximum operating temperature °C 70 70 70 70 70 70 70
Minimum operating temperature °C -40 -40 -40 -40 -40 -40 -40
Minimum storage temperature °C -50 -50 -50 -50 -50 -50 -50
Maximum storage temperature °C 70 70 70 70 70 70 70
Min. Breakdown AC RMS Voltage 2200 2200 2200 2200 2200 2200 2200
Operating altitude
Maximum operating altitude feet 10,000 10,000 10,000 10,000 10,000 10,000 10,000
Dynamic braking
DC Drive
1
1.192 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Approximate dimensions
Type DA, 2 & 3 pole
DA75
DA75M
Dynamic braking
DC Drive
1
Low Voltage Products & Systems 1.193
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
F1
G
K1
D
0.19
4.8
F
B
C
C1 H1
E
P
P1
T T1
H
C1
C C2
0.22
5.69
EHDB960 Main Terminal
C3
G K1
Approximate dimensions
Type EHDB, 2 & 3 pole
Mounting positions
EHDB220 – EHDB960
Type DA & EHDB mounting positions
DIM. B B2 C C1 C2 E D F G H H1 K1 P P1 T T1 C3
1, 2 3 4 1 2 3 4
Aux. contact block
EHDB220 in 5.35 5.83 6.30 6.46 4.72 5.51 5.39 5.39 5.87 6.34 0.59 0.24 1.77 0.79 6.14 7.79 0.39 6.65 4.06 0.41 0.20 ––
mm 136 148 160 164 120 140 137 137 149 161 15 6 45 20 156 198 10 169 103 10.5 5 ––
EHDB280 in 5.35 5.83 6.30 6.46 4.72 5.51 5.39 5.39 5.87 6.34 0.59 0.24 1.77 0.79 6.14 7.79 0.39 6.65 4.06 0.41 0.20 ––
mm 136 148 160 164 120 140 137 137 149 161 15 6 45 20 156 198 10 169 103 10.5 5 ––
EHDB360 in 6.92 7.44 7.72 8.11 6.30 5.51 7.20 7.32 7.48 7.76 1.18 0.24 2.44 0.98 6.14 8.14 0.49 6.88 4.21 0.7 0.20 ––
mm 176 189 196 206 160 140 183 186 190 197 30 6 62 25 156 207 12.5 175 107 19 5 ––
EHDB520 in 7.80 8.23 8.62 8.90 6.69 7.87 7.91 7.91 8.19 8.54 1.57 0.24 2.64 0.98 8.78 10.71 0.49 8.90 5.51 0.9 0.24 ––
mm 198 209 219 226 170 200 201 201 208 217 40 6 67 25 223 272 12.5 226 140 23 6 ––
EHDB650 in 7.80 8.23 8.62 8.90 6.69 7.87 7.91 7.91 8.19 8.54 1.57 0.24 2.64 0.98 8.78 10.71 0.49 8.90 5.51 0.9 0.24 ––
mm 198 209 219 226 170 200 201 201 208 217 40 6 67 25 223 272 12.5 226 140 23 6 ––
EHDB800 in 9.61 9.96 10.31 10.63 8.66 7.87 9.69 9.690 10.00 10.35 1.57 0.24 3.23 1.57 8.78 11.57 0.79 8.90 5.51 0.9 0.24 ––
mm 244 253 262 270 220 200 246 246 254 263 40 6 82 40 223 294 20 226 140 23 6 ––
EHDB960 in 9.61 9.96 10.31 10.63 8.66 7.87 9.69 9.690 10.00 10.35 1.57 0.24 3.23 1.57 8.78 11.57 0.79 8.90 5.51 0.9 0.24 1.36
mm 244 253 262 270 220 200 246 246 254 263 40 6 82 40 223 294 20 226 140 23 6 34.5
1 Minimum dimension
2 Makes distance F1 = F
3 Includes space for three auxiliary contact blocks between the contactors.
4 Includes space for four auxiliary contact blocks between the contactors.
5 Damping elements are included.
NOTE: Screw, nut and washer are included for terminal hardware.
BHD & EHDB MOUNTING POSITION ON BACK PANEL AS SHOWN
Dynamic braking
DC Drive
1
1.194 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Notes
Lighting
Contactors
Low Voltage Products & Systems 1.195
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
Lighting contactors
A9 – A300
Lighting
Contactors
Features
CE mark
Compact space saving design
Standard auxiliary contact congurations:
A9 - A40 1 NO or 1 NC
A50 - A110 1 NO & 1 NC
Additional auxiliary contact blocks are available
Panel mounting with screws or fast, snap-on DIN rail mounting
Silver alloy double break contact design
Snap-on front mounted accessories include mechanical latch, pneumatic timer, and 1 & 4 pole auxiliary contact
blocks
Contactors ensure positive safety between their auxiliary contact blocks.
Easy coil change
Captive terminal screws
NEMA, UL, IEC, CSA, VDE and most other international standards
Touch safe design: All connection terminals are protected against accidental touch
Terminals supplied open for ease of wiring
Operates over an extended voltage range of 85% to 110% of rated control voltage
Screwdriver guide holes
UL File No: E39231 (A9 - A75); (AE9 - AE75); (AL9 - AL40); (AF50 - AF75)
UL File No: E36588 (A95 - A110); (AE95 - AE110); (AF145 - AF750)
CSA File No: LR56745 (A9 - A75); (AE9 - AE75); (AF50 - AF75)
CSA File No: LR19700 (A95 - A110); (AE95 - AE110); (AF145 - AF750)
Applications
Lighting contactors can be used to control a variety of lighting loads including:
Tungsten lament lighting loads (incandescent), iodine lamps, quartz-iodine and infrared lamps
Electric discharge lighting loads (ballast), high intensity discharge (HID), mercury vapor, metal halide
and high pressure sodium and uorescent lamps
Typical applications
Parking lots • Shopping centers
• Industrial plants • Airports
• Ofce buildings • Hospitals
• Theaters and auditoriums • Transportation lighting
• Stadiums • Institutions
Description
The A-Line lighting contactors are available with or without an enclosure.
Maximum operating voltage of 600VAC 60Hz
Includes 3, 4, 8 or 12 pole versions, other versions on request
Electrically or mechanically held contactors
IP 20 protection for connection terminals
• Can be mounted onto a mounting plate or a 35 x 7.5mm DIN rail
UL/CSA Approved
Lighting
Contactors
1.196 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
A9 - A300
Electrically & mechanically held
A9-40-00 A45-40-00 A145-30-11
Normally Open Power Poles Electrically Held Mechanically Held
Open Type UL Type 1 Enclosed Open Type UL Type 1 Enclosed
Ballast
Amp
Rating
Incandescent
(Tungsten)
Amp Rating
Number
of Power
Poles
Catalog
number
Enclosure
Size
Catalog
number
Catalog
number
Enclosure
Size
Catalog
number
15 15 4 A9-40-00-84 A A9C4P1-84 A9L-40-00-84 B A9LC4P1-84
15 15 8 A9-80-00-84 A A9C8P1-84 A9L-80-00-84 B A9LC8P1-84
15 15 12 A9-120-00-84 A A9C12P1-84 A9L-120-00-84 B A9LC12P1-84
30 20 4 A16-40-00-84 A A16C4P1-84 A16L-40-00-84 B A16LC4P1-84
30 20 8 A16-80-00-84 A A16C8P1-84 A16L-80-00-84 B A16LC8P1-84
30 20 12 A16-120-00-84 A A16C12P1-84 A16L-120-00-84 B A16LC12P1-84
30 30 4 A16-40L-00-84 A A16C4PL1-84 A16L-40L-00-84 B A16LC4PL1-84
30 30 8 A16-80L-00-84 A A16C8PL1-84 A16L-80L-00-84 B A16LC8PL1-84
30 30 12 A16-120L-00-84 A A16C12PL1-84 A16L-120L-00-84 B A16LC12PL1-84
35 35 4 A26-40-00-84 B A26C4P1-84 A26L-40-00-84 B A26LC4P1-84
35 35 8 A26-80-00-84 B A26C8P1-84 A26L-80-00-84 B A26LC8P1-84
35 35 12 A26-120-00-84 B A26C12P1-84 A26L-120-00-84 B A26LC12P1-84
50 50 3 A30-30-10-84 B A30C3P1-84 A30L-30-10-84 C A30LC3P1-84
60 60 3 A40-30-10-84 B A40C3P1-84 A40L-30-10-84 C A40LC3P1-84
60 60 4 A45-40-00-84 B A45C4P1-84 A45L-40-00-84 C A45LC4P1-84
65 65 3 A50-30-00-84 B A50C3P1-84 A50L-30-00-84 C A50LC3P1-84
65 65 4 A50-40-00-84 B A50C4P1-84 A50L-40-00-84 C A50LC4P1-84
85 85 3 A63-30-00-84 B A63C3P1-84 A63L-30-00-84 C A63LC3P1-84
105 105 3 A75-30-00-84 B A75C3P1-84 A75L-30-00-84 C A75LC3P1-84
105 105 4 A75-40-00-84 B A75C4P1-84 A75L-40-00-84 C A75LC4P1-84
120 120 3 A95-30-00-84 B A95C3P1-84 --- --- ---
200 200 3 A145-30-00-84 E A145C3P1-84 --- --- ---
300 300 3 A210-30-00-84 F A210C3P1-84 --- ---
400 400 3 A300-30-00-84 F A300C3P1-84 --- --- ---
Normally Closed Power Poles Electrically Held Mechanically Held
Open Type UL Type 1 Enclosed Open Type UL Type 1 Enclosed
Ballast
Amp
Rating
Incandescent
(Tungsten)
Amp Rating
Number
of Power
Poles
Catalog
number
Enclosure
Size
Catalog
number
Catalog
number
Enclosure
Size
Catalog
number
30 20 4 A16-04-00-84 B A16C4NCP1-84 A16L-04-00-84 BA16LC4NCP1-84
30 20 8 A16-08-00-84 B A16C8NCP1-84 A16L-08-00-84 BA16LC8NCP1-84
30 20 12 A16-012-00-84 B
A16C12NCP1-84
A16L-012-00-84 BA16LC12NCP1-84
Coil voltage selection
All catalog numbers include a 120VAC coil. To select other coil voltages, substitute
the code from the Coil Voltage Selection Chart for the two digits after the last dash
in the catalog number.
Ex.: A 240V coil is required for an A75 contactor: A75-30-00-80
Coil voltage selection
Cntr Volts
Hz Type 12 24 48 110 120 125 208 220 240 277 380 415 440 480 500 600
60 A81 83 84 84 34 36 80 42 86 86 51 53 55
50 A81 83 84 80 85 86 55
For other voltages, consult factory
Control transformer voltage selection chart
Volts
Hz Type 208/120 230 – 240/120 460 – 480/120 575 – 600/120
50/60 A0 7 8 9
For other voltages, consult factory
Control transformer option
Contactor
size
VA
rating
A9 A40 50
A50 A75 75
A95 100
A145 150
A210 A300 250
Lighting
Contactors
Low Voltage Products & Systems 1.197
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
A9 - A300
Electrically & mechanically held
Coil voltage selection
All catalog numbers include a 120VAC coil. To select other coil voltages, substitute
the code from the Coil Voltage Selection Chart for the two digits after the last dash
in the catalog number.
Ex.: A 240V coil is required for an A75 contactor: A75-30-00-80
Coil voltage selection
Cntr Volts
Hz Type 12 24 48 110 120 125 208 220 240 277 380 415 440 480 500 600
60 A81 83 84 84 34 36 80 42 86 86 51 53 55
50 A81 83 84 80 85 86 55
For other voltages, consult factory
Control transformer voltage selection chart
Volts
Hz Type 208/120 230 – 240/120 460 – 480/120 575 – 600/120
50/60 A0 7 8 9
For other voltages, consult factory
NEMA rated
Normally open Power Poles
600 VAC Max.
Electrically held
Open type
Ballast
Amp
Rating
Incandescent
(Tungsten)
Amp rating
Number of
Power poles
1
Catalog
number
30
60
100
200
30
60
100
200
3
3
3
3
L30A3010
L60A3010
L100A3000
L200A3000
2 Normally Open & 2 Normally
Closed Power Poles
Electrically Held Mechanically Held
Open Type UL Type 1 Enclosed Open Type UL Type 1 Enclosed
Ballast
Amp
Rating
Incandescent
(Tungsten)
Amp Rating
Number
of Power
Poles
Catalog
number
Enclosure
Size
Catalog
number
Catalog
number
Enclosure
Size
Catalog
number
15 15 2 NO / 2 NC A9-22-00-84 A A9C22P1-84 A9L-22-00-84 AA9LC22P1-84
30 20 2 NO / 2 NC A16-22-00-84 B A16C22P1-84 A16L-22-00-84 BA16LC22P1-84
35 35 2 NO / 2 NC A26-22-00-84 B A26C22P1-84 A26L-22-00-84 BA26LC22P1-84
60 60 2 NO / 2 NC A45-22-00-84 B A45C22CP1-84 A45L-22-00-84 C A45LC22CP1-84
105 105 2 NO / 2 NC A75-22-00-84 B A75C22CP1-84 A75L-22-00-84 C A75LC22CP1-84
Control transformer option
Contactor
size
VA
rating
A9 A40 50
A50 A75 75
A95 100
A145 150
A210 A300 250
Lighting
Contactors
1.198 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Accessories
Factory modifications
Accessories
Auxiliary contact blocks
Mounting on contactors Positioning
Contacts
Catalog number
A 9 … A 95 Front face 1 - CA5-10
- 1 CA5-01
A 9 … A 40 Front face 3 1 CA5-31M
2 2 CA5-22M
A 9 … A 75 Side 1 1 CAL5-11
A 95 … A 300 Side 1 1 CAL18-11
A145... A 300 Side 1 1 CAL18-11B
Mechanical latch
For contactors Voltage Catalog number
A 9 … A 75
24 … 28 V a.c./d.c. WB75A-01
48 … 55 V a.c./d.c. WB75A-03
110 … 127V a.c./d.c. WB75A-04
230 … 277 V a.c./d.c. WB75A-05
380 … 440 V a.c./d.c. WB75A-07
440 … 480 V a.c./d.c. WB75A-08
Surge suppressor, varistor
For contactors Voltage range Catalog number
A 9 … A 110
24 … 50 V a.c./d.c. RV5/50
50 … 133 V a.c./d.c. RV5/133
110 … 250 V a.c./d.c. RV5/250
250 … 440 V a.c./d.c. RV5/440
Factory modifications for enclosed contactors
Pilot devices
Description Sufx code
Selector - 2 position maintained OFF - ON C
Selector - 3 position maintained HAND OFF - AUTO D
Pilot light - ON (green) R
CAL5-11 CA5-10 WB75-01 RV5/50
Lighting
Contactors
Low Voltage Products & Systems 1.199
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
1
H
W D
ABB Inc.
Approximate dimensions
Enclosure dimensions (in)
Type H WD
A 11 65
B13 97
C 14 12 8
D 24 12 8
E 30 24 9
Lighting
Contactors
1.200 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
1
Notes
1
Railway
applications
contactors
Low Voltage Products & Systems 1.201
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Railway application contactors
Types TBC, TAL & TAE
TNL, ring-tongue termination
Description
Rolling stock applications necessitate compliance to
national and international standards tailored to railway
environments (see “Reference Standards” on the following
page). In order to improve reliability and durability, most
railway applications employ specic connection methods,
such as ring-tongue termination.
Coil surge suppression is also popular among rail appli-
cations. ABB’s AF Series contactors are equipped with
integral surge suppression in the form of a free-wheel
diode, eliminating the need for additional accessories.
AF Series devices are also immune to short time voltage
interruption (or voltage dips) up to 20 ms.
Railway application
Contactors
Contactors and contactor relays are used
in versatile rolling stock applications:
Lighting
Heating
Braking
Air conditioning
Ventilation
Door control
Requirements of railway applications
Control networks typically utilizing DC (battery source)
with wide voltage ranges:
– 0.7 Uc ... 1.25 Uc (Operating limits included as Uc)
Wide temperature range: -40 °C… +70 °C
Shock & vibration withstand
Fire-retardant / low smoke materials required
1
Railway
application
conactors
1.202 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Reference standards
The contactor and control relays described in the following pages are in accordance with the following standards:
• IEC 60077-1 and IEC 60077-2 : Railway applications - Electric equipment for rolling stock.
• IEC 61373 : Railway applications - Rolling stock - Shocks and vibration tests.
• NF F 60002 : French standard - Vibration tests.
• IEC 60947-4-1 / EN 60947-4-1 : Low voltage controlgear - Contactors and motor starters.
• IEC 60947-5-1 / EN 60947-5-1 : Low voltage controlgear - Control circuit devices and switching elements.
• NF F 62000 : French standard - Functional tests for French railways (SNCF).
"Fire and Smoke" classification
According to ASTM standards:
ASTM standards, mainly used in North America, device products into two categories:
• For surfaces < 16 inch2 the products are tested in accordance with:
– ASTM E1354 : ammability and visible smoke
• For surfaces > 16 inch2 the products are tested in accordance with:
– E662 (97): density of smoke,
– E162 (98): ammability of surface and
– BSS 7239: toxicity of smoke (CO, HF, NO2, HCl, HCN, SO2).
Most of contactors, contactor relays and accessories have been tested according to the above standards. Certicates are available on request.
According to NF F standards:
French standards NF F (Normes Francaises Ferroviaires) are mainly used in Europe and Asia.
• NF F 16101: Fire behavior - Material choosing.
• NF F 16102: Fire behavior - Application to electrical equipment.
The contactors and accessories are at severity level 2 or 3 (classication level from 1 to 4) according to ammability (mark I) on the one hand, the opacity
and toxicity of smoke (mark F) (CO, CO2, HCl, HBr, HCN, HF, SO2) in other hand.
Note: French standards are still used as references in some international railways because they were used for a long time and were alone to qualify the
re and smoke problem. There is no links between ASTM and NFF standards. A plastic material acceptable in NF F frame doesn't mean the acceptability
in ASTM frame.
Technical data
Technical data for the following devices is provided in Literature no. 1SBC104032D0201. Please reference this document number at ABB.com to down-
load or contact Technical Support at 1 (888) 385.1221, Option 4
1
Railway
applications
contactors
Low Voltage Products & Systems 1.203
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Standard devices, ring-tongue, 3-pole
A/L9…A/F75
AC or DC controlled
A26..RT A50…A75..RT
Electrical ratings
AC general
purpose ratings
(A) Maximum
motor switching
current (A)
AC motor ratings, breaking all lines,
three phase, 50/60 Hz (hp) Standard auxiliary contacts Catalog
number,
AC controlled
Catalog
number,
DC controlled
600V 200…
208V
220…
240V
440…
480V
550…
600V NO NC
21 9225 7.5 1- A93010RT AL93010RT
-1A93001RT AL93001RT
25 11 3 3 7.5 10 1- A123010RT AL123010RT
-1A123001RT AL123001RT
30 17 5 5 10 15 1- A163010RT AL163010RT
-1A163001RT AL163001RT
40 28 7.5 10 20 25 1- A263010RT AL263010RT
-1A263001RT AL263001RT
50 34 10 10 25 30 1- A303010RT AL303010RT
-1A303001RT AL303001RT
60 42 10 15 30 40 1- A403010RT AL403010RT
-1A403001RT AL403001RT
80 54 15 20 40 50 1 1 A503011RT AF503011RT
90 68 20 25 50 60 1 1 A633011RT AF633011RT
105 80 25 30 60 75 1 1 A753011RT AF753011RT
Note: devices with ring-tongue termination UL recognized
Coil voltage selection chart (Δ)
Rated control circuit
voltage Uc
A9…
A75
AL9...
AL40
AF50…
AF75
12V DC - 80 80
24V AC 81 - -
24V DC - 81 81
20…60V DC - 72
110V/50, 110…120V/60 84 - -
48…130V AC/DC - - 69
100…250V AC/DC - - 70
125V DC - 87 87
220V DC - 88 88
230..240V/60 80 - -
240V DC - 89 89
480V/60 51 - -
600V/60 55 - -
Example:
24V DC input voltage: AL303010RT-81
120V AC input voltage: A753011RT-84
1
Railway
application
conactors
1.204 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Traction-specific, ring-tongue, 3-pole
TBC7, TAL9…AF300B
DC controlled, standard & ring-tongue termination
TBC7-30 TAL26..RT TAE50…TAE75..RT AF210B…AF300B
Electrical ratings
AC general
purpose ratings
(A) Maximum
motor switching
current (A)
AC motor ratings, breaking all lines,
three phase, 50/60 Hz (hp)
Standard auxiliary
contacts
Catalog
number,
Standard
termination
Catalog
number,
Ring-tongue
termination
600V 200…
208V
220…
240V
440…
480V
550…
600V NO NC
16 9.6 23551- TBC7-30-10-Δ -
-1TBC7-30-01-Δ -
21 9225 7.5 1- TAL9-30-10-Δ TAL9-30-10RT
-1TAL9-30-01-Δ TAL9-30-01RT
25 11 3 3 7.5 10 1- TAL12-30-10-Δ TAL12-30-10RT
-1TAL12-30-01-Δ TAL12-30-01RT
30 17 5 5 10 15 1- TAL16-30-10-Δ TAL16-30-10RT
-1TAL16-30-01-Δ TAL16-30-01RT
40 28 7.5 10 20 25 1- TAL26-30-10-Δ TAL26-30-10RT
-1TAL26-30-01-Δ TAL26-30-01RT
50 34 10 10 25 30 1- TAL30-30-10-Δ TAL30-30-10RT
-1TAL30-30-01-Δ TAL30-30-01RT
60 42 10 15 30 40 1- TAL40-30-10-Δ TAL40-30-10RT
1TAL40-30-01-Δ TAL40-30-01RT
80 54 15 20 40 50 1 1 TAE50-30-11-Δ TAE50-30-11RT
105 80 25 30 60 75 1 1 TAE75-30-11-Δ TAE75-30-11RT
150 88 30 30 60 75 1 1 AF95B-30-11-Δ AF95B-30-11RT
150 104 30 40 75 100 1 1 AF110B-30-11-Δ AF110B-30-11RT
230 130 40 50 100 125 1 1 AF145B-30-11-Δ AF145B-30-11RT
250 156 50 60 125 150 1 1 AF185B-30-11-Δ AF185B-30-11RT
300 192 60 75 150 200 1 1 AF210B-30-11-Δ AF210B-30-11RT
350 248 75 100 200 250 1 1 AF260B-30-11-Δ AF260B-30-11RT
400 302 100 100 250 300 1 1 AF300B-30-11-Δ AF300B-30-11RT
Note: devices with ring-tongue termination UL recognized
Coil voltage selection chart (Δ)
Rated control circuit
voltage Uc
TBC7 TAL9…
TAL40
TAE50…
TAE75
AF95B…
AF300B
17…32V DC 51 51 51 -
24…45V DC 52 52 52 -
20…60V DC - - - 72
36…65V DC 54 54 54 -
42…78V DC 58 58 58 -
50…90V DC 55 55 55 -
48…130V AC/DC - - - 69
77..143V DC 62 62 62 -
90…150V DC 66 66 66 -
100…250V AC/DC - - - 70
152…264V DC 68 68 68 -
Example:
24V DC input voltage: TAL9-30-10-52
120V AC input voltage: AF300B-30-11RT-70
Coil operating limits
For traction-specic catalog numbers starting with “T”, the coil operating limits are in-
cluded in the coil voltage range (Uc min…Uc max.). For AF..B devices, the coil range
is nominal with operating limits 15% below and 10% above the range specied.
1
Railway
applications
contactors
Low Voltage Products & Systems 1.205
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Traction-specific, ring-tongue, 4-pole & relays
TBC7, TAL9…TAE75, TNL
DC controlled
TBC7-30 TAL26-40..RT TAE50-40…TAE75-40..RT TNL80E
4-pole contactors – Electrical ratings
AC general
purpose ratings (A)
Main (power) pole
Configuration Standard auxiliary contacts Catalog
number,
Standard
termination
Catalog
number,
Ring-tongue
termination
600V NO NO NO NC
16 4 - - - TBC7-40-00-Δ -
2 2 TBC7-22-00-Δ -
21 4 - - - TAL9-40-00-Δ TAL9-40-00RT
2 2 TAL9-22-00-Δ TAL9-22-00RT
30 4 - - - TAL16-40-00-Δ TAL16-40-00RT
2 2 TAL16-22-00-Δ TAL16-22-00RT
40 4 - - - TAL26-40-00-Δ TAL26-40-00RT
2 2 TAL26-22-00-Δ TAL26-22-00RT
65 4 - - - TAL45-40-00-Δ TAL40-40-00RT
80 4 - - - TAE50-40-00-Δ TAE50-40-00RT
105 4 - - - TAE75-40-00-Δ TAE75-40-00RT
Note: devices with ring-tongue termination UL recognized
Control relays
Pilot duty ratings
Number of contacts Catalog
number,
Standard
termination
Catalog
number,
Ring-tongue
termination
1st stack 2nd stack
NO NO NO NC
A600, Q300
2 2 - - TNL22E-Δ TNL22ERT
31- - TNL31E-Δ TNL31ERT
4 - - - TNL40E-Δ TNL40ERT
4 - - 4 TNL44E-Δ TNL44ERT
4-2 2 TNL62E-Δ TNL62ERT
4 - 4 - TNL80E-Δ TNL80ERT
Note: devices with ring-tongue termination UL recognized
Coil voltage selection chart (Δ)
Rated control circuit
voltage Uc
TBC7 TAL9…
TAL40
TAE50…
TAE75
AF95B…
AF300B
17…32V DC 51 51 51 51
24…45V DC 52 52 52 52
36…65V DC 54 54 54 54
42…78V DC 58 58 58 58
50…90V DC 55 55 55 55
77..143V DC 62 62 62 62
90…150V DC 66 66 66 66
152…264V DC 68 68 68 68
Example:
24V DC input voltage: TAL9-22-00-52
120V AC input voltage: TAE75-40-00RT-62
Coil operating limits
For traction-specic catalog numbers starting with “T”, the coil operating limits are
included in the coil voltage range (Uc min…Uc max.).
Load / supply requirements
4-pole devices can be utilized for controlling either 2 separate loads from 2 separate
supplies, or 2 separate loads from 1 supply. These devices are not suitable for
controlling 1 load from 2 separate supplies. There is no mechanical overlapping (NO
poles will break before NC poles make).
1
Railway
application
conactors
1.206 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Accessories
Devices in this section of the catalog utilize the same accessories as ABB’s standard across-the-line motor switching devices.
Please see the below page references for accessories:
Accessory type Page reference
Surge suppressors 1.52…1.53
Mechanical / electrical interlocks 1.57
Electronic timers 1.59
Replacement coils 1.73
1
DC Circuit
switching
contactors
Low Voltage Products & Systems 1.207
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
DC Circuit switching contactors
Up to 2050A, 1000V DC
Type GA/E, GAF, AF
Description
The new GAF range contactors are the latest addition to ABB’s well established A/AF range. This
further extends our offering of contactors for DC switching at voltages up to 1000 V DC. The
GAF contactors utilize all the well known features of the existing A/AF range such as modern and
compact design. In addition all the benets from the AF coil technology and reliability of a proven
contactor design. These contactors are rated for DC-1 or DC general purpose applications accord-
ing to IEC 1000V DC or cULus 600V DC. The new GAF contactors share the external dimensions of
its corresponding standard AF contactor.
DC Circuit switching
Contactors
Applications
• Solar / Photovoltaic power
• Traction / rolling-stock
• Power distribution
• Switchgear
• Battery systems
• Telecom
Type GA / GAE
• DC general use up to 1000V DC, 35A
• AC or DC input voltages
• Pre-wired 3-poles-in-series
• Permanent magnets for high DC breaking
• cULus Listed – File # E319322
– Switches, Industrial Control (NRNT, NRNT7)
Type AF / GAF
• DC general use up to 600V, 1900A
• DC-1 up to 1000V DC, 2050A
• Electronic AC/ DC coil input voltages
• PLC interface (GAF460…GAF2050)
• Series busbar kits available
• Permanent magnets for high DC breaking
• GAF185…GAF300 cULus Listed – File #
E73397
– Switches, Industrial Control (NRNT, NRNT7)
• GAF460…GAF2050 IEC/EN only
• AF145…AF2650 cULus Listed – File #
E73397
– Switches, Industrial Control (NRNT, NRNT7)
1
DC Circuit
switching
contactors
1.208 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
A1
1
L1 +
2
T1 –
A2
13X
21X
14X
22X
13X 21X
A1
1L1 +
14X 22X
A2
2T1 –
13X
A1
1L1 +
14X
21X
22X
A2
2T1 –
A3
35X
36X
A1 A2
13X
21X
14X
22X
C
D
L
5
1
L1 +
2
T1
A3
36X
35X
GA75 - GAE75
GAE75-10-00-84
Wiring diagrams
In D.C. circuits, the source to earth (or frame) connection mode is an important element.
Three modes are mainly used:
A – insulated source, i.e. unearthed (or not connected to the frame).
B – source earthed via its central point.
C – source earthed via one of its outer poles.
Modes A and B do not impose any constraints with regard to the distribution of the contactor poles between the two source/load
connecting branches. Mode C requirements are therefore suitable for modes A and B.
For mode C, all the poles necessary for breaking must be installed in series between the load and the ungrounded source polar-
ity.We recommend this solution for all connection modes.
The above provisions relate to power circuit switching, the SCPD (Short-Circuit Protection Device) must comply with protection
rules.
Accessories
Standard A and AE 40 - 75 contactor accessories are suitable for GA75 and GAE75 contactors.
Coils are the standard coils for A and AE50 - 75 contactors.
Contacts cannot be changed.
Coil voltage selection chart (∆)
Hz Cntr Volts
type 12 24 48 110 120 125 208 220 240 277 380 415 440 480 500 600
60 GA 81 83 84 84 34 75 80 42 48 86 86 51 53 55
50 GA 81 83 84 80 85 86 55
DC GAE 80 81 83 86 87 88 89
For other voltages, see page 1.35.
GA75-10-00-84
GA 75 / GAE 75
SCPD
+
– 2
T1
+ 1
L1
Load
{
GA 75 / GAE 75
SCPD
+
Load
{
– 2
T1
+ 1
L1
Electrical ratings
UL/CSA
DC general use (A)
IEC / EN
DC-1, θ≤40° (A)
Standard auxiliary
contacts Catalog
number
440V 600V 1000V 440V 600V 1000V N.O. N.C.
100 75 35 100 75 35 GA75-10-00-Δ
100 75 35 100 75 35 1 1 GAE75-10-11-Δ
Rated insulation voltage Ui = 1000V d.c. according to IEC 947-4-1.
Maximum switching frequencies: 300 operating cycles/
Additional IEC/EN electrical
ratings for GA/E75
Utilization
category
Maximum
voltage
Rated
operational
current le (A)
DC-3 440V 85
DC-5 220V 85
440V 35
1
DC Circuit
switching
contactors
Low Voltage Products & Systems 1.209
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
GAF1650, GAF 2050
AF1350 ... AF2050
GAF185
AF145, AF185
GAF750, GAF1250
AF580 ... AF1250
LP185
AC / DC coils with electronic coil interface
Contactors GAF185 ... GAF300, AF145 ... AF300 Contactors GAF460 ... GAF1250, AF400 ... AF1250
Voltage Voltage Code Voltage Voltage Code
V - 50/60Hz V - DC Δ Δ V - 50/60Hz V - DC Δ Δ
20 ... 60 7 2 24 ... 60 6 8
48 ... 130 48 ... 130 6 9 48 ... 130 48 ... 130 6 9
100...250 100 ... 250 7 0 100 ... 250 100 ... 250 7 0
250 ... 500 250 ... 500 7 1
Contactors GAF1650, GAF2050,
AF1350, AF1650, AF2050
100 ... 250 100 ... 250 7 0
GAF - 1000 V DC max. (IEC)
L/R 1 ms, air temperature close to contactor Catalog
number
Reference
code
Pkg
qty
Weight
(1 pce) kg
40 °C 55 °C 60 °C 65 °C 70 °C
A
275 250 230 205 180 GAF185-10-11-Δ 1SFL497025RΔ11 3.60
500 400 375 350 325 GAF300-10-11-Δ 1SFL557025RΔ11 6.20
700 600 560 520 480 GAF460-10-11-Δ 1SFL597025RΔ11 12.00
1050 875 800 760 720 GAF750-10-11-Δ 1SFL637025RΔ11 15.00
1250 1040 970 920 875 GAF1250-10-11-Δ 1SFL647025RΔ11 16.00
1650 1450 1380 1325 1270 GAF1650-10-11-Δ 1SFL677025RΔ11 35.00
2050 1750 1650 1575 1500 GAF2050-10-11-Δ 1SFL707025RΔ11 35.00
GAF & AF - 600 V DC max. (UL/CSA) & 850...1000 V DC max. (IEC)
UL/CSA general use, 40 °C IEC DC-1, 40 °C
A A
250 250 GAF185-10-11-Δ1SFL497025RΔ11 3.60
400 500 GAF300-10-11-Δ1SFL557025RΔ11 6.20
Use GAF185 - GAF300
See next page for
IEC data at various
voltages.
AF145-30-11-Δ 1SFL477001RΔ11
3.60
AF185-30-11-Δ 1SFL497001RΔ11
3.60
AF210-30-11-Δ 1SFL517001RΔ11
6.20
AF260-30-11-Δ 1SFL537001RΔ11
6.20
AF300-30-11-Δ 1SFL597001RΔ11
6.20
550 AF400-30-11-Δ1SFL637001RΔ11 12.00
650 AF460-30-11-Δ1SFL597001RΔ11 12.00
750 AF580-30-11-Δ1SFL617001RΔ11 15.00
900 AF750-30-11-Δ1SFL637001RΔ11 15.00
1210 AF1250-30-11-Δ1SFL647001RΔ11 16.00
AF1350-30-11-Δ1SFL657001RΔ11 34.00
1350 AF1650-30-11-Δ1SFL677001RΔ11 35.00
1900 AF2050-30-11-Δ1SFL707001RΔ11 35.00
Connection bar for contactor 1
GAF185, AF145, AF185 LP185 1SFN074712R1000 20.30
GAF300, AF210 ... AF300 LP300 1SFN075112R1000 20.40
GAF460, AF400, AF460 LP460 1SFN075712R1000 4 0.55
GAF750, AF580, AF750 LP750 1SFN076112R1000 4 0.95
GAF1250, AF1250 LP1250 1SFN076412R1000 21.90
GAF1650, GAF2050, AF1350, AF1650, AF2050 LP2050 1SFN076512R1000 4 2.90
1 Not included with the contactor; connection diagrams must be respected
Auxiliary contact blocks, low energy microswitch 0.1 A, N.O or N.C.
AF145...AF2050
GAF185...GAF2050 N.C. CEL18-01 1SFN010716R1001 0.05
N.O. CEL18-10 1SFN010716R1010 0.05
GAF300
AF210 ... AF300
GAF460
AF400, AF460
LP2050
GAF185 - GAF2050
DC circuit switching GAF & AF
3 contacts in series
1
DC Circuit
switching
contactors
1.210 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Technical data
DC switching ratings AF contactors
IEC
AF145 AF185 AF210 AF260 AF300 AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050
Utilization category DC-1 A A A A A A A A A A A A A
Contacts
in series L/R 1 ms
1 contact 110 V 600 700 800 1050
2 contacts 110 V 250 275 350 400 450 600 700 800 1050
3 contacts 220 V 250 275 350 400 450 600 700 800 1050 1250 1350 1650 2050
3 contacts 600 V 600 700 800 1050 1250 1350 1650 2050
3 contacts 850 V 800 1050 1250 1350 1650 2050
Conductor
cross-sectional
area mm2120 150 185 240 3001) 2x185 2x240 2 x 50x82) 10003) 2 x 100x52) 3 x 100x52) 4 x 100x52)
Utilization category DC-3
Contacts
in series L/R 2.5 ms
1 contact 110 V 600 700 800 1050
2 contacts 110 V 250 275 350 400 450 600 700 800 1050
3 contacts 220 V 250 275 350 400 450 600 700 800 1050
3 contacts 600 V 600 700 800 1050
Conductor
cross-sectional
area mm2120 150 185 240 3001) 2x185 2x240 2 x 50x82) 100032 x 100x52) 3 x 100x52) 4 x 100x52)
Utilization category DC-5
Contacts
in series L/R 15 ms
1 contact 110 V 600 700 800 1050
2 contacts 110 V 250 275 350 400 450 600 700 800 1050
3 contacts 220 V 250 275 350 400 450 600 700 800 1050
3 contacts 600 V 600 700 800 1050
Conductor
cross-sectional
area mm2120 150 185 240 3001) 2x185 2x240 2 x 50x82) 100032 x 100x52) 3 x 100x52) 4 x 100x52)
1) For currents above 450 A use 300 mm2 and terminal extension / enlargement pieces ( LW300: see www.abb.com/lowvoltage or local ABB catalog)
2) Dimension of the bars (mm)
3) Max connection bar width 50 mm
cULus
AF145 AF185 AF210 AF260 AF300 AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050
Intended device application general purpose
Contacts
in series
3 contacts 240 V 250 550 650 750 900 1210 1350 1900
3 contacts 600 V 550 650 750 900 1210 1350 1900
General
When selecting a contactor for DC switching it is essential to determine the current, the voltage and the L/R time constant
of the controlled load.
• The loads are dened by the time constant L/R: non inductive loads such as resistance furnaces (L/R ≈ 1 ms), inductive loads
such as shunt motors (L/R ≈ 2 ms) or series motors (L/R ≈ 7.5 ms).
• In addition to the block contactors shown in this document:
1) ABB also offers bar mounted contactors (R-series). Bar contactors can typically be used for higher amps and voltages or
other congurations or number of main poles (contacts).
1
DC Circuit
switching
contactors
Low Voltage Products & Systems 1.211
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Main technical data
IEC60947-4-1
Contactor type GAF GAF185 GAF300 GAF460 GAF750 GAF1250 GAF1650 GAF2050
Rated operational voltage U
e
max V DC
1000
IEC 60947-4-1, DC-1, θ40 °C A275 500 700 1050 1250 1650 2050
Conductor cross-sectional area mm2150 3001) 2x240 2 x 50x82) 10003) 3 x 100x52) 4 x 100x52)
1) For currents above 450 A use 300 mm2 and terminal extension / enlargement pieces ( LW300: see www.abb.com/lowvoltage or local ABB catalog)
2) Dimension of the bars (mm)
3) Max connection bar width 50 mm
cULus
Contactor type GAF GAF185 GAF300
Rated operational voltage U
e
max V DC
600
Amp-ratings general purpose A250 400
General technical data
Contactor type
GAF185 GAF300 GAF460 GAF750 GAF1250 GAF1650 GAF2050
AF145 AF185 AF210 AF260 AF300 AF400 AF460 AF580 AF750 AF1250 AF1350
AF1650
AF2050
Rated making capacity DC-1
1.5 x I
e
acc. to IEC60947-4-1
Rated breaking capacity DC-1
Rated frequency limits Hz 25 ... 400
Short-circuit protection
for contactors without thermal O/L relay -
Motor protection excluded
On request or see www.abb.com/lowvoltage or local ABB catalog
Rated short-time withstand current, Icw On request or see www.abb.com/lowvoltage or local ABB catalog
Heat dissipation per pole Ie /DC-1 W13 16 18 25 32 30 42 32 50 80 80 125
Rated impulse withstand voltage, Uimp kV 8
Ambient temperature close to contactor see ”Conditions for use”, for control voltage limits and authorized mounting
- during operation / storage °C -40 to +70
Operating altitude m 3000 without derating
Magnet system characteristics
Rated control circuit voltage Uc
- at 50 Hz and 60 Hz V48 ... 250 48 ... 500 100 ... 250
- d.c. V20 ... 250 24 ... 500 100 ... 250
Coil operating limits
acc. IEC60947-4-1
0.85 x Uc min. ... 1.1 x Uc max. (at θ≤ 70 °C)
Please also refer to ”Mounting characteristics”
Drop-out voltage
in % of Uc min. % 55
Coil consumption
Average pull-in value 50 Hz and 60 Hz VA 430 470 890 850 850 1900
d.c. W 500 520 990 950 950 1700
Average holding value 50 Hz and 60 Hz VA/W 12/3.5 10/2.5 12/4 12/4.5 12/4 48/17
d.c. W 2 2 4 4.5 4 16
Operating time coil supply between A1-A2 On request or see www.abb.com/lowvoltage or local ABB catalog
Mounting characteristics
Mounting positions - mounting on a vertical plane: any position with a tilt up to ± 30°
- mounting on a horizontal plane: any position with a tilt up to ± 30°, except up-side down
Fixing
- by screws (not supplied) 4 x M5 4 x M6 4 x M8
Technical data
DC contactors GAF and AF
1
DC Circuit
switching
contactors
1.212 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Connections
Points to consider
The above relates to power circuit switching. The SCPD (Short Circuit Protection Device) must comply with applicable
protection rules.
The direction of the current must be as shown on the contactor front label.
Connection bars for connecting three contacts in series are not delivered with the contactor as standard, but are
available as accessories.
For further information regarding connections see Technical paper.
Recommended connection
All three contacts connected in series without the load in between. This connection is recommended in systems according to
the configurations below.
+
Device equipped with
permmanent magnets
IEC 60947-4-1
Ui = 1000V DC
Ith=2050A
Ue = 1000V DC
1G1129
Ie DC-1 = 2050A
GAF2050-10
EN 60947-4-1
All 3 poles must be
connected in series
Alternative connection
The load is placed in between the three contacts in an indirect earhted system or in a fully isolated system. If not connected ac-
cording to the configuration below, a fault to earth could result in one or two contacts breaking the full load which the contactor
is not approved for.
Direct earthed system
Load
Indirect earthed system
(Isolated system)
Load
Load
Indirect earthed system
(Isolated system)
Load
Centre earthed system
Load
+-
+
-
Load
1
DC Circuit
switching
contactors
Low Voltage Products & Systems 1.213
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Approximate dimensions (mm)
GA75
GAE75
70
110 1111
6.56
10
4
10
75 mm EN 50023
35 mm x15 EN 50022
108
72
72
60
90
5
5
5
5
(M6)
82
1111011
6.56
10
4
10
75 mm EN 50023
35 mm x15 EN 50022
108
72
72
60
90
5
5
5
5
(M6)
1
DC Circuit
switching
contactors
1.214 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Approximate dimensions
12
17.5
105
111.5
ø 8.5
35
10
187
160
35.5
196
5
GAF185
AF145, AF185
43.75
10.2
219
14
14012
17.5 180.5
535.5
227
GAF300
AF210 ... AF300
63
186
25 22.5
11.5
268
ø10.5ø6.5 216
48.5 6
278
GAF460
AF400, AF460
72
210
40 22.5
11.5
273
ø12.5ø6.5 242
48.5 6
283
GAF750
AF580, AF750
GAF1650, GAF2050
AF1350, AF1650, AF2050
438
80
104
392 312
136 136
136 9
3
244
47 10
50
27 72
72 72
210
249344
O13
O7
242
48,5 8
GAF1250,
AF1250 Dimensions in mm
Inch converter: 1 mm = 0.0394 in
1
Bar
contactors
Low Voltage Products & Systems 1.215
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Bar contactors
50 to 5000 A
Bar
Contactors
R contactors with variable number of poles and their variants (contactors
with N.C. + N.O. poles, couplers...) are used for controlling power circuits
up to 1000VAC or 1500VDC. They are designed with common standard
components. With the combination of these elements and the adaptation
possibilities, special versions can be provided. Designed for long-lasting
operation and demanding applications, the ABB R contactors are used for
many applications all over the world.
Flexibility of design
Variable number of poles
Adjustable number of auxiliary contacts
Optional combination of N.O. & N.C. poles
Mechanical or magnetic latching available.
Easy maintenance
Direct access to all the components of
the contactor
Complete and didactic instruction manual
Spare parts available
Dedicated service for bar contactors.
Exceptional durability
Mechanical durability up to 10 millions
operating cycles
Mechanical switching frequency up to
1200 cycles per hour
Electrical durability up to 350 000 operat-
ing cycles.
Ideal for heavy duty applications
High making and breaking capacity
Fully compatible with the requirements
of utilization categories AC-3, DC-3 and
DC-5 (control of AC / DC motors for
mining, iron and steel industries...).
Custom-made solutions
More than 60 years' experience in deal-
ing with customers projects
Development of solutions from specifica-
tions
Pre-sales support to identify and define
customer requirements
Specialists available to help you, select
your product or optimize your configura-
tion.
1
Bar
contactors
1.216 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Bar contactors
For heavy duty applications
R contactors meet the particular requirements of each
AC / DC control application up to 5000 A, where the
demands are increasing:
Power distribution
Photovoltaic, hydroelectric power stations
Batteries
Mining
Railway networks and rolling stock
Induction furnaces
Pump stations
Travelling cranes.
Control your AC applications up to 5000 A
AC-1 Rated operational current up to 5000 A
AC-3 Rated power up to 1500 kW (1520 A - 440 V)
Control your DC applications up to 5000 A
DC-1 Rated operational current up to 5000 A
DC-3 / DC-5 Rated operational current up to 2000 A
1500 V with poles in series
1
Bar
contactors
Low Voltage Products & Systems 1.217
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Special applications
AC / DC coupling: LOR.. contactors
Slip ring motor control: FOR.. contactors
AC / DC switching (N.C. / N.O. main poles): NOR & JOR..
contactors
Latching contactors for energy saving and safety require-
ments: AMA or AME contactors
Field discharge: AM(F)-CC-JORE.. contactors
1
Bar
contactors
1.218 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Bar contactors for the AC circuits switching
Recap:
All contactors fulll the IEC 60947-4-1 / EN 60947-4-1 standards.
Utilization category AC-1: max. breaking current = 1.5 x Ie,
max. making current = 1.5 x Ie.
Utilization category AC-3: max. breaking current = 8 x Ie,
max. making current = 10 x Ie.
Contactors with NC poles, magnetic or mechanical latching devices
on request.
Voltage Ue up to 500 V AC
Current Ie up to 5000 A
Contactor
type
AC control circuit IORR800 IORR1000 IORR1400 IORR1700 IORR2100 IORR2500 IORR3200 IORR3800 IORR4500 IORR5100
DC control circuit IORE800 IORE1000 IORE1400 IORE1700 IORE2100 IORE2500 IORE3200 IORE3800 IORE4500 IORE5100
Categories Ue
AC-1 at 40 °C Ie From 85 A to 550 A, select above IOR..-MT 900 A 1000 A 1350 A 1650 A 2000 A 2400 A 3200 A 3800 A 4500 A 5000 A
AC-3
380-415-440 V AC
Ie 800 A 800 A 1060 A 1260 A 1520 A –––––
500 V AC max. Ie 800 A 800 A 1080 A 1220 A 1340 A –––––
AC-3 400 V AC Power 450 kW 450 kW 630 kW 750 kW 900 kW –––––
Voltage Ue up to 1000 V AC
Current Ie up to 4500 A
Contactor
type
AC control circuit
IORR63..-MT IORR125..-MT IORR200..-MT IORR400..-MT IORR500..-MT IORR800..-MT
IORR1400..-MT IORR1700..-MT IORR2100..-MT IORR2500..-MT IORR3200..-MT IORR3800..-MT IORR4500..-MT IORR5100..-MT
DC control circuit
IORE63..-MT IORE125..-MT IORE200..-MT IORE400..-MT IORE500..-MT IORE800..-MT
IORE1400..-MT IORE1700..-MT IORE2100..-MT IORE2500..-MT IORE3200..-MT IORE3800..-MT IORE4500..-MT IORE5100..-MT
Categories Ue
AC-1 at 40 °C Ie 85 A 170 A 260 A 400 A 550 A 800 A 1250 A 1650 A 1850 A 2200 A 3000 A 3500 A 4000 A 4500 A
AC-3 690 V AC Ie 85 A 160 A 260 A 400 A 550 A 800 A 970 A 1170 A 1270 A –––
1000 V AC max. Ie 56 A 105 A 180 A 280 A 380 A 580 A 610 A 680 A 810 A –––––
AC-3 690 V AC Power 80 kW 150 kW 240 kW 400 kW 540 kW 780 kW 1000 kW 1200 kW 1300 kW –––
1
Bar
contactors
Low Voltage Products & Systems 1.219
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Contactor
type
AC control circuit IORR800 IORR1000 IORR1400 IORR1700 IORR2100 IORR2500 IORR3200 IORR3800 IORR4500 IORR5100
DC control circuit IORE800 IORE1000 IORE1400 IORE1700 IORE2100 IORE2500 IORE3200 IORE3800 IORE4500 IORE5100
Categories Ue
AC-1 at 40 °C Ie From 85 A to 550 A, select above IOR..-MT 900 A 1000 A 1350 A 1650 A 2000 A 2400 A 3200 A 3800 A 4500 A 5000 A
AC-3
380-415-440 V AC
Ie 800 A 800 A 1060 A 1260 A 1520 A –––––
500 V AC max. Ie 800 A 800 A 1080 A 1220 A 1340 A –––––
AC-3 400 V AC Power 450 kW 450 kW 630 kW 750 kW 900 kW –––––
Contactor
type
AC control circuit
IORR63..-MT IORR125..-MT IORR200..-MT IORR400..-MT IORR500..-MT IORR800..-MT
IORR1400..-MT IORR1700..-MT IORR2100..-MT IORR2500..-MT IORR3200..-MT IORR3800..-MT IORR4500..-MT IORR5100..-MT
DC control circuit
IORE63..-MT IORE125..-MT IORE200..-MT IORE400..-MT IORE500..-MT IORE800..-MT
IORE1400..-MT IORE1700..-MT IORE2100..-MT IORE2500..-MT IORE3200..-MT IORE3800..-MT IORE4500..-MT IORE5100..-MT
Categories Ue
AC-1 at 40 °C Ie 85 A 170 A 260 A 400 A 550 A 800 A 1250 A 1650 A 1850 A 2200 A 3000 A 3500 A 4000 A 4500 A
AC-3 690 V AC Ie 85 A 160 A 260 A 400 A 550 A 800 A 970 A 1170 A 1270 A –––
1000 V AC max. Ie 56 A 105 A 180 A 280 A 380 A 580 A 610 A 680 A 810 A –––––
AC-3 690 V AC Power 80 kW 150 kW 240 kW 400 kW 540 kW 780 kW 1000 kW 1200 kW 1300 kW –––
1
Bar
contactors
1.220 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Voltage Ue up to 1500VDC
Current Ie up to 5000 A
Contactor
type
AC control circuit
IORR63..-CC IORR125..-CC IORR200..-CC IORR400..-CC IORR500..-CC
IORR800..-CC IORR1000..-CC IORR1400..-CC IORR1700..-CC IORR2100..-CC IORR2500..-CC IORR3200..-CC IORR3800..-CC IORR4500..-CC IORR5100..-CC
DC control circuit
IORE63..-CC IORE125..-CC IORE200..-CC IORE400..-CC IORE500..-CC
IORE800..-CC IORE1000..-CC IORE1400..-CC IORE1700..-CC IORE2100..-CC IORE2500..-CC IORE3200..-CC IORE3800..-CC IORE4500..-CC IORE5100..-CC
Number of poles
in series*
Categories Ue max. Ue max.
1 pole DC-1 500VDC Ie 85 A 170 A 275 A 400 A 550 A 750VDC 800 A 1000 A 1250 A 1600 A 2000 A 2300 A 3200 A 3800 A 4500 A 5000 A
DC-3 / DC-5 500VDC Ie 68 A 140 A 205 A 350 A 500 A 600VDC 720 A 1000 A 1250 A 1600 A 2000 A On request On request On request On request On request
2 poles DC-1 1000VDC Ie 85 A 170 A 275 A 400 A 550 A 1500VDC 800 A 1000 A 1250 A 1600 A 2000 A 2300 A 3200 A 3800 A 4500 A 5000 A
DC-3 / DC-5 1000VDC Ie 68 A 140 A 205 A 350 A 500 A 1000VDC 720 A 1000 A 1250 A 1600 A 2000 A On request On request On request On request On request
3 poles DC-1 1500VDC Ie 85 A** 170 A** 275 A** 400 A** 550 A** 1500VDC 800 A 1000 A 1250 A 1600 A 2000 A 2300 A 3200 A 3800 A 4500 A 5000 A
DC-3 / DC-5 1500VDC Ie 68 A** 140 A** 205 A** 350 A** 500 A** 1500VDC 720 A 1000 A 1250 A 1600 A 2000 A On request On request On request On request On request
*Number of poles to be tted in series according to the operational voltage and the utilization categories.
**Version with increased insulation for 1000VDC < Ue ≤ 1500VDC, please consult us.
Contactor
type
AC control circuit
IORR800-10-CC IORR1000-10-CC IORR1400-10-CC IORR1700-10-CC IORR2100-10-CC
DC control circuit
IORE800-10-CC IORE1000-10-CC IORE1400-10-CC IORE1700-10-CC IORE2100-10-CC
U max.
1 pole General use 600VDC Ie 800 A 1000 A 1300 A 1700 A 2000 A
Recap:
All contactors fulll the IEC 60947-4-1 / EN 60947-4-1 standards.
Utilization category DC-1: max. breaking current = 1.5 x Ie,
max. making current = 1.5 x Ie.
Utilization categories DC-3 / DC-5: max. breaking current = 4 x Ie,
max. making current = 4 x Ie.
Contactors with NC poles, magnetic or mechanical latching devices
on request.
Voltage Ue up to 600VDC
Current Ie up to 2000 A
Contactors
UL / CSA approved
Bar contactors for the DC circuits switching
1
Bar
contactors
Low Voltage Products & Systems 1.221
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Product overview
Upper terminal plate
for power circuit (network)
CA15.. auxiliary contacts
1 N.O. + 1 N.C. fitted as
standard (extra auxiliary
contacts on request)
2 N.O. main poles with arc chutes Auxiliary frame
for auxiliary contacts
Main frame
for contactor fixing
Connecting terminals
for coil supply
Lower terminal plate
for power circuit (utilization)
Electro-magnet (RR type),
laminated magnetic circuit,
AC coil, direct supply
Contactor
type
AC control circuit
IORR63..-CC IORR125..-CC IORR200..-CC IORR400..-CC IORR500..-CC
IORR800..-CC IORR1000..-CC IORR1400..-CC IORR1700..-CC IORR2100..-CC IORR2500..-CC IORR3200..-CC IORR3800..-CC IORR4500..-CC IORR5100..-CC
DC control circuit
IORE63..-CC IORE125..-CC IORE200..-CC IORE400..-CC IORE500..-CC
IORE800..-CC IORE1000..-CC IORE1400..-CC IORE1700..-CC IORE2100..-CC IORE2500..-CC IORE3200..-CC IORE3800..-CC IORE4500..-CC IORE5100..-CC
Number of poles
in series*
Categories Ue max. Ue max.
1 pole DC-1 500VDC Ie 85 A 170 A 275 A 400 A 550 A 750VDC 800 A 1000 A 1250 A 1600 A 2000 A 2300 A 3200 A 3800 A 4500 A 5000 A
DC-3 / DC-5 500VDC Ie 68 A 140 A 205 A 350 A 500 A 600VDC 720 A 1000 A 1250 A 1600 A 2000 A On request On request On request On request On request
2 poles DC-1 1000VDC Ie 85 A 170 A 275 A 400 A 550 A 1500VDC 800 A 1000 A 1250 A 1600 A 2000 A 2300 A 3200 A 3800 A 4500 A 5000 A
DC-3 / DC-5 1000VDC Ie 68 A 140 A 205 A 350 A 500 A 1000VDC 720 A 1000 A 1250 A 1600 A 2000 A On request On request On request On request On request
3 poles DC-1 1500VDC Ie 85 A** 170 A** 275 A** 400 A** 550 A** 1500VDC 800 A 1000 A 1250 A 1600 A 2000 A 2300 A 3200 A 3800 A 4500 A 5000 A
DC-3 / DC-5 1500VDC Ie 68 A** 140 A** 205 A** 350 A** 500 A** 1500VDC 720 A 1000 A 1250 A 1600 A 2000 A On request On request On request On request On request
*Number of poles to be tted in series according to the operational voltage and the utilization categories.
**Version with increased insulation for 1000VDC < Ue ≤ 1500VDC, please consult us.
1
Bar
contactors
1.222 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
F
H
W
D
Questionnaire
Specification for R contactors
Control circuit (coil)
AC Voltage ..................... V ............... Hz
DC Voltage ..................... V DC
Options
Magnetical latching
Mechanical latching
Auxiliary contacts
Number of N.O. auxiliary contacts
............
Number of N.C. auxiliary contacts
.............
Replacement of an existing contactor
Brand ................................................................
Type ..................................................................
Fixing dimension F = ............... mm
Overall dimensions W = ............... mm
H = ............... mm
D = ............... mm
Customer .................................................................................................................
Contact person ...................................................... Date ..............................
Tel. .......................................................... e-mail ..................................................
ABB .............................................................................................................................
Contact person ....................................................................................................
Tel. ...............................................................................................................................
Operating conditions
Switching frequency ............................................. cycles/h
Mech. durability required (millions of operating cycles) ..............
Remarks ..........................................................................................
Please add any other useful documents for further information e.g. technical specication, drawing, wiring diagram, etc.
Accessories .............................................................................................................................................................................................................................................
Power circuit
AC switching
Application type
AC-1 (resistive load)
AC-3 (direct starting, switching off running motors)
No load breaking
Other ..............................................................................................
Number of poles: N.O. ..................... N.C. .....................
Rated operational current Ie .................. A
Max. making current ............................ A
Max. breaking current ......................... A
Rated operational voltage Ue ............... V ............... Hz
or
DC switching
Application type
DC-1 (resistive load)
DC-3 (shunt motors)
DC-5 (series motors)
No load breaking
Other ....................................... L/R .............. ms
Number of poles: N.O. ..................... N.C. .....................
Rated operational current Ie .................. A
Making current ........................................ A
Breaking current min. .......... A max. .......... A
Rated operational voltage Ue ............... V DC
Quantity ................... Requested delivery date .....................................
Project / Application ...........................................................................................................................................................................................................................................
Please photocopy and forward. Questionnaire also available on the ABB Website:
www.abb.com/lowvoltage Section: Our offering Select: Control Products > Contactors > Bar mounted contactors
1
Bar
contactors
Low Voltage Products & Systems 1.223
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Please photocopy and forward. Questionnaire also available on the ABB Website:
www.abb.com/lowvoltage Section: Our offering Select: Control Products > Contactors > Bar mounted contactors
Other information / Application type
This document is used to define the contactor specification according to the complete information on the application
1
Bar
contactors
1.224 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Notes