- 2 -
Anderson Power Products® has lead the connector industry
in development of DC power connection solutions since the
introduction of the SB® electrical connector in 1953. Saf-D-Grid®
builds on the proven contact technology used in SB® and
Powerpole® connectors by offering features required in 380-400
VDC power distribution systems.
APP® introduced the Saf-D-Grid® connector system in January
2009 as a safe appliance power connector for server, telecom-
munication, and other devices up to 600 VDC.
The APP® Saf-D-Grid® plug and receptacle provide for the
direct connection of DC electronic devices to a DC micro-grid
powered by renewable energy or high efciency DC sources.
The connector meets international safety requirements for
hazardous, low voltage applications including UL 950 and IEC
60950. The Saf-D-Grid® is size compatible with the IEC 320
C13 and C14 AC connection system. It is the only connector
system so sized that is UL rated for disconnect of a 400 VDC,
20 amp load.
Saf-D-Grid® also enables greater power density by allowing up
to 40A and 600V DC or AC within the same space of the IEC
320 C13 & C14 system that is limited to 10A and 250 VAC.
This allows the use of Saf-D-Grid® in AC systems that require
more power by increasing the wattage capability within the
existing connector space.
Safe Connections for Higher Voltage Power Distribution Systems
Materials (RoHS Compliant)
Housings
• 2006G1 Series Receptacles Hi Temp Nylon + 30% GF, UL94 V-0, Halogen Free
All other Receptacles & Plugs Polycarbonate UL94 V-0
Springs Stainless Steel
Contacts Copper, Silver Plate
Cable / Strain Relief Thermoplastic UL94 V-2
Electrical
Voltage (AC/DC)
• UL 1977 / CSA 22.2 600
• IEC 400
Current Rating (Amperes) 40
Wire Range (AWG) #12 to #18
(mm²) 2.5 to 0.75
Hot Plug Rated
• 250 cycles 400V @ 440A in-rush
• 250 cycles (UL) 400V @ 20A load
Dielectric Withstanding Voltage 3,300
Operating Temperature (°C) -20° to 80°
(°F) -4° to 176°
Fault Current Withstand
UL 467 14 AWG, 300A, 4 Sec.
| SPECIFICATIONS |
Hot Plug Rated
• The connectors are rated for current interruption for both
electronic (capacitive) and electrical (resistive) loads.
Touch Safe / Shock Protection
• Minimizes the risk of personal contact with a hazardous voltage.
Passes UL & IEC nger probe (plug & receptacle) and 3mm probe
tests (receptacle).
Arcing Protection
• Housings contain the arc if connectors are mated or unmated
while under load minimizing risk to personnel.
First Mate, Last Break
Ground Contact
• Provides the safety of an
earthing path before
engagement of the power
contacts.
Integral Latch
• Connectors cannot be
accidentally unmated,
preventing unwanted
power loss to critical
equipment.
Protection
IEC 60529 IP20
A Applicable only to receptacles intended for termination to PCB
B Tested with straight plug and ush mount receptacle with
#14 AWG wire and 2003G1 contacts.
Ultra Short
Receptacle
T-Latch
Straight Plug
Mechanical
Contact Retention (lbf) 20
(N) 89
Plug Latch Retention (lbf) 20
(N) 89
Panel Latch Retention (lbf) 60
(N) 267
Durability 5,000 cycles - no load
Receptacle Max Wire OD (in) 0.22
(mm) 5.6
Creep & Clearance per UL & IEC 60950
Between live parts of different polarity,
earthing circuit and the mating surface.
• Short and Flush Receptacle
with Crimp Contacts 8.0 mm
• Ultra Short Receptacle, Short
and Flush Receptacle
with Solder or PCB Contacts 7.0 mm
Maximum PCB Thickness A (in) 0.093
(mm) 2.4
Mechanical Shock B
IEC 60512-4-6C 50g’s
Vibration, High Frequency B
IEC 60512-4-6d 20g’s
- 3 -
| TEMPERATURE CHARTS |
| UL 1977 & IEC 61984 RATINGS | | UL 817 RATINGS |
3 Note: No IEC 61984 approvals for 2002N, 2002V, 2005N & 2005V series receptacles.
• UL1977 ratings are for recognized components under UL1977 le# E26226. Ratings may vary once the nal listing category is considered. Do not exceed
maximum operating temperature of connector or wire insulation. Ratings are based on an ambient temperature of 25˚C.
• CNR - indicates investigation to Canadian National Standards, C22.2 No. 182.3.
• UL817 recognized or listed cord sets under UL le number E 343569.
• IEC 61984 certication by TUV certication number R 7212289.
• “Disconnect Only” indicates the devices are not for interrupting current.
• “Current Interrupt” indicates the devices have been investigated for the interruption of current.
APP assembly tooling is required for UL, CSA & other safety agency compliance. Use of unapproved tooling will void connector warranty.
• CCC Certication to: GB/T11918-2001: Part 1 (idt IEC 60309-1:1999) & GB/T11919-2001: Part 2 (idt IEC 60309-2:1999)
• CCC Certication is only required for connectors which are built to CCC recognized dimensional & performance standards. Saf-D-Grid was voluntarily submitted to CCC
under performance only aspects of relevant standards.
0
10
20
30
40
50
60
0 5 10 15 20 25 30 35 40 45
Saf-D-Grid
Temperature Rise at Constant Current
A mperes Applied
12 AWG 14 AWG
16 AWG 18 AWG
®
Temperature (°C)
25
35
45
55
65
75
85
0 5 10 15 20 25 30 35 40 45 50
Derating vs. Ambient Temperature
Temperature (°C)
Saf-D-Grid®
Amperes Applied
12 AWG 14 AWG
16 AWG 18 AWG
| CCC RATINGS | - Pending
Rated
Current
Amp
Rated
Voltage
AC / DC
Receptacle
Series
Wire Size
AWG
Conditions
of Use
Ultra Short
2006G
2.5 mm² plug
& receptacle
Current
Interrupt 20 400
Rated
Current
Amp
Rated
Voltage
AC / DC
Receptacle
Series Wire Size
Agency
Rating
Conditions
of Use
CNR 12 600
UL 1977 18 600
Current
Interrupt UL 1977 12 400
CNR 14 600
UL 1977 18 600
Current
Interrupt UL 1977 14 400
Disconnect
Only
Current
Interrupt
Disconnect
Only IEC 61984
3
25 400
UL 1977, CNR
CNR 30 600
UL 1977 40 600
Current
Interrupt UL 1977 30 400
CNR 13 600
IEC 61984 13 400
UL 1977 21 600
IEC 61984 13 400
UL 1977, CNR 12 400
Disconnect
Only
Current
Interrupt
CNR 25 600
IEC 61984 25 400
UL 1977 35 600
UL 1977, CNR
IEC 61984
16 AWG plug
& receptacle
Disconnect
Only
18 AWG plug
& receptacle
Disconnect
Only
20 400
14 AWG plug
& receptacle
18 AWG plug
& receptacle
Disconnect
Only
Current
Interrupt 20
IEC 61984
400
Current
Interrupt
14 AWG plug
& receptacle
12 AWG plug
& receptacle
Disconnect
Only
Disconnect
Only
400
14 400
1.5 mm² plug
& receptacle
1.5 mm² plug
& receptacle IEC 61984
3
14
Current
Interrupt
Flush 2002
& Short 2005
Flush 2002
& Short 2005
Ultra Short
2006G
Flush 2002
& Short 2005
Ultra Short
2006G
Flush 2002
& Short 2005
Ultra Short
2006G
Flush 2002
& Short 2005
IEC 61984
3
Disconnect
Only
(600V Max)
Current
Interrupt
(400V Max)
Straight Plug /
SOOW 600V 14 AWG
18
18
18 AWG
10
10
16 AWG
13
13
14 AWG
18
18
Straight Plug /
SJT 300V 14 AWG
18
18
IEC C20 Plug /
SJT 250V 14 AWG
16
N/A
18 AWG
10
10
16 AWG
13
13
14 AWG
18
18
18 AWG
10
10
16 AWG
13
13
14 AWG
18
18
Connector T ype /
Cable T ype W ire Size
Right Angle Plug /
ST 600V
T-Latch Plug /
ST 600V
Straight Plug /
ST 600V
1 Note: Voltage limited by wire insulation rating
2 Note: Voltage limited by the IEC connector on the cord set
11
2
- 4 -
| PANEL MOUNT RECEPTACLES | - For Crimp Termination to Wire
Short Receptacle
Mid-ange snap-in panel mount
design shortens space required
inside the panel. For use with
crimp wire contacts.
NOTE: Shading Indicates Build to Order
Receptacle Housings Only
Housing Style & Non-Bulk Std. Bulk Std.
Panel Thickness - Part Numbers - Pack - Part Numbers - Pack
Short Depth
0.8mm 2005G1 1 2005G1-BK 100
1.0mm 2005G3 1 2005G3-BK 100
1.6mm 2005G4 1 2005G4-BK 100
Flush Mount
0.8mm 2002G1 1 2002G1-BK 100
1.0mm 2002G3 1 2002G3-BK 100
1.2mm 2002G2 1 2002G2-BK 100
1.6mm 2002G4 1 2002G4-BK 100
2.0mm 2002G5 1 2002G5-BK 100
2.5mm 2002G6 1 2002G6-BK 100
Contact ATS Directly to Purchase or Lease Tooling
P.O. Box 6780, Harrisburg, PA 17112 USA
T: 877-671-2955 F: 717-810-2862
www.applicationtooling.com
Hand Tool
Applicator
| TOOLING |
NOTE: Tooling recommended by APP is required for UL, CSA & other safety
agency compliance. Use of unapproved tooling will void connector warranty.
Press
Contacts - #12 to 18 AWG
Compatible Loose Piece Std. Reeled Std.
Receptacles - Part Numbers - Pack - Part Numbers - Pack
Flush Mount 2003G1-LPBK 1 2003G1 2,500
Crimp Contact
Flush snap-in panel
mount design is
compatible with
crimp wire contacts.
Flush Mount Receptacle
Automated Tooling
Contact
Part Number Description
Hand
Tool Press Applicator
2003G1 Receptacle Contact, Reeled 115V = TE0101
230V = TE0102 TD0104
2003G1-LPBK Receptacle Contact, Loose Piece 1309G9
2003G1 Receptacle Contact, Reeled 354500-1 354578-1 1852859-3
Description Press Air Feed Applicator
Contact
Part Number
Automated Tooling
Additional Tooling Available Directly from ATS (North American Customers Only)
Tooling Available Directly from Anderson Power Products (All Customers)
- 5 -
NOTE: Shading Indicates Build to Order
| PANEL MOUNT RECEPTACLES | - For Solder Termination to Wire
Ultra Short Receptacle
Mid-ange snap in panel mount
design for direct solder wire
termination uses minimal space
inside the panel. Halogen free.
Short Receptacle
Short receptacle housing fully
assembled with contacts for
direct solder wire termination.
Flush Mount Receptacle
Standard receptacle housing fully
assembled with contacts for direct
solder wire termination.
Short Receptacle
Short receptacle housing fully
assembled with PCB contacts
for 0.062 (1.57 mm) to 0.093
(2.36 mm) inch boards.
Flush Mount Receptacle
Standard receptacle housing fully
assembled with PCB contacts for
0.062 (1.57 mm) to 0.093
(2.36 mm) inch boards.
Receptacle Kits (Housing & Contacts)
Termination Panel Non-Bulk Std. Bulk Std.
Housing Type Thickness - Part Numbers - Pack - Part Numbers - Pack
Flush Mount PCB, Solder 0.8mm 2002V1 1 2002V1-BK 100
Flush Mount PCB, Solder 1.0mm 2002V3 1 2002V3-BK 100
Flush Mount PCB, Solder 1.2mm 2002V2 1 2002V2-BK 100
Flush Mount PCB, Solder 1.6mm 2002V4 1 2002V4-BK 100
Short Depth PCB, Solder 0.8mm 2005V1 1 2005V1-BK 100
Short Depth PCB, Solder 1.0mm 2005V3 1 2005V3-BK 100
Short Depth PCB, Solder 1.6mm 2005V4 1 2005V4-BK 100
| PANEL MOUNT RECEPTACLES | - For Solder Termination to PCB
Receptacle Housings Only
Housing Style & Non-Bulk Std. Bulk Std.
Panel Thickness - Part Numbers - Pack - Part Numbers - Pack
Ultra Short Depth
0.8mm 2006G1-NC 1 2006G1-NC-BK 100
1.0mm 2006G3-NC 1 2006G3-NC-BK 100
1.2mm 2006G2-NC 1 2006G2-NC-BK 100
1.6mm 2006G4-NC 1 2006G4-NC-BK 100
2.0mm 2006G5-NC 1 2006G5-NC-BK 100
2.5mm 2006G6-NC 1 2006G6-NC-BK 100
Receptacle Kits (Housing & Contacts)
Termination Panel Non-Bulk Std. Bulk Std.
Housing Type Thickness - Part Numbers - Pack - Part Numbers - Pack
Flush Mount Wire, Crimp* 0.8mm 2002G1KIT 1 N/A N/A
Flush Mount Wire, Crimp* 1.0mm 2002G3KIT 1 N/A N/A
Flush Mount Wire, Crimp* 1.2mm 2002G2KIT 1 N/A N/A
Flush Mount Wire, Crimp* 1.6mm 2002G4KIT 1 N/A N/A
Flush Mount Wire, Solder 0.8mm 2002N1 1 2002N1-BK 100
Flush Mount Wire, Solder 1.0mm 2002N3 1 2002N3-BK 100
Flush Mount Wire, Solder 1.2mm 2002N2 1 2002N2-BK 100
Flush Mount Wire, Solder 1.6mm 2002N4 1 2002N4-BK 100
Short Depth Wire, Crimp* 0.8mm 2005G1KIT 1 N/A N/A
Short Depth Wire, Crimp* 1.0mm 2005G3KIT 1 N/A N/A
Short Depth Wire, Crimp* 1.6mm 2005G4KIT 1 N/A N/A
Short Depth Wire, Solder 0.8mm 2005N1 1 2005N1-BK 100
Short Depth Wire, Solder 1.0mm 2005N3 1 2005N3-BK 100
Short Depth Wire, Solder 1.6mm 2005N4 1 2005N4-BK 100
Ultra Short Depth Wire, Solder 0.8mm 2006G1 1 2006G1-BK 100
Ultra Short Depth Wire, Solder 1.0mm 2006G3 1 2006G3-BK 100
Ultra Short Depth Wire, Solder 1.2mm 2006G2 1 2006G2-BK 100
Ultra Short Depth Wire, Solder 1.6mm 2006G4 1 2006G4-BK 100
Ultra Short Depth Wire, Solder 2.0mm 2006G5 1 2006G5-BK 100
Ultra Short Depth Wire, Solder 2.5mm 2006G6 1 2006G6-BK 100
*Includes Contact Part Number 2003G1 Pre-Terminated to 12 inches of #16 AWG, 600V Wire
Contacts - #14 to 18 AWG
Compatible Loose Piece Std. Reeled Std.
Receptacles - Part Numbers - Pack - Part Numbers - Pack
Ultra Short 2016G1-LPBK 1 - -
NOTE:
• Ultra short contacts are to be used with ultra short depth housings
only, for soldering to stranded copper wire.
Ultra Short Solder Contact
- 6 -
DIM "A"
(3) PLC'S
[ 1.05 ]
26.7 [ 0.78 ]
19.8
[ 1.97 ]
50.1
[ 0.55 ]
14.0
[ 1.42 ]
36.1
[ 0.21 ]
5.3
DIM "A"
(3) PLC'S
[ 2.26 ]
57.4
[ 1.05 ]
26.6 [ 0.77 ]
19.7
[ 1.71 ]
43.5
[ 1.14 ]
29.0
[ 0.55 ]
14.0
Short Depth - For Solder Termination to Wire Short Depth - For Solder Termination to PCB
Flush Mount - For Solder Termination to Wire Flush Mount - For Solder Termination to PCB
| DRAWINGS | - See Product Drawings on the Website for Additional Information
Panel Cut Out for All Receptacle Types
[ 3.08 ]
0.15
[ 2.5 ]
R. 10
MAX TYP.
26.80
1.055
+ 0.10
0.00
+ 0.004
- 0.000
19.90
0.783
+ 0.10
0.00
+ 0.004
- 0.000
[ 22.6 ]
0.89
[ 40.7 ]
1.60 [ 33.4 ]
1.32
[ 24.1 ]
0.95
GROUND
NEGATIVE (-) (+) POSITIVE
[ 29.0 ]
1.14
[ 14.0 ]
0.55
[ 12.4 ]
0.49
GROUND
[ 31.0 ]
1.22
[ 24.0 ]
0.94
NEGATIVE (-) (+) POSITIVE
[ 17.0 ]
0.67
[ 17.1 ]
0.67
[ 31.0 ]
1.22
[ 24.0 ]
0.94
GROUND
NEGATIVE (-) (+) POSITIVE
[ 44.5 ]
1.75
Ultra Short Depth - For Solder Termination to Wire
Short Depth - For Crimp Termination to Wire
Flush Mount - For Crimp Termination to Wire
Ultra Short Contact
Flush Mount & Short Contact
[ 5.0 ]
0.20
[ 5.4 ]
0.21
[ 3.8 ]
0.15
[ 6.4 ]
0.25
[ 26.9 ]
1.06
[ 0.8 ]
0.03
[ 29.6 ]
1.17
[ 5.6 ]
0.22
[ 2.2 ]
0.09
[ 3.8 ]
0.15
[ 3.0 ]
0.12
DIM "A"
(3) PLC'S
[ 2.26 ]
57.4
[ 1.05 ]
26.6
[ 0.77 ]
19.7
[ 2.11 ]
53.6
[ 1.60 ]
40.7
[ 1.97 ]
50.1
[ 1.05 ]
26.6
[ 0.77 ]
19.7
[ 1.82 ]
46.3 REF.
DIM "A"
(3) PLC'S
[ 0.21 ]
5.3
- 7 -
| POWER CORDS | - All Plug Types Mate to All Receptacle Types
Wide “T” Latch Plug Small Latch Plug Right Angle “T” Latch Plug
Small latch release button in the
center top of the plug body.
Wide latch release button across
the top of the plug body to allow
easy latch access around PSU
handles or other obstacles.
Right angle cord over mold to the
plug with wide latch button.
POSITIVE (+)
GROUND
NEGATIVE (-)
[ 1.03 ]
26
[ 0.74 ]
18.9
[ 1.22 ]
31
[ 0.94 ]
23.9
[ 0.74 ]
18.9
[ 0.66 ]
Ø 16.8
[ 1.03 ]
26.0 [ 2.05 ± 0.04 ]
52.0 ± 1.0
[ 2.90 ± 0.04 ]
73.7 ± 1.0
POSITIVE (+)
GROUND
NEGATIVE (-)
POSITIVE (+)
GROUND
NEGATIVE (-)
18 - 14 AWG | 1.0mm² - 2.0mm² 12 AWG
| Common Cable Types Used in Saf-D-Grid® Power Cords |
NOTE: Reference the plug cordset drawings for exact information on the cable used. Some of the above cables may be for special order use only. Plug cordsets that
are available with short lead times are shown in the part number charts of this catalog without a shaded background. Additional cable types may be available on request.
Contact customer service.
Cable
Type
Voltage
Rating Approvals
Jacket
Material
Conductor
Insulation
Conductor Insulation
Coloring Notes
SJT 300V UL, CSA PVC PVC Black, White, Green North American Junior Hard Service, Suitable
for Medium Duties in Office or Home, Not Outdoor Rated
ST 600V UL, CSA PVC PVC Black, White, Green North American Hard Service, Suitable for Medium
Duties in Office or Home, Not Outdoor Rated
SOOW 600V UL, CSA Rubber Rubber Black, White, Green North American Extra Hard Service, Outdoor
Rated, Oil Resistant
HVCT 600V PSE PVC PVC Black, White, Green Japanese, JIS C 3312, Suitable for Medium Duties
in Office or Home, Not Outdoor Rated
H05VVF 300/500V IEC PVC PVC Blue, Brown,
Green/Yellow
International Harmonized, Suitable for Medium
Duties in Office or Home, Not Outdoor Rated
60245
IEC 57
300/500V CCC Rubber Rubber Blue, Brown,
Green/Yellow
Suitable for Low Mechanical Stress
Open Air Environment
1. The Same Receptacle is Used on Both the
Power & Load Sides.
2. The Same Plug is Used on Both Sides of the
Power Cord.
3. Both Plug & Receptacle Connectors are Touch Safe.
1
2
1
2
Simplied Power Connection Design
3
Wide “T” Latch Plug
Ultra Short
Receptacle 3
- 8 -
Single-Ended “T” Latch Plug Power Cord
Length Non-Bulk Std. Bulk Std.
M FT Description UL 817 TUV CCC * - Part Numbers - Pack - Part Numbers - Pack
2.0 6.56 12 AWG ST UL 600V 90C 2034KZ2 1 2034KZ2-BK 20
3.0 9.84 12 AWG ST UL 600V 90C 2034KZ3 1 2034KZ3-BK 13
6.0 19.68 12 AWG ST UL 600V 90C 2034KZ6 1 2034KZ6-BK 7
2.0 6.56 14 AWG ST UL 600V 90C 2031KZ2 1 2031KZ2-BK 50
3.0 9.84 14 AWG ST UL 600V 90C 2031KZ3 1 2031KZ3-BK 30
6.0 19.68 14 AWG ST UL 600V 90C 2031KZ6 1 2031KZ6-BK 6
2.0 6.56 16 AWG ST UL 600V 90C 2036KZ2 1 2036KZ2-BK 50
3.0 9.84 16 AWG ST UL 600V 90C 2036KZ3 1 2036KZ3-BK 30
6.0 19.68 16 AWG ST UL 600V 90C 2036KZ6 1 2036KZ6-BK 6
2.0 6.56 18 AWG ST UL 600V 90C 2033KZ2 1 2033KZ2-BK 50
3.0 9.84 18 AWG ST UL 600V 90C 2033KZ3 1 2033KZ3-BK 30
6.0 19.68 18 AWG ST UL 600V 90C 2033KZ6 1 2033KZ6-BK 6
2.0 6.56 1.0 mm² H05VVF CE 500/300V 75C 2043KZ2 1 2043KZ2-BK 50
3.0 9.84 1.0 mm² H05VVF CE 500/300V 75C 2043KZ3 1 2043KZ3-BK 30
6.0 19.68 1.0 mm² H05VVF CE 500/300V 75C 2043KZ6 1 2043KZ6-BK 6
2.0 6.56 1.5 mm² H05VVF CE 500/300V 75C 2047KZ2 1 2047KZ2-BK 50
3.0 9.84 1.5 mm² H05VVF CE 500/300V 75C 2047KZ3 1 2047KZ3-BK 30
6.0 19.68 1.5 mm² H05VVF CE 500/300V 75C 2047KZ6 1 2047KZ6-BK 6
2.0 6.56 2.5 mm² 60245 IEC 57 / CCC 500/300V 60C 2045KZ2 1 2045KZ2-BK 50
3.0 9.84 2.5 mm² 60245 IEC 57 / CCC 500/300V 60C 2045KZ3 1 2045KZ3-BK 30
6.0 19.68 2.5 mm² 60245 IEC 57 / CCC 500/300V 60C 2045KZ6 1 2045KZ6-BK 6
2.0 6.56 1.0 mm² HVCT PSE 600V 75C 2023KZ2 1 2023KZ2-BK 50
3.0 9.84 1.0 mm² HVCT PSE 600V 75C 2023KZ3 1 2023KZ3-BK 30
6.0 19.68 1.0 mm² HVCT PSE 600V 75C 2023KZ6 1 2023KZ6-BK 6
2.0 6.56 1.25 mm² HVCT PSE 600V 75C 2025KZ2 1 2025KZ2-BK 50
3.0 9.84 1.25 mm² HVCT PSE 600V 75C 2025KZ3 1 2025KZ3-BK 30
6.0 19.68 1.25 mm² HVCT PSE 600V 75C 2025KZ6 1 2025KZ6-BK 6
2.0 6.56 2.0 mm² HVCT PSE 600V 75C 2021KZ2 1 2021KZ2-BK 50
3.0 9.84 2.0 mm² HVCT PSE 600V 75C 2021KZ3 1 2021KZ3-BK 30
6.0 19.68 2.0 mm² HVCT PSE 600V 75C 2021KZ6 1 2021KZ6-BK 6
* CCC Pending
Single-Ended Small Latch Plug Power Cord
Length Non-Bulk Std. Bulk Std.
M FT Description UL 817 TUV - Part Numbers - Pack - Part Numbers - Pack
2.0 6.56 12 AWG ST UL 600V 90C 2034G2 1 2034G2-BK 20
3.0 9.84 12 AWG ST UL 600V 90C 2034G3 1 2034G3-BK 13
6.0 19.68 12 AWG ST UL 600V 90C 2034G6 1 2034G6-BK 7
2.0 6.56 14 AWG ST UL 600V 90C 2030G2 1 2030G2-BK 50
3.0 9.84 14 AWG ST UL 600V 90C 2030G3 1 2030G3-BK 30
6.0 19.68 14 AWG ST UL 600V 90C 2030G6 1 2030G6-BK 6
2.0 6.56 18 AWG ST UL 600V 90C 2032G2 1 2032G2-BK 50
3.0 9.84 18 AWG ST UL 600V 90C 2032G3 1 2032G3-BK 30
6.0 19.68 18 AWG ST UL 600V 90C 2032G6 1 2032G6-BK 6
2.0 6.56 1.5 mm² H05VVF CE 500/300V 75C 2040G2 1 2040G2-BK 50
3.0 9.84 1.5 mm² H05VVF CE 500/300V 75C 2040G3 1 2040G3-BK 30
6.0 19.68 1.5 mm² H05VVF CE 500/300V 75C 2040G6 1 2040G6-BK 6
1.5 4.92 2.0 mm² HVCT PSE 600V 75C 2020G1 1 2020G1-BK 50
2.0 6.56 2.0 mm² HVCT PSE 600V 75C 2020G2 1 2020G2-BK 50
3.0 9.84 2.0 mm² HVCT PSE 600V 75C 2020G3 1 2020G3-BK 30
6.0 19.68 2.0 mm² HVCT PSE 600V 75C 2020G6 1 2020G6-BK 6
NOTE: Shading Indicates Build to Order
Top View
Single Ended Plug Assembly
L
Top View
Single Ended Plug Assembly
L
- 9 -
Single-Ended Right Angle “T” Latch Plug Power Cord
Length Non-Bulk Std. Bulk Std.
M FT Description UL 817 TUV - Part Numbers - Pack - Part Numbers - Pack
2.0 6.56 14 AWG ST UL 600V 90C 2031LZ2 1 2031LZ2-BK 50
3.0 9.84 14 AWG ST UL 600V 90C 2031LZ3 1 2031LZ3-BK 30
6.0 19.68 14 AWG ST UL 600V 90C 2031LZ6 1 2031LZ6-BK 6
2.0 6.56 16 AWG ST UL 600V 90C 2036LZ2 1 2036LZ2-BK 50
3.0 9.84 16 AWG ST UL 600V 90C 2036LZ3 1 2036LZ3-BK 30
6.0 19.68 16 AWG ST UL 600V 90C 2036LZ6 1 2036LZ6-BK 6
2.0 6.56 18 AWG ST UL 600V 90C 2033LZ2 1 2033LZ2-BK 50
3.0 9.84 18 AWG ST UL 600V 90C 2033LZ3 1 2033LZ3-BK 30
6.0 19.68 18 AWG ST UL 600V 90C 2033LZ6 1 2033LZ6-BK 6
2.0 6.56 2.0 mm² HVCT PSE 600V 75C 2021LZ2 1 2021LZ2-BK 50
3.0 9.84 2.0 mm² HVCT PSE 600V 75C 2021LZ3 1 2021LZ3-BK 30
6.0 19.68 2.0 mm² HVCT PSE 600V 75C 2021LZ6 1 2021LZ6-BK 6
Double-Ended “T” Latch Plug Power Cord
Length Non-Bulk Std. Bulk Std.
M FT Description UL 817 TUV CCC * - Part Numbers - Pack - Part Numbers - Pack
2.0 6.56 12 AWG ST UL 600V 90C 2035KK2 1 2035KK2-BK 20
3.0 9.84 12 AWG ST UL 600V 90C 2035KK3 1 2035KK3-BK 13
6.0 19.68 12 AWG ST UL 600V 90C 2035KK6 1 2035KK6-BK 7
2.0 6.56 14 AWG ST UL 600V 90C 2031KK2 1 2031KK2-BK 50
3.0 9.84 14 AWG ST UL 600V 90C 2031KK3 1 2031KK3-BK 30
6.0 19.68 14 AWG ST UL 600V 90C 2031KK6 1 2031KK6-BK 6
2.0 6.56 16 AWG ST UL 600V 90C 2036KK2 1 2036KK2-BK 50
3.0 9.84 16 AWG ST UL 600V 90C 2036KK3 1 2036KK3-BK 30
6.0 19.68 16 AWG ST UL 600V 90C 2036KK6 1 2036KK6-BK 6
2.0 6.56 18 AWG ST UL 600V 90C 2033KK2 1 2033KK2-BK 50
3.0 9.84 18 AWG ST UL 600V 90C 2033KK3 1 2033KK3-BK 30
6.0 19.68 18 AWG ST UL 600V 90C 2033KK6 1 2033KK6-BK 6
2.0 6.56 1.0 mm² H05VVF CE 500/300V 75C 2043KK2 1 2043KK2-BK 50
3.0 9.84 1.0 mm² H05VVF CE 500/300V 75C 2043KK3 1 2043KK3-BK 30
6.0 19.68 1.0 mm² H05VVF CE 500/300V 75C 2043KK6 1 2043KK6-BK 6
2.0 6.56 1.5 mm² H05VVF CE 500/300V 75C 2047KK2 1 2047KK2-BK 50
3.0 9.84 1.5 mm² H05VVF CE 500/300V 75C 2047KK3 1 2047KK3-BK 30
6.0 19.68 1.5 mm² H05VVF CE 500/300V 75C 2047KK6 1 2047KK6-BK 6
2.0 6.56 2.5 mm² 60245 IEC 57 / CCC 500/300V 60C 2045KK2 1 2045KK2-BK 50
3.0 9.84 2.5 mm² 60245 IEC 57 / CCC 500/300V 60C 2045KK3 1 2045KK3-BK 30
6.0 19.68 2.5 mm² 60245 IEC 57 / CCC 500/300V 60C 2045KK6 1 2045KK6-BK 6
2.0 6.56 1.0 mm² HVCT PSE 600V 75C 2023KK2 1 2023KK2-BK 50
3.0 9.84 1.0 mm² HVCT PSE 600V 75C 2023KK3 1 2023KK3-BK 30
6.0 19.68 1.0 mm² HVCT PSE 600V 75C 2023KK6 1 2023KK6-BK 6
2.0 6.56 1.25 mm² HVCT PSE 600V 75C 2025KK2 1 2025KK2-BK 50
3.0 9.84 1.25 mm² HVCT PSE 600V 75C 2025KK3 1 2025KK3-BK 30
6.0 19.68 1.25 mm² HVCT PSE 600V 75C 2025KK6 1 2025KK6-BK 6
2.0 6.56 2.0 mm² HVCT PSE 600V 75C 2021KK2 1 2021KK2-BK 50
3.0 9.84 2.0 mm² HVCT PSE 600V 75C 2021KK3 1 2021KK3-BK 30
6.0 19.68 2.0 mm² HVCT PSE 600V 75C 2021KK6 1 2021KK6-BK 6
* CCC Pending
NOTE: Shading Indicates Build to Order
L
Top View
L
Double Ended Plug Assembly
- 10 -
Double-Ended Small Latch Plug Power Cord
Length Non-Bulk Std. Bulk Std
M FT Description UL 817 TUV - Part Numbers - Pack - Part Numbers - Pack
2.0 6.56 12 AWG ST UL 600V 90C 2035G2 1 2035G2-BK 20
3.0 9.84 12 AWG ST UL 600V 90C 2035G3 1 2035G3-BK 13
6.0 19.68 12 AWG ST UL 600V 90C 2035G6 1 2035G6-BK 7
2.0 6.56 14 AWG ST UL 600V 90C 2031G2 1 2031G2-BK 50
3.0 9.84 14 AWG ST UL 600V 90C 2031G3 1 2031G3-BK 30
6.0 19.68 14 AWG ST UL 600V 90C 2031G6 1 2031G6-BK 6
2.0 6.56 18 AWG ST UL 600V 90C 2033G2 1 2033G2-BK 50
3.0 9.84 18 AWG ST UL 600V 90C 2033G3 1 2033G3-BK 30
6.0 19.68 18 AWG ST UL 600V 90C 2033G6 1 2033G6-BK 6
2.0 6.56 1.5 mm² H05VVF CE 500/300V 75C 2041G2 1 2041G2-BK 50
3.0 9.84 1.5 mm² H05VVF CE 500/300V 75C 2041G3 1 2041G3-BK 30
6.0 19.68 1.5 mm² H05VVF CE 500/300V 75C 2041G6 1 2041G6-BK 6
2.0 6.56 2.0 mm² HVCT PSE 600V 75C 2021G2 1 2021G2-BK 50
3.0 9.84 2.0 mm² HVCT PSE 600V 75C 2021G3 1 2021G3-BK 30
6.0 19.68 2.0 mm² HVCT PSE 600V 75C 2021G6 1 2021G6-BK 6
Double-Ended “T” Latch / IEC C20 Power Cord
Length Non-Bulk Std. Bulk Std.
M FT Description UL 817 TUV* - Part Numbers - Pack - Part Numbers - Pack
2.0 6.56 14 AWG SJT UL 250V 105C 2052KH2 1 2052KH2-BK 50
3.0 9.84 14 AWG SJT UL 250V 105C 2052KH3 1 2052KH3-BK 30
6.0 19.68 14 AWG SJT UL 250V 105C 2052KH6 1 2052KH6-BK 6
* TUV applies only to Saf-D-Grid® connector side.
Double-Ended Right Angle “T” Latch / Straight “T” Latch Plug Power Cord
Length Non-Bulk Std. Bulk Std.
M FT Description UL 817 TUV - Part Numbers - Pack - Part Numbers - Pack
2.0 6.56 14 AWG ST UL 600V 90C 2031KL2 1 2031KL2-BK 50
3.0 9.84 14 AWG ST UL 600V 90C 2031KL3 1 2031KL3-BK 30
6.0 19.68 14 AWG ST UL 600V 90C 2031KL6 1 2031KL6-BK 6
2.0 6.56 16 AWG ST UL 600V 90C 2036KL2 1 2036KL2-BK 50
3.0 9.84 16 AWG ST UL 600V 90C 2036KL3 1 2036KL3-BK 30
6.0 19.68 16 AWG ST UL 600V 90C 2036KL6 1 2036KL6-BK 6
2.0 6.56 18 AWG ST UL 600V 90C 2033KL2 1 2033KL2-BK 50
3.0 9.84 18 AWG ST UL 600V 90C 2033KL3 1 2033KL3-BK 30
6.0 19.68 18 AWG ST UL 600V 90C 2033KL6 1 2033KL3-BK 6
2.0 6.56 2.0 mm² HVCT PSE 600V 75C 2021KL2 1 2021KL2-BK 50
3.0 9.84 2.0 mm² HVCT PSE 600V 75C 2021KL3 1 2021KL3-BK 30
6.0 19.68 2.0 mm² HVCT PSE 600V 75C 2021KL6 1 2021KL6-BK 6
NOTE: Shading Indicates Build to Order
L
Top View
L
Top View
IEC C20 Plug
Saf-D-Grid Plug
L
- 11 -
Double-Ended Right Angle “T” Latch / Right Angle “T” Latch Power Cord
Length Non-Bulk Std. Bulk Std.
M FT Description UL 817 TUV - Part Numbers - Pack - Part Numbers - Pack
2.0 6.56 14 AWG ST UL 600V 90C 2031LL2 1 2031LL2-BK 50
3.0 9.84 14 AWG ST UL 600V 90C 2031LL3 1 2031LL3-BK 30
6.0 19.68 14 AWG ST UL 600V 90C 2031LL6 1 2031LL6-BK 6
2.0 6.56 16 AWG ST UL 600V 90C 2036LL2 1 2036LL2-BK 50
3.0 9.84 16 AWG ST UL 600V 90C 2036LL3 1 2036LL3-BK 30
6.0 19.68 16 AWG ST UL 600V 90C 2036LL6 1 2036LL6-BK 6
2.0 6.56 18 AWG ST UL 600V 90C 2033LL2 1 2033LL2-BK 50
3.0 9.84 18 AWG ST UL 600V 90C 2033LL3 1 2033LL3-BK 30
6.0 19.68 18 AWG ST UL 600V 90C 2033LL6 1 2033LL6-BK 6
2.0 6.56 2.0 mm² HVCT PSE 600V 75C 2021LL2 1 2021LL2-BK 50
3.0 9.84 2.0 mm² HVCT PSE 600V 75C 2021LL3 1 2021LL3-BK 30
6.0 19.68 2.0 mm² HVCT PSE 600V 75C 2021LL6 1 2021LL6-BK 6
Double-Ended Right Angle “T” Latch / Left Angle “T” Latch Power Cord
Length Non-Bulk Std. Bulk Std.
M FT Description UL 817 TUV - Part Numbers - Pack - Part Numbers - Pack
2.0 6.56 14 AWG ST UL 600V 90C 2031LM2 1 2031LM2-BK 50
3.0 9.84 14 AWG ST UL 600V 90C 2031LM3 1 2031LM3-BK 30
6.0 19.68 14 AWG ST UL 600V 90C 2031LM6 1 2031LM6-BK 6
2.0 6.56 16 AWG ST UL 600V 90C 2036LM2 1 2036LM2-BK 50
3.0 9.84 16 AWG ST UL 600V 90C 2036LM3 1 2036LM3-BK 30
6.0 19.68 16 AWG ST UL 600V 90C 2036LM6 1 2036LM6-BK 6
2.0 6.56 18 AWG ST UL 600V 90C 2033LM2 1 2033LM2-BK 50
3.0 9.84 18 AWG ST UL 600V 90C 2033LM3 1 2033LM3-BK 30
6.0 19.68 18 AWG ST UL 600V 90C 2033LM6 1 2033LM6-BK 6
2.0 6.56 2.0 mm² HVCT PSE 600V 75C 2021LM2 1 2021LM2-BK 50
3.0 9.84 2.0 mm² HVCT PSE 600V 75C 2021LM3 1 2021LM3-BK 30
6.0 19.68 2.0 mm² HVCT PSE 600V 75C 2021LM6 1 2021LM6-BK 6
NOTE: Shading Indicates Build to Order
L
L
All Data Subject To Change Without Notice 15709 DS-SDG REV 15
HEADQUARTERS: Anderson Power Products®, 13 Pratts Junction Road, Sterling, MA 01564-2305 USA T:978-422-3600 F:978-422-0128 • EUROPE: Anderson Power Products® Ltd.,
Unit 3, Europa Court, Europa Boulevard, Westbrook, Warrington, Cheshire, WA5 7TN United Kingdom T: +44 (0) 1925 428390 F: +44 (0) 1925 520203 • ASIA / PACIFIC: IDEAL Anderson
Asia Pacic Ltd., Unit 922-928 Topsail Plaza, 11 On Sum Street, Shatin N.T., Hong Kong T:+(852) 2636 0836 F:+(852) 2635 9036 CHINA: IDEAL Anderson Technologies (Shenzhen) Ltd.,
Block A8 Tantou Western Industrial Park, Songgang Baoan District, Shenzhen, PR. China 518105 T: +(86) 755 2768 2118 F: +(86) 755 2768 2218 • TAIWAN: IDEAL Anderson Asia Pacic
Ltd., Taiwan Branch, 4F.-2, No.116, Dadun 20th St., Situn District, Taichung City 407, Taiwan (R.O.C.) T: +(886) 4 2310 6451 F:+(886) 4 2310 6460 • www.andersonpower.com
“Saf-D-Grid, APP and Anderson Power Products are registered trademarks of Anderson Power Products”
DC Electrical Power Distribution Systems
DC Efciency
DC electrical distribution systems have a basic advantage over AC systems. By eliminating AC to DC conversions a DC distribution system is simpler than
an AC system. With less electrical and electronic devices, a DC system can be designed with lower electrical losses and higher reliability. These advan-
tages are further multiplied for systems having DC energy storage for backup power or peak shaving, or a local DC energy source such as photovoltaic
cells, wind turbines or fuel cells.
Standardization
APP® has been a leader in the development of system and product safety standards for low voltage DC. We are active on key product and safety commit-
tees within the EMerge Alliance®, NEMA and the IEC.
Saf-D-Grid® meets or exceeds all relevant industry safety standards. The product has also been successfully tested to new product safety standards under
consideration for adoption.
On September 26, 2012 the Emerge Alliance® board of directors ratied the Emerge Standard for DC Power Distribution Systems (DC-PDS) in Data &
Telecom Centers (DTC). Within the Standard, the APP® Saf-D-Grid® connector system is designated as the interconnection of choice for power strip,
power cord and device inlet power connections.
DC Arcing
AC system voltage phases cause the voltage to pass through zero at some point during the disconnection sequence. This zero crossing signicantly
reduces the damage to a contact system from an AC arc. DC arcing is more destructive to contact systems due to the lack of phasing to a zero voltage
point. The APP® Saf-D-Grid® connector overcame this technical challenge by using adequate contact mass, arc reducing geometry, and a sacricial
contact tip. Saf-D-Grid® has undamaged electrical contact surfaces after 250 DC arcing cycles.
DC Safety
There is near global acceptance that 380V is the most practical voltage for low voltage DC distribution systems. By using a center-point ground, a +/- 190
volt DC distribution system can be constructed which has lower risk of electrocution than the 200-250 VAC systems installed throughout the world. The
system can additionally be made safe by using connectors such as Saf-D-Grid®, which meet IEC and UL nger probe requirements for touch safety and
have a latching system to avoid accidental disconnection. Saf-D-Grid® also has adequate voltage isolation to contain arcing from disconnection within the
insulating housings. Video of the disconnection of APP® Saf-D-Grid® connectors under load shows extinguishing of the internal arc well in advance of the
connector separation and potential exposure to the user.
EMerge Alliance is a registered trademark of the EMerge Alliance Industry Association
NEMA is a registered trademark of the National Electric Manufacturers Association
The Saf-D-Grid® connector
applies to power supplies and
PDU’s inside information and