Relay socket with industrial relay
Coil voltage: 24 V DC
4 changeover contacts
Relay socket with industrial relay
Coil voltage: 24 V DC
4 changeover contacts (gold contacts)
Series 858, Relay Sockets with Industrial Relay
Description Item No. Pack. Unit Item No. Pack. Unit
Relay socket with industrial relay, for DIN 35 rail 858-304 1 858-314 1
Technical Data
Coil
Coil voltage 24 V DC 24 V DC
Rated Power 0.9 W 0.9 W
Coil Current 36.9 mA 36.9 mA
Operating Range 0.8 - 1.1 x V 0.8 - 1.1 x V
Holding Voltage 50% of VN50% of VN
Release Voltage 0.1 x V 0.1 x V
Contacts
Contact Material AgCe AgCe + 5 μm Au
Continuous Current 5 A 50 mA*
Inrush Current 15 A/4 s 15 A/4 s
Max. Switching Voltage 250 V AC/ 30 V DC 30 V DC *
Switching Power (Max.) AC1/AC15 1250 VA/300 VA 1250 VA/300 VA
1-Phase Motor Load AC3 0.12 kW 0.12 kW
Switching Current (Max.) DC1 5 A at 30 V DC 5 A at 30 V DC
Min. Switching Load 12 V/100 mA 12 V/100 mA
Switching Frequency Under Load 20 cycles/min. 20 cycles/min.
General Specifications
Mechanical Life 20 x 106 switching operations 20 x 106 switching operations
Electrical Life 1 x 105 switching operations 1 x 105 switching operations
Response Time/Drop-Out Time/Bounce Time (typ.) 25 ms/25 ms/4 ms 25 ms/25 ms/4 ms
Nominal Voltage Acc. to VDE 0110 Part 1/4.97,
IEC 60664-1 250 V/2.5 kV/2 250 V/2.5 kV/2
Dielectric Strength Contact-Coil (1.2/50 μs) 4 kV 4 kV
Dielectric Strength Contact-Coil (AC, 1 min) 1.5 kV 1.5 kV
Dielectric Strength Open Contact 1 kV 1 kV
Dielectric Strength Contact-Contact 1.5 kV 1.5 kV
Ambient Operating Temperature -25oC - +70oC -25oC - +70oC
Storage Temperature -40oC - +80oC -40oC - +80oC
Dimensions (mm) W x H x L 31 x 73 x 97, Height from upper-edge of DIN 35 rail 31 x 73 x 97, Height from upper-edge of DIN 35 rail
Wire Connecion CAGE CLAMP®S CAGE CLAMP®S
Cross Sections 2 x 0.34 mm2 - 2 x 1.5 mm2/1 x 2.5 mm2/22 - 16 AWG 2 x 0.34 mm2 - 2 x 1.5 mm2/1 x 2.5 mm2/22 - 16 AWG
Stripped Lengths 9 - 10 mm/0.37 in 9 - 10 mm/0.37 in
14
34
24
44
12
32
22
42
11
31
21
41
A1
-
A2
+
14
34
24
44
12
32
22
42
11
31
21
41
A1
-
A2
+
* In order to prevent the gold layer from being dam-
aged, these values shall not be exceeded. Higher
switching power leads to evaporation of the gold layer.
The resulting deposits in the enclosure may cause
sparkovers between the coil and the contact.
Relay socket with industrial relay
Coil voltage: 120 V AC
4 changeover contacts
Relay socket with industrial relay
Coil voltage: 120 V AC
4 changeover contacts (gold contacts)
Series 858, Relay Sockets with Industrial Relay
Description Item No. Pack. Unit Item No. Pack. Unit
Relay socket with industrial relay, for DIN 35 rail 858-507 1 858-517 1
Technical Data
Coil
Coil voltage 120 V AC 120 V AC
Rated Power 1.2 VA 1.2 VA
Coil Current 15 mA 15 mA
Operating Range 0.8 - 1.1 x V 0.8 - 1.1 x V
Holding Voltage 80% of VN80% of VN
Release Voltage 0.3 x V 0.3 x V
Contacts
Contact Material AgCe AgCe + 5 μm Au
Continuous Current 5 A 50 mA*
Inrush Current 15 A/4 s 15 A/4 s
Max. Switching Voltage 250 V AC/ 30 V DC 30 V DC *
Switching Power (Max.) AC1/AC15 1250 VA/300 VA 1250 VA/300 VA
1-Phase Motor Load AC3 0.12 kW 0.12 kW
Switching Current (Max.) DC1 5 A at 30 V DC 5 A at 30 V DC
Min. Switching Load 12 V/100 mA 12 V/100 mA
Switching Frequency Under Load 20 cycles/min. 20 cycles/min.
General Specifications
Mechanical Life 20 x 106 switching operations 20 x 106 switching operations
Electrical Life 1 x 105 switching operations 1 x 105 switching operations
Response Time/Drop-Out Time/Bounce Time (typ.) 25 ms/25 ms/4 ms 25 ms/25 ms/4 ms
Nominal Voltage Acc. to VDE 0110 Part 1/4.97,
IEC 60664-1 250 V/2.5 kV/2 250 V/2.5 kV/2
Dielectric Strength Contact-Coil (1.2/50 μs) 4 kV 4 kV
Dielectric Strength Contact-Coil (AC, 1 min) 1.5 kV 1.5 kV
Dielectric Strength Open Contact 1 kV 1 kV
Dielectric Strength Contact-Contact 1.5 kV 1.5 kV
Ambient Operating Temperature -25oC - +70oC -25oC - +70oC
Storage Temperature -40oC - +80oC -40oC - +80oC
Dimensions (mm) W x H x L 31 x 73 x 97, Height from upper-edge of DIN 35 rail 31 x 73 x 97, Height from upper-edge of DIN 35 rail
Wire Connecion CAGE CLAMP®S CAGE CLAMP®S
Cross Sections 2 x 0.34 mm2 - 2 x 1.5 mm2/1 x 2.5 mm2/22 - 16 AWG 2 x 0.34 mm2 - 2 x 1.5 mm2/1 x 2.5 mm2/22 - 16 AWG
Stripped Lengths 9 - 10 mm/0.37 in 9 - 10 mm/0.37 in
14
34
24
44
12
32
22
42
11
31
21
41
A1
~
A2
~
* In order to prevent the gold layer from being dam-
aged, these values shall not be exceeded. Higher
switching power leads to evaporation of the gold layer.
The resulting deposits in the enclosure may cause
sparkovers between the coil and the contact.
14
34
24
44
12
32
22
42
11
31
21
41
A1
~
A2
~
Relay socket with industrial relay
Coil voltage: 230 V AC
4 changeover contacts
Relay socket with industrial relay
Coil voltage: 230 V AC
4 changeover contacts (gold contacts)
Series 858, Relay Sockets with Industrial Relay
Description Item No. Pack. Unit Item No. Pack. Unit
Relay socket with industrial relay, for DIN 35 rail 858-508 1 858-518 1
Technical Data
Coil
Coil voltage 230 V AC 230 V AC
Rated Power 1.2 VA 1.2 VA
Coil Current 8.3 mA 8.3 mA
Operating Range 0.8 - 1.1 x V 0.8 - 1.1 x V
Holding Voltage 80% of VN80% of VN
Release Voltage 0.3 x V 0.3 x V
Contacts
Contact Material AgCe AgCe + 5 μm Au
Continuous Current 5 A 50 mA*
Inrush Current 15 A/4 s 15 A/4 s
Max. Switching Voltage 250 V AC/ 30 V DC 30 V DC *
Switching Power (Max.) AC1/AC15 1250 VA/300 VA 1250 VA/300 VA
1-Phase Motor Load AC3 0.12 kW 0.12 kW
Switching Current (Max.) DC1 5 A at 30 V DC 5 A at 30 V DC
Min. Switching Load 12 V/100 mA 12 V/100 mA
Switching Frequency Under Load 20 cycles/min. 20 cycles/min.
General Specifications
Mechanical Life 20 x 106 switching operations 20 x 106 switching operations
Electrical Life 1 x 105 switching operations 1 x 105 switching operations
Response Time/Drop-Out Time/Bounce Time (typ.) 25 ms/25 ms/4 ms 25 ms/25 ms/4 ms
Nominal Voltage Acc. to VDE 0110 Part 1/4.97,
IEC 60664-1 250 V/2.5 kV/2 250 V/2.5 kV/2
Dielectric Strength Contact-Coil (1.2/50 μs) 4 kV 4 kV
Dielectric Strength Contact-Coil (AC, 1 min) 1.5 kV 1.5 kV
Dielectric Strength Open Contact 1 kV 1 kV
Dielectric Strength Contact-Contact 1.5 kV 1.5 kV
Ambient Operating Temperature -25oC - +70oC -25oC - +70oC
Storage Temperature -40oC - +80oC -40oC - +80oC
Dimensions (mm) W x H x L 31 x 73 x 97, Height from upper-edge of DIN 35 rail 31 x 73 x 97, Height from upper-edge of DIN 35 rail
Wire Connecion CAGE CLAMP®S CAGE CLAMP®S
Cross Sections 2 x 0.34 mm2 - 2 x 1.5 mm2/1 x 2.5 mm2/22 - 16 AWG 2 x 0.34 mm2 - 2 x 1.5 mm2/1 x 2.5 mm2/22 - 16 AWG
Stripped Lengths 9 - 10 mm/0.37 in 9 - 10 mm/0.37 in
14
34
24
44
12
32
22
42
11
31
21
41
A1
~
A2
~
* In order to prevent the gold layer from being dam-
aged, these values shall not be exceeded. Higher
switching power leads to evaporation of the gold layer.
The resulting deposits in the enclosure may cause
sparkovers between the coil and the contact.
14
34
24
44
12
32
22
42
11
31
21
41
A1
~
A2
~
Relay socket for industrial relays
2 and 4 changeover contacts
Series 858, Relay Sockets for Industrial Relay
Description Item No. Pack. Unit Item No. Pack. Unit
Relay socket for industrial relays, for DIN 35 rail 858-100 1
Technical Data
Nominal Input Voltage (VN) Depending on relay; max. 250 V AC
Max. Switching Voltage 250 V AC
Max. Continuous Current 4 x 8 A (4 changeover contacts);
2 x 12 A (2 changeover contacts)
Max. Switching Power (resistive) 4000 VA AC
Nominal Operating Mode Conituous duty
Voltage Resistance 4 kV (depending on relay)
Nominal Voltage Acc. to VDE 0110 Part 1/4.97,
IEC 60664-1 250 V/4 kV/3
Degree of Protection IP 20
Ambient Operating Temperature -25oC - +70oC (depending on relay)
Storage Temperature -40oC - +80oC
Dimensions (mm) W x H x L 31 x 38 x 97, Height from upper-edge of DIN 35 rail
Wire Connecion CAGE CLAMP®S
Stripped Lengths 9 - 10 mm/0.37 in
Cross Sections 2 x 0.34 mm2 - 2 x 1.5 mm2/1 x 2.5 mm2/22 - 16 AWG
Standards/Specifications IEC60664/IEC60664A/DIN VDE0110
Degree of pollution 2
Overvoltage category 2
41
31
21
11
44
34
24
14
42
32
22
12
A1
A2
Note: Inductive loads have to be attenuated by an
appropriate protective circuit in order to protect relay
coils and contacts.
Pluggable industrial relays
4 changeover contacts with integrated LED
and recovery diode and manual operation
Pluggable industrial relays
4 changeover contacts with integrated LED
and manual operation
Series 858, Accessories for Relay Socket
Description Item No. Pack. Unit Item No. Pack. Unit
Pluggable Industrial Relay 24 V DC 858-150 1 240 V AC 858-151 1
24 V DC* 858-152 1 240 V AC* 858-153 1
Technical Data
Coil
Coil voltage 24 V DC 240 V AC
Rated Power 0.9 W 1.2 W
Coil Current 36.9 mA 8.3 mA
Operating Range 0.8 - 1.1 x V 0.8 - 1.1 x V
Holding Voltage 50% of VN80% of VN
Release Voltage 0.1 x V 0.3 x V
Contacts
Contact Material AgCe, AgCe + 5 μm Au* AgCe, AgCe + 5 μm Au*
Continuous Current 5 A* 5 A*
Inrush Current 15 A/4 s 15 A/4 s
Max. Switching Voltage 250 V AC/ 30 V DC 250 V AC/30 V DC *
Switching Power (Max.) AC1/AC15 1250 VA/300 VA 1250 VA/300 VA
1-Phase Motor Load AC3 0.12 kW 0.12 kW
Switching Current (Max.) DC1 5 A at 30 V DC 5 A at 30 V DC
Min. Switching Load 12 V/100 mA 12 V/100 mA
Switching Frequency Under Load 20 cycles/min. 20 cycles/min.
General Specifications
Mechanical Life 20 x 106 switching operations 20 x 106 switching operations
Electrical Life 1 x 105 switching operations 1 x 105 switching operations
Response Time/Drop-Out Time/Bounce Time (typ.) 25 ms/25 ms/4 ms 25 ms/25 ms/4 ms
Nominal Voltage Acc. to VDE 0110 Part 1/4.97,
IEC 60664-1 250 V/2.5 kV/2 250 V/2.5 kV/2
Dielectric Strength Contact-Coil (1.2/50 μs) 4 kV 4 kV
Dielectric Strength Contact-Coil (AC, 1 min) 1.5 kV 1.5 kV
Dielectric Strength Open Contact 1 kV 1 kV
Dielectric Strength Contact-Contact 1.5 kV 1.5 kV
Ambient Operating Temperature -25oC - +70oC -25oC - +70oC
Mounting Distance in a Row 6 mm 6 mm
Weight approx. 37 g approx. 37 g
Nominal Input
Voltage (VN)
Nominal Input
Voltage (VN)
13.2
4.4
6.4
12.7
16.8
6.3
1234
5678
9101112
13 14
* In order to prevent the gold
layer from being damaged,
these values shall not be
exceeded. Higher switching
power leads to evaporation
of the gold layer. The resulting
deposits in the enclosure may
cause sparkovers between the
coil and the contact.
13.2
4.4
6.4
12.7
16.8
6.3
1234
5678
9101112
13 14
28 max 21,5 max
35 max
5,8
Series 858, Accessories
Description Item No. Pack. Unit
Holding Bracket for Industrial Relays 858-110 8
Description Item No. Pack. Unit
Push-In Type Jumper Bar 858-402 200
Description Power Consumption at VN Item No. Pack. Unit
Status Indication* 2.4 mA 788-120 1
1.9 mA 788-121 1
1.9 mA 788-122 1
2.1 mA 788-123 1
1.7 mA 788-124 1
1.6 mA 788-125 1
WAGO Corporation • N120 W19129 Freistadt Road • Germantown, Wisconsin 53022
Telephone: 800 / DIN Rail (346-7245) • Fax: 262 / 255-3232 • info.us@wago.com • www.wago.us
*Only required when using relays without integrated operating indicator.