Operation Manual Smart-UPSTM X Uninterruptible Power Supply Low Voltage 100-127 VA SMX2000RMLV2U SMX2200RMLV2U SMX3000RMLV2U SMX3000RMLV2UNC SMX3000RMJ2U High Voltage 200-240 VA su0787a SMX2200RMHV2U SMX3000RMHV2U SMX3000RMHV2UNC Product Description The APCTM by Schneider Electric Smart-UPSTM is a high performance uninterruptible power supply (UPS). The UPS provides protection for electronic equipment from utility power blackouts, brownouts, sags, and surges, small utility power fluctuations and large disturbances. The UPS also provides battery backup power for connected equipment until utility power returns to safe levels or the batteries are fully discharged. This user manual is available on the enclosed CD and on the APC by Schneider Electric web site, www.apc.com. Important Safety Messages Read the instructions carefully to become familiar with the equipment before trying to install, operate, service or maintain it. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of this symbol to a Caution product safety label indicates that a hazard exists that can result in injury and product damage if the instructions are not followed. The following safety messages may appear throughout this manual to warn of potential hazards. CAUTION CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage and minor or moderate injury. CAUTION CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage. Safety and General Information Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage. Read the Safety Guide supplied with this unit before installing the UPS. * Adhere to all local and national electrical codes. * This UPS is intended for indoor use only. * Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity. * Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation. * The battery typically lasts for two to five years. Environmental factors impact battery life. Elevated ambient temperatures, poor quality utility power, and frequent short duration discharges will shorten battery life. * Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords. * The batteries are heavy. Remove the batteries prior to installing the UPS in a rack. * Always install external battery packs (XLBPs) at the bottom of the rack. The UPS must be installed above the XLBPs. * The UPS display interface will recognize as many as 10 external battery packs connected to the UPS. However there is no limit to the number of XLBPs that can be used with the UPS. Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U 1 Product Overview Specifications Environmental Specifications For additional specifications, refer to the APC by Schneider Electric web site at www.apc.com. Operating 0 to 40 C (32 to 104 F) Temperature Storage -15 to 45 C (5 to 113 F) charge UPS battery every six months Maximum Elevation Operating 3,000 m (10,000 ft) Storage 15,000 m (50,000 ft) Humidity 0% to 95% relative humidity, non-condensing High and Low Voltage Models Low Voltage (100-127 V) High Voltage (200-240 V) SMX2000RMLV2U SMX2200RMHV2U SMX2200RMLV2U SMX3000RMHV2U SMX3000RMLV2U SMX3000RMHV2UNC SMX3000RMLV2UNC SMX3000RMJ2U 2 Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U Front Panel Features Battery su0498a Battery connector Display interface Bezel Rear Panel Features SmartSlot UPS input Controllable Outlet Group 3 External battery pack connector Chassis ground screw Controllable Outlet Group 1 EPO connector Serial port Controllable Outlet Group 2 USB port 2000 VA Low Voltage Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U su0493a 2200/3000 VA High Voltage su0495a 3000 VA Low Voltage su0492a su0494a 2200 VA Low Voltage 3 Installation UPS For UPS installation information, refer to the Smart-UPS X 2000-3000 VA Installation Guide that is included with the UPS. The guide is also available on the enclosed CD and the APC by Schneider Electric web site at www.apc.com. Network Management Card For installation information, refer to the user manual provided with the Network Management Card (NMC). The user manual is also available on the APC by Schneider Electric web site at www.apc.com. External Battery Pack For installation information, refer to the SMX 120RMBP2U external battery pack Installation Guide that is included with the external battery pack (XLBP). The guide is also available on the enclosed CD and the APC by Schneider Electric web site at www.apc.com. 4 Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U Operation Connect Equipment to the UPS CAUTION RISK OF EQUIPMENT DAMAGE * Adhere to all local and national electrical codes. * Wiring should be performed by qualified electrician. * Always connect the UPS to a grounded outlet. Failure to follow these instructions can result in equipment damage Note: The UPS will charge to 90% capacity in the first three hours of normal operation. Do not expect full battery runtime capability during this initial charge period. 1. Connect equipment to the outlets on the rear panel of the UPS. 2. Connect the UPS to the building utility power. Always connect the UPS to a two pole, three wire, grounded source. 3. To use the UPS as a master ON/OFF switch, turn on all the equipment that is connected to the UPS. 4. Press the ON/OFF button on the front panel of the UPS to turn on the UPS and all connected equipment. su0475a 5. See "Switched Outlet Groups" on page 12 for information on how to use the switched outlet groups. Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U 5 Basic Connections Serial port: Connect to a computer to use power management software, use the serial cable included with the unit. USB port: Connect to a computer to use power management software. Note: Serial and USB communication can not be used simultaneously. External Battery Pack connector: Connect external battery packs to provide extended runtime during power outages. The UPS can support up to 10 external battery packs. Ground Screw: The UPS features a ground screw for connecting the ground leads on transient voltage devices. Prior to connecting a ground lead, disconnect the UPS from utility power. 6 Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U Display Interface Overview Online LED UPS Output On/Off button On Battery LED Site Wiring Fault LED Replace Battery LED Display screen UP/DOWN arrow buttons ENTER button APC By Schneider Electric ESCAPE button su0343a Using the display interface Use the UP/DOWN arrow buttons to scroll through the main menu options. Press ENTER to view the submenu under each main menu option. Press ESCAPE to exit a submenu and return to a main menu. Menu Overview The Smart-UPS has Standard and Advanced menu screens. The Standard menu screens are the most commonly used screens. The Advanced menu screens are for more advanced users to configure additional features on the UPS. Note: Actual menu screens may vary. Main Menu Scrolling Screens Status Overview Standard Advanced On Utility (the UPS is operating on utility power) x Outlet Group Status x Input and Output voltage x Load meter x Battery charge and runtime x Warnings x Load and Battery graphs x Operating Mode x x Efficiency in % (Green mode only) x x Input and output voltage x x Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U 7 Main Menu Overview Load power (W) and VA Configuration Control Test & Diagnostics Statistics Logs 8 Standard Advanced x x Load (A) x Load meter (kWh) x Last transfer to battery power information x x Battery charge and estimated run time x x Battery voltage x Number of external battery packs x Internal battery temperature x Run time calibration test results x x Self-test results x x Status of the switched outlet group(s): On, Off, Sleep, Reboot, Turning On, Turning Off x Smart Slot information (if applicable) x Language x x Local power quality x x Standard or Advanced menus x x Audible alarms x x High and low transfer points x Low run time warning x Green mode (enable/disable) x Output voltage x x Battery self-test interval x x Battery installation date x x UPS firmware update (only available when output is off) x x UPS setup wizard x x Reset to factory defaults x x Switched outlet group(s) delays and settings x Smart Slot configuration (if applicable) x Switched outlet group(s): Turn on, turn off, put to sleep, or reboot x UPS self-test. x x Runtime calibration test. x x Alarm and display test. x x Statistics about transfers to battery power, time on battery, and total operating time x Transfer log x Status log x Fault log x Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U Main Menu About Overview General information about the UPS, including: model numbers, output voltage setting, serial number, manufacture date, replacement battery cartridge information, firmware versions, and suggested battery replacement date. Standard Advanced x x SmartSlot card information (if applicable), including IP address x PowerChute Business Edition information (if applicable) x Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U 9 Configuration UPS Settings Start up Settings Use the display interface to configure these settings at initial start up. The UPS will prompt for a response to each setting, if no response is given, the default setting will be used. Note: The unit will not turn on until all of these settings are entered. Function Language Output Voltage Factory Default Options English * English * French* * German* * Spanish* * Italian* * Portuguese* The language for the display interface. *Language options will vary by model. * 100 * 110 Low Voltage: 120 V * 120 * 127 * 200 * 208 High Voltage: 230 V * 220 * 230 * 240 * Good * Fair * Poor Input Power Good Quality 10 Description Set the output voltage setting while the UPS is in Standby mode. Select the quality of input utility power. * If Good is selected, the unit will go on battery power more often to provide the cleanest power supply to the connected equipment. * If Poor is selected, the UPS will tolerate more fluctuations in power and will go on battery power less often. If unsure of the local power quality, select Good. Menu Type Standard Standard or Advanced The advanced menus include all parameters. The Standard menus display a limited set of menus and options. Date UPS manufacture date + 90 days mm-yyyy Enter the current date. Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U General Settings Configure these settings at any time, using the display interface, PowerChuteTM software, or a network management card. Function Factory Default Options Description Low Voltage 100 V: 108 Vac High Transfer Point 108-114 Vac 110 V: 116 Vac 116-125 Vac 120 V: 127 Vac 127-136 Vac 127 V: 134 Vac 134-143 Vac High Voltage 200 V: 216 Vac 216-228 Vac 208 V: 220 Vac 220-235 Vac 220 V: 242 Vac 242-254 Vac 230 V: 253 Vac 253-265 Vac 240 V: 264 Vac 264-276 Vac To avoid unnecessary battery usage, set the transfer point higher if the utility voltage is chronically high and the connected equipment is known to work under this condition. The POWER QUALITY setting will automatically change this setting. Note: Use the Advanced Menus to configure this setting. Low Voltage Low Transfer Point Green Mode 100 V: 92 Vac 86-92 Vac 110 V: 98 Vac 89-98 Vac 120 V: 106 Vac 97-106 Vac 127 V: 112 Vac 103-112 Vac High Voltage 200 V: 184 Vac 172-184 Vac 208 V: 184 Vac 169-184 Vac 220 V: 198 Vac 186-198 Vac 230 V: 207 Vac 195-207 Vac 240 V: 216 Vac 204-216 Vac If the UPS input voltage is between the high transfer point and the lower transfer point, the unit will operate in green mode. Configure this setting using the Advanced menus. * Normal * Reduced * Low Transfer Sensitivity Set the transfer point lower if the utility voltage is chronically low and the connected equipment can tolerate this condition.The POWER QUALITY setting will automatically change this setting. Note: Use the Advanced Menus to configure this setting. Normal Select the level of sensitivity to power events that the UPS will tolerate. * Normal: The UPS will go on battery power more often to provide the cleanest power supply to the connected equipment. * Reduced: The UPS will tolerate some fluctuations in power. * Low: The UPS will tolerate more fluctuations in power and will go on battery power less often. If the connected load is sensitive to power disturbances, set the sensitivity to Normal using the advanced Configuration menu. Low Runtime Warning 150 sec Set the value in seconds The UPS will emit an audible alarm when the remaining runtime has reached this level. Date of Last Battery Replacement Date set at factory Reset this date when the battery module is replaced. Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U 11 Function Factory Default Audible Alarm On Options Description On/Off The UPS will never beep if all audible alarms are set to Off or when the display buttons are pressed. * Last test + 14 days * Last test + 7 days Auto Self-Test On start-up and every 14 * Turn on + 14 days Interval Setting days since the last test * Turn on + 7 days * On startup only * Never The interval at which the UPS will execute a self-test. The batteries much be charged to at least 70% capacity to perform the test. Reset to Factory No Default Restore the UPS factory default settings. Yes/No Switched Outlet Groups Overview The Switched Outlet Groups can be configured to independently turn off, turn on, shut down, put into sleep mode, and reboot connected equipment. The Switched Outlet Groups can be commanded to do the following: * Turn off: Disconnect from power immediately and restart only with a manual command * Turn on: Connect to power immediately * Shutdown: Disconnect power in sequence, and automatically reapply power in sequence when utility power becomes available * Reboot: Shut down and restart * Sleep: Reboot after a long delay In addition, the Switched Outlet Groups can be configured to do the following: * Turn on or off in a specified sequence * Automatically turn off or shut down when various conditions occur Note: Whether the Switched Outlet Groups are configured or not, all of the outlets provide battery backup power. Using the Switched Outlet Groups 1. Connect critical equipment to a Switched Outlet Group. 2. Connect peripheral equipment to the other Switched Outlet Groups. - During a power outage, to conserve battery runtime, nonessential equipment can be configured to shut down after a short delay - If equipment has dependent peripherals that must restart or shut down in a specific order, such as an ethernet switch that must restart before a connected server, connect the devices to separate groups - Equipment that needs to reboot independently from other equipment should be added to a separate group 3. Use the Configuration menus to configure how the Switched Outlet Groups will react in the event of a power outage. 12 Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U Customize the Switched Outlet Groups Use the Control menus to customize the Switched Outlet Groups. Function Factory Default Options Description Name String Outlet Outlet Group 1, 2, 3 Edit these names using an external interface, such as the Network Group Management Card web interface. UPS Name String APC UPS Turn On Delay 0 sec Set the value in seconds The amount of time the Switched Outlet Groups will wait between receiving the command to turn on and the actual startup. Turn Off Delay 90 sec Set the value in seconds The amount of time that the Switched Outlet Groups will wait between receiving the command to turn off and the actual shut down. Reboot Duration 8 sec Set the value in seconds The amount of time that the Switched Outlet Groups must remain off before it will restart. Minimum Return Time 0 sec Set the value in seconds The amount of battery runtime that must be available before the Switched Outlet Groups will turn on again after a shutdown. When the unit switches to battery power, the UPS can * Shutdown with disconnect power to the Switched Outlet Groups to Delay save runtime. * Shutdown immediately * Turn off immediately Configure this delay time, use the LOAD SHED TIME * Turn off with delay WHEN ON BATTERY setting. * Disabled Load Shed On Battery Disabled Load Shed Time when On Battery Disabled Set the value in seconds Load Shed On Runtime Disabled * Shutdown with delay * Shutdown Configure this time using the LOAD SHED RUNTIME immediately * Turn off immediately REMAINING setting. * Turn off with delay * Disabled Load Shed On Runtime Remaining Disabled Set the value in seconds When the remaining runtime reaches this level, the Switched Outlet Groups will turn off. * Disabled * Enabled In the event of an overload (greater than 105% output), the Switched Outlet Groups will immediately turn off to conserve power for critical loads. The Switched Outlet Groups will only turn on again with a manual command. Load Shed on Overload Disabled The amount of time the outlets will function on battery power before they will turn off. Network Management Card Settings These settings are available only on units that have a Network Management Card (NMC). * NMC IP Address Mode * NMC Default Gateway Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U 13 Emergency Power Off EPO Overview The Emergency Power Off (EPO) option is a safety feature that will immediately disconnect all connected equipment from utility power. The UPS will immediately shut down and will not switch to battery power. Connect each UPS to the EPO switch. The UPS must be manually restarted to reapply power to connected equipment. Press ON/OFF on the front panel of the UPS. Adhere to all national and local electrical codes. Wiring must be performed by a qualified electrician. Normally open contacts 1. If the EPO switch or relay contacts are normally open, insert the wires from the switch or contacts at pins 1 and 2 of the EPO terminal block. Use 16-28 AWG wire. 2. Secure the wires by tightening the screws. If the contacts are closed, the UPS will turn OFF and power will be removed from the load. Normally closed contacts 1. If the EPO switch or relay contacts are normally closed, insert the wires from the switch or contacts at pins 2 and 3 of the EPO terminal block. Use 16-28 AWG wire. 2. Insert a wire jumper between pins 1 and 2. Secure the wires by tightening the three screws at positions 1, 2, and 3. If the contacts are opened, the UPS will turn OFF and power will be removed from the load. Note: Pin 1 is the power source for the EPO circuit, it provides a few milliampere of 24 V power. If the normally closed (NC) EPO configuration is used, the EPO switch or relay should be rated for dry circuit applications, the rating should be for low voltage and low current applications. This normally implies the contacts are gold-plated. The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect the EPO interface only to other SELV circuits. The EPO interface monitors circuits that have no determined voltage potential. SELV circuits are controlled by a switch or relay properly isolated from utility power. To avoid damage to the UPS, do not connect the EPO interface to any circuit other than a SELV circuit. Use one of the following cable types to connect the UPS to the EPO switch. * CL2: Class 2 cable for general use. * CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air. * CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft. * CLEX: Limited use cable for use in dwellings and for use in raceways. * Installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable). * Installation in countries other than Canada and the USA: Use standard low-voltage cable in accordance with national and local regulations. 14 Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U Troubleshooting Problem and Possible Cause Solution The UPS will not turn on or there is no output The unit has not been turned on. Press the ON button to turn on the UPS. The UPS is not connected to utility power. Ensure that the power cable is securely connected to the unit and to the utility power supply. There is an internal UPS fault. Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately. The UPS is operating on battery, while connected to utility power Move the UPS to a different outlet on a different circuit. Test the input voltage with the utility voltage display. If acceptable to the connected equipment, There is very high, very low, or distorted reduce the UPS sensitivity. input line voltage or frequency. Test the utility input power to ensure the unit is receiving input power. UPS is emits intermittent beeps The UPS is in normal operation. The UPS is protecting the connected equipment. See the display interface to view the status of the UPS. UPS does not provide expected backup time The UPS battery is weak due to a recent outage or is near the end of its service life. Charge the battery. Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the battery even if the replace battery indicator is not yet illuminated. The UPS is overloaded. Check the UPS load display. Unplug unnecessary equipment, such as printers. The Fault LED is illuminated The UPS displays a fault message and emits a constant beeping sound Internal UPS fault. Do not attempt to use the UPS. Turn the UPS off and have it serviced immediately. The Replace Battery LED is illuminated The battery has a weak charge. Allow the battery to recharge for at least four hours. Then, perform a self-test. If the problem persists after recharging, replace the battery. The replacement battery is not properly connected. Ensure that the battery connector is securely connected. The display interface has a Site Wiring Fault message Wiring faults detected include missing ground, hot-neutral polarity reversal, and overloaded neutral circuit. If the UPS indicates a site wiring fault, have a qualified electrician inspect the building wiring. (Applicable for Low Voltage (120 V) units only.) Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U 15 Service If the unit requires service, do not return it to the dealer. Follow these steps: 1. Review the Troubleshooting section of the manual to eliminate common problems. 2. If the problem persists, contact APC by Schneider Electric Customer Support through the APC by Schneider Electric web site, www.apc.com. a. Note the model number and serial number and the date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models. b. Call APC by Schneider Electric Customer Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#). c. If the unit is under warranty, the repairs are free. d. Service procedures and returns may vary internationally. Refer to the APC by Schneider Electric web site for country specific instructions. 3. Pack the unit in the original packaging whenever possible to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty. a. Always DISCONNECT THE UPS BATTERIES before shipping. The United States Department of Transportation (DOT), and the International Air Transport Association (IATA) regulations require that UPS batteries be disconnected before shipping. The internal batteries may remain in the UPS. b. External Battery Pack products are deenergized when disconnected from the associated UPS product. It is not necessary to disconnect the internal batteries for shipping. Not all units utilize an external battery pack. 4. Write the RMA# provided by Customer Support on the outside of the package. 5. Return the unit by insured, prepaid carrier to the address provided by Customer Support. Transport 1. Shut down and disconnect all connected equipment. 2. Disconnect the unit from utility power. 3. Disconnect all internal and external batteries (if applicable). 4. Follow the shipping instructions outlined in the Service section of this manual. 16 Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U Limited Factory Warranty Schneider Electric IT Corporation (SEIT), warrants its products to be free from defects in materials and workmanship for a period of two (2) years from the date of purchase. The SEIT obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. Repair or replacement of a defective product or parts thereof does not extend the original warranty period. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase. Products may be registered online at warranty.apc.com. SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user or any third person misuse, negligence, improper installation, testing, operation or use of the product contrary to SEIT recommendations or specifications. Further, SEIT shall not be liable for defects resulting from: 1) unauthorized attempts to repair or modify the product, 2) incorrect or inadequate electrical voltage or connection, 3) inappropriate on site operation conditions, 4) Acts of God, 5) exposure to the elements, or 6) theft. In no event shall SEIT have any liability under this warranty for any product where the serial number has been altered, defaced, or removed. EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT SOLE LIABILITY AND PURCHASER EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES. IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEIT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT OR INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE. NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT LIABILITY FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LIMITED BY APPLICABLE LAW. To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Customers with warranty claims issues may access the SEIT worldwide customer support network through the APC web site: www.apc.com. Select your country from the country selection drop down menu. Open the Support tab at the top of the web page to obtain information for customer support in your region. Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase. Smart-UPS X 2000/2200/3000 VA 100/120/230 Vac Tower/Rack-Mount 2U 17 APC by Schneider Electric Worldwide Customer Support Customer support for this or any other APC by Schneider Electric product is available at no charge in any of the following ways: * Visit the APC by Schneider Electric web site, www.apc.com to access documents in the APC Knowledge Base and to submit customer support requests. - www.apc.com (Corporate Headquarters) Connect to localized APC by Schneider Electric web site for specific countries, each of which provides customer support information. - www.apc.com/support/ Global support searching APC Knowledge Base and using e-support. * Contact the APC by Schneider Electric Customer Support Center by telephone or e-mail. - Local, country specific centers: go to www.apc.com/support/contact for contact information. - For information on how to obtain local customer support, contact the APC by Schneider Electric representative or other distributor from whom you purchased your APC by Schneider Electric product. Select models are ENERGY STAR(R) qualified. For more information go to www.apc.com/site/recycle/index.cfm/energy-efficiency/energy-star/ (c) 2014 APC by Schneider Electric. APC, the APC logo, Smart-UPS and PowerChute are owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are property of their respective owners. EN 990-3651E 09/2014