Protection Relays & Controls
© 2014 Littelfuse Protection Relays & Controls
Littelfuse.com/ArcFlash
Rev: 4-G-032714
Based on Manual Rev 3-A-112913
Description
The PGR-8800 is a microprocessor-based relay that limits
arc-fault damage by detecting the light from an arc flash and
rapidly tripping. Phase-current-transformer inputs are provided
for current-constrained arc-flash protection and, when so
equipped, a programmable definite-time overcurrent function
can be enabled. An optical sensor on the PGR-8800 and
adjustable trip level reduce the chance of nuisance tripping
by setting a threshold for ambient light. Sensors, inputs, and
connections are monitored to ensure fail-safe operation. A
secondary solid-state trip circuit provides a redundant trip path.
A USB port is used for configuration and access to event logs
and graphs.
Optical Sensors
The PGR-8800 accepts both PGA-LS10 and PGA-LS20/PGA-
LS25/PGA-LS30 optical sensors, designed to collect light over
a wide angle and with high sensitivity. For fast fault location,
front-panel and sensor LED’s indicate sensor health and which
sensor detected an arc fault.
Sensor Placement
The PGR-8800 Arc-Flash Relay and sensors are easily
installed in retrofit projects and new switchgear with little or
no re-configuration. Even elaborate systems with multiple
power sources take minutes to configure using the relay’s
built-in USB interface software.
Generally, it is recommended to mount 1 or 2 sensors per
cubicle to cover all horizontal and vertical bus bars, breaker
compartments, drawers, and anywhere that there is potential
for an arc-fault. Threading a fiber-optic sensor through
the cabinets and in areas where point-sensor coverage is
uncertain results in complete coverage and an added level
of redundancy. Even if policy is to only work on de-energized
systems, all maintenance areas should be monitored to
prevent potential damage and additional cost. At least one
sensor should have visibility of an arc fault if a person blocks
the other sensor(s).
Simplified Circuit Diagram
PGA-LS10
(Point Sensor)
PGA-LS20/
PGA-LS25/
PGA-LS30
(Fiber-Optic Sensor)
PGA-1100
(Diode Logic Unit)
(Optional)
24 Vdc Battery
Backup
(Optional)
(Recommended)
(Arc-Flash Protection Relay)
PGR-8800
Trip
5-A-SECONDARY PHASE CT’s
L2
L1
A
B
C
A
B
Ordering Information
PGR-8800 SERIES (D1000)
Arc-Flash Relay
C
D
ORDERING NUMBER COMMUNICATIONS
PGR-8800-00 (UL, CE, C-tick) Multi-unit linking, Modbus® RTU
ACCESSORIES REQUIREMENT
PGA-LS10 (A1000) Required*
PGA-LS20 (A2000)/
PGA-LS25 (A2000.0020)
PGA-LS30 (A2000.0030)
Required*
PGA-1100 (D1100) Optional
Current Transformer Optional
*At least one sensor is required. However, the exact number of sensors for proper coverage
depends on the application.
DDD
Local
Circuit Breaker
For detailed wiring diagram, see adjacent page.
Arc-Flash Monitoring
Protection Relays & Controls
© 2014 Littelfuse Protection Relays & Controls
Littelfuse.com/ArcFlash
Wiring Diagram
FEATURES BENEFITS
Arc-Flash trip time <1 ms Limits arc-flash damage and risk of injury
Multiple sensors (up to 24) Single module can monitor 6 sensors. Up to 4 PGR-8800 units can be linked into one system
Fail-safe system Continuous monitoring of optical sensors and inputs ensures protection
Redundant trip circuit Solid-state backup arc-detection circuit adds a second layer of safety
Adjustable light sensitivity Allows for operation in bright environments and maximum sensitivity in dark environments
LED indication (on unit and each sensor) 18 LEDs provide at-a glance status for module and I/O state
Current detection Phase-CT inputs provide overcurrent protection and prevent nuisance trips
Optical detection Point and fiber-optic sensors provide wide detection area with sensor health trip indication
Digital inputs (6) Two each: remote trip, inhibit, and reset inputs
Service mode Allows for system test without tripping
Trip coil contact Solid-state 24-300 Vdc/24-300 Vac IGBT
Indication contacts Form C and status outputs
USB interface Data logging and configuration software uses a USB interface with no drivers or software installation
Built-in sensor Can be used in single-sensor systems, as a seventh sensor, and for calibration
Universal power supply/Battery backup 100-240 Vac, 14-48 Vdc, or 110-250 Vdc supply accepted. Ability to charge and run off an external, user-supplied
24 Vdc battery.
Data logging On-board event recorder helps with system diagnostics
Modbus Remotely view measured values, event records & reset trips
Upstream Tripping Ability to trip upstream device if the local breaker fails to clear the fault
Features & Benefits
PGR-8800 SERIES (D1000)
Arc-Flash Relay
1
31 36 39 37 45 46 47 48 49 50 51 52 53 54 55 56 57 59 60 38
4
........ 5 8
........ 9 12
........ 13 16
........ 17 20
........ 21 24
........
.............
.....................
25 26 27 28 29 30
STATUS STATUS STATUS
TRIP COILTRIPPEDSERVICE
LINK
ONLINE
+
CONTROL POWER
and BATTERY
DIGITAL INPUTS
ARC-FLASH RELAY
PGR-8800 SERIES
ARC-FLASH RELAY
PGR-8800
(optional)
DIODE LOGIC
UNIT
PGA-1100
(optional)
ARC-FLASH RELAY
PGR-8800
(optional)
ARC-FLASH RELAY
PGR-8800
(optional)
PHASE CT
(recommended)
PHASE CT
(recommended)
PHASE CT
(recommended)
PGA-LS10
PGA-LS20
PGA-LS25
or
PGA-LS30
OPTICAL
SENSOR
PGA-LS10
PGA-LS20
PGA-LS25
or
PGA-LS30
OPTICAL
SENSOR
PGA-LS10
PGA-LS20
PGA-LS25
or
PGA-LS30
OPTICAL
SENSOR
PGA-LS10
PGA-LS20
PGA-LS25
or
PGA-LS30
OPTICAL
SENSOR
PGA-LS10
PGA-LS20
PGA-LS25
or
PGA-LS30
OPTICAL
SENSOR
PGA-LS10
PGA-LS20
PGA-LS25
or
PGA-LS30
OPTICAL
SENSOR
Specifications
IEEE Device Numbers Overcurrent (50), Arc Flash (AFD)
Input Voltage 100-240 Vac, 14-48 Vdc, and 110-250 Vdc
Dimensions H 130 mm (5.2”); W 200 mm (7.9”);
D 54 mm (2.2”)
Optical Trip Settings 9-25 klux, 800 μs-20 s
Current Trip Setting (A) Programmable
Indication Contact Mode Fail-safe
Trip Coil Voltage(1) 24-300 Vdc, 24-300 Vac
Trip Coil Contact Mode Selectable fail-safe or non-fail-safe
Redundant Trip Circuit Standard feature
Input Monitoring Standard feature
USB Interface Standard feature
Trip, Reset,
Service Buttons Standard feature
Expandable System Link up to 4 PGR-8800 units
Warranty 5 years
Mounting DIN (with D0050 adapter clips), Surface
PGA-LS10 (A1000) Point Sensor
Line-of-sight light sensor detects an arc as small as 3 kA
within a 2-m half-sphere. Sensor health and trip indication.
Dimensions: See PGR-8800 Manual
PGA-LS20 (A2000)/PGA-LS25 (A2000.0020)/PGA-
LS30(A2000.0030) Fiber-Optic Sensor
360° light sensor for tricky installations with many shadows
or to run along bus bars. Sensor health and trip indication.
Dimensions: See PGR-8800 Manual
PGA-1100 (D1100) Diode Logic Unit
This module allows multiple PGR-8800 relays to trip the
same breaker, for example an upstream or a tie-breaker.
Dimensions: H 80mm (3.15”) W 20mm (.79”) D 70mm(2.76”)
Current Transformers
Eliminate nuisance arc-flash trips and use for
overcurrent protection.
Accessories
A
B
D
C
Littelfuse reserves the right to make product changes, without notice. Material in this document is as accurate as known at the time of publication. Visit Littelfuse.com for the most up-to-date information.
NOTE (1) - Contact Littelfuse for trip coil voltages higher than 300 Vdc/Vac.
Rev: 4-F-012214
Based on Manual Rev 3-A-112913
Arc-Flash Monitoring