3-phase filters FN 3359 High-current three-phase EMC/RFI filter n n n n Off-the-shelf high-power filter for rated currents up to 2500A HV versions designed for 690VAC IT power networks Busbars for convenient and universal electrical connection Protective plastic covers optionally available for unsurpassed safety Technical specifications Maximum continuous operating voltage: Operating frequency: Rated currents: High potential test voltage: Protection category: Overload capability: Temperature range (operation and storage): Flammability corresponding to: Design corresponding to: MTBF @ 45C/480V (Mil-HB-217F): n n High-power filter for Class A compliance. 3x 520/300VAC (FN 3359) 3x 690/400VAC (FN 3359HV) dc to 60Hz 150 to 2500A @ 50C P -> E 2700VDC for 2 sec (FN 3359) P -> P 2150VDC for 2 sec (FN 3359) P -> E 3100VDC for 2 sec (FN 3359HV) P -> P 3000VDC for 2 sec (FN 3359HV) IP00 4x rated current at switch on, 1.5x rated current for 1 minute, once per hour -25C to +100C (25/100/21) UL 94V-2 or better UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939 130,000 hours * Note: HV versions without discharge resistor to ground. Typical applications n Optionally available transparent protective n High-power motor drives, inverters and With approval measurement also Class B covers for all filters up to 1000A, to protect compliance possible for some applications. the installer, operator or inspector from n Industrial three-phase systems Extremely compact high-current filter undeliberate touching of life conductors. n Entire factories, plants and installations solution with minimum space require- They can easily be retrofitted even if the n Large UPS ment. filter is already installed and connected. n Machinery FN 3359 also improves conducted n Mining equipment immunity of installations. n Photovoltaic systems with galvanic FN 3359HV versions for 690VAC are also designed for use in IT power networks. n (600VAC) Typical electrical schematic Features and benefits n Approvals (filters up to 1000A) n All filters 320A and above are suitable for regenerative motor drive system (with a suitable line reactor). For EMI solutions for PV system without galvanic isolation, please contact your local Schaffner partner. converters isolation* n Wind turbines > Components > FN 3359 Filter selection table Filter FN FN FN FN FN FN FN FN FN FN FN FN FN FN FN FN FN FN FN FN Rated current @ 50C (40C) Typical drive power rating* Leakage current** @ 480VAC/50Hz [A] 150 (164) 180 (197) 250 (250) 320 (350) 400 (438) 600 (657) 800 (876) 1000 (1095) 1600 (1600) 2500 (2500) 150 (164) 180 (197) 250 (250) 320 (350) 400 (438) 600 (657) 800 (876) 1000 (1095) 1600 (1600) 2500 (2500) [kW] 75 90 132 160 220 315 400 560 900 1320 110 132 200 250 315 500 630 710 1320 2000 [mA] <6 <6 <6 <6 <6 <6 <6 <6 <6 <6 <6 <6 <6 <6 <6 <6 <6 <6 <6 <6 3359-150-28 3359-180-28 3359-250-28 3359-320-99 3359-400-99 3359-600-99 3359-800-99 3359-1000-99 3359-1600-99 3359-2500-99 3359HV-150-28 3359HV-180-28 3359HV-250-28 3359HV-320-99 3359HV-400-99 3359HV-600-99 3359HV-800-99 3359HV-1000-99 3359HV-1600-99 3359HV-2500-99 Power loss @ 25C/50Hz Input/Output Weight connections [W] 24 -28 34 -28 49 -28 19 -99 29 -99 44 -99 39 -99 60 -99 131 -99 300 -99 24 -28 34 -28 49 -28 19 -99 29 -99 44 -99 39 -99 60 -99 131 -99 300 -99 [kg] 6.5 6.5 7.0 10.5 10.5 11.0 18.0 18.0 27.0 55.0 6.5 6.5 7.0 10.5 10.5 11.0 18.0 18.0 27.0 55.0 Protective covers*** Order code 1151-050 1151-050 1151-051 1151-052 1151-052 1151-053 1151-054 1151-054 * Calculated at rated current, 480VAC (FN 3359) / 690VAC (FN 3359HV) and cos phi = 0.8. The exact value depends upon the efficiency of the drive, the motor and the entire application. ** Maximum leakage under normal operating conditions. Note: if two phases are interrupted, worst case leakage could be much higher than the value shown. *** Please contact your local Schaffner partner to order the optional protective covers with the order code in the table above Typical filter attenuation Per CISPR 17; A = 50/50 sym; B = 50/50 asym; C = 0.1/100 sym; D = 100/0.1 sym 150 to 180A types 250 to 600A types 800 and 1000A types 1600 and 2500A types 1151-050 1151-050 1151-051 1151-052 1151-052 1151-053 1151-054 1151-054 > Components > FN 3359 Mechanical data 150 to 250A types 320 to 2500A types Busbar connections 320 to 1000A types 1600A types 2500A types Dimensions 150A 180A 250A 320A 400A 600A 800A 1000A A 300 300 300 300 300 300 350 350 B 210 210 230 260 260 260 280 280 C 120 120 125 115 115 135 170 170 D 160 160 180 210 210 210 230 230 E 120 120 120 120 120 120 145 145 F 185 185 205 235 235 235 255 255 G O12 O12 O12 O12 O12 O12 O12 O12 H 2 2 2 2 2 2 3 3 I 33 33 33 43 43 43 53 53 J M10 M10 M10 M12 M12 M12 M12 M12 K 55 55 62.5 20 20 20 25 25 L 30 30 35 20 20 20 25 25 M 420 420 420 440 440 440 510 510 N 171 171 191 221 221 221 241 241 O 127 127 132 122 122 142 177 177 S T U 50 50 55 60 60 60 60 60 V 25 25 25 40 40 W 6 6 8 8 8 X 15 15 15 20 20 Y 40 40 40 50 50 Z O10.5 O10.5 O10.5 O14 O14 1600A 2500A 400 300 160 250 170 275 O12 3 93 M12 25 25 600 370 200 300 250 330 O14 3 98 M16 25 25 26 26 60 60 10 17 90 O14 35 35 100 70 15 20 95 O14 All dimensions in mm; 1 inch = 25.4mm Tolerances according: ISO 2768-m / EN 22768-m Your local partner: To find your local partner within Schaffner's global network, please go to www.schaffner.com March 2010