Frequency/Rate Meter
K3MA-F
Highly Visible LCD Display with 2-color (Red and
Green) LEDs
Contact, NPN, PNP, or voltage pulse input.
Front-panel key operation for easy setting.
Average processing function suppresses flicker.
Includes scaling, auto-zero time, startup compensation time functions.
Easy confirmation of max/min display.
Short 80-mm depth (measured from edge of face plate).
Finger protective cover (standard equipment) guards against electric
shock.
Water- and dust-proof NEMA4X (IP66 equivalent) front panel.
Recognized to U.S. and Canadian requirements under the Compo-
nent Recognition Program of UL.
•CE marking.
Built-in external power supply (12 VDC, 40 mA).
Model Number Structure
Model Number Legend
:
1. Input Type
F: Rotary pulse
2. Output Type
None: No output
A2: 2 relay contact outputs (SPST-NO)
3. Supply Voltage
100-240VAC: 100 to 240 VAC
24VAC/VDC: 24 VAC/VDC
Ordering Information
List of Models
Refer to Safety Precautions for All Digital Panel
Meters.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
1 2 3
K3MA-F-@
Input type Supply voltage Output Model
Rotary pulse 100 to 240 VAC None K3MA-F 100-240VAC
2 relay contact outputs (SPST-NO) K3MA-F-A2 100-240VAC
24 VAC/VDC None K3MA-F 24VAC/VDC
2 relay contact outputs (SPST-NO) K3MA-F-A2 24VAC/VDC
K3MA-F
2
Accessories (Order Separately)
Specifications
Ratings
Name Shape Model
Splash-proof Soft Cover K32-49SC
Hard Cover K32-49HC
Watertight Cover Y92A-49N
Rubber Packing K32-P1
Model K3MA-F 100-240VDC, K3MA-F-A2 100-240VAC K3MA-F 24VAC/VDC, K3MA-F-A2 24VAC/VDC
Supply voltage 100 to 240 VAC 24 VAC/VDC
Operating voltage range 85% to 110% of the rated supply voltage
Power consumption
(under maximum load)
6 VA max. 4.5 VA max. (24 VAC)
4.5 W max. (24 VDC)
External power supply 12 VDC, 40 mA
Insulation resistance 20 MΩ min. (at 500 VDC) between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
Dielectric strength 2,000 VAC for 1 min between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
Noise immunity ±1,500 V on power supply terminals in normal or com-
mon mode.
±1 μs, or 100 ns for square-wave noise with 1 ns.
±480 V on power supply terminals in normal mode.
±1,500 V in common mode.
±1 μs, or 100 ns for square-wave noise with 1 ns.
Vibration resistance Vibration: 10 to 55 Hz, Acceleration: 50 m/s2
5 min each in X, Y, and Z directions for 10 sweeps.
Shock resistance 150 m/s2 (100 m/s2 for relay contact outputs) 3 times each on 3 axes, 6 directions.
Ambient temperature Operating: 10°C to 55°C (with no condensation or icing)
Storage: 25°C to 65°C (with no condensation or icing)
Approved safety standards UL61010-1, CSA C22.2 No.61010-1-04, conforms to EN61010-1 (Pollution degree 2/overvoltage category II)
Conforms to VDE0106/P100 (finger protection)
EMC (EMI) EN61326+A1 Industry
Emission Enclosure: CISPR 11 Group 1 class A: CISRP16-1/-2
Emission AC Mains: CISPR 11 Group 1 class A: CISRP16-1/-2
(EMS) EN61326+A1 Industry
Immunity ESD: EN61000-4-2: 4 kV contact discharge
8 kV air discharge
Immunity RF-interference: EN61000-4-3: 10 V/m (amplitude-modulated, 80 MHz to 1 GHz)
Electrical Fast Transient Noise: EN61000-4-4: 2 kV (power line)
Immunity Burst Noise: 1 kV line to line (I/O signal line)
Immunity Surge: EN61000-4-5: 1 kV (power line)
2 kV line to ground (power line)
Immunity Conducted Disturbance: EN61000-4-6: 3 V (0.15 to 80 MHz)
Immunity Voltage Dip/Interrupting: EN61000-4-11: 0.5 cycle, 0, 180°, 100% (rated voltage)
Weight Approx. 200 g
3
K3MA-F
Characteristics
Measuring Ranges
No-voltage Contact/Open Collector Inputs
Input/Output Ratings
Relay Contact Output
Input signal No-voltage contact (30 Hz max., ON/OFF pulse width: 15 ms min.)
Voltage pulse (5 kHz max., ON/OFF pulse width: 90 μs min., ON voltage: 4.5 to 30 V/OFF voltage:
0 to 2 V)
Open collector (5 kHz max., ON/OFF pulse width 90 μs min.)
Connectable Sensors
ON residual voltage: 2.5 V max.
OFF leakage current: 0.1 mA max.
Load current: Must have switching capacity of 15 mA min.
Must be able to dependably switch a load current of 5 mA max.
Measuring accuracy ±0.1%FS ±1 digit (at 23±5°C)
Measurement method Cycle measurement
Max. displayed digits 5 digits (19999 to 99999)
Display 7-segment digital display, Character height: 14.2 mm
Polarity display ” is displayed automatically with a negative input signal.
Zero display Leading zeros are not displayed.
Scaling function Programmable with front-panel key inputs (range of display: 19999 to 99999).
The decimal point position can be set as desired.
Hold function Max hold (maximum value), Min hold (minimum value)
Hysteresis setting Programmable with front-panel key inputs (0001 to 9999).
Other functions Scaling teach function
Display color change (green (red), green, red (green), red)
OUT type change (upper limit, lower limit, upper/lower limit)
Average processing (simple average OFF/2/4/8 operations)
Auto-zero time
Startup compensation time
Setting change lockout
Parameter initialization
Display auto-return time
Output Relays: 2 SPST-NO
Delay in comparative outputs 750 ms max.
Degree of protection Front panel: NEMA4X for indoor use (equivalent to IP66)
Rear case: IEC standard IP20
Terminals: IEC standard IP00 + finger protection (VDE0106/100)
Memory protection Non-volatile memory (EEPROM) (possible to rewrite 100,000 times)
Input Measuring range Measuring accuracy Displayable range
No-voltage contact (30 Hz max.) with
ON/OFF pulse width of 15 ms min.
0.05 to 30.00 Hz ±0.1% FS ±1 digit max.
(at 23±5°C)
–19999 to 99999
(with scaling function)
Open collector (5 kHz max.) with
ON/OFF pulse width of 90 μs min.
0 to 5 kHz
Item Resistive load (cosφ = 1) Inductive load (cosφ = 0.4, L/R = 7 ms)
Rated load (UL ratings) 5 A at 250 VAC, 5 A at 30 VDC 1 A at 250 VAC, 1 A at 30 VDC
Rated carry current 5 A max. (at COM terminal)
Max. contact voltage 250 VAC, 150 VDC
Max. contact current 5 A (at COM terminal)
Max. switching capacity 1,250 VA, 150 W 250 VA, 30 W
Min. permissible load
(P level, reference value)
10 mA at 5 VDC
Mechanical life 5,000,000 times min. (at a switching frequency of 1,200 times/min)
Electrical life
(at an ambient temperature of 20°C)
100,000 times min. (at a rated load switching frequency of 10 times/min)
K3MA-F
4
Connections
Terminal Arrangement
Block Diagram
Input Circuits
Pulse Input
Power
supply Output
terminals
Input
terminals
External power supply
+
A1
B5
E1
E2
E3
E4
E5
E6
B6
A2
Models with
comparative
output
OUT1
OUT2100- to 240-VAC type or
24-VAC/VDC type
(No polarity for 24-VDC
connection.)
Note: Refer to Input Circuits on page 5.
12 V
40 mA
Terminal No. Name Description
Operation power Connects the operation power supply.
Pulse input No-voltage contact/open collector input
Outputs Outputs the relay outputs.
External power supply Use as the power supply for sensors.
A1 - A2
E4 , E6 - E5
E1 , E2 - E3
B5 - B6
X
InputInput circuit
Micro-
computer
Key
Display
Output
circuit
Contact output
(See note.)
Power supply circuit
Constant voltage circuit
EEP ROM
5 V12 V
Note: Relay output models only.
E4
E5
E6
B5
+
B6
The negative pole of the sensor power
supply and COM are connected
internally.
Pulse
detection
circuit
Voltage
detection
circuit
Voltage pulse
PNP
NPN
12 V
12 V
200 Ω
1 kΩ
10 kΩ
NPN, contact input
PNP, voltage pulse input
5
K3MA-F
Operation
Main Functions
Input Types and Ranges
Pulse Frequency Selection
Note: The default value is “0 to 5 kHz (5k).
Scaling
When the desired display value is set for a corresponding input, the value will be displayed on a line between two points determining the zero point.
Frequency range
(setting parameter)
Function Input range (setting parameters) Setting range
Pulse frequency selection
(p-fre)
Selects pulse input signal. 0.05 to 30.00 Hz (30) Displayable from 19999 to 99999
with scaling function.
The position of the decimal point
can be set as desired.
0 to 5 kHz (5k)
Parameter Setting value Meaning
p-fre 30 0.05 to 30.00 Hz
measurement range
5k 0 to 5 kHz measure-
ment range
Parameter Setting value Meaning Parameter Setting value Meaning
inp 0 to 99999 Input value for dsp dp %.%%%% Display four digits after decimal point
dsp -19999 to 99999 Display value for inp %%.%%% Display three digits after decimal point
%%%.%% Display two digits after decimal point
%%%%.% Display one digit after decimal point
%%%%% No decimal point
The decimal point can be optionally displayed.
Display value
DISPLAY
Input value
INPUT
Teaching with actual values is possible.
Instead of setting by inputting with the Up Key and Shift Key, current values can be
input as scaling input values for teaching. This is useful for making settings while checking the
operation status of the K3MA-F.
The initial value will change depending on the
pulse frequency selection.
When displaying the decimal point, consider the
number of digits to follow the decimal point prior to
setting the scaling display value.
If p-fre is set to 30, the initial setting for the
decimal display will be 000.00.
Note:
K3MA-F
6
Convenient Functions
Scaling Teach
The parameter (inp) for the K3MA-F’s initial setting level can be set using actual input values with the teaching function. After displaying the param-
eter, the actual input settings can be made with the following operation.
OUT Types (Comparative Output Models Only)
OUT 1 and OUT 2 can be set to operate in one of the three following
modes in accordance with the compared values:
Upper limit (High Acting):
The output is turned ON when the measurement value is greater
than its set value.
Lower limit (Low Acting):
The output is turned ON when the measurement value is less than
its set value.
Upper and lower limits (Outside Band Acting):
An upper limit (H set value) and lower limit (L set value) can be set
independently.
The output is turned ON when the measurement value is greater
than upper-limit set value or less than the lower-limit set value.
The three types of output operations shown above can be combined as desired. The following are examples of possible combinations.
Parameter Initialization
This function returns all of the parameters to their initial values.
Use this to reset the K3MA-F after returning it to its factory-set condi-
tion.
Parameter Set value Meaning
out1.t
or
out2.t
hi Upper limit: Upper-limit alarm
operation
lo Lower limit: Lower-limit alarm
operation
hi-lo Upper and lower limits: Upper-
and lower limit alarm operation
Upper Limit (High Acting)
OUT1 value
OUT1 value
Hysteresis
Hysteresis
Hysteresis
Hysteresis
ON
OFF
OutputON
OFF
OutputON
OFF
Output
Measurement valueMeasurement valueMeasurement value
OUT1 upper-limit
value
OUT1 lower-limit
value
Lower Limit (Low Acting)Upper and Lower Limits
(Outside Band Acting)
Upper Limit 2-stage Output
Measurement
value
Measurement
value
Measurement
value
OUT2
value
OUT2 upper-limit
value
OUT2 upper-limit
value
OUT1 lower-limit
value
OUT2 lower-limit
value
OUT2 lower-limit
value
OUT1 upper-limit
value
OUT2 ON
OFF
ON
OFF
OUT1
OUT2 ON
OFF
ON
OFF
OUT1
OUT2 ON
OFF
ON
OFF
OUT1
OUT1
value
OUT1 value
Threshold Output Combination of Upper Limit and
Upper/Lower Limits
Parameter Setting value Meaning
init off ---
on Initializes all parame-
ters.
7
K3MA-F
Average Processing
Average processing stabilizes the display by minimizing any pulsat-
ing or flicker caused by fluctuations in the pulse width of sensor input
or by eccentricity in rotating shafts.
Hysteresis (Comparative Output
Models Only)
The hysteresis of comparative outputs can be set to prevent chatter-
ing in the output when the measurement value fluctuates finely near
the OUT value.
Auto-zero Time
This function sets the time for the display to return to zero when input
pulses stop. Set the time longer than the expected input pulse cycle
(the interval between one input pulse and the next). Proper measure-
ment is not possible if the time is set shorter than the input pulse
cycle.
Setting range: 0.0 to 19.9 s
Startup Compensation Time
The startup compensation time is the time to wait for the
measurement operation to be entered after the power supply of the
K3MA-F is turned ON. Use this parameter to cancel measurement
and comparative output operation until the a rotating body reaches
its normal speed when the power supply to the K3MA-F and rotating
body are turned ON at the same time.
Changing the Display Color
The color of the value displayed can be set to either red or green. For
comparative output models, the display color can be set to change
from green to red, or from red to green, according to the status of the
comparison criterion.
Display Auto-return Time
This function automatically returns the display to the operation level’s
current value if no keys are pressed for a preset time (called the dis-
play auto-return time).
Move-to-Protect-Level Time
The time required to shift to the protect level can be set as desired.
MAX/MIN Display
The maximum and minimum measurement (display) values from the
time the power is turned ON until the current time can be stored and
displayed. This is useful, for example, when measuring the maximum
value.
Upper limit (high acting)
Measurement value
Set valueHysteresis
OutputOFF
ON
Display
Time
Startup
compensation
time
Lower limit
setting
(OUT2)
Power supply
00000 displayed
OUT2
output
8.781
100.05
113.36
OUT1 value
OUT2 value
Red
Red
Green
MAX/MIN
MAX/MIN
MAX/MIN
Current value
MAX value
MIN value
MAX/MIN LEVEL MODE SHIFT UP
MAX/MIN LEVEL MODE SHIFT UP
MAX/MIN LEVEL MODE SHIFT UP
Min
Max
K3MA-F
8
Nomenclature
Name Functions
1. Main indicator Displays current values, parameter names (abbreviations), and comparative value settings.
2. Opera-
tion indica-
tors
1 Lit when output 1 is ON.
2 Lit when output 2 is ON.
SV Lit when a set value is being displayed or changed.
Max Lit when the main indicator is showing the MAX value.
Min Lit when the main indicator is showing the MIN value.
T Lit when the teaching function is operable. Blinks while the teaching function is operating.
3. Level indicator Displays the current level that the K3MA-F is in. (See below for details.)
4. MAX/MIN Key Used to display the MAX and MIN values when a measurement value is being displayed.
5. Level Key Used to change the level. The level can be switched between operation level and initial setting level.
6. Mode Key Used to allow the main indicator to indicate parameters sequentially.
7. Shift Key Used to enable a set value to be changed. When changing a set value, this key is used to move along the digits.
8. Up Key Used to change a set value. Used to set or clear a forced-zero function when a measurement value is being displayed.
Level indicator Level
pProtect
Not lit Operation
sInitial setting
fAdvanced function setting
1
2
T
MAX/MIN LEVEL MODE SHIFT UP
Max
Min
SV
2. Operation indicators
3. Level indicator
4. MAX/MIN key
5. Level key 6. Mode key 7. Shift key
8. Up key
1. Main indicator
9
K3MA-F
Dimensions
Application Examples
A B C D E
UP SHIFT MODE LEVEL MAX/MIN
101.2
91
85
97
12
1.3
96
48
80
44.8
45+0.5
0
92+0.5
0
Terminal cover
(provided) Main indicator
character size Panel cut-out
7.6 mm
14.2 mm
120 min.
75 min.
The K3MA-F uses M3 terminals.
A terminal cover is provided.
Mounting Recommended Panel Thickness
1 to 8 mm.
Mount the product horizontally.
Displaying conveyor
belt feed speed
Monitoring the rotations
of a mixer or churner
Displaying the monitor
output from an inverter
as rotations or line speed
Gear Mixer or churner
K3MA-F
Inverter
Motor Voltage pulse
Note: If the monitor output from the inverter is analog,
such as 0 to 10 V, use the K3MA-J.
K3MA-F
K3MA-F m/min rpm
rpm
Proximity sensor
Monitoring line speed for a reflow
furnace
Displaying feed speed for food
processing, conveying, sintering
Mixers for resin molding
Powdering/pelleting machines,
centrifugal separators
Monitoring conveyor speed
Machining equipment (grinders,
polishers)
K3MA-F
10
Installation
1. Insert the K3MA-F into the panel cut-out hole.
2. For a waterproof installation, insert the rubber gasket onto the
body of the K3MA-F.
3. Fit the adaptor into the grooves on the left and right sides of the
rear case, then push it until it contacts the panel to secure the
K3MA-F.
LCD Angle of View
The K3MA is designed to provide the best visibility at the angles
shown in the following diagram.
Watertight Cover
Y92A-49N
Rubber Packing
K32-P1
If the rubber packing is lost or damaged, it can
be ordered using the following model number:
K32-P1.
(Depending on the operating environment,
deterioration, contraction, or hardening of the
rubber packing may occur and so, in order to
ensure the level of waterproofing specified in
NEMA4, periodic replacement is
recommended.)
Note: Rubber packing is provided with the
Controller.
Wiring Precautions
Use crimp terminals.
Tighten the terminal screws to a torque of approximately 0.5 Nm.
To avoid the influence of noise, route signal lines and power lines
separately.
Wiring
Use the following M3 crimp terminals.
Unit Labels (Provided)
The unit labels are not attached to the K3MA-F. Select the desired
labels from the provided sheet.
Note: For scales and gauges, use the unit labels that are specified by
the relevant laws or regulations.
10°
30°
5.8 mm max.
5.8 mm max.
11
K3MA-F
Operating Procedures
Operations in Run Mode
Levels
“Level” refers to a grouping of parameters. The following table lists the operations that are possible in each of the levels, and the diagram tells how
to move between levels. There are some parameters that are not displayed for certain models.
Level name Function Measurement
Protect Setting lockouts. Continue
Operation Displaying current values, and setting OUT 1/2 set values. Continue
Initial setting Making initial settings of input type, scaling, output operating action,
and other parameters.
Stopped
Advanced function setting Setting average processing, display color settings, and other ad-
vanced function parameters.
Stopped
Checking the Maximum and Minimum Values
The maximum and minimum values can be displayed by pressing the MAX/MIN Key while
the measurement is being displayed.
The maximum and minimum values can be reset by pressing the MAX/MIN Key for 1 s
min. when the maximum or minimum value is displayed.
Checking and Setting Comparative Set Values (for
Models with the Comparative Output Function)
Each time the Mode Key is pressed when the measurement value, maximum value, or
minimum value is displayed, the comparative values will be displayed in the following
order: OUT1 value (or OUT1 upper-limit value, OUT1 lower-limit 1), OUT 2 value (or
OUT2 upper-limit value, OUT2 lower limit value 2).
Note: When the comparative value is displayed, it can be changed by pressing the Shift
Key and the Up Key (when key protection is OFF).
Measurement
value
MAX value MIN value
MAX/MIN Key MAX/MIN KeyMAX/MIN Key
Measurement
value
MAX value
MIN value
OUT1 upper-
limit value
OUT1
value
OUT2
value
OUT1 lower-
limit value
OUT2 upper-
limit value
OUT2 lower-
limit value
Power ON
Operation level Protect level
Initial setting level
Advanced function
setting level
Measurement in progress
Measurement stopped
Level change
Level Key Level Key
Level Key
1 s min.
Password input
Level Key
MODE Key
+
Level Key
MODE Key
+
for at least user-set time
1 s min.
3 s min.
1 s min.
K3MA-F
12
Parameters
For models with the
comparative output
function.
MODE
MODE
MODE
MODE
MODE
MODE
MODE
Set one of these.
Set one of these.
Current value
OUT1
value
OUT2
value
OUT1
upper-limit
value
OUT2
upper-limit
value
OUT1
lower-limit
value
OUT2
lower-limit
value
Power ON
Operation level
Note: 1. Some parameters are not displayed for certain models.
2. The K3MA-F will stop measurement if the level is changed to the initial setting level or
the advanced-function setting level.
3. If the input range is changed, some parameters are set to default values. Therefore,
set the input range first.
4. Settings displayed in reversed colors are defaults.
13
K3MA-F
/
/
/
//
/
Models
with the
compara-
tive output
function
Models
with the
compara-
tive
output
function
Pulse frequency
Scaling
Pulse
frequency
MODE MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
Press Level
Key for
more than 3 s.
Press Level
Key for
more than 1 s.
Initial setting level Advanced-function
setting level
Enter
password
"-0169"
Press Level Key for less than 1 s.
Scaling
input
value
Scaling
display
value
Decimal
point
position
Move to
advanced-
function
setting level
OUT1 type
OUT2 type
Upper Limit
Lower Limit
Upper/Lower
Limits
Upper Limit
Lower Limit
Upper/Lower
Limits
Parameter
initialization
Average
processing
OUT1
hysteresis
OUT2
hysteresis
Auto-zero
time
Startup
compensation
time
Display
color
change
Display
auto-return
time
Move-to-
protect-
level time
Settings displayed in reversed colors are initial settings.
Unit: s
Unit: s
Unit: times
Comparative hysteresis
Green (red)
Red (green)
Red
Green
To change a setting, press the Shift Key again, and then
make the change with the Up Key .
K3MA-F
14
Operation/Adjustment Lockouts
Restricts key operations for operation level and adjustment level.
Initial setting is 0.
This is not displayed on models with no comparative output func-
tion.
Setting Level Lockouts
Restricts shifting to initial setting level or advanced function setting
level.
Setting Change Lockout
Restricts setting changes by key operation. When this lockout is set,
it is no longer possible to shift to a setting change mode.
However, all protect level parameters can still be changed.
Initial Settings
/ /
/ /
/
Operation level
Press Level Key + Mode Key for more than 1 s.
Press Level Key + Mode Key for more
than preset time.
Protect level
MODE
MODE
MODE
Operation/adjustment
lockouts
Setting level lockouts
Setting change lockout
Parameter Setting Operation level
Current value
display
Set value
display
oapt 0Allowed Allowed
1Allowed Allowed
2Allowed Prohibited
Parameter Setting Shift to initial
setting level
Shift to
advanced
function
setting level
icpt 0 Allowed Allowed
1Allowed Prohibited
2Prohibited Prohibited
Parameter Setting Setting change by key
operation
wtpt off Allowed
on Prohibited
Select the pulse frequency for measurement.
Set the scaling values and OUT type as required.
Press the Level Key for 3 s min. to move to the initial setting
level.
Press the Level Key for more than 1 second to return to
the operation level.
If required, shift to the advanced-function setting level to set
the number of measurements for average processing,
hysteresis values, auto-zero time, startup compensation time,
display color change, display auto-return time, or move-to-
protect-level time.
Power ON
Measurement starts.
Specify set value of OUT 1 and 2.
15
K3MA-F
Setting Example
Initial Settings
The settings for the following example are shown here.
Example: Display conveyor belt feed speed
Here, the conveyor belt feed speed is to be displayed in units of
0.1 m/min.
Proximity Sensor: E2E-X5E1, NPN output
When displaying a flowrate (e.g., in l/min or l/h), make the scaling
settings after confirming the I/O characteristics of the flowrate sen-
sor. There are flowrate sensors that output analog signals. If this kind
of flowrate sensor is used, consider using the K3MA-J.
1. Select the maximum input frequency for the K3MA-F.
Set the pulse frequency selection to either 30 Hz or 5 kHz. In the
example, this is set to 30 Hz because the conveyor belt is turning
at a slow speed.
Parameter: p-fre (pulse frequency), Setting value: 30
2. Set the scaling. The display value (D) is shown with the following
formula.
D = f × α,
f: frequency and
α: prescaling value
The value of α will be internally calculated and registered if the
input value (f) and the display value (D) are set.
The number of rotations or speed is shown with the following for-
mula.
Rotations (rpm) = Frequency input/No. of pulses
per rotation × 60
Cycle speed D (m/min)= Rotations × roll circumference
= 1/N × f × 60 × d × π
N: No. of pulses per rotation
f: Frequency (Hz)
d: Roller diameter (m)
When the input conditions are applied to this equation, we obtain
the following:
Display value = 1/1 × f × 60 × 0.1 × π
For an input of 1 Hz, the display value is 18.8495 (m/min).
The scaling settings for the K3MA-F must be integers. Also, to
decrease error, the scaling value is multiplied by 1,000, to obtain
an input of 1000 Hz and a display value of 18850. However,
because the display value in this case is displayed to the first dec-
imal place, the scaling is set as shown in the following example so
that 1885.0 is displayed for an input of 100 Hz.
Parameter Setting value
inp (scaling input value) 100
dsp (scaling display value) 18850
dp (decimal point position) %%%%.%
Note: The decimal point position here refers to the position in the
number after scaling. When setting the scaling display value, it
is necessary to consider the number of digits to be displayed
past the decimal point.
Troubleshooting
When an error occurs, error details will be displayed on the main indicator. Confirm the error from the main indicator and take the appropriate coun-
termeasures.
1
2
E2E-X5E1
Proximity Sensor
K3MA-F-A2 100-240VAC
0.1 m
MAX/MIN LEVEL MODE SHIFT UP
Max
Min
SV
dsp
18850
inp
100
1 pulse/rotation, roller diameter 0.1 m
Display value
Input value
Level
display
Main indicator Error contents Countermeasures
Not lit e111 RAM memory error Repair is necessary.
Consult your OMRON sales representative.
5e111 EEPROM memory error When this error is displayed, press the Level Key for 3 sec-
onds, and the settings will be restored to the factory set-
tings.
If the error cannot be recovered, repair is necessary. Con-
sult your OMRON sales representative.
Not lit Flashes 99999 The scaling display value exceeds 99999. Promptly change the input to a value that falls within the
specified range.
The scaling value may be inappropriate. Review the scal-
ing value at the initial setting level.
Not lit Flashes -19999 The scaling display value is lower than 19999. Promptly change the input to a value that falls within the
specified range.
The scaling value may be inappropriate. Review the scal-
ing value at the initial setting level.
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyers request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyers application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omrons representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2014.10
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2014 All Right Reserved.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
K32-49HC K3MA-F 24VAC/VDC K3MA-F-A2 24VAC/VDC K32-49SC