System pro
M
compact®
Miniature Circuit Breaker S 200/S 200 M
Data Sheet
The miniature circuit breakers of the
System pro
M
compact® series S 200
and S 200 M provide state-of-the-art
safety and comfort. They stand out due
to their high performance and the wide
range of accessories and approvals.
2CDC021023S0012
Features
Clear contact position indication in red/green (“real CPI”)
Unique, patented twin terminal with captive screws and
an increased opening for cables up to max. 35 mm2,
finger-proof (IP20)
Busbar slot in the back for best visibility during installation
High performance at an increased rated voltage for marine
and industrial applications: 10 kA/15 kA at Un = 440 V AC
acc. to IEC/EN 60947-2
Individual product identification code
Approved acc. to IEC/EN 60898-1, IEC/EN 60947-2 and
UL 1077/CSA 22.2 No. 235 for global use
2CDC021038S0012
2 - 2CDC002157D0201
Miniature Circuit Breaker S 200/S 200 M
Technical data
S 200 S 200 M
General Data
Standards IEC/EN 60898-1, IEC/EN 60947-2
UL 1077
IEC/EN 60898-1, IEC/EN 60947-2
UL 1077, CSA 22.2 No. 235
Poles 1P, 2P, 3P, 4P, 1P+N, 3P+N
Tripping Characteristics B, C, D, K, Z
Rated current In 0.5 up to 63 A
Rated insulation voltage Ui250 V AC (phase to ground), 500 V AC (phase to phase)
Rated frequency 50/60 Hz
Overvoltage Category III
Pollution Degree 3
IEC/EN 60898-1
Rated operational voltage Un 1P: 230/400 V AC; 1P+N: 230 V AC; 2P, 3P, 4P: 400 V AC; 3P+N: 400 V AC
Power frequency recovery voltage Umax 1P: 253 V AC; 1P+N: 253 V AC; 2P, 3P, 4P: 440 V AC; 3P+N: 440 V AC;
1P: 72 V DC; 2P: 125 V DC
Min. operating voltage 12 V AC, 12 V DC
Rated short-circuit capacity Icn 6 kA 10 kA
Energy limiting class (B, C up to 40 A) 3
Rated impulse withstand voltage Uimp (1.2/50 µs) 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)
Dielectric test voltage 2.0 kV (50/60 Hz, 1 min)
Reference temperature for tripping characteristics B, C, D: 30 °C
Electrical endurance In < 32 A: 20,000 ops. (AC), 1,000 ops. (DC); one cycle 2 s - ON, 13 s - OFF
In ≥ 32 A: 10,000 ops. (AC), 1,000 ops. (DC); one cycle 2 s - ON, 28 s - OFF
IEC/EN 60947-2
Rated operational voltage Ue1P: 230 V AC; 1P+N: 230 V AC; 2P, 3P, 4P: 440 V AC; 3P+N: 440 V AC
Power frequency recovery voltage Umax 1P: 253 V AC; 1P+N: 253 V AC; 2P, 3P,4P: 462 V AC; 3P+N: 462 V AC;
1P: 72 V DC; 2P: 125 V DC
Min. operating voltage 12 V AC, 12 V DC
Rated ultimate short-circuit breaking capacity Icu 10 kA 15 kA
Rated service short-circuit breaking capacity Ics 7.5 kA ≤ 40 A: 11.2 kA
50, 63 A: 7.5 kA
Rated impulse withstand voltage Uimp (1.2/50 µs) 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)
Dielectric test voltage 2.0 kV (50/60 Hz, 1 min)
Reference temperature for tripping characteristics B, C, D: 55 °C; K, Z: 20 °C
Electrical endurance In < 32 A: 20,000 ops. (AC), 1,000 ops. (DC); one cycle 2 s - ON, 13 s - OFF
In ≥ 32 A: 10,000 ops. (AC), 1,000 ops. (DC); one cycle 2 s - ON, 28 s - OFF
Data acc. to UL/CSA
Rated voltage 480Y / 277 V AC
Rated interrupting capacity 6 kA
Application Suppl. prot. for general use. Application Codes: TC2, OL0, SC: U1
Reference temperature for tripping characteristic B, C, D, K, Z: 25 °C
Electrical endurance 6,000 ops. (AC), 6,000 ops. (DC); one cycle 1 s - ON, 9 s - OFF
Mechanical data
Housing Insulation group II, RAL 7035 Insulation group I, RAL 7035
Toggle Insulation group II, black, sealable
Contact position indication Marking on toggle (I ON/0 OFF), Real CPI (red ON/green OFF)
Protection degree acc. to EN 60529 IP20*, IP40 in enclosure with cover
Mechanical endurance 20,000 ops.
Shock resistance acc. to IEC/EN 60068-2-27 25 g, 3 shocks, 11 ms
Vibration resistance acc. to IEC/EN 60068-2-6 5 g, 20 cycles at 5…150…5 Hz with load 0.8 In
Environmental conditions acc. to IEC/EN 60068-2-30 28 cycles with 55 °C/90-96 % and 25 °C/95-100 %
Ambient temperature -25 ... +55 °C
Storage temperature -40 ... +70 °C
* Also fulfilling the requirements acc. to the protection degree IPXXB
2CDC002157D0201 - 3
Miniature Circuit Breaker S 200/S 200 M
Technical data and tripping characteristics
S 200 S 200 M
Installation
Terminal Failsafe bi-directional cylinder-lift terminal
Cross-section of conductors (top/bottom) 35 mm2 / 35 mm2
18 – 4 AWG
Cross-section of busbars (top/bottom) 10 mm2 / 10 mm2
18 – 8 AWG
Torque 2.8 Nm
25 in-Ibs.
Screwdriver No. 2 Pozidrive
Mounting On DIN rail 35 mm acc. to EN 60715 by fast clip
Mounting position any
Supply optional
Dimensions and weight
Mounting dimensions acc. to DIN 43880 Mounting dimension 1
Pole dimensions (H x D x W) 85 x 69 x 17.5
Pole weight approx. 125 g
Combination with auxiliary elements
Auxiliary contact Yes
Signal/auxiliary contact Yes
Shunt trip Yes
Undervoltage release Yes
Motor Operating Device Yes
Tripping characteristics
Acc. to Tripping
characte-
ristics
Rated
current
Thermal release 1) Electromagnetic release 2)
In
Currents:
conventional
non-tripping
current
I1
conventional
tripping
current
I2
Tripping
time
Range of
instantaneous
tripping
Tripping time
IEC/EN 60898-1 B6 to 63 A 1.13 · In
1.45 · In
> 1 h
< 1 h
3 · In
5 · In
0.1 ... 45 s (In ≤ 32 A)/0.1 ... 90 s (In > 32 A)
< 0.1 s
C0.5 to 63 A 1.13 · In
1.45 · In
> 1 h
< 1 h 3)
5 · In
10 · In
0.1 ... 15 s (In ≤ 32 A)/0.1 ... 30 s (In > 32 A)
< 0.1 s
D0.5 to 63 A 1.13 · In
1.45 · In
> 1 h
< 1 h 3)
10 · In
20 · In
0.1 ... 4 s (In ≤ 32 A)/0.1 ... 8 s (In > 32 A)
< 0.1 s
IEC/EN 60947-2 K0.5 to 63 A 1.05 · In
1.2 · In
> 1 h
< 1 h not applicable
1.05 · In
1.2 · In
> 2 h
< 1 h 3)
10 · In
14 · In
> 0.2 s
< 0.2 s
Z0.5 to 63 A 1.05 · In
1.2 · In
> 1 h
< 1 h not applicable
1.05 · In
1.2 · In
> 2 h
< 1 h 3)
2 · In
3 · In
> 0.2 s
< 0.2 s
1) The thermal releases are calibrated to a nominal reference ambient temperature; for B, C, D the reference value is 30 °C, for K and Z the reference value is 20 °C.
In the case of higher ambient temperatures, the current values fall by approx. 6 % for each 10 K temperature rise.
2) The indicated tripping values of electromagnetic tripping devices apply to a frequency of 50/60 Hz. The thermal release operates independent of frequency.
3) As from operating temperature (after I1 > 1h or, as applicable, 2h)
4 - 2CDC002157D0201
Miniature Circuit Breaker S 200/S 200 M
2CDC022060F0211
Z characteristic
Tripping characteristics
2CDC022006F0211
2CDC022008F0211
B characteristic C characteristic
2CDC022010F0211
K characteristic
D characteristic
2CDC022108F0209
2CDC002157D0201 - 5
Miniature Circuit Breaker S 200/S 200 M
For installations of miniature circuit breakers at other temperatures than the reference value and installations of several minia-
ture circuit breakers directly side by side, derating factors have to be considered.
Deviating ambient temperature
The rated value of the current of a miniature circuit breaker refers to a reference ambient temperature of 30 °C for circuit breakers
with the characteristics B, C and D and 20 °C for circuit breakers with the characteristics K and Z. The following table contains
the derating of the load capability at ambient temperatures from -40 °C to 70 °C for the characteristics B, C, D, K and Z.
Derating
Tripping Rated Maximum operating current at ambient temperature T
charac- current
teristics In
A- 40 °C - 30 °C - 20 °C - 10 °C 0 °C 10 °C 20 °C 30 °C 40 °C 50 °C 60 °C 70 °C
B, C, D 0.5 0.67 0.65 0.62 0.60 0.58 0.55 0.53 0.50 0.47 0.44 0.41 0.37
1.0 1.33 1.29 1.25 1.20 1.15 1.11 1.05 1.00 0.94 0.88 0.82 0.75
1.6 2.13 2.07 2.00 1.92 1.85 1.77 1.69 1.60 1.51 1.41 1.31 1.19
2.0 2.67 2.58 2.49 2.40 2.31 2.21 2.11 2.00 1.89 1.76 1.63 1.49
3.0 4.0 3.9 3.7 3.6 3.5 3.3 3.2 3.0 2.8 2.6 2.4 2.2
4.0 5.3 5.2 5.0 4.8 4.6 4.4 4.2 4.0 3.8 3.5 3.3 3.0
6.0 8.0 7.7 7.5 7.2 6.9 6.6 6.3 6.0 5.7 5.3 4.9 4.5
8.0 10.7 10.3 10.0 9.6 9.2 8.8 8.4 8.0 7.5 7.1 6.5 6.0
10.0 13.3 12.9 12.5 12.0 11.5 11.1 10.5 10.0 9.4 8.8 8.2 7.5
13.0 17.3 16.8 16.2 15.6 15.0 14.4 13.7 13.0 12.3 11.5 10.6 9.7
16.0 21.3 20.7 20.0 19.2 18.5 17.7 16.9 16.0 15.1 14.1 13.1 11.9
20.0 26.7 25.8 24.9 24.0 23.1 22.1 21.1 20.0 18.9 17.6 16.3 14.9
25.0 33.3 32.3 31.2 30.0 28.9 27.6 26.4 25.0 23.6 22.0 20.4 18.6
32.0 42.7 41.3 39.9 38.5 37.0 35.4 33.7 32.0 30.2 28.2 26.1 23.9
40.0 53.3 51.6 49.9 48.1 46.2 44.2 42.2 40.0 37.7 35.3 32.7 29.8
50.0 66.7 64.5 62.4 60.1 57.7 55.3 52.7 50.0 47.1 44.1 40.8 37.3
63.0 84.0 81.3 78.6 75.7 72.7 69.6 66.4 63.0 59.4 55.6 51.4 47.0
K, Z 0.5 0.66 0.64 0.61 0.59 0.56 0.53 0.50 0.47 0.43 0.40 0.35 0.31
1.0 1.32 1.27 1.22 1.17 1.12 1.06 1.00 0.94 0.87 0.79 0.71 0.61
1.6 2.12 2.04 1.96 1.88 1.79 1.70 1.60 1.50 1.39 1.26 1.13 0.98
2.0 2.65 2.55 2.45 2.35 2.24 2.12 2.00 1.87 1.73 1.58 1.41 1.22
3.0 4.0 3.8 3.7 3.5 3.4 3.2 3.0 2.8 2.6 2.4 2.1 1.8
4.0 5.3 5.1 4.9 4.7 4.5 4.2 4.0 3.7 3.5 3.2 2.8 2.4
6.0 7.9 7.6 7.3 7.0 6.7 6.4 6.0 5.6 5.2 4.7 4.2 3.7
8.0 10.8 10.2 9.8 9.4 8.9 8.5 8.0 7.5 6.9 6.3 5.7 4.9
10.0 13.2 12.7 12.2 11.7 11.2 10.6 10.0 9.4 8.7 7.9 7.1 6.1
13.0 17.2 16.6 15.9 15.2 14.5 13.8 13.0 12.2 11.3 10.3 9.2 8.0
16.0 21.2 20.4 19.6 18.8 17.9 17.0 16.0 15.0 13.9 12.6 11.3 9.8
20.0 26.5 25.5 24.5 23.5 22.4 21.2 20.0 18.7 17.3 15.8 14.1 12.2
25.0 33.1 31.9 30.6 29.3 28.0 26.5 25.0 23.4 21.7 19.8 17.7 15.3
32.0 42.3 40.8 39.2 37.5 35.8 33.9 32.0 29.9 27.7 25.3 22.6 19.6
40.0 52.9 51.0 49.0 46.9 44.7 42.4 40.0 37.4 34.6 31.6 28.3 24.5
50.0 66.1 63.7 61.2 58.6 55.9 53.0 50.0 46.8 43.3 39.5 35.4 30.6
63.0 83.3 80.3 77.2 73.9 70.4 66.8 63.0 58.9 54.6 49.8 44.5 38.6
Influence of adjacent devices
If several miniature circuit breakers are installed directly side
by side with high load on all poles, a correction factor has to
be applied to the rated current (see table). If distance pieces
are used, the factor is not to be considered.
No. of adjacent devices Factor F
1 1
2, 3 0.9
4, 5 0.8
≥ 6 0.75
Example
S201-C16 at T = 40 °C
Conditions
of use
Values to use Calculation Result
Load at ambient
temperature
40 °C with
8 adjacent
devices
In (40 °C),
Factor F
15.1 A x 0.75 In = 11.33 A
6 - 2CDC002157D0201
Miniature Circuit Breaker S 200/S 200 M
Accessory overview
Dimensional drawing
2CDC022007F0010
Accessories and dimensional drawing
H Auxiliary contact S2C-H6R
(change-over contact)
H-R Auxiliary contact S2C-H6-...R
S/H Signal/Auxiliary contact S2C-S/H6R
S/H (H) Signal/Auxiliary contact
used as auxiliary contact S2C-S/H6R
ST Shunt trip S2C-A...
UR Undervoltage release S2C-UA
OR Overvoltage release S2C-OVP
2CDC092002F0212
H-L Auxiliary contact S2C-H...L
H-BF Auxiliary contact for bottom fitting S2C-H01
(1 per pole) S2C-H10
BP Mechanical tripping device S2C-BP
NT Neutral disconnector S2C-Nt
MOD-S* Motor operating device S2C-CM
DDA 200 RCD-block DDA 20...
* In case of using S 200/S 200 M coupled with DDA 200, MOD-S does not
operate in case of earth-leakage fault.
ABB STOTZ-KONTAKT GmbH
Eppelheimer Straße 82
69123 Heidelberg, Germany
Phone: +49 (0) 6221 7 01-0
Fax: +49 (0) 6221 7 01-13 25
E-Mail: info.desto@de.abb.com
You can find the address of your
local sales organization on the
ABB home page
http://www.abb.com/contacts
-> Low Voltage Products and Systems
Contact us
Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. With regard to purchase orders, the
agreed particulars shall prevail. ABB AG does
not accept any responsibility whatsoever for
potential errors or possible lack of information in
this document.
We reserve all rights in this document and in
the subject matter and illustrations contained
therein. Any reproduction, disclosure to third
parties or utilization of its contents – in whole
or in parts – is forbidden without prior written
consent of ABB AG.
Copyright© 2012 ABB