Product: 29513
VFD 300% Gnd, 3C+G #10 Str TC, XLPE Ins+PVC Gnd, OS+TC Brd, 1 Pr
#16 Str TC XLPE IS, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet 1000V Flexible
Motor Supply Cable
Product Description
Belden 300% Ground Flexible VFD, 3 Conductor 10AWG (105x30) Tinned Copper, XLPE Insulation M4 Color Code+PVC Insulated Ground, Overall
Beldfoil®+Tinned Copper Braid(85%) Shield, 1 Pair 16AWG (26x30) Tinned Copper XLPE Beldfoil, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet 1000V
Flexible Motor Supply Cable 1000V CSA AWM I/II A/B 600V CIC TC SUN RES DIR BUR Oil Resistant
Technical Specifications
Product Overview
Suitable Applications: AC Motor drives, VFD, Variable Frequency drives; Systems with composite power and control requirements
Physical Characteristics (Overall)
Conductor
AWG Stranding Material No. of Conductors
10 105x30 TC - Tinned Copper 3
16 26x30 TC - Tinned Copper 2
10 105x30 TC - Tinned Copper 1
Conductor Count: 5
Insulation
Material Nominal Wall Thickness
XLPE - Cross-Linked Polyethylene (Thermoset) 0.046 in
XLPE - Cross-Linked Polyethylene (Thermoset) 0.032 in
PVC - Polyvinyl Chloride 0.046 in
Color Chart
Number Color
1Black and Numbered
2
3
4
5
Color Chart 2
Color
Black
White
Color Chart 3
Color
Green with Yellow Stripe
Inner Shield Material
Material Trade Name Drainwire Material Drainwire AWG
Beldfoil® TC - Tinned Copper 18
Outer Shield Material
Type Layer Material Material Trade Name Coverage [%] Drainwire Material Drainwire AWG Drainwire Construction n x D
Tape 1Tri-Laminate
(Alum+Poly+Alum) Duofoil® 100% TC - Tinned Copper 10 105x30
Braid 2Tinned Copper (TC) 85%
Table Notes: Foil+braid shield on power conductors only; extra pair has foil shield only
Outer Jacket Material
Material Nominal Diameter Nominal Wall Thickness Ripcord
PVC - Polyvinyl Chloride 0.985 in 0.105 in Yes
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR Nominal Inner Shield DCR
0.988 Ohm/1000ft
4 Ohm/1000ft 4.99 Ohm/1000ft
Capacitance
Nom. Capacitance Conductor to Conductor Nom. Capacitance Conductor to Shield
29 pF/ft 53 pF/ft
34 pF/ft
Inductance
Nominal Inductance
0.184 µH/ft
Voltage
UL Voltage Rating
1000 V RMS
600 V RMS (Type TC)
Temperature Range
UL Temp Rating: 90°C Dry, 90°C Wet
Operating Temp Range: -40°C To +90°C
Mechanical Characteristics
Max. Pull Tension: 718 lbs
Min Bend Radius/Minor Axis: 9.9 in
Standards
NEC Articles: Article 336
NEC/(UL) Compliance: RHW-2, TC-ER
CEC/C(UL) Compliance: CIC, TC
CSA AWM Compliance: AWM I/II A/B
PMSHA Compliance: P-07-KA070003
Other Compliance: 1000V UL Flexible Motor Supply Cable
Applicable Environmental and Other Programs
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2003/96/EC (BFR): Yes
EU Directive 2011/65/EU (ROHS II): Yes
EU Directive 2012/19/EU (WEEE): Yes
EU Directive 2015/863/EU: Yes
EU Directive Compliance: EU Directive 2003/11/EC (BFR)
EU CE Mark: Yes
EU RoHS Compliance Date (yyyy-mm-dd): 2006-09-21
CA Prop 65: Yes
MII Order #39 (China RoHS): Yes
Suitability
Suitability - Burial: Yes
Suitability - Indoor: Yes
Suitability - Outdoor: Yes
Suitability - Sunlight Resistance: Yes
Flammability, LS0H, Toxicity Testing
UL Flammability: UL1685 UL Loading
CSA Flammability: FT4
IEEE Flammability: 1202, 383
UL voltage rating: 1000 V RMS (Flexible Motor Supply Cable)
Plenum/Non-Plenum
Plenum (Y/N): No
Part Number
Variants
Item # Color Putup Type Length UPC
29513 010100 Black Reel 100 ft 612825137580
29513 0101000 Black Reel 1,000 ft 612825137597
29513 0103000 Black Reel 3,000 ft 612825137603
Footnote: C - CRATE REEL PUT-UP.
History
Update and Revision: Revision Number: 0.349 Revision Date: 06-30-2020
© 2020 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without
notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages
(including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief
at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product
Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and
regulations based on their individual usage of the product.