IB IL AO 2/SF ... Inline terminal with two analog outputs 4 x AUTOMATION Data sheet 6655_en_06 1 (c) PHOENIX CONTACT 2010-03-15 Description The terminal is designed for use within an Inline station. It is used to output analog voltage or current signals. The signals are available with a 16-bit resolution. Features - - - - - - - Two analog signal outputs to connect either voltage or current signals Actuator connection in 2-wire technology with shield connection Two current ranges, one voltage range: 0 mA to 20 mA, 4 mA to 20 mA, 0 V to 10 V Process data update including conversion time of the digital/analog converter <1 ms 16-bit resolution with high precision (voltage output 0.008%, typical, current output 0.01%, typical) High level of operational safety in the event of an error thanks to real 4 mA to 20 mA output Load range (mA outputs) 0 to 500 This data sheet is only valid in association with the user manual. Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.net/catalog. This data sheet is valid for the products listed on the following page: 6 8 5 7 A 0 0 2 IB IL AO 2/SF ... 2 Ordering data Products Description Type Order No. Pcs./Pkt. Terminal with two analog outputs to output either voltage or current signals; without accessories; 500 kbps transmission speed IB IL AO 2/SF 2862806 1 Terminal with two analog outputs to output either voltage or current signals; with accessories (connectors and labeling fields); 500 kbps transmission speed IB IL AO 2/SF-PAC 2863083 1 Terminal with two analog outputs to output either voltage or current signals; without accessories; 2 Mbps transmission speed IB IL AO 2/SF-2MBD 2860426 1 Terminal with two analog outputs to output either voltage or current signals; with accessories (connectors and labeling fields); 2 Mbps transmission speed IB IL AO 2/SF-2MBD-PAC 2862194 1 You need two of the connector set listed below for the complete fitting of the IB IL AO 2/SF and IB IL AO 2/SF-2MBD terminals. Accessories Description Type Order No. Pcs./Pkt. Connector set IB IL AO/CNT-PLSET 2732664 1 set Description Type The shield connector must be used for connecting an actuator: Order No. Pcs./Pkt. Inline shield connector for analog Inline terminals, without color print 2726353 5 Accessories as replacement items IB IL SCN-6 SHIELD On slots that are not used for actuator connection you may use one of the following connectors: Inline shield connector for analog Inline terminals, without color print IB IL SCN-6 SHIELD 2726353 5 Connector for digital 1, 2 or 8-channel Inline terminals, without color print IB IL SCN-8 2726337 10 Inline connector, with color print IB IL SCN-8-CP 2727608 10 Description Type Order No. Pcs./Pkt. "Automation terminals of the Inline product range" user manual IL SYS INST UM E 2698737 1 "Configuring and installing the INTERBUS Inline product range" user manual IB IL SYS PRO UM E 2743048 1 "INTERBUS addressing" data sheet DB GB IBS SYS ADDRESS 9000990 1 Documentation 3 Technical data General data Housing dimensions (width x height x depth) 48.8 mm x 120 mm x 71.5 mm Weight 125 g (without connectors), 190 g (with connectors) Operating mode Process data mode with 2 words Connection method for actuators 2-wire technology Ambient temperatures (operation) -25C to +55C Ambient temperature (storage/transport) -25C to +85C Permissible humidity (operation/storage/transport) 10% to 95% according to DIN EN 61131-2 Permissible air pressure (operation/storage/transport) 70 kPa to 106 kPa (up to 3000 m above sea level) Degree of protection IP20 according to IEC 60529 Protection class Class 3 according to EN 61131-2, IEC 61131-2 Connection data for Inline connectors Connection method Spring-cage terminals Conductor cross-section 0.2 mm2 to 1.5 mm2 (solid or stranded), 24 - 16 AWG 6655_en_06 PHOENIX CONTACT 2 IB IL AO 2/SF ... Deviations from common technical data that are indicated in the IB IL SYS PRO UM E user manual: Mechanical requirements Shock test according to EN 60068-2-27; IEC 60068-2-27 15g load for 11 ms, half sinusoidal wave, three shocks in each space direction and orientation 25g load for 6 ms, half sinusoidal wave, three shocks in each space direction and orientation Interface Local bus Data routing Transmission speed IB IL AO 2/SF; IB IL AO 2/SF-PAC 500 kbps IB IL AO 2/SF-2MBD; IB IL AO 2/SF-2MBD-PAC 2 Mbps Power consumption 500 kbps 2 Mbps Communications power UL 7.5 V DC 7.5 V DC Current consumption at UL 36 mA (typical), 45 mA (maximum) 60 mA (typical), 75 mA (maximum) Analog supply voltage UANA 24 V DC 24 V DC Current consumption at UANA 75 mA (typical), 95 mA (maximum) 75 mA (typical), 95 mA (maximum) Total power consumption 2.1 W (typical) 2.3 W (typical) Supply of the module electronics and I/O through bus coupler/power terminal Connection method Potential routing Analog output Number 2; configured depending on the terminal point used Signals/resolution in the process data bytes (quantization) for Inline Voltage 0 V to 10 V 0 V to 10.837 V; 0.333 mV/LSB Current 0 mA to 20 mA 0 mA to 21.6764 mA; 0.667 A/LSB 4 mA to 20 mA 4 mA to 21.3397 mA; 0.533 A/LSB Signals/resolution in the process data bytes (quantization) for ST Voltage 0 V to 10 V 0 V to 9.9975 V; 2.441 mV Current 0 mA to 20 mA 0 mA to 19.9951 mA; 4.8828 A 4 mA to 20 mA 4 mA to 19.9961 mA; 3.906 A Basic error limit 0.003% Output load Voltage output 2 k, minimum Current output 0 to 500 Process data update of the module including conversion time of the digital/ analog converter 6655_en_06 < 1 ms PHOENIX CONTACT 3 IB IL AO 2/SF ... Signal rise times: Voltage output 0 V to 10 V (typical values) 10% to 90% 0% to > 99% No-load operation 44 s 72 s Ohmic load RL = 2 k 46 s 74 s Ohmic/capacitive load RL = 2 k / CL = 10 nF 47 s 95 s Ohmic/capacitive load RL = 2 k / CL = 220 nF 79 s 350 s Ohmic/inductive load RL = 2 k / LL = 3.3 mH 48 s 75 s Signal rise times: Current output 0 mA to 20 mA (typical values) 10% to 90% 0% to > 99% Ohmic load RL = 500 126 s 380 s Ohmic/capacitive load RL = 500 /CL = 10 nF 140 s 425 s Ohmic/capacitive load RL = 500 /CL = 220 nF 350 s 1200 s Ohmic/inductive load RL = 500 /LL = 3.3 mH 110 s 368 s Signal rise times: Current output 4 mA to 20 mA (typical values) 10% to 90% 0% to > 99% Ohmic load RL = 500 140 s 508 s Ohmic/capacitive load RL = 500 /CL = 10 nF 145 s 534 s Ohmic/capacitive load RL = 500 /CL = 220 nF 380 s 1200 s Ohmic/inductive load RL = 500 /LL = 3.3 mH 116 s 410 s Tolerance and temperature response of the outputs for TA = 25C Output range Absolute tolerance Typical Maximum Relative tolerance Typical Maximum 0 V to 10 V 0.8 mV 2.0 mV 0.008% 0 mA to 20 mA 2 A 6 A 0.01% 0.02% 0.03% 4 mA to 20 mA 2 A 6 A 0.01% 0.03% Tolerance and temperature response of the outputs for TA = -25C to +55C Output range Temperature coefficient Typical Maximum 0 V to 10 V 8 ppm/K 0 mA to 20 mA 18 ppm/K 25 ppm/K 45 ppm/K 4 mA to 20 mA 18 ppm/K 45 ppm/K Outside the specified range, tolerances at the analog outputs might increase when gradually switching off the 24 V supply voltage UANA. They occur below UANA = +13.5 V. If UANA continues to fall, an I/O error is triggered. All percentage tolerance values refer to the relevant measuring range final value. The maximum tolerance values contain the theoretical maximum possible tolerances. The validity of the values is 12 months at least. The data refers to nominal operation (installation on horizontal DIN rail, US = 24 V). Please also observe the values for temperature drift and the tolerances under EMC influences. The tolerances for the different voltage and current output areas are documented with a high level of accuracy for the keying. 6655_en_06 PHOENIX CONTACT 4 IB IL AO 2/SF ... Additional tolerances influenced by electromagnetic fields Type of electromagnetic interference Typical deviation from the output range final value (voltage output) Relative Typical deviation of the output range final value (current output) Relative Electromagnetic fields; Field strength 10 V/m according to EN 61000-4-3/IEC 61000-4-3 < 0.1% < 0.1% Conducted interference Class 3 (test voltage 10 V) according to EN 61000-4-6/IEC 61000-4-6 < 0.1% < 0.3% Fast transients (burst) 2 kV supply, 1 kV output according to EN 61000-4-4/IEC 61000-4-4 Class A Class A Fast transients (burst) 4 kV supply, 2 kV output according to EN 61000-4-4/IEC 61000-4-4 Class B Class B Protective equipment Transient protection for voltage and current outputs Electrical isolation/isolation of the voltage areas Electrical isolation of the logic level from the I/O area is ensured through optocouplers and the DC/DC converters. Common potentials 24 V I/O voltage, 24 V segment voltage, and GND have the same potential. FE is a separate potential area. Separate potentials in the system consisting of bus coupler/power terminal and I/O terminal Test distance Test voltage 7.5 V supply (bus logic), 24 V supply UANA / I/O 500 V AC, 50 Hz, 1 min. 7.5 V supply (bus logic), 24 V supply UANA/functional earth ground 500 V AC, 50 Hz, 1 min. 24 V supply (I/O) / functional earth ground 500 V AC, 50 Hz, 1 min. Error messages to the higher-level control or computer system Failure or insufficient analog supply voltage UANA Yes, I/O error message sent to the bus coupler Approvals For the latest approvals, please visit www.phoenixcontact.net/catalog. 6655_en_06 PHOENIX CONTACT 5 IB IL AO 2/SF ... 4 Local diagnostic and status indicators and terminal point assignment 4.2 Function identification Yellow 2 Mbps: White stripe in the vicinity of the D LED 4.3 Terminal point assignment Connector Terminal Signal point 1 1.1, 2.1 +U D O -S A O 2 S F 1.2, 2.2 1.3, 2.3 1.4, 2.4 1.1 B1 AGND Shield +I0-20 2.1 +I4-20 3 1.2, 2.2 1.3, 2.3 1.4, 2.4 1.1, 2.1 B2 AGND Shield +U 4 1.2, 2.2 1.3, 2.3 1.4, 2.4 1.1 B1 AGND Shield +I0-20 2.1 +I4-20 1.2, 2.2 1.3, 2.3 1.4, 2.4 B2 AGND Shield 2 1 2 1 .1 1 1 2 .1 1 .2 2 2 2 .2 1 .3 3 3 2 .3 1 .4 4 4 2 .4 6 6 5 5 B 0 0 1 Figure 1 4.1 Terminal with an appropriate connector Local diagnostic and status indicators Des. D O-S Color Green Orange Meaning Diagnostics Original default state parameterized Note on the O-S LED: Assignment Voltage output of channel 1 Jumper 1 Analog ground Shield connection Current output of channel 1 0 mA to 20 mA Current output of channel 1 4 mA to 20 mA Jumper 2 Analog ground Shield connection Voltage output of channel 2 Jumper 1 Analog ground Shield connection Current output of channel 2 0 mA to 20 mA Current output of channel 2 4 mA to 20 mA Jumper 2 Analog ground Shield connection By default upon delivery, the terminal parameters are set as follows: Data format: Behavior of the outputs in the event of an error (failsafe): IB IL Outputs hold the last value (hold) As soon as these parameters are identified on the terminal, the O-S LED will light up. If at least one of the parameters is different (because of non-volatile or volatile parameterization) the LED will not light up. After power up the non-volatile stored parameterization always becomes valid. 6655_en_06 PHOENIX CONTACT 6 IB IL AO 2/SF ... 5 Installation instructions High current flowing through potential jumpers UM and US leads to a temperature rise in the potential jumpers and inside the terminal. To keep the current flowing through the potential jumpers of the analog terminals as low as possible, always place the analog terminals after all the other terminals at the end of the main circuit. (For the sequence of the Inline terminals: see also IL SYS INST UM E user manual or Inline system manual for your bus system). 6 Installation instruction Installing jumpers may influence the accuracy of the channels independently of each other. Without using jumpers the voltage channels have a high level of accuracy and the current channels have a low level of accuracy. Installing a jumper for a channel increases the accuracy of a current output. This also reduces the accuracy of the voltage output. Only install the jumper when using a current channel. Installing a jumper when using a voltage channel will not be indicated as an error. Changing the jumper will only take effect upon power up. Encoding table Represen- Connec- Jumper Status tation in tor Figure 2 A X* J1 Not installed Y* J2 Not installed B X* J1 Installed Y* J2 Not installed Meaning High level of accuracy 0 V to +10 V High level of accuracy 0 mA to +20 mA C X* J1 Not High level of installed accuracy Y* J2 Installed 4 mA to +20 mA X*Y* represent connectors 1 and 2 (channel 1) or connectors 3 and 4 (channel 2). A C h a n n e l 1 C h a n n e l 2 Y X 1 2 1 2 1 1 2 B Y X Y X 2 1 2 1 1 2 1 1 1 1 1 1 1 1 11 1 2 2 2 2 2 2 2 2 2 22 2 3 3 3 3 3 3 4 4 4 4 4 4 J 1 1 3 4 3 33 3 4 4 44 C Y X 3 2 2 1 Y 1 2 2 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 J 2 1 3 3 3 4 1 X 4 4 4 3 3 3 3 4 4 4 4 3 4 6 6 5 5 A 0 0 3 Figure 2 6655_en_06 Figure for the encoding table PHOENIX CONTACT 7 IB IL AO 2/SF ... 7 Internal basic circuit diagram L o c a l b u s U O P C L + A N A L - U U 2 4 V P E E P R O M S E C + 7 ,5 V / + 1 5 V R E F 4 U I0 -2 0 I4 I0 U -2 0 + 2 4 V (U S ) -2 0 I4 -2 0 2 + 2 4 V (U M ) 1 6 6 5 5 B 0 0 9 Figure 3 Internal basic circuit diagram Key: Protocol chip OPC P Reference voltage Optocoupler Amplifier Microprocessor Digital/analog converter Protective circuit (security) S E C R E F 1 Analog ground, electrically isolated from ground of the potential jumper Electrically erasable re-programmable read-only memory E E P R O M x x x DC/DC converter with electrical isolation X X X Other symbols used are explained in the IL SYS INST UM E user manual. 6655_en_06 PHOENIX CONTACT 8 IB IL AO 2/SF ... 8 Electrical isolation Local bus (IN) Bus connection OPC UL (7.5 V DC) Local bus (OUT) D O-S /SF AO2 D UL (7.5 V DC) O-S UANA (24 V DC) UANA (24 V DC) AO2SF 24 V A 5V +-15 V 1 Electrical isolation between area A and B 5V +-15 V Figure 4 Analog outputs 6857A008 Connection notes Always connect the analog actuators using shielded, twisted pair cables. At the terminal, connect one end of the shielding to FE. At the module, fold the outer cable sheath back and connect the shield to the terminal via the shield connection clamp. The clamp connects the shield directly to FE on the module side. 1 2 1 2 J2 1 11 11 11 1 2 22 22 22 2 3 33 33 33 3 4 44 44 44 4 B Use connectors with shield connection when installing the actuator. On free slots you may use one of the connectors listed in the ordering data. Figure 5 and Figure 6 show the connection schematically (without shield connector). OUT2 6655C007 Actuator connection to the voltage and current outputs using 2-wire technology with shield connection B: Channel 2, signals for one actuator at the current output 4 mA to 20 mA with high precision D O-S AO2 /SF D O-S AO2SF 1 J1 Connection examples I A: Channel 1, signals for an actuator at the voltage output 0 V to 10 V When using cables longer than 10 m in environments prone to interference, we recommend connecting the shield on the actuator to the FE potential additionally via an RC element. The capacitor C should typically have values of 1 nF to 15 nF. The resistor R should have a resistance of at least 10 M. 10 2 A Electrical isolation of the individual function areas Figure 5 9 1 OUT1 U FE potential 2 B I/O interface OUT1 I 1 2 1 2 1 2 J2 1 11 11 11 1 2 22 22 22 2 3 33 33 33 3 4 44 44 44 4 A Figure 6 2 I B OUT2 6655C008 Actuator connection to the current outputs using 2-wire technology with shield connection J1, J2: External jumpers A: Channel 1, signals for an actuator at the current output 0 mA to 20 mA with a high level of accuracy B: Channel 2, signals for an actuator at the current output 4 mA to 20 mA with a high level of accuracy 6655_en_06 PHOENIX CONTACT 9 IB IL AO 2/SF ... 11 Programming data/ configuration data 11.1 Local bus (INTERBUS) ID code Length code Process data channel Input address area Output address area Parameter channel (PCP) Register length (bus) 11.2 5Bhex (91dec) 02hex 32 bits 2 words 2 words 0 bytes 2 words Other bus systems For the programming data of other bus systems, please refer to the corresponding electronic device data sheet (e.g., GSD, EDS). 6655_en_06 PHOENIX CONTACT 10 IB IL AO 2/SF ... 12 Process data For the assignment of the illustrated (byte.bit) view to your INTERBUS control or computer system, please refer to the DB GB IBS SYS ADDRESS data sheet. 12.1 Assignment of the terminal points to OUT process data (Word.Bit) view Word Bit (Byte.Bit) view Byte Bit Assignment IB IL format Assignment IB ST format Terminal points Signal slot 1 AGND Shielding (FE) Terminal points Signal slot 2 AGND Shielding (FE) (Word.Bit) view Word Bit (Byte.Bit) view Byte Bit Assignment IB IL format Assignment IB ST format Terminal points Signal slot 3 AGND Shielding (FE) Terminal points Signal slot 4 AGND Shielding (FE) SB 0 15 14 13 7 SB SB 6 5 15 14 13 7 SB SB 6 5 12 11 Byte 0 4 3 10 9 Word 0 8 7 6 5 1 0 7 6 5 Output value channel 1 Output value channel 1 Terminal point 1.1.1: Voltage output Terminal point 1.1.3, 1.2.3 Terminal point 1.1.4, 1.2.4 Terminal point 2.1.1: Current output 0 mA to 20 mA Terminal point 2.2.1: Current output 4 mA to 20 mA Terminal point 2.1.3, 2.2.3 Terminal point 2.1.4, 2.2.4 12 11 Byte 2 4 3 2 4 3 Byte 1 4 3 10 9 2 Word 1 8 7 6 5 4 3 Byte 3 4 3 1 0 7 6 5 Output value channel 2 Output value channel 2 Terminal point 3.1.1: Voltage output Terminal point 3.1.3, 3.2.3 Terminal point 3.1.4, 3.2.4 Terminal point 4.1.1: Current output 0 mA to 20 mA Terminal point 4.2.1: Current output 4 mA to 20 mA Terminal point 4.1.3, 4.2.3 Terminal point 4.1.4, 4.2.4 2 1 0 2 1 0 0 0 0 2 1 0 2 1 0 0 0 0 Sign bit In "IB ST" format bits 2 through 0 are irrelevant. Set these bits to "0". 6655_en_06 PHOENIX CONTACT 11 IB IL AO 2/SF ... 12.2 Assignment of the IN process data (Word.Bit) view Byte Bit (Byte.Bit) view Byte Bit Assignment (Word.Bit) view Byte Bit (Byte.Bit) view Byte Bit Assignment SB F H 12.3 15 14 13 7 SB 6 5 15 14 13 7 SB 6 5 Word 0 12 11 10 9 8 7 6 5 Byte 0 4 3 2 1 0 7 6 5 Mirrored channel 1 output value 4 3 Byte 1 4 3 Word 1 12 11 10 9 8 7 6 5 Byte 2 4 3 2 1 0 7 6 5 Mirrored channel 2 output value 4 3 Byte 3 4 3 OUT process data OUT 0 12.4 0 2 F 1 0 0 H 2 1 0 2 F 1 0 0 H OUT1 IN process data Bits 15 through 3 of the process data output values are mirrored in the IN process data. Bit 15 is the sign bit. Bits 2 through 0 are available as status bits. The bits contain information on the parameterized behavior of the terminal. IN0 MSB LSB 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 IB IL OV SB 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 SB OV X X X 5660A006 Figure 7 OUT MSB LSB SB OV X 1 Sign bit Format of output data HOLD/RESET The OUT process data specifies the output values in each cycle. IB ST 2 OUT process data words in IB IL and IB ST formats Process data output word Most significant bit Least significant bit Sign bit Output value Irrelevant bit Set the irrelevant bits to 0. MSB LSB 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 SB F 0 H OV* 6655B002 Figure 8 IN MSB LSB SB OV* F H IN process data words Process data input word Most significant bit Least significant bit Sign bit Mirrored output value Format of output data HOLD/RESET Bits 2 through 0 have the following meaning: Bit 2 1 0 6655_en_06 IN1 Designa- Meaning tion F Format of output data Reserved H HOLD/RESET see page 15 Bit x = 0 Bit x = 1 IB IL IB ST HOLD RESET PHOENIX CONTACT 12 IB IL AO 2/SF ... 13 Formats for representing the output values "IB IL" is the default format on the terminal. To ensure that the terminal can be operated in the ST data format, the output value representation can be switched to the "IB ST" format. 13.1 "IB IL" format The output value is represented in bits 14 through 0. An additional bit (bit 15) is available as a sign bit. The sign bit is 0 for the output value 0 V to 10 V. If the sign bit is 1, which corresponds to a negative value, the value 0 V (or 0 mA/ 4 mA) is output. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 SB OV SB OV Sign bit Output value Bits 2 through 0 are not mirrored in the input data. 13.2 Significant output values in the "IB IL" format The terminal has two analog output channels, which are able to output voltages in the range of 0 V to +10 V or currents in the range of 0 mA to 20 mA and 4 mA to 20 mA with a resolution of 15 bits plus the sign bit. Value range 0 V to +10 V Area Overflow Overload capability range Nominal range Underflow 6655_en_06 Output data word (two's complement) hex dec 7FFF 32767 7F01 32513 7F00 32512 7531 30001 7530 3A98 0001 0000 < 0000 30000 15000 1 0 <0 0 V to +10 V UOutput Output range 0 mA to +20 mA IOutput +4 mA to +20 mA IOutput V +10.8373 +10.8373 +10.8373 +10.0003 mA + 21.6764 + 21.6764 + 21.6764 + 20.0007 mA + 21.3397 + 21.3397 + 21.3397 + 20.0005 +10.0000 5.0000 + 333.33 x 10-6 0 0 + 20.0000 +10.0000 + 0.667 x 10-6 0 0 + 20.0000 +12.0000 + 4.000533 + 4.000 + 4.000 PHOENIX CONTACT 13 IB IL AO 2/SF ... 13.3 "IB ST" format The output value is represented in bits 14 through 3. Bit 15 is available as sign bit. Bits 2 through 0 are irrelevant. This format corresponds to the data format used on INTERBUS ST modules. 15 14 13 12 11 10 9 8 7 SB OV SB OV X 6 5 4 3 2 x 1 0 x x Sign bit Output value Irrelevant bit (set this bit to 0.) Bits 2 through 0 are not mirrored in the input data. Significant output values in the "IB ST" format Value range 0 V to 10 V and 0 mA to 20 mA Output data word (two's complement) hex > 7FF8 7FF8 4000 0008 0000 0 V to +10 V UOutput 0 mA to +20 mA IOutput V 9.9975 9.9975 5.0000 0.0024 0 mA 19.9951 19.9951 10.0000 0.0048 0 Value range 4 mA to 20 mA Output data word (two's complement) hex >7FFC 7FFC 4000 000C 0004 4 mA to +20 mA IOutput mA 19.9961 19.9961 12.0000 4.003906 4.0000 All three ranges are available in parallel for this terminal. Therefore, bit 2, which is designed to distinguish the measuring ranges 0 mA to 20 mA/ 4 mA to 20 mA in the ST format, is irrelevant. 6655_en_06 PHOENIX CONTACT 14 IB IL AO 2/SF ... 14 Output behavior 14.1 Output behavior during error-free operation (normal operation) 14.2 After power up the stored values for the data format and the behavior of the outputs are read in the event of an error (reset value). These are either the values of the configuration upon delivery or a non-volatile stored configuration. Output behavior in the event of an error (failsafe) In the event of an error the outputs respond according to the parameterization (see "Parameterization" on page 17). That means the outputs hold the last value (HOLD, default setting) or they return to zero (RESET, can be parameterized). The data format and the behavior of the outputs in the event of an error can be parameterized non-volatile or volatile by a process data sequence during runtime (see "Parameterization" on page 17). 14.3 Output behavior of the voltage and current outputs Switching operation/state of the supply voltage UANA from 0 V to 24 V UANA from 24 V to 0 V Local bus stopped Local bus stopped Bus reset (e.g., remote bus cable break) UANA UL xxxx 14.4 Take the output behavior in the event of an error into account when configuring your system, especially a fail-safe behavior that was possibly parameterized twice (for the bus coupler and the analog terminal). Marginal condition UL = 0 V UL = 7.5 V UANA = 0 V UANA = 24 V Process data word OUT (hex) xxxx xxxx xxxx xxxx xxxx Behavior/status of the analog output 0 V to 10 V 0 mA to 20 mA 4 mA to 20 mA 0V 0V 0V 0 mA 0 mA 0 mA Hold last value Can be parameterized: Hold last value (default setting) 0 mA 0V 4 mA 0 mA 0 mA 4 mA Analog supply voltage of the terminal Supply voltage for module electronics (communications power) Any value in the range from 0000hex to FFFFhex Response of the voltage and current outputs to a control command of the controller board Command STOP ALARM STOP (reset) OUT process data word (hexadecimal) xxxx xxxx State after switching operation Analog output 0 V to 10 V 0 mA to 20 mA 0V 6655_en_06 4 mA to 20 mA Hold last value Can be parameterized: Hold last value (default setting) 0 mA 4 mA PHOENIX CONTACT 15 IB IL AO 2/SF ... 15 Input data in normal operation and in the event of an error During error-free operation (normal operation) the output data is mirrored in the input words as "acknowledgment" in bits 15 through 3 as soon as it has been transmitted to the DAC. Bits 2 through 0 are available as status bits and are used to display and read the set behavior of the terminal (see "IN process data" on page 12). If an error is detected by the terminal, it is indicated by means of an error code in the first or second process IN process data word depending on the error type. Possible error codes are given in the following table. Error codes: Output data word (two's complement) hex 8010 8020 8040 Cause Remedy The jumpers for selecting the "high accuracy" Connect the jumpers correctly. range are contradictory (e.g., 0 mA to 20 mA and at the same time 4 mA to 20 mA). The error message is indicated on the corresponding channel only. The user parameterization cannot be stored. Carry out a power up. The error message is indicated on both channels. Error in the I/O voltage supply Check the voltage supply on the bus coupler. Check that the potential jumpers are connecting safely. Replace the terminal. Terminal is defective. Replace the terminal. An I/O error is triggered with codes 8020hex and 8040hex. The error codes overwrite the status bits (bits 2 through 0) with "0". 6655_en_06 PHOENIX CONTACT 16 IB IL AO 2/SF ... 16 Parameterization By default upon delivery, the terminal parameters are set as follows: Data format: Behavior of the outputs in the event of an error: The following terminal parameters can be configured according to your conditions using the process data: IB IL Outputs hold the last value (Hold) Data format: Behavior of the outputs in the event of an error (failsafe): IB ST Outputs are set to 0 (reset) In order to parameterize the terminal you must change to parameterization mode. Steps to be taken to parameterize the terminal: Step 1: Transmission of code 8030hex in the first OUT process data word. In bits 15 through 3 of the first IN process data word this code is acknowledged as a normal process data item. Step 2: Transmission of the parameterization code in the second OUT process data word. Bit bin hex 15 1 14 0 13 0 12 0 11 0 10 0 8 9 0 8 0 0 7 0 6 1 5 0 4 1 3 p3 5 2 p2 1 0 0 p1 X Where px are the terminal parameters: p3: Volatile or non-volatile (0: Volatile; 1: Non-volatile) p2: Data format (0: IB IL; 1: IB ST) p1: Reset behavior (0: Hold; 1: Reset) Both output data words must be written with a maximum time of 10 s between each other. This makes data consistency over two words unnecessary. The writing sequence is not important. If the time has elapsed, something else, differing from the parameter value, must be written in the two words. The parameter words must be kept for 2 s until the parameterization is accepted. Step 4: Acceptance of the value is confirmed in bits 15 through 3 of the first input word through mirroring of the code. No timer is required in the application as monitoring the input data is sufficient. When mirroring, note that bits 2 through 0 still indicate the current terminal parameterization in each word. As soon as the new parameterization is valid the corresponding parameter bit is set in the input data. Step 5: The terminal is in normal process data mode again. Prior to a new parameterization, the data on both output words must have changed. The orange O-S LED on the terminal indicates whether the original configuration is present or whether the active configuration differs from the default configuration of the terminal upon delivery. The LED is on if the default state has been parameterized (see also "Local diagnostic and status indicators" on page 6). 6655_en_06 PHOENIX CONTACT GmbH & Co. KG * 32823 Blomberg * Germany * Phone: +49-(0) 5235-3-00 PHOENIX CONTACT * P.O.Box 4100 * Harrisburg * PA 17111-0100 * USA * Phone: +717-944-1300 www.phoenixcontact.com 17