321-800-526-2324 • www.us.tdk-lambda.com/lp/ Disclaimer: us.tdk-lambda.com/lp/legal.htm
HWS300-1500 Series
Features
Limited Lifetime Warranty
UL508 approved
SEMI F47 Compliant (high line AC)
Universal Input (85 - 265VAC)
High Effi ciency
Class 1 Div 2 option (/RY suffi x)
Wide Range AC Input
300-1500W Single Output Industrial Power Supplies
Specifi cations
(1) 100/200VAC
(2) HWS start up -20°C. (-40°C see options table)
(3) HWS1000/1500 with 85VAC input: See installation manual
(4) 2kVAC HWS1000/1500 Input to ground
HWS1000: -10 to +71°C. HWS1000-5, HWS1500-3, -5 derate linearly above 40°C
(5) UL60601-1, EN60601-1, see options.
UL508; HWS300/600 5V, 12V, 24V & 48V models
(6) Not on HWS1500/ME, /HD or /RY versions
(*) Class 1 Div 2 option (/RY suffi x)
(**) Safety certifi ed for AC input only
(***) 24V output model, 25°C ambient, full load, 230VAC input
Key Market Segments & Applications
Model HWS300 HWS600 HWS1000 HWS1500
Input Voltage range (47-63Hz) - 85 - 265VAC or 120 - 330VDC (6)**
Input Current (Typ) (1) A 5V: 3.8/1.9; 5V: 7.5/3.6; 3.3V: 9.6/5.0; 3.3V: 15.0/8.0;
12-48V: 4.2/2.1 12-48V: 8.1/3.9 5-60V: 13.5/7.0 5-60V: 19.5/10.0
Inrush Current (1) A 20 / 40
Power Factor - Meets EN61000-3-2
Temperature Coeffi cient - <0.02%/°C
Overcurrent Protection - >105% (>101% of peak current for peak current capable models)
Overvoltage Protection V See table on page 2 (Recycle AC or remote on/off to reset)
Hold Up Time (Typ) ms 20
Leakage Curr. (at 240VAC, 60Hz) mA <0.75mA <1.2mA <1.5mA
Remote Sense - Yes
Indicator - Green LED = ON
Remote on/off - Yes (Isolated from output)
Parallel operation - Single wire connection (up to 5 units)
DC Good - Yes
Remote Adjust (PV) - External voltage adjusts output, see options table
Operating Temperature - -10°C to +70°C, derate linearly to 50% load from 50C to 70C (2, 3)
Storage Temperature °C -30 to +85°C
Humidity (non condensing) - Operating: 10 - 90%RH, Non operating 10 - 95%RH
Cooling - Internal fan
Withstand Voltage (4) - Input to Ground 2.5kVAC, Input to Output 3kVAC, Output to Ground 500VAC for 1 min.
Isolation Resistance - >100M at 25°C & 70%RH, Output to Ground 500VDC
Vibration (non operating) - 10 - 55Hz (1 minute sweep), 19.6m/s2 constant X, Y, Z 1 hour
Shock - < 196.1 m/s2
Safety Agency Certifi cations (5) - UL60950-1, CSA60950-1, EN60950-1, EN50178, UL508, CE Mark
Line Dip - Complies with SEMI F47 (200VAC line only)
Conducted & Radiated EMI - EN55011 / EN55022, FCC VCCI (HWS300, 600 & 1000: Class B, HWS1500: Class A)
Immunity - IEC61000-4-2, -3, -4, -6 (Level 3), -5, -8 (Level 4), -11
Weight (Typ) g 1,000 1,600 3,200 3.3-7.5V: 4000; 12V+: 3800
Size (WxHxD) in 2.4 x 3.23 x 6.5” 3.94 x 3.23 x 6.5” 5 x 3.25 x 9.45” 5 x 3.25 x 11”
MTBF - Telcordia SR-332 issue 3*** hours 2,145,809 1,998,996 1,087,031 1,152,309
Warranty yrs Limited lifetime warranty (See TDK-Lambda’s terms and conditions)