DLP Series
3055 Del Sol Blvd • San Diego, CA 92154 • 1-800-LAMBDA-4 23
Low Cost
3 Year Warranty
UL508 Listed, NEC NFPA70 Class 2(1) (/C2 Models)
Convection Cooled
Conforms to EN61000-3-2 (PFC)
Conducted and Radiated EMI, Class B
Input Transient Protection, IEC61000-4
Semi F47 Compliant (DLP180 & 240 only)
75 to 240W, 24V Output DIN Rail Mount Power Supplies
(1) Evaluated to NEC NFPA70 Class 2 output per UL1310 (3) DLP240-24-1/E, 170-265VAC: -10°C~+70°C, derated linearly to 60% load from 50° to 70°C.
(2) DC input is not safety approved DLP75-24-1/C2EJ: -10°C~+70°C, derated linearly to 75% load from 50° to 60°C.
DLP100-24-1/C2EJ: -10°C~+70°C, derated linearly to 80% load from 50° to 60°C.
MODELS DLP75-24-1/E DLP100-24-1/E DLP120-24-1/E DLP180-24-1/E DLP240-24-1/E
ITEMS DLP75-24-1/C2EJ DLP100-24-1/C2EJ
Output Voltage V 24 24 24 24 24
Output Current (/C2 models) A 3.1 (2.5) 4.1 (3.7) 5.0 7.5 10
Output Power (/C2 models) W 75 (60) 98.4 (88.8) 120 180 240
Output Voltage Adjustment V 21.6 - 28 (fixed for /C2 models)
Load Regulation - 192mV
Line Regulation - 120mV
Ripple/Noise (0-600C) mV 240
AC Input Voltage & Frequency - 85-132/170-265VAC, 47-63Hz Auto select 85-265VAC (47-63Hz)
or 120-370VDC(2)
Input Current 100/230VAC A 1.7/0.8 2.3/1.2 2.4/1.3 2.3/1.0 3.0/1.3
/C2 A 1.4/0.7 2.0/1.0 -
Efficiency 100/230VAC % 81/83 82/85 83/85 84/87 82/86
Power Factor - Meets EN61000-3-2 (DLP180, 240: >0.95)
Inrush Current(Typ)100/230VAC A 20/45
Leakage Current mA Less than 0.75mA
Hold-up Time 100/230VAC ms 20/30 (Semi F47 Compliance, DLP 180 & 240 only)
Overcurrent Protection - >105%,Fold Back >105%, Constant Current
/C2 - ~2.6A ~3.75A -
Overvoltage Protection - 30-35V, latching, cycle AC line to reset (26-30V DLP75-24-1/C2EJ)
LED Indicators - Green LED = DC ok Red LED = overcurrent
Operating Temperature (3) - Convection cooled, -10°C to 60°C, derate linearly to 60% load from 50 to 60°C
Storage Temperature - -30°C~+85°C
Humidity (Non-Condensing) %RH 30-90% operating 10-95% non operating
Withstand Voltage - Input - Ground 2kVAC, Input to Output 3kVAC, Output - Ground 500VAC
Vibration - 9.8m/s2(1.0G) at DIN rail; (10-55Hz: 9.8m/s2Constant, X,Y, Z each 1 hour)
Shock - 196m/s2(20G)
Safety Agency Approvals - UL508, NEC Class 2(1) (/C2 models), UL60950-1, CSA60950-1, EN60950-1, CE, EN50178 Cat III (Pri)
Conducted EMI - FCC-B, EN55011/EN55022-B, VCCI-B; Meets IEC61000-4-1
Radiated EMI - EN55011/EN55022-B, FCC-Class B, VCCI-B
ESD - IEC61000-4-2 ±10kV (Air), ±5kV (Contact)
Radiated RFI - IEC61000-4-3 80-1000MHz,12V/m 80% AM 1kHz
Fast Transient Burst - IEC61000-4-4 2.4kV 5kHz
Lightning Surge - IEC61000-4-5 4.4kV, 1.2x50µs (Common Mode) 2.4kV 1.2x50µs (Normal)
Conducted RFI - IEC61000-4-6 150kHz-80MHz, 12V, 80% AM 1kHz
Magnetic Field - IEC61000-4-8 36A/m
Voltage Dips - IEC61000-4-11 70% 10ms, 40% 100ms, 0% 5s
Size mm 50 x 97 x 110 60 x 97 x 110 60 x 97 x 110 80 x 97 x 110 120 x 97 x 110
Weight g 470 540 540 780 1000
Warranty - 3 Years
Specifications