GPC80 Commercial/GPM80 Medical
80 Watt Global Single and Multiple Output Performance Switchers
Ac Input
85-264 Vac, 47-63 Hz single phase.
Input Current
Maximum input current at 120 Vac, 60 Hz with full rated
output load: 2.3 A
Hold-Up Time
20 ms minimum from loss of ac input at full load, nominal
line (115 Vac).
Output Power
80 W continuous, 110 W with air flow. Peak ratings are for
60 s maximum duration, 10% duty cycle. During peak
load condition, output regulation may exceed total
regulation limits.
Overload Protection
Fully protected against short circuit and output overload.
Short circuit protection is cycling type power limit on
outputs 1 & 2; foldback type on outputs 3 & 4. Recovery
after fault is automatic. Factory set to begin power limiting
at 120 W. See output ratings chart for additional notes or
conditions.
Overvoltage Protection
Main outputs: 124% ± 12% typical.
Efficiency
70% at full rated load, nominal input voltage, depending
on model and load distribution.
Input Protection
Internal ac fuse provided. Designed to blow only if a
catastrophic failure occurs in the unit.
Inrush Current
Inrush is limited by internal thermistors. Inrush at 240 Vac
under cold start conditions will not exceed 34 A.
Temperature Coefficient
0.03%/°C typical on all outputs.
Environmental
Designed for 0 to 50°C operation at full rated output
power; derate output current and total output power by
2.5% per °C above 50°C. See Environmental and
Packaging Specifications on next page.
Power Fail (optional)
TTL- or CMOS-compatible output goes low (< 0.5 V) 5 ms
before output voltage drops more than 4% below nominal
voltage upon loss of ac power. The signal is factory set to
trip on 84 to 94 Vac brown-out depending upon incoming
line impedance and distortion. Other settings are avail-
able to the user through adjustment of built-in potentiom-
eter (consult factory for assistance). For Power fail option,
add -PF after model number.
Output Noise
0.5% rms, 1% pk-pk, 20 MHz bandwidth, differential
mode. Measured with noise probe directly across output
terminals of the power supply.
Transient Response
Main output—500 µs typical response time for return to
within 0.5% of final value for a 50% load step change. ∆i/
∆t<0.2 A/µs. Maximum voltage deviation is 3.5%. Startup/
shutdown overshoot less than 3%.
Remote Sense
Provided as a standard feature on single-output models.
Voltage Adjustment
Built-in potentiometer adjusts voltage ±5% on outputs 1 & 2.
EMI/EMC Compliance
All models include built-in EMI filtering to meet the
following emissions requirements:
EMI SPECIFICATIONS COMPLIANCE LEVEL
Conducted Emissions GPC80 EN55022 Class B; FCC Class B
Conducted Emissions GPM80 EN55011Class B; FCC Class B
Static Discharge EN61000-4-2, 6 kV contact, 8 kV air
RF Field Susceptibility EN61000-4-3, 3 V/meter
Fast Transients/Bursts EN61000-4-4, 2 kV, 5 kHz
Surge Susceptibility EN61000-4-5, 1 kV diff., 2 kV com.
Line Frequency Harmonics EN61000-3-2 Class A
Commercial Leakage Current
0.7 mA 254 Vac @ 60 Hz input.
Commercial Safety
Approved to UL1950, CSA22.2 No. 234 Level 3, IEC950
and EN60950. UL file #E135803 commercial; CSA
#LR46516 all. The output(s) are intended for safety
earthed Signal Output and Intermediate Circuits only. All
dc outputs are SELV under normal and single fault
conditions.
Medical Leakage Current
35 µA 254 Vac @ 60 Hz input.
Medical Commercial Safety
Approved to UL2601-1, CSA-C22.2 No. 601.1 Level 3
and IEC601.1. UL file E116994; CSA #LR46516. The
output(s) are intended for safety earthed Signal Output
and Intermediate Circuits only. The output(s) are not
acceptable for patient connection without additional
isolation. All dc outputs are SELV under normal and
single fault conditions.
FEATURES:
• Wide-range ac input 85-264 Vac
• 2-year warranty
• Conducted EMI exceeds FCC Class B and CISPR 22
Class B (Commercial models) and CISPR 11 Class B
(Medical models)
• Commercial Approved to UL1950, IEC950,
EN60950 and CSA22.2-234 L3
• Medical Approved to UL2601-1, IEC601-1 and
CSA22.2 No. 601.1
• Complies with EN61000-3-2 Class A
•marked to LVD
SPECIFICATIONS: