Product data sheet
Characteristics
TVS2HWA50X
Surge protection device, Surgelogic, HWA, 50kA,
208Y/120 VAC, 3 phase, 4 wire, NEMA 4X
Main
Product Surge protection device
Range Surgelogic
Device Short Name HWA
Complementary
Surge Current 50kA per phase
Voltage Rating 208Y/120 V AC
Number of Phases 3 phases
Wiring Configuration 4-wire
MCOV 150V
Nominal Discharge Current 20kA
SCCR 200kA
Local Signalling LED green normal operation
Alarm
Height 9.4in (238.76mm)
Width 4.8in (121.92mm)
Depth 3.1in (78.74mm)
Cable length 33.6in (853.44mm)
Environment
Enclosure Rating NEMA 4X
Standards UL 1449:ed. 4 type II
UL 1283
NEC 285
CSA C22.2 No 8
UL 96A:ed. 12
Ambient Operating 149°F (65°C)
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
17-Nov-2020