Siemens
Energy & Automation, Inc. Installation and Service Instruction
SD39VIM-2
Rev: 3
July 1998
(Updated April 2012)
APACS+
Voltage Input Module(VIM)
SD39VIM-2r3 update
Changes Since Revision 1
Preface (Conventions and Symbols) - New Section
Product Support - Contact information updated
2.2 Considerations and Preparation - Danger Alert Added
2.2.2 Page 2-3a added.
3 Maintenance - Danger Alert Added
Siemens Energy & Automation, Inc., assumes no liability for errors or omissions in this document or for the application and use of
information included in this document. The information herein is subject to change without notice.
P
rocedures included in this document have been reviewed for compliance with applicable approval agency requir ements and are cons idere
d
sound practice. Neither Siemens Energy & Automation, Inc., nor these agencies are responsible for repairs made by the user.
ProcessSuite, QUADLOG, 4-mation, and APACS+ are trademarks of Siemens Energy & Automation, Inc. All other trademarks are the
property of t h ei r respective owners.
© 2006 Siemens Energy & Automation, Inc. All rights reserved.
PREFACE
Conventions and Symbols
The following symbols may appear in this manual and may be applied to the equipment. The reader
should become familiar with the symbols and their meaning. Symbols are provided to quickly alert the
user to safety related situations, issues, and text.
Symbol Meaning
DANGER
Indicates an immediate hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in
minor or moderate injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in
property damage.
NOTICE
Indicates a potential situation which, if not avoided, may result in an
undesirable result or state.
Important Identifies an action that should be taken to avoid an undesirable result or state.
Note Identifies additional information that should be read.
Electrical shock hazard. The included Warning text states that the danger of
electrical shock is present.
Electrical shock hazard. Indicated that the danger of electrical shock is
present.
Explosion hazard. Indicates that the danger of an explosion hazard exists.
Electrostatic discharge. The presence of this symbol indicates that
electrostatic discharge can damage the electronic assembly.
Qualified Persons
The described equipment should be installed, configured, operated, and serviced only by qualified persons
thoroughly familiar with this publication. The current version, in Portable Document Format (PDF), is
available at http://sitescape.sea.siemens.com/.
For the purpose of this publication and product labels, a qualified person is one who is familiar with the
installation, construction, and operation of the equipment, and the involved hazards. In addition, he or she
has the following qualifications:
Is trained and authorized to energize, de-energize, clear, ground and tag circuits and equipment in
accordance with established safety practices.
Is trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety
glasses or face shields, flash clothing, etc., in accordance with established safety practices.
Is trained in rendering first aid.
Scope
This publication does not purport to cover all details or variations in equipment, nor to provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should further
information be desired or should particular problems arise which are not covered sufficiently for the
purchaser’s purposes, the matter should be referred to one of the support groups listed in the Product
Support section of this manual.
The contents of this manual shall not become part of or modify any prior or existing agreement,
commitment or relationship. The sales contract contains the entire obligation of Siemens. The warranty
contained in the contract between the parties is the sole warranty of Siemens. Any statements continued
herein do not create new warranties or modify the existing warranty.
General Warnings and Cautions
WARNING
This equipment contains hazardous voltages, and it has been certified for use in the hazardous locations
specified on the product nameplate and in the Model Designation and Specifications section. Death,
serious personal injury, or property damage can result if safety instructions are not followed. Only
qualified personnel should work on or around this equipment after becoming thoroughly familiar with all
warning, safety notices, and maintenance procedures contained herein. The successful and safe operation
of this equipment is dependent upon proper handling, installation, operation, and maintenance.
The perfect and safe operation of the equipment is conditional upon proper transport, proper storage,
installation and assembly, as well as, on careful operation and commissioning.
The equipment may be used only for the purposes specified in this publication.
CAUTION
Electrostatic discharge can damage or cause the failure of semiconductor devices such as
integrated circuits and transistors. The symbol at right may appear on a circuit board or other
electronic assembly to indicate that special handling precautions are needed.
A properly grounded conductive wrist strap must be worn whenever an electronics
module or circuit board is handled or touched. A service kit with a wrist strap and static dissipative
mat is available from Siemens (PN15545-110). Equivalent kits are available from both mail order and
local electronic supply companies.
Electronic assemblies must be stored in anti-static protective bags when not installed in equipment.
DANGER
Electrical shock hazard
Explosion hazard
Will cause death, serious injury or property damage
Remove power from all wires and terminals and verify that there
are no hazardous voltages before working on equipment.
In potentially hazardous atmosphere, remove power from
equipment before connecting or disconnecting power, signal, or
other circuit, or extracting/inserting module.
Observe all pertinent regulations regarding installation in
hazardous area.
Ensure all devices are rated for hazardous (classified) locations.
SD39VIM-2 CONTENTS
July 1998 i
TABLE OF CONTENTS
SECTION TITLE PAGE
1.0 INTRODUCTION ...........................................................1-1
1.1 PRODUCT DESCRIPTION .................................................1-1
1.1.1 Channel Types ........................................................1-4
1.1.2 Diagnostics ...........................................................1-4
1.1.2.1 Overall Module Performance Diagnostics ................................1-4
1.1.2.2 Input Circuit Diagnostics .............................................1-5
1.1.3 LED Indicators ........................................................1-5
1.1.4 Configuration .........................................................1-5
1.1.4.1 Thermocouple Input Channel Parameters ................................1-6
1.1.4.2 Voltage Input Channel Parameters .....................................1-6
1.1.5 Terminations .........................................................1-6
1.2 PRODUCT SUPPORT .....................................................1-6
1.3 INTERNATIONAL STANDARDS ORGANIZATION (ISO) SYMBOLS ............1-8
1.4 RELATED LITERATURE .................................................1-9
2.0 INSTALLATION ...........................................................2-1
2.1 HARDWARE IDENTIFICATION ...........................................2-1
2.1.1 Voltage Input Module (VIM) .............................................2-1
2.1.2 VIM Local Termination Strip Identification ..................................2-1
2.1.3 VIM Marshalled Termination Assembly Identification .........................2-2
2.2 CONSIDERATIONS AND PREPARATION ...................................2-2
2.2.1 EMC Directive Installation Considerations ..................................2-2
2.2.2 Preparations ..........................................................2-2
2.3 ENVIRONMENTAL CONSIDERATIONS ....................................2-3
2.4 EQUIPMENT DELIVERY AND HANDLING ..................................2-4
2.4.1 Predelivery Test .......................................................2-4
2.4.2 Factory Shipment ......................................................2-4
2.4.3 Receipt of Shipment ....................................................2-4
2.4.4 Equipment Handling ...................................................2-4
2.4.5 Equipment Storage .....................................................2-5
2.5 VIM TERMINATION STRIP INSTALLATION ................................2-5
2.6 VIM MARSHALLED TERMINATION ASSEMBLY AND CABLE INSTALLATION .2-8
2.6.1 Marshalled Termination Assembly Installation ...............................2-8
2.6.2 Optional (Flat Surface) Marshalled Termination Assembly Installation ...........2-13
2.6.3 Interconnect I/O Cable Installation ........................................2-14
2.7 VIM INSTALLATION ....................................................2-16
2.7.1 Module and Module Rack Mechanical Keying ..............................2-18
2.7.2 Module Installation ...................................................2-18
CONTENTS SD39VIM-2
July 1998ii
TABLE OF CONTENTS (continued)
SECTION TITLE PAGE
2.8 ELECTRICAL INSTALLATION ...........................................2-19
2.8.1 Field Input Wire Selection ..............................................2-19
2.8.2 Field Input Wiring Connections ..........................................2-20
2.8.3 Unterminated I/O Cable Assembly Connections .............................2-25
2.8.4 Configuration ........................................................2-25
2.9 APACS+ CALIBRATION VERIFICATION REQUIREMENTS—LONG TERM DRIFT2-25
3.0 MAINTENANCE ...........................................................3-1
3.1 TOOL AND EQUIPMENT REQUIREMENTS .................................3-1
3.2 VISUAL INSPECTION ....................................................3-1
3.3 CLEANING .............................................................3-1
3.4 TROUBLESHOOTING ....................................................3-1
3.5 VIM REMOVAL/REPLACEMENT ..........................................3-3
3.5.1 Removal .............................................................3-3
3.5.2 Replacement ..........................................................3-3
3.6 VIM TERMINATION STRIP REMOVAL/REPLACEMENT ......................3-4
3.6.1 Removal .............................................................3-4
3.6.2 Replacement ..........................................................3-4
3.7 VIM MARSHALLED TERMINATION ASSEMBLY REMOVAL/REPLACEMENT ...3-4
3.7.1 Removal .............................................................3-4
3.7.2 Replacement ..........................................................3-5
3.8 INTERCONNECT I/O CABLE ASSEMBLY REMOVAL/REPLACEMENT ..........3-5
3.8.1 Removal .............................................................3-5
3.8.2 Replacement ..........................................................3-6
3.9 RETURN OF EQUIPMENT WITHIN NORTH AMERICA ........................3-6
3.10 RETURN OF EQUIPMENT OUTSIDE OF NORTH AMERICA ...................3-6
3.11 SPARE AND REPLACEMENT PARTS .......................................3-7
3.12 MAINTENANCE RECORDS ...............................................3-7
4.0 CIRCUIT DESCRIPTION ....................................................4-1
4.1 THERMOCOUPLE INPUT CIRCUITRY ......................................4-1
4.2 SENSOR SELECTION ....................................................4-3
4.3 MULTIPLEXING, AMPLIFYING, AND DIGITIZING ...........................4-3
4.4 IOBUS MODEM .........................................................4-3
4.5 THERMOCOUPLE BURNOUT DETECTION .................................4-3
4.6 CALIBRATOR ...........................................................4-4
4.7 VIM REDUNDANCY .....................................................4-4
4.8 VIM DIAGNOSTICS ......................................................4-4
5.0 MODEL DESIGNATION ....................................................5-1
5.1 ACCESSORIES ..........................................................5-1
5.2 OPTIONS ...............................................................5-2
SD39VIM-2 CONTENTS
July 1998 iii
TABLE OF CONTENTS (continued)
SECTION TITLE PAGE
6.0 SPECIFICATIONS ..........................................................6-1
6.1 MODULE SPECIFICATIONS ...............................................6-1
6.2 ENVIRONMENTAL SPECIFICATIONS ......................................6-2
6.3 ELECTRICAL CLASSIFICATION ...........................................6-3
6.3.1 Approvals (see important note) ...........................................6-3
6.3.2 CSA Hazardous Locations Precautions .....................................6-4
6.3.2.1 Precautions - English ................................................6-4
6.3.2.2 Précautions - Français ...............................................6-5
6.4 ELECTROMAGNETIC COMPATIBILITY (EMC) ..............................6-5
DECLARATION OF CONFORMITY
WARRANTY
LIST OF FIGURES
FIGURE AND TITLE PAGE
FIGURE 1-1 APACS+ Voltage Input Module and Associated Hardware .......................1-2
FIGURE 1-2 Basic Input Wiring .......................................................1-3
FIGURE 2-1 VIM Termination Strip and Interconnect I/O Cable Mounting .....................2-7
FIGURE 2-2 VIM Marshalled Termination Assembly ......................................2-9
FIGURE 2-3 Marshalling Utility Panel Dimensions .......................................2-10
FIGURE 2-4 Mounting Marshalled Termination Assembly .................................2-12
FIGURE 2-5 VIM Marshalled Termination Assembly Mounting Ear Installation ................2-13
FIGURE 2-6 Interconnect I/O Cable Keying ............................................2-15
FIGURE 2-7 Module Keying Assignment and Installation ..................................2-17
FIGURE 2-8 Using a Pin-type Crimp-on Connector .......................................2-21
FIGURE 2-9 Typical Signal Input Connections ..........................................2-23
FIGURE 2-10 Signal Input Cable End Preparation ........................................2-24
FIGURE 4-1 VIM Input Circuit Block Diagram ...........................................4-2
FIGURE 5-1 Model Designation .......................................................5-1
CONTENTS SD39VIM-2
July 1998iv
LIST OF TABLES
TABLE AND TITLE PAGE
TABLE 1-1 TIC Contact Information ...................................................1-7
TABLE 1-2 ISO/IEC Symbols ........................................................1-8
TABLE 2-1 Voltage and Millivoltage Input Cable Selection ................................2-19
TABLE 2-2 Thermocouple and Extension Grade Wire Characteristics ........................2-20
TABLE 2-3 Termination Assembly Channel/Terminal Identification .........................2-22
TABLE 2-4 Unterminated I/O Cable Assembly ..........................................2-27
TABLE 3-1 LED Indications .........................................................3-2
TABLE 5-1 VIM Accessories .........................................................5-1
TABLE 5-2 VIM Options ............................................................5-2
TABLE 6-1 VIM Specifications .......................................................6-1
TABLE 6-2 VIM Environmental Specifications ...........................................6-2
TABLE 6-3 Agency Approvals ........................................................6-3
SD39VIM-2 INTRODUCTION
July 1998 1-1
1.0 INTRODUCTION
This Instruction provides installation and service information for the following APACS+ components:
®
Model VIMCCN Voltage Input Module (VIM) P/N 16171-126
VIM Local Termination Strip P/N 16187-1
VIM Marshalled Termination Assembly P/N 16170-1
This Instruction is divided into six major sections.
Section 1, Introduction—Contains product description, product support, and lists related literature.
Section 2, Installation—Describes environmental considerations and mechanical and electrical
installation.
Section 3, Maintenance—Consists of preventive maintenance, troubleshooting, assembly replacement
procedures, and spare and replacement parts suggestions.
Section 4, Circuit Description—Contains a brief system level description of the VIM.
Section 5, Model Designation—Provides model designation and tables of accessories, attachments,
and options.
Section 6, Specifications—Consists of mechanical, electrical, and environmental specifications.
1.1 PRODUCT DESCRIPTION
The Voltage Input Module (VIM), which is shown in Figure 1-1, is an I/O element of the APACS+
Advanced Controller. It is an intelligent (microprocessor-based), configurable module, which interfaces
thermocouple and voltage input signals with an APACS+ control module’s IOBUS. Figure 1-2 illustrates
basic input wiring.
The VIM:
Minimizes hardware costs with 16 software-configurable channels (thermocouple or voltage input)
Improves accuracy and simplifies configuration with integral linearization, autoranging, self-
calibration, and cold junction compensation
Facilitates faster response to field problems with a configurable burnout detection feature (up or down
scale)
Provides greater protection against short circuits via individually isolated channels
Supports redundant architecture for high availability
Reduces servicing time by allowing the module to be inserted or removed while powered without
disturbing field wiring
Isolates field faults by electrically isolating all input channels from the backplane and ground
Complies with the European Union’s Electromagnetic Compatibility (EMC) Directive, which requires
process control equipment to be immune to electromagnetic interference (EMI) and limits the amount
of electromagnetic emissions (see module specifications in Table 6-2 for more detailed information)
INTRODUCTION SD39VIM-2
July 19981-2
FIGURE 1-1 APACS+ Voltage Input Module and Associated Hardware
SD39VIM-2 INTRODUCTION
July 1998 1-3
FIGURE 1-2 Basic Input Wiring
INTRODUCTION SD39VIM-2
July 19981-4
1.1.1 Channel Types
The VIM provides 16 channels, each of which can be configured to be a thermocouple or voltage input.
Several standard features allow the VIM to accommodate many input types with minimal configuration
and high accuracy, such as:
Automatic linearization for thermocouple types J, K, E, T, R, S, B, N to user-selectable engineering
units, such as °C, °F, °K, or °R
Cold junction compensation provided for all thermocouple input measurements
Autoranging input circuitry for thermocouple inputs, eliminating the need to specify a temperature
range while maintaining high accuracy
Self-calibration feature eliminating the need for field calibration
Integral burnout detection to determine if a thermocouple has opened or, if, due to aging, its resistance
has increased
In addition, the VIM’s configurable channels reduce hardware costs and spare parts requirements by
allowing one module to accommodate several input requirements.
1.1.2 Diagnostics
The VIM is designed to provide years of trouble-free service. However, in the event of unexpected
operation, the VIM is equipped with extensive self-diagnostics. The goals of these diagnostics are to:
Notify the appropriate personnel of a module malfunction or wiring error
Perform automatic switchover in a fully redundant (1oo2D) APACS+ system
Any errors detected by these diagnostics are reported to the associated control module. The control module
and the VIM maintain a log of current and historical errors that can be reviewed using the Diagnostic
Logger Utility or the 4-mation configuration software. In addition, errors are indicated by the module’s
®
LED indicators.
There are two types of circuit diagnostics: those diagnostics that monitor overall module performance,
which are common to all I/O modules, and those that cover individual input channels.
1.1.2.1 Overall Module Performance Diagnostics
Diagnostics for overall module performance include failure detection in the communications, processor,
and common circuits. These diagnostics include:
Power supply diagnostics (monitor the three 24 Vdc power input busses for under voltage and the
onboard isolated power supply for voltages within tolerance)
Over temperature diagnostics (check the module for over temperature conditions via an online
monitor)
Memory diagnostics [run a complete IEEE published test on RAM memory at module startup, detect
RAM failure modes in the optimal amount of time via galpat tests, and verify critical RAM data and
ROM memory online with cyclical redundancy checking (CRC)]
SD39VIM-2 INTRODUCTION
July 1998 1-5
Communication diagnostics (verify IOBUS communications for each message via CRC)
Redundancy diagnostics (monitor logic signals for valid combinations, compare redundancy status
information from the IOBUS with logical signals on the module, reporting any discrepancies as errors)
Watchdog timer diagnostics (detect processor operation failures via external and CPU hardware timers
and monitor IOBUS and scanning operation via additional timers)
CPU diagnostics (run manufacturer-supplied tests on CPU components, where results from the
instruction sequences must match predetermined values)
Software diagnostics (verify program flow control to ensure that software functions execute in proper
sequence and time, perform data integrity checks, and compare data to predetermined ranges)
Addressing diagnostics (compare module slot/rack addresses against their addresses at startup)
1.1.2.2 Input Circuit Diagnostics
Redundant isothermal sensors on the termination strip are compared to detect failures. To detect excessive
drift failures, duplicate voltage references are also compared, while amplifiers and A/D converter circuits
are continually automatically recalibrated online. Any component failures that require abnormal
calibration correction are also detected. Input source impedance is monitored for up and down scale
thermocouple burnout detection and fault detection for other components.
1.1.3 LED Indicators
The VIM’s LEDs support local troubleshooting without an operator interface. The module includes two
LEDs that indicate a combination of two of the following module statuses:
Module OK
Channel(s) faulted
Module faulted
Module unconfigured
IOBUS communication failed
Module failed
Module active (calculate mode)
Module inactive (verify mode)
1.1.4 Configuration
Like all APACS+ I/O modules, the VIM is configured using the 4-mation software. The configuration is
loaded into the module’s memory, and a copy of the configuration is stored in the associated control
module’s non-volatile memory. This approach to configuration allows the module to be removed and
replaced on-line without the need for reconfiguration.
During configuration, 4-mation is used to assign a type to each channel (thermocouple input or voltage
input) and several parameters which vary according to channel type.
INTRODUCTION SD39VIM-2
July 19981-6
1.1.4.1 Thermocouple Input Channel Parameters
Thermocouple Type (J, K, E, T, R, S, B, or N)
Engineering Units (°C, °F, °K, °R)
Bias (in engineering units)
Minimum and Maximum Scale
Burnout (upscale, downscale, or no detection)
Digital Filter Time Constant
Step Response Time (defines the time for a moving aver-age digital filter for the input signal, thus
specifying the time to fully respond to an input step; this filter reduces periodic noise and improves
repeatability and resolution)
1.1.4.2 Voltage Input Channel Parameters
Input Range (1 to 5 Vdc, 0 to 5 Vdc, -10 to 10 Vdc, -5 to 5 Vdc, -1 to 1 Vdc, or custom range between
-10 and 10 Vdc)
Minimum and Maximum Scale
Engineering Units
Digital Filter Time Constant
Step Response Time
1.1.5 Terminations
The VIM’s field I/O can be terminated locally or remotely according to user needs and preferences. Local
terminations reside directly below the VIM. Marshalled Termination Assemblies or Rail Termination
Assemblies provide for terminations up to 100 feet (30.5 m) away from the VIM. Figure 1-2 is an example
of the wiring used for any of these options.
1.2 PRODUCT SUPPORT
Product Support
Our Technical Support Centers (TSC) offer a variety of technical support services that are
designed to assist you with Siemens products and systems. Our support engineers have
experience with troubleshooting, development, system startup, and system test. They will help
you to solve your issues in an efficient and professional manner.
Customers in North America can contact Siemens Technical Support Center at 1-800-333-
7421, on the web at: http://support.automation.siemens.com, or by e-mail:
techsupport.sea@siemens.com
Customers outside North America can contact their local Siemens subsidiary; addresses and
telephone numbers are listed on the Internet at the web site:
http://support.automation.siemens.com.
When contacting Siemens, customers will be asked to provide site-contact information (name,
address, and phone number), the product involved and detailed information regarding the nature
of the issue.
Product documentation is now located in the Library forum of the Process Automation User
Connection at: http://sitescape.sea.siemens.com/. The Process Automation User Connection is a
secure site. Registration is open to all verified users of Siemens process automation systems. If
you are not already, and would like to become a member, please visit our Process Automation
User Connection web page at: http://www.sea.siemens.com/process/support/papauc.html
Contained within the Process Automation User Connection is the APACS+/QUADLOG Secure
Site at: http://sitescape.sea.siemens.com/forum/aca-1/dispatch.cgi/f.apacsquadlo forum. This site
is only open to customers with an active service agreement. It contains all service manuals,
service memos, service notes, configuration manuals, etc. for the APACS+ and QUADLOG
family of products. If you are experiencing technical difficulties with the site, please contact
SiteScape technical support at: toll free 1-877-234-1122 (US) or 1-513-336-1474.
1-6a
A&D Technical Support
Worldwide, available 24 hours a day:
Beijing
Nürnberg
Johnson City
United States: Johnson City, TN Worldwide: Nürnberg Asia / Australia: Beijing
Technical Support
24 hours a day, 365 days a year
Phone:+49 (180) 5050-222
Fax:+49 (180) 5050-223
E-Mail: ad.support@siemens.com
GMT:+1:00
Technical Support and Authorization
Local time: Monday to Friday
8:00 AM to 5:00 PM
Telephone:+1 (423) 262 2522
or +1 (800) 333-7421 (USA only)
Fax:+1 (423) 262 2289
Mail to: techsupport.sea@siemens.com
GMT: -5:00 Authorization
Local time: Monday to Friday
8:00 AM to 5:00 PM
Phone: +49 (180) 5050-222
Fax: +49 (180) 5050-223
Mail to: ad.support@siemens.com
GMT: +1:00
Technical Support and Authorization
Local time: Monday to Friday
8:00 AM to 5:00 PM
Phone:+86 10 64 75 75 75
Fax:+86 10 64 74 74 74
Mail to:ad.support.asia@siemens.com
GMT:+8:00
Automation and Drives Service and Support International
http://www.siemens.com/automation/service&support
The languages of the SIMATIC Hotlines and the authorization hotline are ge nerally German and English.
INTRODUCTION SD39VIM-2
July 19981-8
TIC
EUROPE
Tel: See previous table for updated information.
Fax:
E-mail:
Hours of Operation:
Secure Web Site:
1.3 INTERNATIONAL STANDARDS ORGANIZATION (ISO) SYMBOLS
Refer to Table 1-2 for an explanation of ISO and IEC symbols that, when appropriate, are prominently
displayed on the surfaces of hardware. The symbols are also used in instructions to denote CAUTION
and WARNING notes.
TABLE 1-2 ISO/IEC Symbols
SYMBOL PUBLICATION DESCRIPTION
Background Color
=Yellow
Symbol Color = Black
Outline Color = Black
ISO 3864,
No. B.3.6 WARNING: Risk of Electric Shock. The symbol is
prominently displayed on the surfaces of hardware. When
used in an instruction, text accompanies the symbol which
identifies something that can be dangerous and possibly life
threatening to personnel. For example:
WARNING: Risk of electric shock. Remove power from
all involved wires before making connections to the
Marshalled Termination Assembly.
Background Color
=Yellow
Symbol Color = Black
Outline Color = Black
ISO 3864,
No. B.3.1 CAUTION: Refer to accompanying Installation and Service
Instruction. The symbol is prominently displayed on the
surfaces of hardware. When used in an instruction, text
accompanies the symbol which identifies something that can
damage equipment or cause a control problem with a
process. For example:
CAUTION: The safety system should not be operated
with forced I/O.
Background Color = White
Symbol Color = Black
Outline Color = Black
IEC 417,
No. 5019 Symbol is prominently displayed on the surfaces of
PROTECTIVE CONDUCTOR TERMINAL
hardware.
SD39VIM-2 INTRODUCTION
July 1998 1-9
1.4 RELATED LITERATURE
The following literature should be available when performing the VIM installation.
APACS+ MODULRAC Installation and Service Instruction (SD39MODULRAC-1)
APACS+ SIXRAC Installation and Service Instruction (SD39SIXRAC-1)
APACS+ UNIRAC Installation and Service Instruction (SD39UNIRAC-1)
APACS MODULPAC 1000 Installation and Service Instruction (SD39MODULPAC-1)
APACS MODULPAC 2000 Installation and Service Instruction (SD39MODULPAC-2)
APACS Relay Marshalled Termination Assembly Installation and Service Instruction (SD39RMTA-1)
##
SD39VIM-2 INSTALLATION
July 1998 2-1
2.0 INSTALLATION
This section describes installation of the VIM and its associated assemblies. Be sure to review and
complete the steps in section 2.2 before proceeding with the VIM installation.
IMPORTANT
The VIM installation should be in accordance with the National Electrical
Code (NEC) and other applicable construction and electrical codes.
2.1 HARDWARE IDENTIFICATION
2.1.1 Voltage Input Module (VIM)
The Voltage Input Module is identified by the letters “VIM” on the bezel and by two nameplate labels: a
large label, shown below, located on the tracking plate (left side of VIM in Figure 1-1), and a small label
inside the bezel compartment. Both labels contain the module’s model designation, part number/issue
level, ROM version number or software compatibility identification, and serial number. The larger label
also lists the current and voltage requirements of the module, and space is provided for additional
information, such as agency certifications.
MODEL VIMxxN AMPS 0.14 A P/N 16171-121
ROM VERSION xx.x VOLTS 24 VDC S/N xxxxxxxx
2.1.2 VIM Local Termination Strip Identification
The VIM Local Termination Strip is identified by the following information printed on its surface:
VIM
VOLTAGE INPUT
MODULE
MOORE PRODUCTS CO.
TERMINATION STRIP
PN 16187-1
INSTALLATION SD39VIM-2
July 19982-2
2.1.3 VIM Marshalled Termination Assembly Identification
The VIM Marshalled Termination Assembly is identified by the following information printed on its
surface:
VIM
VOLTAGE INPUT
MODULE
MOORE PRODUCTS CO.
MARSHALLED TERMINATION
ASSEMBLY
PN 16170-1
2.2 CONSIDERATIONS AND PREPARATION - See Danger Alert on the last page
Read sections 2.2.1 and 2.2.2 before continuing with the VIM installation. Section 2.2.1 describes
considerations required to ensure that the modules are compliant with the European Union’s
Electromagnetic Compatibility (EMC) Directive.
2.2.1 EMC Directive Installation Considerations
Some installations of VIM modules may require adherence to the European Union’s Electromagnetic
Compatibility (EMC) Directive. Refer to the “Declaration of Conformity” statement at the back of this
document that lists the certificate number of the Technical Construction File issued to the Voltage Input
Modules. Compliance with the Directive requires some or all of the following:
APACS+ systems must use enclosures having sufficient RF attenuation.
AC power input conductors to the enclosure must be filtered.
MODULBUS (M-BUS) cables that enter or exit the enclosure must be filtered.
The “shield” of all shielded cables that exit the enclosure must be connected to the enclosure.
Consult the factory for additional information concerning EMC Directive installation and the availability
of enclosures and needed hardware.
2.2.2 Preparations
1. Install the MODULRAC, SIXRAC, or UNIRAC and the Local Termination Panel (for local
termination only) in the cabinet where VIMs are to be installed. VIMs should not be installed in the
rack at this time, however, the rack address (1 TO 16) and rack slot numbers (1 to 10) for VIM
installation should be known.
2. If local I/O termination is employed, tag all I/O cables and route them into the cabinet. They should be
ready for cable end preparation and connection to the VIM Termination Strips. Cable wire sizes: 14 to
26 AWG (American Wire Gage).
SD39VIM-2 INSTALLATION
July 1998 2-3
3. If remote I/O termination is employed, complete the following:
1) If Marshalling Utility Panels are being used, install them in their respective marshalling cabinets.
2) Tag all I/O cables and route them into the marshalling cabinet. They should be ready for cable end
preparation and connection to the VIM Marshalled Termination Assemblies (cable wire sizes: 10
to 26 AWG) or user supplied termination assemblies. User supplied termination assemblies
require a VIM Temperature Transducer Kit and an unterminated Interconnect I/O Cable. The
VIM Temperature Transducer Kit is listed under "Accessories" in section 5.2 of this Instruction.
3) Route the Interconnect I/O Cable (or Unterminated I/O Cable) between the marshalling cabinet
and the cabinet and rack in which the VIM will be installed. Refer to Figure 1-1; J1 will be
installed in the rack and P2 will connect to the VIM Marshalled Termination Assembly in the
marshalling cabinet.
4) If an Unterminated I/O Cable is installed, user-supplied terminations (e.g. terminal blocks) must
be installed for field signal input wiring and the I/O Cable.
4. A dedicated, reliable, electrically clean power source should be furnished by the user to power field
devices providing voltage input signals. An uninterruptible power supply (UPS) can be installed for
increased reliability and power quality.
VIM input channels are isolated from one another, thus permitting voltage inputs to each channel to
originate from dedicated, separate power sources.
High-power EMI-producing equipment should not be connected to any power lines dedicated to VIM
input signals. See inserted Page 2-3a
2.3 ENVIRONMENTAL CONSIDERATIONS
Many industrial environments create severe operating conditions. The conditions at each VIM
location must be within the specifications stated in section 6.2.
CAUTION
Exceeding the specified operating temperature limits can adversely affect
performance and may cause damage. Air temperature should be
periodically checked to ensure that this specification is not being
exceeded.
To ensure operator safety, VIM Marshalled Termination Assemblies shall be installed in enclosures
which require a key or special tool to gain access to the equipment.
Change Since Revision 1
Add to Section 2.2.2 item 4.
WARNING!
Arc welding to surfaces with attached, active thermocouples can damage VIM
termination transducers. Remove VIM from rack or disconnect I/O wiring from VIM
termination before welding.
INSTALLATION SD39VIM-2
July 19982-4
To ensure reliable data communications, it would be prudent to locate APACS+ equipment as far as
possible from sources of interference such as high current electrical equipment which emit strong
electromagnetic fields and switching transients.
2.4 EQUIPMENT DELIVERY AND HANDLING
The following subsections provide information of interest to shipping, receiving, and warehouse personnel.
2.4.1 Predelivery Test
An VIM is fully tested and inspected to ensure proper operation. If the VIM is ordered factory installed in
a MODULPAC or other enclosure, the VIM is tested as part of the overall APACS+ process automation
system and inspected to ensure proper operation.
2.4.2 Factory Shipment
VIMs to be installed by the user are placed in static shielding bags and packaged for shipment.
Accessories are packaged separately. If the VIM is ordered factory installed in a MODULPAC or other
enclosure, the enclosure is bolted to a pallet and wrapped for protection during shipment.
2.4.3 Receipt of Shipment
All cartons should be inspected at the time of their delivery for possible external damage. Any visible
damage should be immediately recorded on the carrier’s copy of the delivery slip.
Each carton should be carefully unpacked and its contents checked against the enclosed packing list. At
the same time, each item should be inspected for hidden damage that may or may not have been
accompanied by exterior carton damage.
If it is found that some items have been damaged or are missing, refer to sections 2.4.4 or 2.4.5 and notify
Moore immediately, providing full details. In addition, damages must be reported to the carrier with a
request for their on-site inspection of the damaged item and its shipping carton.
2.4.4 Equipment Handling
The VIM is completely enclosed and may be safely handled without undertaking special ESD (electrostatic
discharge) handling procedures provided the bezel compartment door is closed and secured. DO NOT
touch the connector pins on the back of the module.
SD39VIM-2 INSTALLATION
July 1998 2-5
CAUTION
Use a grounded wrist strap to provide ESD protection whenever the
module’s bezel door is opened.
2.4.5 Equipment Storage
The storage temperature and humidity parameters of section 6 must be met for storage of an VIM.
2.5 VIM TERMINATION STRIP INSTALLATION
Install a VIM Termination Strip at the rack slot location of each VIM when local I/O termination is
employed. As shown in Figure 2-1, a Local Termination Panel must be installed.
NOTE
On the Termination Strip, delicate temperature sensors U1/U2 are
mounted at each end of the terminal block. Handle the Termination Strip
carefully to avoid sensor damage.
Refer to Figure 2-1 and the following mounting instructions:
1. Consult user’s or system integrator’s rack documentation and note the slot locations assigned to each
VIM in each rack.
2. Note the following on a rack or a Termination Strip:
On a rack, locate and identify the extruded spacer to which the lower edge of the backplane is
mounted. Note that the bottom of the extruded spacer is grooved. The top edge of a Termination
Strip will rest in this groove.
Identify a series of alignment pins located below the rack frame that span the width of the rack
panel. One of these pins will engage a hole located on the Termination Strip above the MOORE
logo. The left-most pin corresponds to rack slot #1.
The Termination Strip’s captive mounting screws can be seen projecting from the bottom of the
plastic extrusion panel.
INSTALLATION SD39VIM-2
July 19982-6
3. Mount each Termination Strip at its assigned location as follows:
1) Angle the top edge of the Termination Strip toward the backplane’s extruded spacer and insert the
tip of the Termination Strip in the spacer’s groove.
2) Slide the Termination Strip in the groove until it is vertically and horizontally aligned with the
appropriate pin (slot #).
3) Carefully lower the Termination Strip and engage the pin with the extrusion and board pin
mounting hole. Firmly push down to seat the strip on the pin. When the strip is properly seated,
the pin will be flush with, or project slightly above the top surface of the strip.
4) Secure the Termination Strip to the rack and Local Termination Panels with the strip’s captive
mounting screws, which are automatically aligned with their respective panel mounting holes.
NOTE
Do not remove any terminal block covers on the VIM Termination Strips.
The purpose of these covers is to prevent temperature shifts due to air
drafts at the terminals.
SD39VIM-2 INSTALLATION
July 1998 2-7
FIGURE 2-1 VIM Termination Strip and Interconnect I/O Cable Mounting
INSTALLATION SD39VIM-2
July 19982-8
2.6 VIM MARSHALLED TERMINATION ASSEMBLY AND CABLE INSTALLATION
Section 2.6.1 describes installing the VIM Marshalled Termination Assembly to a DIN rail. Section 2.6.2
describes installing the VIM Marshalled Termination Assembly to a flat surface. Section 2.6.3 describes
connecting the VIM Interconnect I/O Cable Assembly.
2.6.1 Marshalled Termination Assembly Installation
The VIM Marshalled Termination Assembly snaps onto a user-supplied DIN rail of the following type:
• Preferred: Top hat profile EN 50 022-35mm X 7.5mm or EN 50 022- 35mm X 15mm
• Alternate: G-profile EN 50 035-G 32mm
Refer to the following to mount a VIM Marshalled Termination Assembly to a blank Utility Panel or a
Marshalling Utility Panel:
1. If a P/N 16114-12 blank Utility Panel or a user fabricated panel is being used, mount user-supplied
DIN rails and wire duct. A Utility Panel can be mounted in a MODULPAC marshalling cabinet. A
user fabricated panel is typically mounted in a cabinet provided by the user. Refer to Figures 2-2 and
2-3 for Marshalled Termination Assembly and Utility Panel dimensions.
1) Determine the mounting layout for DIN rails, wire ducts and Marshalled Termination Assemblies.
NOTE
Marshalled Termination Assembly dimensions can vary with type. Refer
to the Installation And Service Instruction for each I/O type to be
installed.
2) Drill and tap DIN rail and wire duct mounting holes in the panel. If applicable, refer to Instruction
SD39MODULPAC-1 for removal of the Utility Panel.
2. Retrieve the VIM Marshalled Termination Assembly to be mounted including a supplied bag of VIM
labels (P/N 14205-679) and Cable Keying Kit (P/N 16056-435). Temporarily set aside the Cable
Keying Kit.
NOTE
On the Marshalled Termination Assembly, delicate temperature sensors
U1/U2 are mounted at each end of the terminal block. Handle the
Assembly carefully to avoid sensor damage.
1) Consult user’s or system integrator’s documentation and note the rack address number (1 to 16)
and slot number assigned to the VIM, and, if applicable, the redundant VIM that will be connected
to this VIM Marshalled Termination Assembly. For rack-to-rack redundant VIMs connected to a
MODULNET, the MODULNET node address (1-63) must also be noted for each rack.
SD39VIM-2 INSTALLATION
July 1998 2-9
FIGURE 2-2 VIM Marshalled Termination Assembly
INSTALLATION SD39VIM-2
July 19982-10
FIGURE 2-3 Marshalling Utility Panel Dimensions
SD39VIM-2 INSTALLATION
July 1998 2-11
2) Retrieve a VIM label and record the node, rack, and slot numbers on the label (see Figure 1-1). If
redundancy is applicable, record the appropriate numbers on a second VIM label. Save the
remaining labels for use in section 2.6.3, step 3.
3. Refer to Figure 1-1 and attach the VIM label adjacent to connector J1. If applicable, attach the
redundant VIM label adjacent to J2.
4. Ensure that J1 and J2 are factory keyed according to the pattern shown in Figure 2-2, detail B.
NOTE
The user then keys the connector on the mating Interconnect I/O Cable as
described in section 2.6.3. This will prevent connection to the VIM Termination
Assembly of an Interconnect I/O Cable from another type of I/O module (e.g.
CDM or SAM).
5. Refer to Figure 2-4 for the procedure to mount the VIM Marshalled Termination Assembly to a DIN
rail.
INSTALLATION SD39VIM-2
July 19982-12
FIGURE 2-4 Mounting Marshalled Termination Assembly
SD39VIM-2 INSTALLATION
July 1998 2-13
2.6.2 Optional (Flat Surface) Marshalled Termination Assembly Installation
The removal of the DIN rail mounting feet from the Marshalled Termination Assembly (MTA), in
conjunction with the installation of four Mounting Ears, permits the MTA to be flat-mounted to a panel.
Four P/N 16056-562 (single piece) Mounting Ears are required per MTA (see Table 5-2).
Refer to Figure 2-5 and the following installation procedure:
1. At one end of the Marshalled Termination Assembly , remove the three end cap securing screws from
the card holder end cap. Remove and set aside the end cap.
2. Slide the DIN rail mounting feet from the grooves in the bottom of the Marshalled Termination
Assembly card holder. Discard the mounting feet. Re-install the just removed end cap.
3. Retrieve four mounting Ears and insert them in the appropriate mounting holes provided in the end
caps as illustrated in Figure 2-5.
4. Use the MTA as a template to mark the location of the mounting ear holes on the surface of the panel.
Typical mounting screw size is M4, or users can select another size. After drilling or punching the
holes, the holes should be threaded. Refer to Figure 2-2 for MTA dimensions.
FIGURE 2-5 VIM Marshalled Termination Assembly Mounting Ear Installation
INSTALLATION SD39VIM-2
July 19982-14
2.6.3 Interconnect I/O Cable Installation
An Interconnect I/O Cable (Figure 2-6) is used to connect each VIM to a VIM Marshalled Termination
Assembly when remote I/O termination is employed. The cable-to-module connector (J1) is installed at
the rack slot location of a VIM. It is assumed that as part of the site preparation procedure all tagged
Interconnect I/O Cables have been routed and pulled into their respective cabinets and are ready for
connection. An Unterminated I/O Cable is installed similarly at the rack, however, terminations in the
marshalling cabinet are user-supplied .
VIM Marshalled Termination Assemblies should already be installed in the marshalling cabinet (see
section 2.6.1) and be ready for cable connection. Refer to Figures 2-1 and 2-6 and the following
procedure:
1. Note the following on the cable’s molded J1 connector.
The lower face area of J1 has a “pin mounting hole” located above a captive mounting screw.
This hole engages one of the rack panel’s alignment pins.
The top edge of J1 will rest in the groove of the backplane’s extruded spacer as illustrated by a
detail in Figure 2-1.
2. Consult user’s or system integrator’s documentation and note the MODULNET node address (if
applicable), rack address number (1-16), and slot number assigned to the VIM. J1 will be installed at
this location.
3. Install J1 at its assigned location as follows:
1) Angle the top edge of the molded connector toward the backplane’s extruded spacer and insert its
tip in the spacer’s groove.
2) Slide the connector in the groove until it is vertically and horizontally aligned with the appropriate
pin (slot #).
3) Carefully lower the molded connector and engage the alignment pin with the connector’s pin
mounting hole. Firmly push down to seat the connector on the pin. When the connector is
properly seated, the pin will be flush with or project slightly above the face of the connector.
4) Secure the connector to the rack panel with its captive mounting screw which is automatically
aligned with its panel mounting hole.
5) Get two labels from the bag of VIM labels. Record on each label the appropriate numbers noted in
the above step 2 (Figure 1-1). Attach one label each to the molded J1 and the P2 connectors.
4. Key cable connector P2.
Get the P/N 16056-435 Cable Keying Kit set aside in step 2 of section 2.6.1. The kit contains keying
pins and an instruction. Refer to Figure 2-6 for the assigned keying pattern and install the pins as
described in the supplied instruction.
SD39VIM-2 INSTALLATION
July 1998 2-15
FIGURE 2-6 Interconnect I/O Cable Keying
INSTALLATION SD39VIM-2
July 19982-16
5. Connect the free end of the I/O Cable Assembly to its respective I/O termination assembly. Perform
either of the following, depending upon cable type:
1) Interconnect I/O Cable Assembly (P2 installed)
a) Connect cable connector P2 (Figure 2-6) to the “A” (J1) connector on the Marshalled
Termination Assembly (Figure 1-1). A keying pin projecting from the face of P2 ensures
correct mating.
b) Press P2 firmly onto J1. Torque the securing screw on the top of P2’s connector shell to 50
inch-pounds maximum.
OR
2) Unterminated I/O Cable Assembly (P2 not installed)
Refer to Table 2-4 for color code and function of each unterminated wire. Refer to user wiring
diagrams to make the proper cable connections to the termination assembly.
6. On redundant VIMs only, connect the redundant I/O Cable as described in step 5 above.
2.7 VIM INSTALLATION
Modules are shipped individually packaged in protective, sealed, static shielding bags. Refer to section
2.4.4 for module handling considerations. Section 2.7.1 describes keying a rack slot. Section 2.7.2
describes installing the module in the rack.
Each rack slot and each module must be keyed to prevent accidental installation of a module into an
incompatible slot which may impair system performance. Keying is highly recommended; see Figure 2-7.
Modules are keyed at the factory. The keying pattern is unique to each module type (e.g. ACM, CCM,
CDM). See Figure 2-7 for the VIM keying pattern.
A factory assembled rack is keyed at the factory. A user-assembled rack is keyed by the user
according to the module type assigned to each slot. This keying pattern complements the module’s
keying pattern. Stop plugs are supplied with the rack.
When adding a module to a rack, be sure to key the rack slot.
SD39VIM-2 INSTALLATION
July 1998 2-17
FIGURE 2-7 Module Keying Assignment and Installation
INSTALLATION SD39VIM-2
July 19982-18
2.7.1 Module and Module Rack Mechanical Keying
To key a VIM module that was not keyed at the factory:
1. Order Keying Kit P/N 16056-166. The kit contains module keying pins and module rack stop plugs.
2. Refer to Figure 2-7 and note the bezel keying pattern that is applicable to the associated VIM.
3. Thread the keying pins into the holes in the back of the module’s bezel identified by the solid dots and
carefully tighten the pins.
To key a module rack:
1. Get the Keying Kit supplied with the rack (or the Keying Kit in step 1 above).
2. Refer to Figure 2-7 and note the rack keying pattern applicable to the associated VIM . Also, locate
the rack top and bottom rails.
3. Press the stop plugs into the holes identified by the solid dots.
2.7.2 Module Installation
To install a module: (Refer to Figure 2-7):
1. Refer to user documentation and note the assigned rack slot number.
2. Remove the VIM from its static shielding bag and insert the module in the assigned slot. Firmly seat
the module in the backplane and lower connectors. A properly seated module will have the rear of its
bezel flush against the rack’s front rails.
A keyed module that is not keyed to that slot will not engage the backplane and lower connectors or
seat flush against the rack’s front rails.
3. Pull open the bezel’s pivoting top and bottom handles to expose the module’s slotted captive mounting
screws and secure the module to the rack. Close the bezel’s handles when finished.
IMPORTANT
Do not use the captive mounting screws to seat the module.
Damage to the bezel can result.
SD39VIM-2 INSTALLATION
July 1998 2-19
2.8 ELECTRICAL INSTALLATION
This section describes field signal input connections to a locally mounted VIM Termination Strip and to a
remote mounted VIM Marshalled Termination Assembly. It is assumed that tagged field I/O wires have
been pulled into the cabinet and are ready for preparation and connection.
2.8.1 Field Input Wire Selection
A VIM Termination Strip and a VIM Marshalled Termination Assembly provide for connection of up to
16 pairs of configurable voltage, millivoltage, or thermocouple inputs. For voltage and millivoltage type
inputs, the recommended cables are given in Table 2-1.
TABLE 2-1 Voltage and Millivoltage Input Cable Selection
TERMINATION WIRE SIZE
Local VIM Termination Strip Twisted pairs of 28 to 14 AWG stranded or solid single
conductor per terminal. Max. wire size of two conductors per
terminal = 16 AWG. Shielded twisted pairs are recommended.
VIM Marshalled Termination Assembly Twisted pairs of 26 to 10 AWG stranded or solid single
conductor per terminal. Max. wire size of two conductors per
terminal = 12 AWG. Shielded twisted pairs are recommended.
Thermocouple leads are usually color coded. Standard ANSI color coding is used on insulated
thermocouple or extension grade wire when the insulation permits. A colored tracer to indicate lead
polarity may be used. Refer to Table 2-2 for color code information and bare wire characteristics for
identifying non-color coded wires.
INSTALLATION SD39VIM-2
July 19982-20
TABLE 2-2 Thermocouple And Extension Grade Wire Characteristics
ANSI POSITIVE LEAD NEGATIVE LEAD BARE WIRE
TYPE CHARACTERISTICS
T/C METAL COLOR METAL COLOR
TCopper Blue Constantan Red Copper: yellow color
Constantan: silver color
JIron White Constantan Red Iron: magnetic
Constantan: non-magnetic
EChromel Purple Constantan Red Chromel: shiny metal
Constantan: dull metal
KChromel Yellow Alumel Red Chromel: non-magnetic
Alumel: magnetic
SPlatinum Black Pure Platinum Red
10% Rhod.
RPlatinum Black Pure Platinum Red
13% Rhod.
BPlatinum Gray Platinum 6% Red
30% Rhod. Rhodium
2.8.2 Field Input Wiring Connections
Figure 2-9 shows typical input connections. Both the local and remote termination assemblies provide for
connection of up to 16 channels of voltage, millivoltage, or thermocouple input. Each termination
assembly is arranged as follows:
Long input signal terminal block with 32 terminals (two terminals per channel).
The channels are consecutively numbered 1 to 16. Refer to Table 2-3 for terminal identification.
Each channel is electrically isolated from other channels.
Two short grounding terminal blocks on either side of the input signal terminal block. These terminals
are used to ground the cable shields.
Refer to the following for input signal wiring:
1. Refer to the user’s or system integrator’s Process and Instrumentation Drawings to determine required
cable connections for I/O power supplies and all field devices. Refer to Table 2-3 for connection data.
2. Prepare the shielded input signal cables as illustrated in Figure 2-10.
Range Resistor
Signal Input Wire Crimp-on
Connector
SD39VIM-2 INSTALLATION
July 1998 2-21
3. Use the following recommendation to prepare wire ends for connection of I/O power supplies (as
necessary) and field devices to terminal blocks.
Do not solder multiple wires or the strands of multiple-strand wires for insertion into DIN rail
terminal blocks. Solder is a malleable material and can loosen, causing open connections. Also,
corrosion to the terminal block can result from the pickling agents or flux used with solder.
Use a pin-type crimp-on connector when two or more wires or a combination of wires and
component leads (for example, resistors and stranded or solid wire) must be inserted into a DIN
rail terminal block. Also, use a pin-type crimp-on connector for connections that will be moved
regularly.
Wires and leads are crimped into the terminal and the terminal pin is inserted into the selected
connection. Moore recommends the use of insulated crimp-on connectors available from electrical
supply sources. Figure 2-8 shows an example of the use of a crimp-on connector.
NOTE
Use a crimping tool recommended by the connector manufacturer to
ensure a strong mechanical, low electrical resistance connection.
FIGURE 2-8 Using a Pin-type Crimp-on Connector
4. Use the following torque specifications when connecting terminals in DIN rail terminal blocks:
CLMI (gray) DIN rail terminal blocks: 3.5 to 5.5 in. lbs.
CPhoenix (green) DIN rail terminal blocks: 6.5 to 8.5 in. lbs.
5. Complete the necessary connections for each configured channel.
WARNING
Electrical shock hazard. Remove power from all involved wires and
terminals.
INSTALLATION SD39VIM-2
July 19982-22
TABLE 2-3 Termination Assembly Channel/Terminal Identification (1)
INPUT CHAN. CHAN. CHAN. CHAN. CHAN. CHAN. CHAN. CHAN.
WIRE 12345678
Vdc/TC TERM. TERM. TERM. TERM. TERM. TERM. TERM. TERM.
+1 3 5 7 9 11 13 15
-2 4 6 8 10 12 14 16
INPUT CAN. CAN. CAN. CAN. CAN. CAN. CAN. CAN.
WIRE 9 10 11 12 13 14 15 16
VDC/TO TERM. TERM. TERM. TERM. TERM. TERM. TERM. TERM.
+17 19 21 23 25 27 29 31
-18 20 22 24 26 28 30 32
Notes:
1. Table supports both the VIM Termination Strip and the VIM Marshalled Termination Assembly.
2. Channel numbers (CHAN.) and wire polarities are printed on the assembly. Terminal Strip numbers (TERM.) are molded
into the assembly terminals.
3. Ground Terminals may be used as tie points for signal cable shields.
SD39VIM-2 INSTALLATION
July 1998 2-23
FIGURE 2-9 Typical Signal Input Connections
INSTALLATION SD39VIM-2
July 19982-24
FIGURE 2-10 Signal Input Cable End Preparation
SD39VIM-2 INSTALLATION
July 1998 2-25
2.8.3 Unterminated I/O Cable Assembly Connections
Connect field devices to user-supplied terminations. Table 2-4 lists the wire color and identification
information needed for termination. Refer to user wiring diagrams as necessary.
WARNING
Electrical shock hazard. Remove power from all involved wires and
terminals.
2.8.4 Configuration
The VIM and its associated control module must be configured before being placed on-line. Details are
provided in the ProcessSuite 4-mation Configuration Guide (UM39-14).
After the initial VIM power-up routine has been successfully completed, the VIM’s OK LED will flash
green and black (OFF) indicating an unconfigured module. When the control module recognizes that the
VIM is on-line, it will automatically download the proper configuration to the VIM. When the config-
uration is accepted, the OK LED will be set to solid green.
If the VIM is non-redundant, the control module will ENABLE the VIM by setting its ACTIVE LED to
solid green, thereby placing it in service. If the VIM is one of a redundant pair and the other VIM is in
service, the control module will DISABLE (ACTIVE LED = OFF) the VIM and place it in the standby
mode.
2.9 APACS+ CALIBRATION VERIFICATION REQUIREMENTS — LONG TERM DRIFT
The APACS+ analog I/O is designed to minimize calibration drift and the need for re-calibration over the
life of the product. Design improvements include:
Elimination of adjustable potentiometers
Elimination of adjustable resistors
Use of high quality low drift components
Calibration is performed through mathematical compensation within the microprocessor program. This
allows the use of matched resistors for voltage dividers and minimizes the problem of temperature
coefficient matching.
INSTALLATION SD39VIM-2
July 19982-26
Because the other sources of drift have been minimized, the dominant contributor to analog long term drift
for all analog modules is the voltage reference used for the A/D or D/A circuit. Manufacturer data
specifies a typical long term drift in terms of the first 1000 hours of operation. Typically, drift for the next
1000 hours will be less. In fact, studies have shown that the I/f noise model is valid for long term drift.
This model indicates that the drift will be proportional to the square root of the time period as a limiting
factor.
20ppm drift over the first 1000 hours is a typical drift for a high quality reference such as used in all
APACS+ analog modules. Using 30ppm to account for the other secondary drifts, such as precision
resistor ratios, indicate it would, on average, take 126 years for a module to drift 0.1% from original
calibration due to this mechanism. Drift of 0.05% would on average take 31 years.
Long term drifts significantly greater than typical would be due to flaws inherent to the manufacturing
process of the individual components or the module itself. APACS+ screens out even these unlikely
occurrences through multiple additional layers of control. In addition, the range of compensation is
restricted to prevent compensation for inherently defective devices. All APACS+ modules go through
environmental stress screening before functional testing and calibration to precipitate failure of weak
components. Finally, all APACS+ modules go through an elevated temperature burn-in followed by a
final functional verification including calibration.
For these reasons, Moore does not recommend the need for periodic verification of analog calibration
more often than once every ten years if the system design can accommodate a 0.1% drift from
original calibration. This recommendation is based on the assumption that specified limits for the
modules have not been exceeded.
Calibration-related error messages and/or known over stress conditions being applied to analog I/O points
could indicate the need for verification before the end of a ten year period.
##
SD39VIM-2 INSTALLATION
July 1998 2-27
J1,
PIN P2,
PIN WIRE/STRI
PE
COLOR
WIRE
IDENT
A2 75 WH/BLK U1 -
C2 74 WH/RED 1 +
E2 73 WH/BLUE 1 -
A4 65 WH/GRN U1 +
C4 49 WH/BRN 2 +
E4 64 WH/OR 2 -
A6 91 WH/YEL U2 -
C6 104 WH/VIO 3 +
E6 90 WH/GRAY 3 -
A8 100 RED/WH U2 +
C8 101 RED/BLK 4 +
E8 102 RED/BLUE 4 -
A10 36 RED/GRN NC
C10 47 RED/BRN 5 +
E10 46 RED/OR 5 -
A12 11 RED/YEL NC
C12 10 RED/VIO 6 +
E12 24 RED/GRAY 6 -
A14 22 BLUE/WH NC
C14 8BLUE/BLK 7 +
E14 21 BLUE/RED 7 -
A16 14 BLUE/GRN NC
C16 27 BLUE/BRN 8 +
E16 13 BLUE/OR 8 -
A18 44 BLUE/YEL NC
C18 43 BLUE/VIO 9 +
E18 45 BLUE/GRAY 9 -
A20 56 GRN/WH NC
C20 57 GRN/BLK 10 +
E20 41 GRN/RED 10 -
J1,
PIN P2,
PIN WIRE/STRI
PE
COLOR
WIRE
IDENT
A22 16 GRN/BLUE NC
C22 3GRN/BRN 11 +
E22 17 GRN/OR 11 -
A24 6GRN/YEL NC
C24 19 GRN/VIO 12 +
E24 5GRN/GRAY 12 -
A26 70 OR/WH NC
C26 71 OR/BLK 13 +
E26 72 OR/RED 13 -
A28 85 OR/BLUE NC
C28 98 OR/GRN 14 +
E28 84 OR/BRN 14 -
A30 96 OR/YEL NC
C30 94 OR/VIO 15 +
E30 95 OR/GRAY 15 -
A32 92 YEL/WH NC
C32 78 YEL/BLK 16 +
E32 79 YEL/RED 16 -
Shield
Wire 1Shield
Wire -------
Notes:
1. Color for wire/stripe
2. NC = No Connection
TABLE 2-4 Unterminated I/O Cable Assembly
SD39VIM-2 MAINTENANCE
July 1998 3-1
3.0 MAINTENANCE - See Danger Alert on the last page
The APACS+ Voltage Input Module (VIM) and its associated assemblies require minimal maintenance.
Some routine maintenance is recommended in the form of a visual inspection and a possible cleaning.
3.1 TOOL AND EQUIPMENT REQUIREMENTS
The following tools and equipment are necessary for servicing:
Common electronic servicing hand tools
Digital Multimeter
3.2 VISUAL INSPECTION
The VIM and its associated assemblies should be subjected to a periodic visual inspection. The frequency
of inspection will depend on the severity of the operating environment. The primary aim of the inspection
is to reveal any excessive accumulation of dust, dirt, or other foreign material adhering to the surfaces of
the VIM Termination Strip and protective covers of the VIM. Accumulation of dirt and dust prevents
efficient heat dissipation and may cause module or system failure. An VIM installed in a cabinet
complying with the NEMA 12/IP55 specification need not be inspected for cleanliness. Refer to section
3.3 for cleaning instructions.
3.3 CLEANING
Cleaning a VIM involves brushing or vacuuming the protective covers to restore cooling efficiency that
may have been degraded by accumulated dust.
Cleaning a VIM Termination Strip or VIM Marshalled Termination Assembly involves careful brushing
and vacuuming to remove accumulated dust and dirt harboring chemical particulate that may accelerate
terminal or connector contact corrosion. Be careful not to disturb the wiring.
3.4 TROUBLESHOOTING
Errors are annunciated by a module’ s status LEDs and displayed as error codes and messages in 4-mation.
The VIM’s status LEDs are located on its bezel. For a description of the error codes and messages, refer
to Module Diagnostic Error Codes (document CG39-19, located in binder UM39-14). Troubleshooting
entails observing the status LEDs and reading the error codes and messages, then referring to Table 3-1
and configuration guide CG39-19 to determine the course of action.
Interconnect I/O Cable pin assignments are given in Table 2-2. These are provided for troubleshooting a
suspect cable. As necessary, check field wiring and field located devices.
MAINTENANCE SD39VIM-2
July 19983-2
TABLE 3-1 LED Indications
LED LED MODULE STATUS ACTION
NAME INDICATION
OK Black (Off) No 24V power input to VIM 1. Properly seat the module
2. Troubleshoot or replace
the 24V power supply
VIM on-board power supply failure Replace module
OK Solid Green Module is OK. Configured, NONE
with no faults or failures.
OK Flashing Module is not configured. No faults or Download configuration
Green/Black failures.
OK Solid Red Module severe failure (Class 4 error) Replace module
OK Flashing Class 2 error detected Check 4-mation error
Red/Green description for user action
OK Flashing (1/sec.) Class 3 error detected Check 4-mation error
Red/Black description for user action
OK Flashing (5/sec.) IOBUS communications error 1. Check 4-mation error
Red/Black description for user action
2. Check IOBUS cables
3. Check control module
4. Check module rack
backplane jumpers
5. Replace module
ACTIVE Solid Green Module Enabled
Black (Off) Module Disabled (in Standby Mode or
off-line)
A digital multimeter can be used to test field input circuitry for correct wiring and input signals to the
termination assembly. Power-off continuity tests can be used to test for correct wiring. When performing
power-on AC voltage tests, refer to section 6 for the voltage levels required at VIM input terminals.
WARNING
Electrical shock hazard. Follow safe electrical troubleshooting practices
when testing for the presence of high voltage AC input signals.
SD39VIM-2 MAINTENANCE
July 1998 3-3
Return a failed assembly to the factory for repair; see section 3.11 for spare and replacement parts and
sections 3.9 and 3.10 for return for repair procedures. There are no user serviceable parts within a VIM
Termination Strip, VIM, or VIM Marshalled Termination Assembly.
3.5 VIM REMOVAL/REPLACEMENT
A module can be removed from or installed in the MODULRAC, SIXRAC, or UNIRAC without removing
power from the module slot, from I/O circuits, or from the rack.
3.5.1 Removal
1. As shown in Figure 2-7, pull open the bezel’s pivoted top and bottom handles to expose the module’s
slotted captive mounting screws. Loosen the screws.
2. Grasp the top and bottom handles and pull the module from the card cage.
3. Place the module in a static shielding bag and package for return. See section 3.9 or 3.10 for return
instructions.
3.5.2 Replacement
1. Remove the replacement VIM from its protective bag. The module may be safely handled as the
circuit card is shielded from access by protective covers.
2. If the module is already keyed, confirm that its keying matches that of the removed module. If not
keyed, key the replacement VIM as described in section 2.7.1.
3. Insert the VIM in its module rack slot. Firmly seat the module in the backplane and termination board
connectors. A properly seated module will have the rear of its bezel flush against the rack’s rails. A
keyed module that is not matched to a slot will not engage the backplane and termination strip
connectors or seat flush against the rack’s front rails.
4. As shown in Figure 2-7, pull open the bezel’s pivoted top and bottom handles to expose the module’s
slotted captive mounting screws and secure the module to the top and bottom rails. Close the bezel’s
handles when finished.
CAUTION
Do not use the captive mounting screws to seat the module.
Damage to the bezel can result.
MAINTENANCE SD39VIM-2
July 19983-4
3.6 VIM TERMINATION STRIP REMOVAL/REPLACEMENT
3.6.1 Removal
Refer to Figure 2-2 and the following procedure:
1. As necessary, take appropriate steps to shutdown the processes monitored or controlled by the field
devices connected to the VIM Termination Strip.
2. Remove the associated VIM from its slot in the MODULRAC, SIXRAC, or UNIRAC. Place the VIM
in a static shielded bag for protection.
3. Disconnect signal cables from the VIM Termination Strip.
IMPORTANT
All signal and power cables should be labeled for correct reconnection.
4. Loosen the VIM Termination Strip’s captive mounting screws. Gently lift the bottom of the strip in an
arc until it is free of its alignment pin located immediately above the MOORE logo. Pull the top of the
strip from the grooved backplane spacer and lift it from the rack.
3.6.2 Replacement
Refer to Figure 2-2 and the following procedure:
1. Refer to section 2.5 and install the replacement VIM Termination Strip.
2. Reconnect the signal and power cables.
3. Install the VIM. See section 3.5.
3.7 VIM MARSHALLED TERMINATION ASSEMBLY REMOVAL/REPLACEMENT
3.7.1 Removal
Refer to Figures 2-3 and 2-5 and the following procedure:
1. As necessary, take appropriate steps to shutdown the processes monitored or controlled by the field
devices connected to the VIM Marshalled Termination Assembly.
2. Remove the associated VIM from its slot in the MODULRAC, SIXRAC, or UNIRAC. Place the VIM
in a static shielded bag for protection.
3. Disconnect signal cables from the VIM Marshalled Termination Assembly.
SD39VIM-2 MAINTENANCE
July 1998 3-5
IMPORTANT
All signal and power cables should be labeled for correct reconnection.
4. Refer to Figure 2-5. Press down on the Marshalled Termination Assembly and carefully pull it away
from the DIN rail.
3.7.2 Replacement
Refer to the following procedure:
1. Refer to section 2.6 and install the replacement Marshalled Termination Assembly.
2. Reconnect the signal cables.
3. Install the VIM. See section 3.5.
3.8 INTERCONNECT I/O CABLE ASSEMBLY REMOVAL/REPLACEMENT
3.8.1 Removal
Refer to Figure 2-2 and the following procedure:
1. As necessary, take appropriate steps to shutdown the processes monitored or controlled by the field
devices connected to the VIM Marshalled Termination Assembly.
2. Remove the associated VIM from its slot in the MODULRAC, SIXRAC, or UNIRAC. Place the VIM
in a static shielded bag for protection.
3. Disconnect Interconnect I/O Cable Assembly connector P2 or individual connections from the
termination assembly. All individual connections should be labeled for correct reconnection.
4. Loosen the captive mounting screws on the cable connector. Gently lift the bottom of the connector in
an arc until the connector is free of its alignment pin. Pull the top of the cable connector from the
grooved backplane spacer and lift it from the rack.
5. Remove the Interconnect I/O Cable Assembly from the cable tray or other cable routing equipment.
MAINTENANCE SD39VIM-2
July 19983-6
3.8.2 Replacement
Refer to Figure 2-2 and the following procedure:
1. Route the Interconnect I/O Cable Assembly between the MODULRAC, SIXRAC, or UNIRAC and
the marshalling cabinet.
2. Label and key the replacement cable as described in section 2.6.3.
3. Reconnect replacement cable as described in section 2.8.2.
4. Install the VIM. See section 3.5.
3.9 RETURN OF EQUIPMENT WITHIN NORTH AMERICA
If an VIM needs to be returned for any reason, perform the following:
To Return Equipment
Call the Repair Order Group at (215) 646-7400, ext 4RMA (4762) weekdays between 8:00 a.m. and
4:45 p.m. eastern time to obtain an RMA number. Mark the RMA number prominently on the outside
of the shipment.
When calling for an RMA number, provide the reason for the return. If returning equipment for repair,
failure information (e.g. error code, failure symptom, installation environment) will be requested.
Supply a purchase order number for repairs.
Material Safety Data Sheet
A Material Safety Data Sheet (MSDS) must be included with each item being returned that was stored or
used anywhere hazardous materials were present.
Packaging
Package assembly in original shipping materials. Otherwise, package it for safe shipment or contact the
factory for shipping recommendations. A module must be placed inside a static shielding bag to protect it
from electrostatic discharge.
3.10 RETURN OF EQUIPMENT OUTSIDE OF NORTH AMERICA
Contact the appropriate Moore product support group listed in section 1.2 of this Instruction. Provide the
reason for the return. For repairs, supply a purchase order number. Request equipment packaging and
shipping instructions.
SD39VIM-2 MAINTENANCE
July 1998 3-7
3.11 SPARE AND REPLACEMENT PARTS
One spare Voltage Input Module (VIM) should be stocked for every 1 to 20 in service. Spare and
replacement assemblies can be ordered from one the addresses in the Warranty statement or through a local
Moore representative. Assembly part numbers are stated in section 5 and printed on most modules. When
ordering, provide the model number from the module’s nameplate to be replaced or spared. A purchase
order number should also be included.
3.12 MAINTENANCE RECORDS
An accurate record keeping system for tracking maintenance operations should be established and kept up
to date. Data extracted from the record may serve as a base for ordering maintenance supplies, including
spare parts. The record may also be useful as a troubleshooting tool. In addition, maintenance records
may be required to provide documentary information in association with a service contract. It is suggested
that the following information be recorded:
1. Date of service incident
2. Name or initials of service person
3. Brief description of incident symptoms and repairs performed
4. Replacement part or assembly number
5. Software compatibility code of original part
6. Software code of replacement part
7. Serial number of original part
8. Serial number of replacement part
9. Issue number of original circuit module
10. Issue number of replacement circuit module
11. Date of completion
There are no user serviceable parts within a VIM, a VIM Termination Strip or a Marshalled Termination
Assembly.
#
SD39VIM-2 CIRCUIT DESCRIPTION
July 1998 4-1
4.0 CIRCUIT DESCRIPTION
The following subsections describe the various circuit elements of the VIM and the processing of a
thermocouple input signal. Processing of a voltage input signal is similar except the thermocouple burnout
detection and temperature sensor selection are not applicable. Most VIM functions are performed or
controlled by the CPU. A block diagram of the VIM is shown in Figure 4-1.
The VIM consists of the following circuit elements:
16 Voltage Input circuits—Process analog input signals.
16 Channel Multiplexer—Performs time-division multiplexing of input signals.
Programmable Gain Amplifier—Performs on-the-fly signal conditioning of each input channel.
Analog-to-Digital Converter—Converts analog input signals to digital data.
Calibrator—Provides precision calibration voltage.
TC Burnout Detector—Indicates when a TC fails.
Sensor Selector—Provides ice point temperature reference signal for TC inputs.
CPU—Performs general control functions and digital data interfacing to IOBUS .
Memory (RAM and EPROM)—Stores module configuration parameters.
IOBUS Modem—Provides digital data and command conversion needed for communication.
LED Indicators (on module bezel)—An ACTIVE LED indicates that the module is enabled. An OK
LED indicates the module status.
Power Supply—24 Vdc to multi-voltage dc converter
4.1 THERMOCOUPLE INPUT CIRCUITRY
Pairs of thermocouple wires are connected to terminal blocks mounted on an isothermal (same
temperature) assembly on either style of VIM termination assembly. The wires themselves create two
dissimilar metallic junctions which generate a thermal EMF (offset) proportional to the junction's ambient
temperature. This offset becomes an unwanted addition to the input signal.
The isothermal assembly is an electrical insulator but a good heat conductor and serves to hold both
junctions to the same temperature. The metallic junctions take the place of an “ice bath” and become a
Reference Junction. In order to determine the true junction temperature of the field thermocouple, the
VIM must compensate the input signal for the reference junction offset.
To do this, the VIM must be able to sense the temperature of the isothermal assembly where the TCs are
connected. Two Sensors mounted on the isothermal assembly provide this information to the VIM.
CIRCUIT DESCRIPTION SD39VIM-2
July 19984-2
FIGURE 4-1 VIM Block Diagram
SD39VIM-2 CIRCUIT DESCRIPTION
July 1998 4-3
4.2 SENSOR SELECTION
Two temperature sensors on the Isothermal Assembly are electrically isolated from, but thermally coupled
to, all thermocouple terminals. These sensors sense the top and bottom temperatures of the terminating
blocks and produce a precision 1 mV/CEoutput signal.
The CPU periodically switches on the Sensor Selector which inputs the combined SENSOR OUT signals
into a Programmable Gain Amplifier for amplification and A/D converter for digitizing. The digitized
reference junction signal is fed into the CPU where the software determines the offset (mV) as referenced
against the ice point temperature. When the CPU reads the thermocouple signal, it subtracts the offset
from the signal. The CPU then converts this signal voltage into a temperature.
4.3 MULTIPLEXING, AMPLIFICATION, AND DIGITIZING
Thermocouple generated millivolt (mV) signals from the isothermal assembly are fed into isolated
channels of a 16 channel multiplexer. The output from the Multiplexer (MUX OUT) is fed into a
Programmable Gain Amplifier (PGA) whose gain is controlled by the CPU. The gain is automatically
adjusted (autoranging) to match the input signal to the full scale range of the A/D converter to provide
maximum accuracy without the need for user recalibration.
AMPLIFIER OUT from the PGA is digitized by an A/D Converter whose output becomes a precision
digital voltmeter input to the CPU. In order to find the true junction temperature of the field thermocouple,
the offset corresponding to the reference junction temperature is subtracted from the thermocouple input
signal. After performing this operation, the CPU performs a voltage to temperature conversion, including
linearization, by accessing the appropriate thermocouple table. The most popular thermocouple curves are
stored in CPU ROM as lookup tables. The computed temperature data is transmitted over the IOBUS via
the IOBUS Modem.
4.4 IOBUS MODEM
The IOBUS elements consists of an IOBUS Modem and dual IOBUS Line Drivers/ Receivers. The CPU
supervises IOBUS communications through handshaking operations with the IOBUS Modem. The
IOBUS Modem performs the following:
CConverts received IOBUS data into a format for data-processing.
CConverts digitized field data from the CPU into a format for transmission over the IOBUS to a control
module (e.g., CCM).
4.5 THERMOCOUPLE BURNOUT DETECTION
A Burnout Detection circuit provides for the detection of a failed thermocouple. Under the control of the
CPU, the Burnout Detector alternately outputs +5 and -5 volt pulses into a TC-configured channel as it is
multiplexed. The combination of low thermocouple impedance and input signal filtering averages the +/-5
volts to a very minor ripple on the input signal.
CIRCUIT DESCRIPTION SD39VIM-2
July 19984-4
Should a thermocouple burn out (infinite impedance) or develop a high impedance fault, a significant
ripple voltage would be generated for that channel and detected by the CPU. The action taken by the CPU
depends upon the BURNOUT configuration parameter selected:
CDISABLE: Burn out detection is disabled.
CUP: Burn out detection enabled. Output returned to maximum value.
CDOWN: Burn out detection enabled. Output returned to minimum value.
4.6 CALIBRATOR
Periodically, the CPU turns on the automatic Calibrator circuit. The Calibrator has a precision 5 volt
regulator, the output of which is divided to create a series of precision output voltages. These outputs
(CAL OUT) are signal input references against which the A/D Converter is software calibrated.
4.7 VIM REDUNDANCY
VIM redundancy is accomplished by rack-to-rack type redundancy through pairs of duplicate racks of I/O
and control modules that share a common I/O termination such as the VIM Marshalled Termination
Assembly.
In a redundant pair of racks, the VIM that is in the verify mode is identified by a solid green OK LED and
a black (OFF) ACTIVE LED. A solid green ACTIVE LED indicates an enabled module.
4.8 VIM DIAGNOSTICS
Part of the VIM program includes the execution of diagnostics that can detect hardware errors. Errors are
annunciated by LEDs located on the front bezel of the VIM. The OK LED is the principal error
annunciator. The green ACTIVE LED lights if the module is enabled. A redundant VIM in the verify
mode will show a solid green OK and black (OFF) ACTIVE LEDs.
At initial turn on, the VIM’s CPU uses a common start up routine to perform certain self-diagnostics such
as ROM and RAM tests and to setup specific board functions. If the common start up routine is
successful, the OK LED will be set to a solid green and the VIM begins to execute common I/O board
diagnostics; if not successful, the OK LED will be set to a flashing red color at a 1 second flash rate. 4-
mation software provides additional diagnostic and status displays.
#
SD39VIM-2 MODEL DESIGNATION
July 1998 5-1
5.0 MODEL DESIGNATION
Refer to Figure 5-1 to decode the VIM model designation.
IMPORTANT
Before installing, applying power, or servicing, review the model
designation on the nameplate and this section for required power, options,
and electrical classification.
VIM C B N Voltage Input Module (VIM)
T
T
T
*
*
.)
ELECTRICAL APPROVALS: N=Not Required
*
.)))
DESIGN LEVEL: Current Design
.)))))
REVISION LEVEL: A to Z
FIGURE 5-1 Model Designation
5.1 ACCESSORIES
Table 5-1 lists the available VIM accessories.
TABLE 5-1 VIM Accessories
PART NUMBER DESCRIPTION
16171-30 VIM Temperature Transducer Kit. When a VIM local or marshalled
termination cannot be used, the kit provides isothermal compensation at a user
supplied thermocouple termination assembly. It must be used with an
unterminated Interconnect I/O Cable.
16114-97 Marshalling Utility Panel (Figure 2-2)
Includes installed wire ducts and DIN rails for mounting APACS marshalled
termination assemblies. For installation in an APACS MODULPAC cabinet.
16114-12 Blank Utility Panel (Figure 2-2)
Similar to above but without installed ducts and rails. For installation in a
MODULPAC cabinet.
16056-562 Mounting Ear (see Figure 2-8). Provides for a flat mounting of the VIM
(single piece number) Marshalled Termination Assy. Four pieces required. Refer to section 2.6.2.
16056-468 End Stop Kit. End Stops prevent the sliding of an VIM Marshalled
Termination Assembly along the mounting DIN rail.
MODEL DESIGNATION SD39VIM-2
July 19985-2
5.2 OPTIONS
Table 5-2 lists the available VIM options. A selection of the type and quantity of termination assemblies
must be made by the user. When marshalling termination assemblies are selected, a selection from the list
of Interconnect I/O Cables must also be made.
TABLE 5-2 VIM Options
PART NUMBER DESCRIPTION
16187-1 VIM Local Termination Strip
16170-1 VIM Marshalled Termination Assembly
16805-5 VIM DIN Rail Marshalled Termination Assembly
16137-122 Marshalled Interconnect I/O Cable Assembly 5.7 ft. (1.75 m)
16137-114 Marshalled Interconnect I/O Cable Assembly 9.8 ft. (3 m)
16137-115 Marshalled Interconnect I/O Cable Assembly 26.2 ft. (8 m)
16137-116 Marshalled Interconnect I/O Cable Assembly 49.2 ft. (15 m)
16137-117 Marshalled Interconnect I/O Cable Assembly 98.4 ft. (30 m)
16137-118 Unterminated Interconnect I/O Cable Assembly 9.8 ft. (3 m)
16137-119 Unterminated Interconnect I/O Cable Assembly 26.2 ft. (8 m)
16137-120 Unterminated Interconnect I/O Cable Assembly 49.2 ft. (15 m)
16137-121 Unterminated Interconnect I/O Cable Assembly 98.4 ft. (30 m)
##
SD39VIM-2 SPECIFICATIONS
July 1998 6-1
6.0 SPECIFICATIONS
This section lists specifications for the Voltage Input Module (VIM).
6.1 MODULE SPECIFICATIONS
Refer to Table 6-1 for VIM specifications.
TABLE 6-1 VIM Specifications
CATEGORY SPECIFICATION DATA
Mechanical Module Weight 4.25 lbs. (1.9 kg.)
Power Requirement Voltage 24 Vdc +/- 10% (from module rack
backplane)
Current, Steady State 0.14 Amperes
Current, Inrush 1.1 Amperes
Current, Start Up 0.2 Amperes
Module Channels per Module 16
Electrical Isolation 30 V channel to channel, tested to 200 Vdc
600 V CSA each channel to CPU, IOBUS,
and ground
Tested at 3734 Vdc for 1 second
Input Over Voltage Protection ±30 V
Heat Dissipation 10 BTU/hour
Linearity #0.05%
A/D Conversion Resolution $12 bits
Ambient Temperature Effect #0.1% of span for 50EC ÎT (±20 ppm/EC)
Common Mode Rejection 120 dB with 100S maximum source
imbalance
Input Impedance > 1 Meg. Ohm at DC
Minimum Module Scan Time 150 msec.
Thermocouple Inputs Ranges J: -210 to 1200EC (-346 to 2192EF)
K: -270 to 1372EC (-454 to 2501EF)
E: -270 to 1000EC (-454 to 1832EF)
T: -270 to 400EC (-454 to 752EF)
S: -50 to 1767EC (-58 to 3212EF)
R: -50 to 1767EC (-58 to 3212EF)
N1: 0 to 1300EC (32 to 2372EF)
N2: -270 to 400EC (-454 to 752EF)
B: 42 to 1820EC (108 to 3300EF)
Accuracy J, K, E, T, R, N, B: ±1.0EC
S: ±2.0EC
SPECIFICATIONS SD39VIM-2
July 19986-2
TABLE 6-1 VIM Module Specifications (Continued)
CATEGORY SPECIFICATION DATA
Thermocouple Inputs Resolution J, E, T: 0.5EC
(Continued) K, S, R, N: 1.0EC
B: 2.0EC
Repeatability J, E, T, K, S, R, N: ±1.0EC
B: ±2.0EC
Conformity to NBS 125 Tables #±0.05EC
Agency Approvals ABS approved
CSA and FM approved for Class I, Division
2, Groups A, B, C, & D
Voltage Inputs Range -10.0 to 10.0 Vdc
Accuracy ±0.1% of span for user ranges:
(-10 to 10 V)
(-5 to 5 V)
(-1 to 1 V)
(0 to 5 V)
(1 to 5 V) - OR -
±0.2% ±25FV of reading
Resolution # 0.15% of reading
Repeatability #±0.05% of full scale
6.2 ENVIRONMENTAL SPECIFICATIONS
Table 6-2 lists the environmental specifications for the VIM module.
TABLE 6-2 VIM Environmental Specifications
SPECIFICATIONS DATA REFERENCE STANDARDS
Ambient Temperature Range IEC 68-2-2 Test Bb
Operating 0 to 60EC, 0.5EC/min IEC 68-2-14 Tests Na, Nb
Storage -25 to 85EC, 10E/min IEC 68-2-1 Tests Ab, Ad
Relative Humidity IEC 68-2-3 Test Ca
Operating: IEC 1131-2-RH2 5 to 95%, non-condensing IEC 68-2-30 Test Dd
Storage 0 to 100%, condensing
Vibration 10-150 Hz IEC 68-2-6 Test F
2 g. max c
Mechanical Shock
Accleration 15 g. IEC 68-2-27 Test E
Duration 11 ms A
SD39VIM-2 SPECIFICATIONS
SPECIFICATIONS DATA REFERENCE STANDARDS
July 1998 6-3
Corrosives Class G3, 10+ years ANSI/ISA S71.04
Radiated Emission, E-Field 30 MHz-230 MHz EN 55011
30 db (FV/m) at 30 m
230 MHz-1000 MHz EN 50081-2
37 db (FV/m) at 30 m
Conducted Emission Power Lines 0.15 MHz-0.5 MHz EN 55011
79 dBm quasi-peak
0.5 MHz-30 MHz EN 50081-2
73 dBm quasi-peak
Immunity, Conducted 150 KHz-80 MHz, 10 V IEC 801-6/IEC 1000-4-6
Electromagnetic Field 10 k Hz-50 MHz, 1V IE 801-6
Immunity, Power Lines Surge 4 kV IEC 801-5
2 kV ANSI/IEEE C62.41 (IEEE 587)
Immunity, Electrical Fast 4 kV Power Lines, 2 kV I/O IEC 801-4/IEC 1000-4-4
Transients and Signal Line Surge 2.5 kV I/O ANSI/IEEE C37.90
(Formally IEEE 472)
Immunity, Radiated E-Field 10 V/m, 27 MHz-1000 MHz IEC 801-3
10 V/m, 80 MHz-1000 MHz IEC 1000-4-3
10 V/m, 30 kHz-150 kHz IEC 801-3
Immunity, Electrostatic Discharge 8 kV contact, 15 kV air IEC 801-2/IEC 1000-4-2, Level 4
Altitude: IEC 1131-2 Up to 2000 meters
6.3 ELECTRICAL CLASSIFICATION
This section provides certification agency ratings and hazardous locations precautions.
6.3.1 Approvals (see important note)
Table 6-3 lists the agency approvals.
IMPORTANT
Before installing, applying power to, or servicing an ACM, see the
module's nameplate for electrical classification.
SPECIFICATIONS SD39VIM-2
July 19986-4
TABLE 6-3 Agency Approvals
AGENCY STANDARD STANDARD TITLE
FM FM Class 3611 Electrical Equipment for use in Class I, Div 2; Class II, Div 2;
and Class III, Div 1 and 2 Hazardous Locations
CSA C22.2 No.213 Non-Incendive Electrical Equipment for use in Class I, Div 2
Hazardous Locations
FM ISA S82.01 Safety Standards for Electrical and Electronic Test, Measuring,
Controlling, and Related Equipment
CSA C22.2 No.142 Process and Control Equipment for Non-Hazardous Locations
6.3.2 CSA Hazardous Locations Precautions
This section provides CSA hazardous location precautions that should be observed by the user when
installing or servicing the equipment described in this Instruction. These statements supplement those
given in the preceding section.
WARNING
Failure to observe the following precautions could result in an
explosion hazard.
6.3.2.1 Precautions - English
For Class I, Division 1 and Class I, Division 2 hazardous locations,
Use only factory-authorized replacement parts. Substitution of components can impair the suitability of
this equipment for hazardous locations.
For Division 2 hazardous locations:
When the equipment described in this Instruction in installed without safety barriers, the following
precautions should be observed. Switch off electrical power at its source (in non-hazardous location)
before:
Connecting or disconnecting power, signal, or other wiring
Replacing a fuse, circuit board, or any other component connected to the electrical circuit
SD39VIM-2 SPECIFICATIONS
July 1998 6-5
6.3.2.2 Précautions - Français
Emplacements dangereux de classe I, division 1 et classe I, division 2:
Les pièces de rechange doivent être autorisées par l'usine. Les substitutions peuvent rendre cet
appareil impropre à l'utilisation dans les emplacements dangereux.
Emplacement dangereux de division 2:
Lorsque l'appareil décrit dans la notice ci-jointe est installé sans barrières de sécurité, on doit couper
l'alimentation électrique a la source (hors de l'emplacement dangereux) avant d'effectuer les opérations
suivantes:
Branchment ou débranchement d'un circuit de puissance, de signalisation ou autre
Replacement d'un fusible, d'une carte de circuit imprimé ou de tout autre élément connecté au circuit
électrique.
6.4 ELECTROMAGNETIC COMPATIBILITY (EMC)
This product has been tested per the European Union’s EMC Directive. See the Declaration of Conformity
statement at the back of this Instruction. Refer to section 2.2.1, for considerations affecting EMC
compliance.
#
WARRANTY
The Company warrants all equipment manufactured by it and bearing its nameplate, and all repairs made
by it, to be free from defects in material and workmanship under normal use and service. If any part of the
equipment herein described, and sold by the Company, proves to be defective in material or workmanship
and if such part is within twelve months from date of shipment from the Company's factory, returned to
such factory, transportation charges prepaid, and if the same is found by the Company to be defective in
material or workmanship, it will be replaced or repaired, free of charge, f.o.b. Company's factory. The
Company assumes no liability for the consequence of its use or misuse by Purchaser, his employees or
others. A defect in the meaning of this warranty in any part of said equipment shall not, when such part is
capable of being renewed, repaired or replaced, operate to condemn such equipment. This warranty is
expressly in lieu of all other warranties, guaranties, obligations, or liabilities, expressed or implied by the
Company or its representatives. All statutory or implied warranties other than title are hereby expressly
negated and excluded.
Warranty repair or replacement requires the equipment to be returned to one of the following addresses.
Equipment manufactured or sold by Moore Process Automation Solutions:
Moore Process Automation Solutions
1201 Sumneytown Pike
Spring House, PA 19477-0900 U.S.A
Equipment manufactured or sold by Moore Products Co. (Canada) Inc.:
Moore Products Co. (Canada) Inc.
P.O. Box 370
Brampton, Ontario L6V 2L3
Canada
Equipment manufactured or sold by Moore Products Co. (UK) Ltd.:
Moore Products Co. (UK) Ltd.
Copse Road
Lufton Industrial Estate
Yeovil, Somerset BA22 8RN
England
The warranty will be null and void if repair is attempted without authorization by a member of the Moore
Process Automation Solutions Service Department.
#
DANGER
Electrical shock hazard
Explosion hazard
Will cause death, serious injury or property damage
Remove power from all wires and terminals and verify that there
are no hazardous voltages before working on equipment.
In potentially hazardous atmosphere, remove power from
equipment before connecting or disconnecting power, signal, or
other circuit, or extracting/inserting module.
Observe all pertinent regulations regarding installation in
hazardous area.
Ensure all devices are rated for hazardous (classified) locations.