https://www.phoenixcontact.com/us/products/2701295
11/23/2020Page4/11
Controller-AXC 1050 XC-2701295
Technical data
Power supply
Residual ripple ± 5%
Power dissipation max. 3 W
Mechanical design
Weight 195 g
Note on weight specifications with connector and bus base module
Diagnostics display No
Controller redundancy No
Safety function No
General data
Processor Altera Nios II 1x 100 MHz
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Interference emission Noise emission test according to EN 61000-6-3 Class B
Immunity to surge
Noise immunity test in accordance with EN 61000-6-2 Transient
overvoltage (surge) EN61000-4-5/IEC61000-4-5 Criterion B, DC supply
lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), fieldbus cable shield:
±1 kV
Immunity to burst Noise immunity test in accordance with EN 61000-6-2 Fast transients
(burst) EN61000-4-4/IEC61000-4-4 Criterion B, 2kV
Immunity to EF Noise immunity test in accordance with EN 61000-6-2 Electromagnetic
fields EN61000-4-3/IEC61000-4-3 Criterion A, Field intensity: 10 V/m
Immunity to ESD
Noise immunity test in accordance with EN 61000-6-2 Electrostatic
discharge (ESD) EN61000-4-2/IEC61000-4-2 Criterion B, 6 kV contact
discharge, 8 kV air discharge
Immunity to conducted interference Noise immunity test in accordance with EN 61000-6-2 Conducted
interference EN61000-4-6/IEC61000-4-6 Criterion A, Test voltage 10 V
Vibration (storage/transport) 5g
Shock 30g, 11 ms period, half-sine shock pulse, according to IEC 60068-2-27
Vibration (operation) 5g
Shock (operation) 10g (Bump endurance test according to DIN EN 60068-2-27)
Environmental Product Compliance
REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings