G7SA G7SA
2
Specifications
Ratings
Coil
Rated
voltage Rated
current
Coil resistance
Must-operate
voltage Must-release
voltage Max.
voltage
Power consumption
24 VDC
4 poles: 15 mA
6 poles: 20.8 mA
4 poles: 1,600
Ω
6 poles: 1,152
Ω
75% max. (V)
10% min. (V)
1
10% (V)
4 poles:
Approx. 360 mW
6 poles: Approx. 500 mW
Note: 1.
The rated current and coil resistance are measured at a coil temperature of 23
°
C with tolerances of
±15%.
2.
Performance characteristics are based on a coil temperature of 23
°C.
3. The
value given for the maximum voltage is for voltages applied instantaneously to the Relay coil (at an ambient temperature of
23°C)
and not continuously
.
Contacts
Load
Resistive load (cos
φ
=1)
Rated load
6 A at 250 V
AC, 6 A at 30 VDC
Rated carry current
6 A
Max. switching voltage
250 V
AC, 125 VDC
Max. switching current
6 A
Characteristics
Safety Relay Sockets
Model Continuous
current
Dielectric strength
Insulation resistance
P7SA-14j
6 A
2,500 V
AC for 1 min. between poles
100 M
Ω
min. (see note)
Note:
Measurement conditions: Measurement of the same points as for the dielectric strength at 500 VDC.
Safety Relays
Contact
resistance
100 m
Ω
max. (The contact resistance was measured with 1 A at 5 VDC using the
voltage-drop method.)
Operating time (see note 2)
20 ms max.
Response time (see note 2) 10 ms max. (The response time is the time it takes for the normally open contacts to open
after the coil voltage is turned OFF
.)
Release time (see note 2)
20 ms max.
Maximum operating
Mechanical
36,000 operations/hr
frequency
Rated load
1,800 operations/hr
Insulation resistance
100 M
Ω
min. (at 500 VDC)
(The insulation resistance was measured with a 500-VDC megger at the same places that the
dielectric strength was measured.)
Dielectric strength (see notes 3, 4)
Between coil contacts/dif
ferent poles: 4,000 V
AC, 50/60 Hz for 1 min
(2,500 V
AC between poles 3–4 in 4-pole Relays or poles 3–5, 4–6, and 5–6 in 6-pole Relays.)
Between contacts of same polarity: 1,500 VAC, 50/60 Hz for 1 min
V
ibration resistance
10 to 55 Hz, 1.5-mm double amplitude
Shock resistance
Destruction
1,000 m/s
2
Malfunction
100 m/s
2
Life expectancy
Mechanical
10,000,000 operations min. (at approx. 36,000 operations/hr)
Electrical
100,000 operations min. (at the rated load and approx. 1,800 operations/hr)
Error rate (see note 5)(P level)
(reference value)
1 mA at 5 VDC
Ambient temperature (see note 6)
Operating: –40°
C to 85
°
C (with no icing or condensation)
Storage: –40°
C to 85
°
C (with no icing or condensation)
Ambient humidity
Operating:
35% to 85%
Storage:
35% to 85%
Weight
4 poles: Approx. 22 g
6 poles: Approx. 25 g
Approved standards (see note 7)
EN61810-1 (IEC61810-1), EN50205, UL508, CSA22.2 No. 14
Note: 1.
The values listed above are initial values.
2.
These times were measured at the rated voltage and an ambient temperature of 23
°
C. Contact bounce time is not included.
3. Pole
3 refers to terminals 31–32 or 33–34, pole 4 refers to terminals 43–44,
pole 5 refers to terminals 53–54, and pole 6 refers to
terminals
63–64.