Macromatic Time Delay Relays Time Ranger Programmable File No. File No. E109466 LR45565 4 c 16 Timing Ranges in a Single Timer c User Selects Desired Time Range by Setting a Rotary Switch N No Math Required or DIP Switches to Set c Pin for Pin Interchangeable with Most Timers in the Field c All Timers Operate on Either AC or DC c 0.1% Repeat Accuracy c Repeat Cycle and Delayed Interval Timers Have Independently Selectable and Adjustable ON and OFF Times Timing range on non-cycle timers is 0.1 seconds to 2 hours and 0.6 seconds to 24 hours on repeat cycle and delayed interval timers. Output: DPDT (TR-68169 is SPDT) 10 A resistive @ 240 VAC/28 VDC, 1/2 hp @ 240 VAC. Repeat Accuracy: 0.1%. Temperature: 28 to 65C (20 to 150F). Power Required: 3 VA. Dimensions: 1.7" 2.4" 3.2". Multi-Function Seven field-selectable operating modes (On Delay, Interval On, Off Delay, Single Shot, Triggered On Delay, On Delay/Off Delay and Instantaneous On) with sixteen timing ranges from 0.1 seconds to 2 hours in one unit. Both function and time range are selectable with rotary switches. Stock No. Mfr.Os Type Input Voltage Socket 819-6017 819-6018 TR-68129 TR-68169 120 VAC and 24 VAC/VDC 120 VAC and 24 VAC/VDC 11 Pin Octal, Diagram 44 8 Pin Octal, Diagram 43 EACH 1-9 10-24 25-49 50-99 76.50 73.32 63.35 60.72 59.63 57.15 57.92 55.52 On Delay Upon application of input voltage, a preset time begins. At the end of the preset time, the relay contacts transfer. Input voltage must be removed and reapplied to reset the time delay relay. 819-0003 819-0007 819-6022 TR-60222 TR-60228 TR-60226 120 VAC/VDC 24 VAC/VDC 12 VAC/VDC 8 Pin Octal Diagram 1 70169-D Interval On Upon application of input voltage, the relay contacts transfer and a preset time begins. At the end of the preset time, the contacts return to their normal condition. Input voltage must be removed and reapplied 819-0522 819-0008 819-6052 TR-60522 TR-60528 TR-60526 120 VAC/VDC 24 VAC/VDC 12 VAC/VDC Input voltage must first be applied. Upon closure of the control switch, the relay contacts transfer and the preset time begins. During time-out, the trigger input is ignored. The time delay relay is reset by TR-61522 TR-61528 TR-61526 120 VAC/VDC 24 VAC/VDC 12 VAC/VDC 53.00 60.93 53.00 Input voltage must first be applied. Upon closure of the control switch, the relay contacts transfer and hold. Upon opening of the control switch, a preset time begins. At the end of the preset time, the relay 36.90 39.01 38.88 36.37 37.91 37.95 43.89 50.45 43.89 41.31 47.49 41.31 40.32 46.13 40.37 48.60 48.60 48.10 47.21 47.21 46.78 applying the trigger when the relay is not energized. 11 Pin Octal Diagram 2 70170-D Off Delay 39.78 41.46 41.31 to reset the time delay relay. 8 Pin Octal Diagram 1 70169-D Single Shot (Momentary Interval) 819-0013 819-0014 819-6152 48.04 50.07 49.88 62.35 62.35 62.09 51.64 51.64 50.97 contacts return to their normal condition. Any application of the control switch will reset the time. The time delay relay is reset by closing the control switch. 819-1622 819-0009 819-0010 TR-61622 TR-61628 TR-61626 120 VAC/VDC 24 VAC/VDC 12 VAC/VDC 11 Pin Octal Diagram 2 70170-D 62.09 62.35 64.50 50.97 51.64 53.42 48.10 48.60 50.28 46.78 47.21 48.84 819-6192 819-0011 819-0012 TR-61922 TR-61928 TR-61926 120 VAC/VDC 24 VAC/VDC 12 VAC/VDC 11 Pin Octal Diagram 4 70170-D 66.40 70.98 68.38 54.98 58.77 56.14 51.74 55.32 52.99 50.28 53.74 51.53 Watchdog (Power Trigger) Input voltage must first be applied. Upon application of the trigger voltage, the relay contacts transfer and the preset time begins. At the end of the preset time, the relay contacts return to their normal condition 819-0019 819-0006 819-0020 TR-61822 TR-61828 TR-61826 120 VAC/DC 24 VAC/DC 12 VAC/DC 11 Pin Octal Diagram 4 70170-D Repeat Cycle (Off Time Followed By On Time) Upon application of input voltage, OOffO time begins. When the OOffO time is completed, the OOnO time begins. The sequence repeats until the input voltage is removed. The OOffO time and OOnO time are 819-0005 819-3128 819-6312 TR-63122 TR-63128 TR-63126 120 VAC/VDC 24 VAC/VDC 12 VAC/VDC Upon application of input voltage, OOnO time begins. When the OOnO time is completed, the OOffO time begins. The sequence repeats until the input voltage is removed. The OOnO time and OOffO time are TR-65122 TR-65128 TR-65126 120 VAC/VDC 24 VAC/VDC 12 VAC/VDC Upon application of input voltage, OOffO time begins. When the OOffO time is completed, the OOnO time begins. When OOnO time is completed, sequence stops. Input voltage must be removed and reapplied to 819-6612 819-0017 819-0018 TR-66122 TR-66128 TR-66126 120 VAC/VDC 24 VAC/VDC 12 VAC/VDC 54.98 54.98 54.98 51.75 51.75 51.75 50.27 50.27 50.27 76.52 76.50 76.52 63.35 63.35 63.35 59.63 59.63 59.63 57.92 57.92 57.92 76.52 76.50 69.11 63.35 63.35 57.21 59.63 59.63 53.85 57.92 57.92 52.31 independently selectable. 8 Pin Octal Diagram 1 70169-D Delayed Interval (Off Time Followed By On Time Followed By Off State Until Reset) 66.40 66.40 66.40 independently selectable. 8 Pin Octal Diagram 1 70169-D Repeat Cycle (On Time Followed By Off Time) 819-6512 819-0015 819-0016 unless the trigger voltage is removed and reapplied before preset time elapses. Continuous cycling of the trigger voltage at a rate faster than the preset time will cause the relay contacts to remain closed. initiate action again. The OOnO time and OOffO time are independently selectable. 8 Pin Octal Diagram 1 70169-D 79.23 76.50 74.04 65.62 63.35 61.30 61.76 59.63 57.70 59.99 57.92 56.05 Note: See page 124 for socket selection. For Fast, Dependable Service, Make Just One Call N 1-800-433-5700 ALLIED c 125