www.advantech.com/products
Online Download
20-43
19
PC-based Controllers
Embedded Controllers
20
PAC
21
Motion Control
22
RS-485 I/O
23
Ethernet I/O
24
Building Automation
25
Self-service Terminals
26
eHome Platforms
27
RoHS
COMPLIANT
2002/95/EC
RoHS
COMPLIANT
2002/95/EC
General
Certifications CE, FM
Connectors 1 x Plug-in screw terminal
(# 14 ~ 22 AWG)
Enclosure ABS+PC
Power Consumption 0.63 W (max.)
Thermocouple Input
Accuracy ±0.1% or better
Bandwidth 13.1 Hz @ 50 Hz
15.72 Hz @ 60 Hz
Channels 7 differential
CMR @ 50/60 Hz 92 dB min
Input Impedance 2 MW
lnput Range ±15 mV, ±50 mV, ±100 mV,
±500 mV,
±1 V, ±2.5 V, ±20 mA
lnput Type mV, V, mA,thermocouple
Resolution 16-bit
Sampling Rate 10 samples/sec. (total)
Span Drift ±25 PPM/ ° C
Zero Drift ±6 μV/ ° C
T/C Type and Temperature Range
J 0° ~ 760° C
K 0° ~ 1,370° C
T -100° ~ 400° C
E 0° ~ 1,000° C
R 500° ~ 1,750° C
S 500° ~ 1,750° C
B 500° ~ 1,800° C
Protection
Fault and Withstands overvoltage up
Overvoltage to ±35 V
Protection
Isolation Voltage 3,000 VDC
Ordering Information
ADAM-5018 7-ch Thermocouple Input
Module
ADAM-5018SK CJC Kit for ADAM-5018
8-ch Ultra High Speed Analog Input
Module
7-ch Thermocouple Input Module
7-ch Thermocouple Input Module
with Independent Input Range
ADAM-5017UH
ADAM-5018
ADAM-5018P
ADAM-5018P
Specifications
ADAM-5018
General
Certifications CE, FCC class A
Connectors 1 x Plug-in screw terminal
(# 14 ~ 22 AWG)
Enclosure ABS+PC
Power Consumption 0.63 W (max.)
Thermocouple Input
Accuracy Voltage mode: ±0.1% or
better
Current mode: ±0.2% or
better
Bandwidth 13.1 Hz @ 50 Hz
15.72 Hz @ 60 Hz
Channels 7 (differential, each channel
can be configured with
different range)
CMR @ 50/60 Hz 92 dB min
Input Impedance 20 MW. (Build-in 120 W
Register for Current Input)
lnput Range and Types
Thermocouple
J 0 ~ 760° C
K 0 ~ 1,370° C
T -100 ~ 400° C
E 0 ~ 1,000° C
R 500 ~ 1,750° C
S 500 ~ 1,750° C
B 500 ~ 1,800° C
Current ±20 mA, 4 ~ 20 mA
Voltage ±15 mV (0.2%), ±50 mV,
±100 mV, ±500 mV
±1 V, ±2.5 V
Resolution 16-bit
Sampling Rate 10 samples/sec. (total)
Span Drift ±25 PPM/°C
Zero Drift ±6 μV/°C
High Common Mode 200 VDC
Protection
Fault and Withstands overvoltage up
Overvoltage to ±35 V
Protection
Isolation Voltage 3,000 VDC
Filter function Yes
Built-in TVS/ESD Protection
Note: Not support ADAM-5510KW series
Ordering Information
ADAM-5018P 7-ch Thermo. Input Module
w/ Ind. Input Range
Specifications
General
Certifications CE
Connectors 1 x Plug-in screw terminal
(# 14 ~ 22 AWG)
Enclosure ABS+PC
Power Consumption 2.2 W (max.)
Analog Input
Accuracy ±0.1% or better
Bandwidth 200 kHz
Channels 8 differential
Differential Non-linear ±1 LSB
Input Impedance Voltage: 2 MW
Current: 120 W
(Build-in 12 W. register for
Current Input)
Integral Non-linear ±1 LSB
Input Range ±10 V, +0 ~ 10 V,
0 ~ 20 mA, +4 ~ 20 mA
Low pass filter Configured by User
Resolution 12-bit
Sampling Rate Depends on base unit
ADAM-5000/485 & 5000E:
100 Samples/sec max (Total): one ADAM-5017UH
installed
ADAM-5000/TCP:
100 Samples/sec max (Total) :one ADAM-5017UH
installed
ADAM-5510 :
200K Samples/sec max (Single Channel): one ADAM-
5017UH installed
ADAM-5550 :
1K Samples/sec per channel: one ADAM-5017UH
installed
*Depending on the performance of client server or
controller
Signal Input 200 kHz for both voltage
Bandwidth and current inputs
Protection
Isolation Voltage 3,000 VDC
Note:
1) The voltage difference between any two pins must not
exceed 15 V
2) Distinct range settings allowed on each channel
Note: Not support ADAM-5510KW series
Ordering Information
ADAM-5017UH 8-ch Ultra High Speed
Analog Input Module
ADAM-5017UH
Specifications
RoHS
COMPLIANT
2002/95/EC