http://www.tracopower.com Page 2 of 3
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
AC/DC Power Supplies
TIW Series 4 – 24 Watt
Input Specifications
Input voltage range – nominal 115 – 230 VAC
– ranges 93 – 264 VAC (universal input)
– output power derating for 12 & 24 W models 0.45 %/V below 187 VAC down to 132 VAC
1 %/V below 115 VAC
Input frequency 47 – 63 Hz
No load power consumption (acc. ErP directive EC No.278/2009) < 300 mW
External input fuse required (recommended values) 2 to 6 A slow blow resp. characteristic C
Harmonic limits EN 61000-3-2, Class A
Output Specifications
Voltage set accuracy ±3 % max.
Regulation – Input variation 1 % max.
– Load variation (0–100%) 2 % max.
Ripple and noise (20 Mhz Bandwidth) <200 mVp-p
Start-up time <1s
Hold-up time – Vin = 115 VAC 5 ms typ.
– Vin = 230 VAC 20 ms typ.
Overload protection by current limit TIW 06-xxx & TIW 24-xxx models: <2.5 A
TIW 12-xxx models: <3.5 A
Short circuit protection foldback (automatic recovery)
General Specifications
Operating Temperature (Ambient) –25°C to +50°C
Please take heat sources (such as lamps) nearby
into consideration for ambient temperature of
the power supply
Over temperature protection built in (for safety reason only)
Preventive fire protection VDE 710-14
Protection class class II as per IEC/EN 61140
Safety standards – CB test certificate IT safety IEC 60950-1:2005(2nd)+A1:2009+A2:2013,
EN 60950-1:2006+A1:2010+A2:2013+
A11:2009+A12:2011
– BV certificate household appliance IEC/EN 60335-1, VDE 710-14
safety of transformers IEC/EN 61558-2-16, IEC/EN 61558-2-8
used in conjunction with IEC/EN 61558-1
lamp controlgear IEC/EN 61347-2-13 used in conjunction with
IEC/EN 61347-1
electronic equipment for power installation IEC 62103 (1st Ed.), EN 50178:1997
– CSA certificate of compliance IT safety UL 60950-1(2nd Ed.)+Am1:2011,
CAN/CSA-C22.2 No.60950-1-07+Am1:201
class 2 power units UL 1310 (6th Edition),
CAN/CSA-C22.2 No.223-M91(R2008)
– Certification documents www.tracopower.com/overview/tiw
Electromagnetic compatibility (EMC), emissions EN 61000-6-3
– Conducted RI suppression on input EN 55022 class B, EN 55014-1
– Radiated RI suppression EN 55022 class B, EN 55014-1
Electromagnetic compatibility (EMC), immunity EN 61000-6-2-1, IEC 61204-3
– Electrostatic discharge (ESD) EN 61000-4-2 4 kV / 8 kV, class B
– Radiated RF field immunity EN 61000-4-3 10 V/m, class A
– Electrical fast transient / burst immunity EN 61000-4-4 2 kV / 0.5 kV, class B+A
– Surge immunity see next page