LOGO!Power ___________________ Overview 1 ___________________ Safety instructions Power supply LOGO!Power Description, device design, 2 ___________________ dimension drawing ___________________ 3 Mounting/disassembly Mounting position, mounting ___________________ 4 clearances 5 ___________________ Installation Operating Instructions ___________________ 6 Technical data ___________________ 7 Safety, approvals, EMC ___________________ 8 Ambient conditions ___________________ 9 Applications ___________________ 10 Environment LOGO!Power 5 V / 3 A 6EP1311-1SH03 LOGO!Power 5 V / 6.3 A 6EP1311-1SH13 LOGO!Power 12 V / 1.9 A 6EP1321-1SH03 LOGO!Power 12 V / 4.5 A 6EP1322-1SH03 LOGO!Power 15 V / 1.9 A 6EP1351-1SH03 LOGO!Power 15 V / 4 A 6EP1352-1SH03 LOGO!Power 24 V / 1.3 A 6EP1331-1SH03 LOGO!Power 24 V / 2.5 A 6EP1332-1SH43 LOGO!Power 24 V / 4 A 6EP1332-1SH52 06.2014 C98130-A7560-A999-3-7629 ___________________ 11 Service and support Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION indicates that minor personal injury can result if proper precautions are not taken. NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. Trademarks All names identified by (R) are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Industry Sector Postfach 48 48 90026 NURNBERG GERMANY C98130-A7560-A999-3-7629 06/2014 Subject to change Copyright (c) Siemens AG 2014. All rights reserved Overview LOGO!Power are powerful power supplies that can be extremely flexibly used in a host of applications - in installation distribution boards for example - as a result of their flat, stepped profile. The 12 V and 24 V versions are ideal as power supplies for the LOGO! logic modules. The key benefits of the product include: Flat LOGO! mechanical design Wide-range input for voltages from 85 to 264 VAC and operation with DC voltage Adjustable output voltage Green LED for "Output voltage OK" Ambient temperature -20 C...+70 C (derating from +55 C) Constant current under overload conditions for reliable connection of difficult loads When you turn on the power supply, a power reserve of 1.5 times rated current is available for typ. 200 ms Export benefits thanks to global certifications LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 3 Overview Ordering data The following device options are available: LOGO!Power stabilized power supply Type Order number Input 85 to 264 VAC 110 to 300 VDC 6EP1311-1SH03 Output 5 VDC / 3 A Input 85 to 264 VAC 110 to 300 VDC 6EP1311-1SH13 Output 5 VDC / 6.3 A Input 85 to 264 VAC 110 to 300 VDC 6EP1321-1SH03 Output 12 VDC / 1.9 A Input 85 to 264 VAC 110 to 300 VDC 6EP1322-1SH03 Output 12 VDC / 4.5 A Input 85 to 264 VAC 110 to 300 VDC 6EP1351-1SH03 Output 15 VDC / 1.9 A Input 85 to 264 VAC 110 to 300 VDC 6EP1352-1SH03 Output 15 VDC / 4 A Input 85 to 264 VAC 110 to 300 VDC 6EP1331-1SH03 Output 24 VDC / 1.3 A Input 85 to 264 VAC 110 to 300 VDC 6EP1332-1SH43 Output 24 VDC / 2.5 A Input 85 to 264 VAC 110 to 300 VDC 6EP1332-1SH52 Output 24 VDC / 4 A LOGO!Power 4 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Table of contents Overview................................................................................................................................................. 3 1 Safety instructions ................................................................................................................................... 7 2 Description, device design, dimension drawing........................................................................................ 9 2.1 Device description .......................................................................................................................... 9 2.2 Connections and terminal designation .........................................................................................10 2.3 Potentiometer ...............................................................................................................................11 2.4 Status displays and signaling.......................................................................................................12 2.5 Block diagram ..............................................................................................................................13 2.6 Dimensions and weight ................................................................................................................14 3 Mounting/disassembly ........................................................................................................................... 17 4 Mounting position, mounting clearances ................................................................................................ 19 5 6 7 4.1 Standard mounting position .........................................................................................................19 4.2 Other mounting positions .............................................................................................................20 Installation ............................................................................................................................................ 23 5.1 Line-side connection ....................................................................................................................23 5.2 Output-side connection ................................................................................................................25 Technical data ...................................................................................................................................... 27 6.1 Input .............................................................................................................................................27 6.2 Output ..........................................................................................................................................29 6.3 Efficiency and power loss ............................................................................................................32 6.4 Closed-loop control ......................................................................................................................36 6.5 Protection and monitoring ............................................................................................................37 6.6 MTBF ...........................................................................................................................................37 6.7 Mechanical system ......................................................................................................................38 6.8 Accessories ..................................................................................................................................38 6.9 Dimension drawing ......................................................................................................................39 Safety, approvals, EMC......................................................................................................................... 41 7.1 Safety ...........................................................................................................................................41 7.2 Test voltage..................................................................................................................................42 7.3 Certifications ................................................................................................................................43 7.4 EMC .............................................................................................................................................44 LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 5 Table of contents 8 Ambient conditions................................................................................................................................ 45 9 Applications .......................................................................................................................................... 47 9.1 Parallel connection to increase power rating .............................................................................. 47 9.2 Parallel connection for redundancy ............................................................................................. 49 9.3 Series connection for increased voltage ..................................................................................... 50 9.4 Protection against short-time voltage dips .................................................................................. 51 10 Environment ......................................................................................................................................... 53 11 Service and support .............................................................................................................................. 55 LOGO!Power 6 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Safety instructions 1 WARNING Correct handling of the devices When operating electrical devices, it is inevitable that certain components will carry dangerous voltages. Therefore, failure to handle the units properly can result in death or serious physical injury as well as extensive property damage. Only appropriately qualified personnel may work on or in the vicinity of this equipment. Perfect, safe, and reliable operation of this equipment is dependent on proper transportation, storage, installation and mounting. Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 7 Safety instructions LOGO!Power 8 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Description, device design, dimension drawing 2.1 2 Device description LOGO!Power are primary switched-mode power supplies for connection to a 1-phase AC system or to DC systems. An electronically regulated DC voltage that can be set via a potentiometer is available at the output of the device. The output of the device is isolated, no-load proof and short-circuit proof. The LED display indicates the operating status. Line input DC output Potentiometer Indicator light (output voltage OK) Lug for unlocking with a screwdriver Natural convection Clearance above/below Figure 2-1 Design (example of 6EP1311-1SH13) LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 9 Description, device design, dimension drawing 2.2 Connections and terminal designation 2.2 Connections and terminal designation Note UL requirement: Use suitable copper cables that are designed for operating temperatures of at least 65 C / 75 C. The line input terminals can be used to establish the connection to supply voltage. The output terminals are used to connect to the loads to be supplied (see also Section Installation (Page 23)). Connections and terminal designations line input L1, N One screw terminal each Output + Two screw terminals Output - Two screw terminals *1) Do not subject the end stop to higher loads Figure 2-2 Terminal data LOGO!Power 10 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Description, device design, dimension drawing 2.3 Potentiometer 2.3 Potentiometer The potentiometer on the front of the device is used to set the output voltage. The output voltage is set to the rated value at the factory and can be set within certain limits; for example, to compensate voltage drops across long supply lines to the connected load. Figure 2-3 Potentiometer (example of 6EP1311-1SH13) Type Factory setting Setting range 6EP1311-1SH03 (5 V / 3 A) 5V 4.6...5.4 V 12 V 10.5...16.1 V 15 V 10.5...16.1 V 24 V 22.2...26.4 V 6EP1311-1SH13 (5 V / 6.3 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A) 6EP1332-1SH52 (24 V / 4 A) NOTICE Thermal overload possible When adjusting the output voltage to > 24 V / > 15 V / > 12 V or > 5 V, the output current must be derated by 4%/V. Note Actuation of the potentiometer is allowed only by means of an insulated screwdriver. The end stop may be subject to a maximum load of 0.04 Nm (0.35 lbf in). For notes on actuating the potentiometer (screwdriver, torque), see Figure 2-2 Terminal data (Page 10). LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 11 Description, device design, dimension drawing 2.4 Status displays and signaling 2.4 Status displays and signaling 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A) 6EP1332-1SH52 (24 V / 4 A) Status display Green LED for output voltage OK Figure 2-4 Signaling Operational displays and signals (example of 6EP1311-1SH13) 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A) 6EP1332-1SH52 (24 V / 4 A) LED lights up green Normal operation, output voltage present LED off Output voltage not present LOGO!Power 12 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Description, device design, dimension drawing 2.5 Block diagram 2.5 Figure 2-5 Block diagram Block diagram LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 13 Description, device design, dimension drawing 2.6 Dimensions and weight 2.6 Dimensions and weight Figure 2-6 Dimension drawing 6EP1311-1SH03, 6EP1321-1SH03, 6EP1351-1SH03, 6EP1331-1SH03 Figure 2-7 Dimension drawing 6EP1311-1SH13, 6EP1322-1SH03, 6EP1352-1SH03, 6EP1332-1SH43 LOGO!Power 14 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Description, device design, dimension drawing 2.6 Dimensions and weight Figure 2-8 Dimension drawing 6EP1332-1SH52 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1332-1SH52 (24 V / 4 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A) Dimensions (W x H x D) in mm 54 x 90 x 53,1 72 x 90 x 53,1 90 x 90 x 53,1 Weight Approx. 0.17 kg Approx. 0.25 kg Approx. 0.34 kg LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 15 Description, device design, dimension drawing 2.6 Dimensions and weight LOGO!Power 16 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Mounting/disassembly 3 WARNING Installing the device in a housing or a control cabinet The LOGO!Power power supplies are built-in units. They must be installed in a casing or control cabinet to which only qualified personnel have access. The devices can be mounted in a control cabinet on standard mounting rails according to EN 60715 35x7,5/15. Mounting To mount the device, position it with the mounting rail guideway at the upper edge of the DIN rail and press down to lock it into place. If this is too difficult, press slider at the same time, as described for "Disassembly". Disassembly To remove, pull up the slider using a screwdriver and disengage the device at the bottom edge of the DIN rail. Then you can remove the device from the upper edge of the DIN rail. Figure 3-1 Disassembly (example of 6EP1311-1SH13) LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 17 Mounting/disassembly WARNING Use in hazardous zones If the device is to be used in a hazardous zone (Ex II 3G Ex nA IIC T3) it must be installed in a distributor box with degree of protection IP54 or higher. LOGO!Power 18 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Mounting position, mounting clearances 4.1 4 Standard mounting position The device is mounted on standard mounting rails according to EN 60715 35x7,5/15. The device must be mounted vertically in such a way that the input terminals and the output terminals are at the top to ensure correct cooling. A clearance of at least 20 mm should be maintained above and below the device. No space is required at the side. Figure 4-1 Output current in the standard mounting position Figure 4-2 Mounting height derating For details, see Section Ambient conditions (Page 45) LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 19 Mounting position, mounting clearances 4.2 Other mounting positions 4.2 Other mounting positions For mounting positions that deviate from the standard mounting position, derating factors (reduction of the output power or the permissible ambient temperature) must be observed in accordance with the following diagrams. Note In the case of mounting postilions that deviate from the standard mounting position, reduced mechanical resistance of the devices against vibration and shock must be expected. Particularly when installing on a vertically fastened standard mounting rail, additional measures may be required, e.g. to prevent the device from slipping on the standard mounting rail. Figure 4-3 Mounting position (1) Figure 4-4 Mounting position (2) LOGO!Power 20 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Mounting position, mounting clearances 4.2 Other mounting positions Figure 4-5 Mounting position (3) Figure 4-6 Mounting position (4) Figure 4-7 Mounting position (5) LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 21 Mounting position, mounting clearances 4.2 Other mounting positions LOGO!Power 22 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 5 Installation WARNING Hazard due to electric shock Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. 5.1 Line-side connection The LOGO!Power power supplies are power packs according. to safety class II (without protective conductor or equivalent without PE). LOGO!Power are designed for connection to a 1-phase AC supply network (TN or TT system according to VDE 0100 T 300 / IEC 364-3) with rated voltage 1-phase 100-240 VAC, 50/60 Hz or to a power supply with 110-300 VDC. Figure 5-1 Line connection The line supply is connected using terminal L1 and N (see Figure 5-1 Line connection (Page 23)), and must be implemented according to IEC 60364 and EN 50178. A protective device (miniature circuit-breaker or circuit-breaker) and a disconnection unit for the power supply must be provided. A ground-fault circuit interrupter must not be used as the only protective measure against indirect contact; this applies to the entire supply system that is protected by the residual current operated circuit-breaker. LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 23 Installation 5.1 Line-side connection Note For operation on a direct voltage network (DC), the plus pole (+) must be connected to L1 and the minus pole (-) to N. Protection LOGO!Power Recommended line-side protection 6EP1311-1SH03 (5 V / 3 A) Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A 6EP1311-1SH13 (5 V / 6.3 A) Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A 6EP1321-1SH03 (12 V / 1.9 A) Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A 6EP1322-1SH03 (12 V / 4.5 A) Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A 6EP1351-1SH03 (15 V / 1.9 A) Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A 6EP1352-1SH03 (15 V / 4 A) Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A 6EP1331-1SH03 (24 V / 1.3 A) Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A 6EP1332-1SH43 (24 V / 2.5 A) Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A 6EP1332-1SH52 (24 V / 4 A) Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A Other country-specific regulations may have to be observed when installing the device. LOGO!Power 24 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Installation 5.2 Output-side connection 5.2 Output-side connection LOGO!Power power supplies provide an isolated (= non-grounded) SELV (Safety Extra Low Voltage) output voltage at the output. The output of the power supplies is no-load, overload and short-circuit proof. If an overload occurs, the electronic current limiting function limits the output current to a maximum value (see Section Technical data (Page 27)). Figure 5-2 Connection of the output voltage (example of 6EP1311-1SH13) The output voltage is connected via the + and - terminals at the output of the power supply (see Figure 5-2 Connection of the output voltage (example of 6EP1311-1SH13) (Page 25)). Make sure that the output cables are dimensioned correctly for the maximum output current rms value and fused accordingly. Note When using LOGO!Power in conjunction with devices of the protection class I (with protective conductor), a connection must be established between "-" and "PE" with at least 1.5 mm. LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 25 Installation 5.2 Output-side connection LOGO!Power 26 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 6 Technical data Note For an AC input voltage, the technical data is applicable for rated input voltage, rated load and +25 C ambient temperature (if nothing else is specified). 6.1 Input 6EP1311-1SH03 6EP1311-1SH13 6EP1321-1SH03 6EP1322-1SH03 6EP1351-1SH03 (5 V / 3 A) (5 V / 6.3 A) (12 V / 1.9 A) (12 V / 4.5 A) (15 V / 1.9 A) 40 ms 40 ms 40 ms 40 ms Input 1-phase AC or DC Rated voltage Ue rated / for AC 100...240 V Voltage range / for AC 85...264 V Input voltage / for DC 110...300 V Wide-range input Yes Overvoltage resistance 2.3 x Ue rated, 1.3 ms Mains buffering at Ia rated, min. 40 ms Mains buffering at Ue = 187 V Rated line frequency 50/60 Hz Line frequency range 47...63 Hz Input current / at rated value of input voltage 120 V 0.36 A 0.71 A 0.53 A 1.13 A 0.63 A Input current / at rated value of input voltage 230 V 0.22 A 0.37 A 0.3 A 0.61 A 0.33 A Switch-on current limitation (+ 25 C), max. 26 A 50 A 25 A 55 A 25 A It, max. 0.8 A*s 3 A*s 0.8 A*s 3 A*s 0.8 A*s Built-in line-side fuse Internal Protection in the line Recommended miniature circuit-breaker: Characteristic B from 16 A or characteristic C from 10 A feeder cable (IEC 898) LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 27 Technical data 6.1 Input 6EP1352-1SH03 6EP1331-1SH03 6EP1332-1SH43 6EP1332-1SH52 (15 V / 4 A) (24 V / 1.3 A) (24 V / 2.5 A) (24 V / 4 A) 40 ms 40 ms 40 ms Input 1-phase AC or DC Rated voltage Ue rated / for AC 100...240 V Voltage range / for AC 85...264 V Input voltage / for DC 110...300 V Wide-range input Yes Overvoltage resistance 2.3 x Ue rated, 1.3 ms Mains buffering at Ia rated, min. 40 ms Mains buffering at Ue = 187 V Rated line frequency 50/60 Hz Line frequency range 47...63 Hz Input current / at rated value of input voltage 120 V 1.24 A 0.7 A 1.22 A 1.95 A Input current / at rated value of input voltage 230 V 0.68 A 0.35 A 0.66 A 0.97 A Switch-on current limitation (+ 25 C), max. 55 A 25 A 46 A 30 A It, max. 3 A*s 0.8 A*s 3 A*s 2.5 A*s Built-in line-side fuse Internal Protection in the line Recommended miniature circuit-breaker: Characteristic B from 16 A or characteristic C from 10 A feeder cable (IEC 898) Figure 6-1 Mains buffering LOGO!Power 28 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Technical data 6.2 Output 6.2 Output 6EP1311-1SH03 6EP1311-1SH13 6EP1321-1SH03 6EP1322-1SH03 6EP1351-1SH03 (5 V / 3 A) (5 V / 6.3 A) (12 V / 1.9 A) (12 V / 4.5 A) (15 V / 1.9 A) Output Regulated, isolated DC voltage Rated voltage value Ua rated DC 5V 5V 12 V 12 V 15 V Total tolerance, static 3% 3% 3% 3% 3% Static line regulation, approx. 0.2% 0.1% 0.1% 0.1% 0.1% Static load regulation, approx. 1.5% 2% 1.5% 1.5% 1.5% Residual ripple peakpeak, max. 100 mV 100 mV 200 mV 200 mV 200 mV Residual ripple peakpeak, typ. 10 mV 15 mV 10 mV 10 mV 10 mV Spikes peak-peak, max. (bandwidth, approx. 20 MHz) 100 mV 100 mV 300 mV 300 mV 300 mV Spikes peak-peak, typ. 20 mV (bandwidth, approx. 20 MHz) 70 mV 20 mV 70 mV 30 mV Setting range 4.6...5.4 V 4.6...5.4 V 10.5...16.1 V 10.5...16.1 V 10.5...16.1 V Product function / output voltage can be adjusted Yes Output voltage setting Using a potentiometer Status display Green LED for output voltage OK Response when switching on/off No overshoot of Ua (soft start) Starting delay, max. 0.5 s 0.5 s 0.5 s 0.5 s 0.5 s Voltage rise, typ. 20 ms 10 ms 10 ms 10 ms 15 ms Rated current Ia rated 3A 6.3 A 1.9 A 4.5 A 1.9 A Current range 0...3 A 0...6.3 A 0...1.9 A 0...4.5 A 0...1.9 A 3 A to +55 C, 2.1 A to +70 C 6.3 A to +55 C, 4.4 A to +70 C 1.9 A to +55 C, 1.3 A to +70 C 4.5 A to +55 C, 3.1 A to +70 C 1.9 A to +55 C, 1.3 A to +70 C 15 W 30 W 23 W 50 W 23 W * Remark Output active power / typical Can be connected in Yes parallel to increase the power rating Number of devices that can be connected in parallel to increase the power rating, units 2 Output characteristic See Figure 6-3 Output characteristic (Page 31) LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 29 Technical data 6.2 Output 6EP1352-1SH03 6EP1331-1SH03 6EP1332-1SH43 6EP1332-1SH52 (15 V / 4 A) (24 V / 1.3 A) (24 V / 2.5 A) (24 V / 4 A) 24 V 24 V 24 V Total tolerance, static 3% 3% 3% 3% Static line regulation, approx. 0.1% 0.1% 0.1% 0.1% Static load regulation, approx. 1.5% 1.5% 1.5% 1.5% Residual ripple peakpeak, max. 200 mV 200 mV 200 mV 200 mV Residual ripple peakpeak, typ. 10 mV 10 mV 10 mV 30 mV Spikes peak-peak, max. (bandwidth, approx. 20 MHz) 300 mV 300 mV 300 mV 300 mV Spikes peak-peak, typ. 70 mV (bandwidth, approx. 20 MHz) 20 mV 50 mV 60 mV Setting range 10.5...16.1 V 22.2...26.4 V 22.2...26.4 V 22.2...26.4 V Product function / output voltage can be adjusted Yes Output voltage setting Using a potentiometer Status display Green LED for output voltage OK Response when switching on/off No overshoot of Ua (soft start) Starting delay, max. 0.5 s 0.5 s 0.5 s 0.5 s Voltage rise, typ. 15 ms 15 ms 10 ms 15 ms Rated current Ia rated 4A 1.3 A 2.5 A 4A Current range 0...4 A 0...1.3 A 0...2.5 A 0...4 A 4 A to +55 C, 2.8 A to +70 C 1.3 A to +55 C, 0.9 A to +70 C 2.5 A to +55 C, 1.7 A to +70 C 4 A to +55 C, 2.8 A to +70 C 50 W 30 W 60 W 96 W Output Regulated, isolated DC voltage Rated voltage value Ua rated DC 15 V * Remark Output active power / typical Can be connected in Yes parallel to increase the power rating Number of devices that can be connected in parallel to increase the power rating, units 2 Output characteristic See Figure 6-3 Output characteristic (Page 31) LOGO!Power 30 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Technical data 6.2 Output Figure 6-2 Startup delay/voltage rise Figure 6-3 Output characteristic The device supplies a constant output voltage until the current limit is reached. In the event of an overload, the output current and the output voltage are reduced. The device does not switch off. LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 31 Technical data 6.3 Efficiency and power loss 6.3 Efficiency and power loss 6EP1311-1SH03 Efficiency at Ua rated, Ia rated, approx. 6EP1321-1SH03 6EP1322-1SH03 6EP1351-1SH03 (5 V / 3 A) (5 V / 6.3 A) (12 V / 1.9 A) (12 V / 4.5 A) (15 V / 1.9 A) 79 % 80 % 80 % 84 % 81 % 6W 5W 10 W 7W Power loss at Ua 4W rated, Ia rated, approx. Efficiency at Ua rated, Ia rated, approx. 6EP1311-1SH13 6EP1352-1SH03 6EP1331-1SH03 (15 V / 4 A) 85 % Power loss at Ua 11 W rated, Ia rated, approx. Figure 6-4 6EP1332-1SH43 6EP1332-1SH52 (24 V / 1.3 A) (24 V / 2.5 A) (24 V / 4 A) 84 % 88 % 87 % 6W 8W 12 W Efficiency 6EP1311-1SH03 LOGO!Power 32 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Technical data 6.3 Efficiency and power loss Figure 6-5 Efficiency 6EP1311-1SH13 Figure 6-6 Efficiency 6EP1321-1SH03 Figure 6-7 Efficiency 6EP1322-1SH03 LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 33 Technical data 6.3 Efficiency and power loss Figure 6-8 Efficiency 6EP1351-1SH03 Figure 6-9 Efficiency 6EP1352-1SH03 Figure 6-10 Efficiency 6EP1331-1SH03 LOGO!Power 34 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Technical data 6.3 Efficiency and power loss Figure 6-11 Efficiency 6EP1332-1SH43 Figure 6-12 Efficiency 6EP1332-1SH52 LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 35 Technical data 6.4 Closed-loop control 6.4 Closed-loop control 6EP1311-1SH03 6EP1311-1SH13 6EP1321-1SH03 6EP1322-1SH03 6EP1351-1SH03 (5 V / 3 A) (5 V / 6.3 A) (12 V / 1.9 A) (12 V / 4.5 A) (15 V / 1.9 A) Dyn. mains compensation (Ue rated 15%) 0.2% 0.2% 0.2% 0.2% 0.2% Dyn. load compensation (Ia: 10/90/10%), Ua typ. 3% 3% 3% 4% 2.8% Load step regulation time 10 to 90%, typ. 2 ms 2 ms 1 ms 1 ms 1 ms Load step regulation time 90 to 10%, typ. 2 ms 2 ms 1 ms 1 ms 1 ms 6EP1352-1SH03 6EP1331-1SH03 6EP1332-1SH43 6EP1332-1SH52 (15 V / 4 A) (24 V / 1.3 A) (24 V / 2.5 A) (24 V / 4 A) Dyn. mains compensation (Ue rated 15%) 0.2% 0.2% 0.2% 0.2% Dyn. load compensation (Ia: 10/90/10%), Ua typ. 3% 1% 2% 1.5% Load step regulation time 10 to 90%, typ. 1 ms 1 ms 1 ms 1 ms Load step regulation time 90 to 10%, typ. 1 ms 1 ms 1 ms 1 ms LOGO!Power 36 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Technical data 6.5 Protection and monitoring 6.5 Protection and monitoring 6EP1311-1SH03 6EP1311-1SH13 6EP1321-1SH03 6EP1322-1SH03 6EP1351-1SH03 (5 V / 3 A) (5 V / 6.3 A) (12 V / 1.9 A) (12 V / 4.5 A) (15 V / 1.9 A) 2.8 A 5.8 A 2.7 A 3.6 A 7A 3.6 A Output overvoltage protection Yes, according to EN 60950-1 Current limitation, typ. 3.8 A Property of the output/short-circuit proof Yes Short-circuit protection Constant current characteristic Continuous shortcircuit current / rms value / maximum 5A Output overvoltage protection 8.2 A 10 A 6EP1352-1SH03 6EP1331-1SH03 6EP1332-1SH43 6EP1332-1SH52 (15 V / 4 A) (24 V / 1.3 A) (24 V / 2.5 A) (24 V / 4 A) 3.3 A 5.2 A 4.8 A 7.9 A Yes, according to EN 60950-1 Current limitation, typ. 5.7 A Property of the output/short-circuit proof Yes Short-circuit protection Constant current characteristic Continuous shortcircuit current / rms value / maximum 7A 6.6 1.7 A 2.4 A MTBF 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A) 6EP1332-1SH52 (24 V / 4 A) Mean Time Between Failures According to SN29500 >3500000 h at 40 C, rated load, 24-h operation LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 37 Technical data 6.7 Mechanical system 6.7 Mechanical system 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1332-1SH52 (24 V / 4 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A) Connection system screw-type terminal Connections / line supply L, N: 1 screw terminal each for 0.5 ... 4 (2.5) mm solid (finely stranded) Connections / output +, -: 2 screw terminals each for 0.5 ... 4 (2.5) mm solid (finely stranded) Connections / auxiliary contacts - Width of the housing 54 mm 72 mm 90 mm Height of the housing 90 mm 90 mm 90 mm Depth of the housing 53.1 mm 53.1 mm 53.1 mm Installation width 54 mm 72 mm 90 mm Mounting height 130 mm 130 mm 130 mm Weight, approx. 0.17 kg 0.25 kg 0.34 kg Product feature of the housing / housing that can be lined up next to one another Yes Type of mounting / panel mounting No Type of mounting / rail mounting Yes Type of mounting / S7-300 rail mounting No Mounting Can be snapped onto standard EN 60715 35x7,5/15 mounting rails 6.8 Accessories No accessories. LOGO!Power 38 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Technical data 6.9 Dimension drawing 6.9 Dimension drawing See Section Dimensions and weight (Page 14) CAD data that can be downloaded from the Internet: 6EP1311-1SH03 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00535) 6EP1311-1SH13 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00538) 6EP1322-1SH03 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00544) 6EP1321-1SH03 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00541) 6EP1351-1SH03 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00556) 6EP1352-1SH03 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00559) 6EP1331-1SH03 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00547) 6EP1332-1SH43 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00550) 6EP1332-1SH52 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00553) LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 39 Technical data 6.9 Dimension drawing LOGO!Power 40 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Safety, approvals, EMC 7.1 7 Safety 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A) 6EP1332-1SH52 (24 V / 4 A) Primary/secondary galvanic isolation Yes Galvanic isolation SELV output voltage Ua according to EN 60950-1 and EN 50178 Protection class Class II (without protective conductor) Degree of protection (EN 60529) IP20 Test voltage See Table 7-1 Test voltage (Page 42) LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 41 Safety, approvals, EMC 7.2 Test voltage 7.2 Test voltage Figure 7-1 Test voltage diagram Only the manufacturer can perform the type test and production test; users can also perform the field test. Preconditions for performing the field test: Test (A) Connect the input terminals to one another Connect the output terminals to one another Table 7- 1 Test voltage Type test Production test Field test Test time Prim sec (A) 60 s 4200 VDC 60 s 3000 VAC 1s 2200 VDC 1s 1500 VAC 1s 2200 VDC 1s 1500 VAC Remark: Tripping current for DC measurement: 0 mA Tripping current for AC measurement: <100 mA LOGO!Power 42 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Safety, approvals, EMC 7.3 Certifications 7.3 Certifications Certifications 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1332-1SH52 (24 V / 4 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A) CE marking Yes (2004/108/EG and 2006/95/EG) UL/cUL approval cULus-Listed (UL 508, CSA C22.2 No.107.1), File E197259 cULus-Listed (UL 508, CSA C22.2 No.107.1), File E197259 cURus-Recognized (UL60950, CSA C22.2 No. 60950) File E151273 cURus-Recognized (UL60950, CSA C22.2 No. 60950) File E151273 NEC class2 (acc. to UL 60950/UL 1310) FM Class I, Div. 2, Groups ABCD; T4 CB scheme IEC 60950-1 Explosion protection ATEX II 3G Ex nA IIC T3 cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I, Div. 2, Group ABCD, T4 SEMI F47 compliance 208 - 240 V IEC 61000-4-11 Marine approval Germanischer Lloyd (GL) 6EP1352-1SH52: Cert. No.:24184-04HH All other types: Cert. No.:47994-03HH ABS, DNV, LRS, BV LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 43 Safety, approvals, EMC 7.4 EMC 7.4 EMC 6EP1311-1SH03 (5 V / 3 A) 6EP1332-1SH52 (24 V / 4 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A) Generic standards EN 61000-6-2 Immunity for industrial environments EN 61000-6-3 Emission for residential areas Electrostatic discharges EN 61000-4-2 6 kV contact, 8 kV air 6 kV contact, 8 kV air Electromagnetic fields EN 61000-4-3 80...1000 MHz 10 V/m 80...1000 MHz 10 V/m 1000...2000 MHz 3 V/m 1000...2000 MHz 3 V/m 2000...2700 MHz 1 V/m 2000...2700 MHz 1 V/m High-speed transient disturbance variables (burst) EN 61000-4-4 Power surges EN 61000-4-5 4 kV on line connections 4 kV on line connections 2 kV at DC output 2 kV at DC output 2 kV symmetrical on line connections 2 kV symmetrical on line connections 4 kV asymmetrical on line connections 4 kV asymmetrical on line connections 500 V symmetrical/asymmetrical on DC output cables 500 V symmetrical/asymmetrical on DC output cables High-frequency fields EN 61000-4-6 10 V; 0.15...80 MHz 10 V; 0.15...80 MHz Voltage dips EN 61000-4-11 100% for 20 ms 100% for 20 ms 60% for 200 ms 60% for 200 ms 30% for 500 ms 30% for 500 ms Voltage interruptions EN 61000-4-11 100% for 5000 ms 100% for 5000 ms Emitted interference EN 55022 Class B Class B Not applicable EN 61000-3-2 Line harmonics limitation LOGO!Power 44 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 8 Ambient conditions 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A) 6EP1332-1SH52 (24 V / 4 A) Ambient temperature -20...+70 C with natural convection Tested according to: Transport and storage temperature * EN 60068-2-1 cold * EN 60068-2-2 dry heat * EN 60068-2-78 humid heat, constant * EN 60068-2-14 temperature change -40 ... +85 C Tests (packed for shipping) according to: * EN 60068-2-1 cold * EN 60068-2-2 dry heat * EN 60068-2-30 humid heat, cyclic Humidity class Climate class 3K3 according to EN 60721, without condensation Degree of pollution 2 Mechanical stressing in operation Tested according to: * * EN 60068-2-6 vibration, test Fc - 7 mm deflection in the range 5...9 Hz - 2 g acceleration in the range 9...150 Hz EN 60068-2-27 shock, test Ea - Acceleration 150 m/s2, test duration 11 ms LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 45 Ambient conditions 6EP1311-1SH03 (5 V / 3 A) 6EP1311-1SH13 (5 V / 6.3 A) 6EP1321-1SH03 (12 V / 1.9 A) 6EP1322-1SH03 (12 V / 4.5 A) 6EP1351-1SH03 (15 V / 1.9 A) 6EP1352-1SH03 (15 V / 4 A) 6EP1331-1SH03 (24 V / 1.3 A) 6EP1332-1SH43 (24 V / 2.5 A) 6EP1332-1SH52 (24 V / 4 A) Damaging gases Atmospheric pressure Tested according to: * EN 60068-2-42Sulfur dioxide: 10 cm3/m3, 4 days * EN 60068-2-43Hydrogen sulfide: 1 cm3/m3, 4 days Operation: * 1080 ... 795 hPa (-1000 ... +2000 m) * For operation at altitudes of 2000 m up to 6000 m above sea level: output must be derated by -7.5% / 1000 m or the ambient temperature must be reduced by 5 K / 1000 m see Figure 4-2 Mounting height derating (Page 19) Overvoltage category: III up to 2000 m (EN 50178) II from 2000 m up to 6000 m (EN 50178) Storage: * * 1080 ... 660 hPa (-1000 ... +3500 m) LOGO!Power 46 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 9 Applications 9.1 Parallel connection to increase power rating To enhance performance, two LOGO!Power power supplies of the same type can be galvanically connected in parallel. The following must be observed: The cables connected to each power supply at terminals "+" and "-" must have identical lengths and the same cable cross-sections (or the same impedance) up to a common external network junction (terminal strip) if possible. The parallel-switched power supplies must be switched on simultaneously with a common switch in the mains supply line (e.g. with the main switch available in control cabinets). The output voltages measured in no-load operation for the power supplies that are not yet connected in parallel should not deviate more than a maximum of 0.2%. This usually corresponds to the factory setting. If the output voltage is changed, you should connect the "-" terminals and then, in no-load operation, measure the voltage difference between the "+" terminals that have not yet been connected. The voltage difference should not exceed 0.2%. Figure 9-1 Parallel connection, correct and incorrect LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 47 Applications 9.1 Parallel connection to increase power rating NOTICE Protective circuit for the parallel connection of more than two power supplies For connection of more than two power supplies in parallel, additional measures must be taken to prevent high backward feeding currents in the event of a secondary device fault. For this purpose, a suitable protective circuit (e.g. decoupling diode or DC-conform circuit-breaker) must be installed between each "+" terminal of the power supply and the common connection point. LOGO!Power 48 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Applications 9.2 Parallel connection for redundancy 9.2 Parallel connection for redundancy The parallel switching of several LOGO!Power power supplies of the same type for redundancy is required when the demands for reliability of the supply are particularly high. If a component in the redundant supply fails, the power supply for the loads must be fully accommodated by the remaining component. It is therefore important when dimensioning the system to make sure that n+1 redundant switched power supplies can handle the total power requirement of the remaining n power supplies. To prevent loading of the remaining power supplies in the event of a secondary-side error when one power supply fails, the respective "+" terminals of the power supplies must be decoupled via diodes. Note For a high reliability of the supply, it is recommended that the redundant switched power supplies are fused separately on the line-side and, if possible, be connected to different power supply networks. Figure 9-2 Parallel connection for redundancy LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 49 Applications 9.3 Series connection for increased voltage 9.3 Series connection for increased voltage To achieve a higher output voltage, two LOGO!Power power supplies of the same type can be connected in series. In this case, connect the "-" terminal of the first power supply to the "+" terminal of the second power supply. The "+" terminal of the first power supply and the "-" terminal of the second power supply are routed to the load. Depending on grounding point of the secondary output voltage, voltages of +2xUA, UA or 2xUAcan be implemented. In the case of asymmetric load distribution, it is not possible to ensure correct functionality. WARNING SELV is not guaranteed in the case of a fault When connecting two power supplies in series, the continuous, permissible SELV voltage of a maximum of 60 VDC according to EN 60950 cannot be guaranteed in the case of a fault. Figure 9-3 Series connection LOGO!Power 50 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Applications 9.4 Protection against short-time voltage dips 9.4 Protection against short-time voltage dips During a drop in the primary-side supply voltage, the LOGO!Power power supplies still maintain the output voltage over a short millisecond period (see Section Technical data (Page 27)). LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 51 Applications 9.4 Protection against short-time voltage dips LOGO!Power 52 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Environment 10 The device is in conformance with RoHS. As a rule, only non-silicon precipitating materials are used. Disposal guidelines Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as domestic refuse. LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 53 Environment LOGO!Power 54 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 Service and support 11 Technical support Technical support for all IA/DT products can be accessed through the following communication channels: Phone: + 49 (0) 911 895 7222 E-Mail (mailto:support.automation@siemens.com) Internet: Online support request form (http://www.siemens.de/automation/support-request) Technical documentation on the Internet Operating instructions and manuals for SITOP are available in the Internet: Operating instructions/manuals (http://www.siemens.de/sitop/manuals) SITOP power supply homepage General news about our power supplies is available in the Internet at the SITOP homepage: SITOP (http://www.siemens.de/sitop) Information material SITOP information can be downloaded from the Internet: Information and download center (http://www.siemens.de/sitop-infomaterial) CAx data 2D/3D data and circuit diagram macros can be downloaded from the Internet: Siemens image database (http://www.siemens.de/sitop-cax) Request all CAx data via the CAx download manager: CAx shopping cart (http://www.siemens.de/cax) SITOP Selection Tool Simply and quickly select the optimum the power supply or DC-UPS: SITOP Selection Tool (http://www.siemens.de/sitop-selection-tool) Online catalog and ordering system The online catalog and the online ordering system are available through the Industry Mall homepage: Industry Mall (http://www.siemens.com/industrymall/de) LOGO!Power Operating Instructions, 06.2014, C98130-A7560-A999-3-7629 55 Service and support Contact persons If you have any questions regarding the use of our products, then contact the Siemens contact person in your regional Siemens sales office. You can find these addresses as follows: On the Internet (http://www.siemens.de/automation/partner) In Catalog CA 01 LOGO!Power 56 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629