Immunity to Environmental Conditions
Test method Standard Test Conditions Status
Cab Damp heat steady state IEC/EN 60068-2-78
MIL-STD-810D section 507.2
Temperature: 40 ±2 °C
Relative humidity: 93 +2/-3 %
Duration: 56 days
Converter not operating
Kb Salt mist, cyclic (sodium
chloride NaCl solution) IEC/EN 60068-2-52
Concentration: 5% (30°C) for 2 hours
Storage: 40°C, 93% rel. humidity for 22 hours
Number of cycles 3 (= 3 days)
Converter not operating
Eb Bump (half-sinusoidal) IEC/EN 60068-2-29
MIL-STD-810D section 516.3
Acceleration amplitude: 25 gn = 245 m/s2
Bump duration: 11 ms
Number of bumps: 6000 (1000 in each direction)
Converter operating
Fc Vibration (sinusoidal) IEC/EN 60068-2-6
MIL-STD-810D section 514.3
Acceleration amplitude: 0.35 mm (10 – 60 Hz)
5 gn = 49 m/s2 (60 - 2000 Hz)
Frequency (1 Oct/min): 10 – 2000 Hz
Test duration: 7.5 hours (2.5 hours in each axis)
Converter operating
Ea Shock (half-sinusoidal) IEC/EN 60068-2-27
MIL-STD-810D section 516.3
Acceleration amplitude: 50 gn = 490 m/s2
Bump duration: 11 ms
Number of bumps: 18 (3 in each direction)
Converter operating
-- Shock EN 50155 / EN 61373 sect. 10,
class A and B body mounted ➀
Acceleration amplitude: 5.1 gn
Bump duration: 30 ms
Number of bumps: 18 (3 in each direction)
Converter operating
Fda Random vibration wide
band Reproducibility high
IEC/EN 60068-2-35
DIN 40046 part 23
Acceleration spectral density: 0.05 gn2/Hz
Frequency band: 20 – 500 Hz
Acceleration magnitude: 4.9 gn rms
Test duration: 3 hours (1 hour in each axis)
Converter operating
--
Simulated long life testing
at increased random vibra-
tion levels
EN 50155 / EN 61373 sect. 9,
cat 1, class B, body mounted ➀
Acceleration spectral density: 0.02 gn2/Hz
Frequency band: 5 – 150 Hz
Acceleration magnitude: 0.8 gn rms
Test duration: 15 hours (5 hours in each axis)
Converter operating
➀ Body mounted = chassis of a railway coach
Technical Notes
Start-Up Threshold and Undervoltage Shutdown
Under normal start-up conditions, the UCR Series will not begin to regulate
properly until the ramping input voltage exceeds the Start-Up Threshold.
Once operating, devices will turn off when the applied voltage drops below
the Undervoltage Shutdown point. Devices will remain off as long as the
undervoltage condition continues. Units will automatically re-start when the
applied voltage is brought back above the Start-Up Threshold. The hysteresis
built into this function avoids an indeterminate on/off condition at a single input
voltage. See Performance/Functional Specifi cations table for actual limits.
Start-Up Time
The VIN to VOUT Start-Up Time is the interval between the point at which a
ramping input voltage crosses the Start-Up Threshold voltage and the point at
which the fully loaded output voltage enters and remains within its specifi ed
1% accuracy band. Actual measured times will vary with input source imped-
ance, external input capacitance, and the slew rate and fi nal value of the input
voltage as it appears to the converter. The On/Off to VOUT start-up time assumes
that the converter is turned off via the Remote On/Off Control with the nominal
input voltage already applied.
On/Off Control
The primary-side, Remote On/Off Control function is off when On/Off is high/
open and on when On/Off is pulled low or grounded. See Figure 4.
Dynamic control of the remote on/off function is best accomplished with a
mechanical relay or an open-collector/open-drain drive circuit (optically iso-
lated if appropriate). The drive circuit should be able to sink appropriate current
(see Performance Specifi cations) when activated and withstand appropriate
voltage when deactivated.
Current Limiting
When power demands from the output falls within the current limit inception
range for the rated output current, the DC-DC converter will go into a current
limiting mode. In this condition the output voltage will decrease proportionately
with increases in output current, thereby maintaining a somewhat constant
power dissipation. This is commonly referred to as power limiting. Current
limit inception is defi ned as the point where the full-power output voltage
falls below the specifi ed tolerance. If the load current being drawn from the
converter is signifi cant enough, the unit will go into a short circuit condition.
See “Short Circuit Condition.”
UCR100 Series
3U High Reliability DC-DC Converters
MDC_UCR100.C02 Page 16 of 20
www.murata-ps.com/support