SIMAT IC NET
Produktinformation
Product Information Ausgabe/Rel ease 07/2001
CP 5613 (DP-Base)
CP 5614 (DP-Base)
CP 5613 FO (D P-Bas e)
CP 5614 FO (D P-Bas e)
DP-5613/Windows
FMS-5613/Windows
S7-5613/Windows
6GK1561-3AA00
6GK1561-4AA00
6GK1561-3FA00
6GK1561-4FA00
6GK1713-5DB60-3AA0
6GK1713-5FB60-3AA0
6GK1713-5CB60-3AA0
Nachfolgend fi nden S ie Informationen i n deutscher Sprac he.
This document c ontains inf ormation in English.
S79220-A5814-X-01-7437
© SIEMENS AG 2001
Änd erun g en vorbehalten
Subject to change
Si em ens Aktiengesellschaft
S79220-A5814-X-01-7437
Sprachenverzeichnis
Language Versions
Pro duktinf ormation, deutsch, S79220-A5424-X-02-7419...........Seite 3
Product Information, English, S79220-A5424-X-02-7419 ..........Page 53
Anhang
OPC-Server für SIMATIC NET, deutsch
OPC-Server for SIMATIC NET, English
S79220-A5790-X-01-7437
2
3
SIMAT IC NET
Produktinformation
Ausgabe 07/200 1
CP 5613 (DP-Base)
CP 5614 (DP-Base)
CP 5613 FO (D P-Bas e)
CP 5614 FO (D P-Bas e)
DP-5613/Windows
FMS-5613/Windows
S7-5613/Windows
6GK1561-3AA00
6GK1561-4AA00
6GK1561-3FA00
6GK1561-4FA00
6GK1713-5DB60-3AA
0
6GK1713-5FB60-3AA
0
6GK1713-5CB60-3AA
0
Nachfolgend fi nden S ie Informationen i n deutscher Sprac he.
S79220-A5814-X-01-7437
© SIEMENS AG 2001
Änd erun g en vorbehalten
Si em ens Aktiengesellschaft
deutsch
S79220-A5814-X-01-7437
Copyright Siemens AG 2001, All rights reserved
Weiter
g
abe sowie Vervielfälti
g
un
g
dieser Unterla
g
e, Verwertun
g
und
Mitteilun
g
ihres Inhalts ist nicht
g
estattet, soweit nicht ausdrücklich
zu
g
estanden. Zuwiderhandlun
g
en verpflichten zu Schadensersatz.
Alle Rechte vorbehalten, insbesondere für den Fall der
Patenterteilung oder GM-Eintragung.
Haftungsausschluss
Wir haben den Inhalt der Druckschrift auf Übereinstimmung mit der
beschriebenen Hard- und Software geprüft. Dennoch können
Abweichungen nicht ausgeschlossen werden, so dass wir für die
vollständige Übereinstimmung keine Gewähr übernehmen. Die
Angaben in dieser Druckschrift werden regelmäßig überprüft und
notwendige Korrekturen sind in den nachfolgenden Auflagen
enthalten. Für Verbesserungsvorschläge sind wir dankbar.
Siemens AG
Bereich Automatisierungs- und Antriebstechnik
Geschäftsgebiet Industrie-Automatisierungssysteme
Postfach 48 48, D-90327 Nürnberg
S79220-A5814-X-01-7437
© Siemens AG 2001
Technische Änderungen vorbehalten.
Siemens Aktiengesellschaft Printed in the Federal Republic of Germany 4
Klassifizierung der Sicherheitshinweise
Dieses Dokum ent enthält Hinweise, di e Si e z u Ihrer per sönl ichen Si c her heit sowi e z ur
Vermeidung von S ac hschäden beachten müssen. Die Hinweise si nd dur c h ein Warndr ei-
eck hervorgehoben und je nach G efährdungsgrad folgendermaßen dar gestellt :
!Gefahr
bedeutet , dass Tod, schwere Körperverletzung ei ntreten wird, wenn die ent sprechenden
Vorsic htsmaßnahmen nicht get r offen werden.
!Warnung
bedeutet , dass Tod, schwere Körperverletzun
g
eintreten kann, wenn die entsprechenden
Vorsic htsmaßnahmen nicht get r offen werden.
!Vorsicht
mi t Warndrei ec k bedeutet, dass eine l eic hte Körperverletzung eintr eten kann, wenn die
entsprechenden Vorsi c htsmaßnahmen nicht getr off en werden.
Vorsicht
ohne Warndreiec k bedeutet, dass ein Sachschaden eintr eten kann, wenn die entspre-
chenden Vorsi c htsmaßnahmen nicht getr off en werden.
Achtung
bedeutet , dass ein uner wünscht es Ergebnis oder Zustand eint r eten kann, wenn der ent-
sprechende Hinweis nic ht beacht et wird.
Hinweis
ist eine wichtige Information über das Produk t, die Handhabung des Produktes oder den
jeweiligen T eil der Dok um entation, auf den besonders aufmerk sam gemac ht werden soll
und deren Beachtung wegen ei nes mögli c hen Nutzens empfohlen wi r d.
Produktinformation/Product Information CP (DP-Base), DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 5
Marken
SIMATIC, SIMATIC NET, SINEC und SIMA TI C NET Networking for Industry ® sind
eingetragene Mar k en der Si em ens AG .
Die übr igen Bezei c hnungen in dieser Schrift können M ar k en sei n, deren B enutzung
durch Dritte für deren Zwecke die Rechte der Inhaber verletzen k önnen.
Sicherhe itstechnische Hinweise zu Ihrem Produkt
Bevor Sie das hier beschriebene Pr oduk t einsetzen, beac hten Sie bit te unbedingt die
nachfolgenden sic her heit stec hnischen Hi nweise.
Qualifiz iertes Personal
Inbet r iebsetzung und B etrieb eines Gerätes dürfen nur von qualifizier tem Personal v or -
genommen werden. Qualifi zi er tes Personal im Si nne der si c her heitstechnischen Hi nwei-
se dieses Handbuc hs si nd P er sonen, die die Berec htigung haben, Geräte, Systeme und
Str om k r eise gemäß den Standards der Si c her heit stec hnik in B etrieb zu nehmen, z u er-
den und zu kennzeichnen.
Bestimmungsgemäßer Gebrauch von Hardware-P rodukten
Beacht en S ie bitte folgendes zum bestimmungsgem äßen Gebrauch v on Har dwarepro-
dukten:
Vorsicht
Das Gerät darf nur für die im Kat alog und in der technischen Beschreibung vorgesehe-
nen Ei nsatzfälle und nur in Verbi ndung mi t von Si em ens empfohlenen bz w. zugelasse-
nen Frem dger äten und -kom ponenten verwendet werden.
Der ei nwandfreie und sicher e Betrieb des Produkt es setzt sachgemäß en Transport ,
sachgemäße Lagerung, A ufstell ung und M ontage sowi e sorgfälti ge B edienung und In-
standhaltung voraus.
Bevor Sie mit geliefert e Bei spi elprogr amme oder sel bst er stellt e P r ogr amme anwenden,
stellen Sie si c her, dass in laufenden A nlagen k eine Schäden an Personen oder Maschi-
nen entstehen können.
EG?Hinweis: Die Inbetri ebnahme ist so l ange untersagt, bis festgestellt wurde, das s di e
Maschine, i n die diese Komponente ei ngebaut werden soll, den Bestim m ungen der
Ric htlini e 89/392/EWG ent spricht.
Produktinformation/Product Information CP (DP-Base), DP-, FMS- und S7-5613/Windows
6S79220-A5814-X-01-7437
Bestimmungsgemäßer Ge brauch von Software-Produkten
Beachten Sie folgendes zum bestimmungsgemäßen Gebrauch v on Soft ware-Produkten:
Vorsicht
Die S oft ware darf nur für die im Kat alog und in der technischen Beschreibung vorgese-
henen Ei nsatz fälle und nur in Ver bindung m it von Siemens empfohlenen bzw. zugelas-
senen Sof tware-Produkten, Fremdger äten und -komponent en ver wendet werden.
Bevor Sie mit geliefert e Bei spi elprogr amme oder sel bst er stellt e P r ogr amme anwenden,
stellen Sie si c her, dass in laufenden A nlagen k eine Schäden an Personen oder Maschi-
nen entstehen können.
Vor der Inbetriebna hme
Beachten Sie vor der Inbetriebnahme folgende Warnung:
Vorsicht
Vor der Inbetriebnahme sind die Hinweise in der entsprechenden akt uellen Dokumentat i-
on zu beacht en. Die Bestelldaten hierfür entnehmen Sie bitt e den K atalogen, oder wen-
den Si e si c h an Ihre ört liche Si em ens-G eschäf tsstelle.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 7
Inhaltsverzeichnis
1 Einleitung....................................................................................................................9
2 Lieferumfang.............................................................................................................14
3 Vora us s e t zungen und Eins chrä nk u ngen ................................................................16
3.1 Voraussetz ungen und E inschränkungen für die Har dware ..............................16
3.2 Voraussetz ungen und E inschränkungen für die S oft ware................................17
4 CP 5613/CP 5614 (DP - Base) .....................................................................................18
4.1 Ausgangssi tuation nach der Install ation..........................................................18
4.2 Star t des einf achen Beispielprogr am ms..........................................................19
4.3 Star t des ausführlichen Bei spi elprogr amms ....................................................21
4.4 Start des „Fast Logic“-Beispiel programm s.......................................................23
4.5 Start des Transfer-Beispiel programm s für CP 5614 ........................................25
4.6 Konfiguration des Transfers für das CP 5614 Transfer-Bei spi elprogramm.......28
5 DP-5613/Windows.....................................................................................................30
5.1 Eigenschaften.................................................................................................30
5.2 Prüf ung und K onfi gur ation von DP-5613/Windows..........................................31
5.3 Ausgangssi tuation nach der Install ation bei DP...............................................32
6 FMS-5613/Windows ..................................................................................................33
6.1 Eigenschaften.................................................................................................33
6.2 Ausgangssi tuation nach der Install ation..........................................................34
7 S7-5613/Windows .....................................................................................................35
7.1 Eigenschaften.................................................................................................35
7.2 Ausgangssi tuation nach der Install ation..........................................................36
8 PG-Betrieb mit STEP 5/STEP 7.................................................................................37
9 F AQ (Frequen tl y Asked Quest ions).........................................................................38
9.1 FAQ zu K ommunikati onsei genschaften des Produkt s .....................................38
9.1. 1 Welche Soft ware-Ver si onen gibt es, und wie unterschei den si e si c h?.............38
9.2 Fragen z u technischen Daten .........................................................................41
9.2. 1 Fragen zu technischen Daten der Sof tware-Produkte......................................41
9.2. 2 Fragen z u den technischen Daten des CP 5613/ CP 5614...............................45
10 Hinweise zur CE-Kennzeichnung von SIMATIC NET-Produkten ............................47
11 Glossar......................................................................................................................49
12 Stichwortverzeichnis................................................................................................52
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
8S79220-A5814-X-01-7437
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 9
1 Einleitung
Kommunikationsprozessor SIMATIC NET CP 5613 und CP 5614
Vi elen Dank , dass Sie sich für SIMATIC NET CP 5613/CP 5614 entschieden ha-
ben. Sie haben ein Pr oduk t gekauft, das auf innovative Wei se einen sehr schnellen
S7-, DP - und FMS-Zugang mit l eic hter Install ation verbindet.
Zweck dieses Dokuments
Si e er halten Informationen über das Produk t. Weit er er gänz t dieses Dokument die
HTML- Dok um ention „I ndustr ielle Kommunikati on für PG/PC“ .
Gültigkeitsbereich dieser Produktinformation/ Insta l lationsanleitung
Dieses Dokum ent i st für folgende Hardware-Ausgabestände gültig:
Bezeichnung Hardware-Ausgabestand
CP 5613> 4
CP 5614> 4
CP 5613 FO> 2
CP 5614 FO> 2
Produktdokumentation
Themen z ur Nutzung des vorliegenden Pr oduk ts finden Sie in folgenden Informati -
onsquellen:
Zugehörige Papierdokumentation
Int egr ierte Hilfe (Taste F1) der Software
Text- und PDF- Dateien der SIMATIC NT-CD
HTML-Dokument „Industrielle Kommunikation für PG/PC“
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
10 S79220-A5814-X-01-7437
Dokumentationsübersicht
Für dieses Produkt gliedert sich die Dokumentation wie f olgt:
Hardw are ( Kommunikati on sbaugruppen )
Produktinformation/Installationsanleitung
Beschrei bt di e Installation der CP 5613/CP 5614-K ommunikationsbaugruppen.
Sof tw are ( S IMATIC NET-Produkte)
Liesmich-Dateien
Produktinformation
Gibt Hinweise auf das Produk t.
Installationsanleitung der Software
Beschrei bt di e Installation der SIM ATIC NET-Produkt e im PG/PC.
HTML-Dokument „Industrielle Kommunikation für PG/PC“
Enthält folgende Themen:
Grundlagen der industriellen Kommun ikation mit OPC
Inbetriebnahme des Produk ts mit Hilfsprogrammen
Konfi gur ation der installi ert en P r oduk te
OPC-Pr ogr ammierung und Beispi elprogr amme
SIMATIC NET-CD
Die gesamte SIMATI C NET- Dok um entation befindet si c h auf den CDs v on
SIMATIC NET:
Produkt-CD 07/ 2001 „ S IMA TI C NET Networki ng for Industry®
(CD beil iegend)
Dokumentations-CD 07/2001 „S IMATI C NET Manual Coll ec tion“
(CD beil iegend)
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 11
Automation and Drives, Service & Support
Der Service & Support v on A&D ist welt weit jederzeit erreic hbar .
Die S pr ac hen si nd gener ell Deut sch und Englisch,
bei der A utorisier ungs-Hot line wird z usätz lich Franz ösi sch, It alienisch und
Spani sch gesprochen.
Technical Support Autorisierungs-Hotline
Europa und A frika (Nürnberg)
Mo . bis F r . 7 :00 bis 17:00 U hr ( O rts zeit, GMT +1 )
Telefon: +49 - (0) 180 - 5050 - 222
Fax: +49 - (0) 180 - 5050 - 223
E-Mail: techsupport@ad.siemens.de
Europa und A frika (Nürnberg)
Mo . bis F r . 7 :00 bis 17:00 U hr ( O rts zeit, GMT +1 )
Telefon: +49 - (0) 911 - 895 - 7200
Fax: +49 - (0) 911 - 895 - 7201
E-Mail: authorization@nbgm.siemens.de
Amerika ( Johnson City)
Mo . bis F r . 8 :00 bis 19:00 U hr ( O rts zeit, GMT -5)
Telefon: +1 - (0) 423 - 262 - 2522
Fax: +1 - (0) 42 3 - 26 2 - 2231
E-Mail: simatic.hotline@sea.siemens.com
Asien und Australien (Singapur)
Mo . bis F r . 8 :30 bis 17:30 U hr ( O rts zeit, GMT +8 )
Telefon: +65 - ( 0) 740 - 7000
Fax: +65 - (0) 740 - 7001
E-Mail: simatic.hotline@sae.siemens.com.sg
SIMATIC Premium-Hotline
Weltweit (Nürnberg)
an We rktage n
0:00 bis 24:00 Uhr (Ortszeit , GMT +1)
Telefon: +49 - (0) 911 - 895 - 7777
Fax: +49 - (0) 911 - 895 - 7001
E-Mail: techsupport@ad.siemens.de
schnel l er Rückruf,
garantier t inn erhalb von max. 2 Stun den
(kostenpflichtig, nur mit SIMATIC Card)
Johnson Cit y Nürnberg
SingapurSingapur
Service & S up po rt
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
12 S79220-A5814-X-01-7437
Service & Support im Interne t
Im World Wide Web finden Sie tagesaktuelle Informationen zum gesamten
SIM ATIC-Produkt ber eich, z. B. Antworten auf oft gestellte Fragen (FAQ ), Tipps
und Tric k s, S oft ware-Updat es und Anwenderinform ationen.
Neben diesen kostenl osen Informationen können Sie aus den kostenpflichtigen
Bereichen direk t beziehen:
Handbücher
Software-Produkte
Beispielanwendungsprogramme
Al s Zahlungsmittel dient die SIM ATIC CARD.
Die Nutzung erfolgt über das Int er net:
http://www.ad.siemens.de/support
Si e k önnen Ihre Frage an den SIMATIC-Knowledge-Manager formulieren, der aus
der Wissensd atenbank die passende Lösung herausf ilt er t.
Für Ei nsatz ber eiche, die über keinen Online-Anschluss verfügen, steht ein Abzug
des kostenfr eien Informationsbereiches auf der CD „SI MATIC Customer Support
Knowledge Base“ zur Verfügung.
Hinweis
Bi tt e halten Sie beim Anruf die folgenden Inform ationen bereit :
Herstel ler und Typ Ihres Rechners
Ihre Betriebssystemversion
BIOS-Version
Weitere im PC gesteckte Baugruppen
Software Version
Die V er si on der SIM ATIC NET PC-Software-Produk te wird I hnen im Star tmenü
angezeigt.
Zum Beispiel erhalten Sie bei der V er si on 6.0 Build 1400 den Eintrag
„SI M ATIC NET-PC-Soft ware V6. 0 B uild 1400“ ( Star t-Leiste Start Sys-
temsteuerung Software SIMATI C NET- P C-So f t ware V6.0 Build 1400).
Ausgabestand des CP
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 13
Ansprechpartner
Soll ten Sie in den angegebenen I nformationsquellen keine Antworten auf techni-
schen Fragen zur Nutzung der beschriebenen Software erhalt en, wenden Sie sic h
bitte an Ihren Si em ens-Ansprechpar tner in den für Si e zuständi gen V er tretungen
oder Geschäftsstellen.
Die A dr essen fi nden S ie:
in der Datei „LIESMI CH.RTF“ im Hauptv er z eic hnis der SIMATI C NT-CD
im Int er net (http://www.ad. si emens.de/net)
in unserem Katalog IK PI
Training für SIMATIC NET
Ansprechpart ner für Kur sanmeldungen:
Siemens AG
Trainings-Center für Automatisierungs- und Antriebstechnik
A&D PT 49 Kursbüro
Östliche Rheinbrück enstr e 50
76181 Karlsruhe
Telefon: +49 - ( 0) 721 - 595 - 2917
Fax: +49 - ( 0) 721 - 595 - 6087
Internet: http://www.ad.siemens.de/training
Zertifizierung
Die P r oduk te v on S IMATIC NET werden unter Anwendung eines von DQS zertifi -
zi er ten Qualität smanagement nac h DIN ISO 9001 (Z er tifikat- Register - Nr . 2613)
hergestel lt und v ert ri eben. Das DQS-Zertifik at ist in allen IQNet - Länder n aner k annt
(Reg. No. 2613).
Normen und Zulassungen
Die K ommunikati onsprozes sort y pen CP 5613, CP 5613 FO, CP 5614, CP 5614 FO
erfüllen die Anforderungen zur CE-Kennzeichnung. Ebenso l iegen die Zulassun-
gen für CSA und UL v or .
Ausf ühr liche A ngaben z u den Zulassungen und Normen f inden Sie im Anhang
„Hinweise zur CE-Kennzeichnung von SIMATIC NET-Produkten“.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
14 S79220-A5814-X-01-7437
2 Lieferumfang
Auflistung
Bi tt e pr üfen Sie, ob all e Komponent en v or handen si nd:
Produkti nformati on CP (DP-Base), DP-5613, FMS-5613, S7-5613
Installationsanleitung für alle SIMATIC NET-Software-Produkte
Beschrei bung „ A dvanc ed P C Configurati on“ (Migrationsanleit ung)
Produkt-CD 07/ 2001 „ S IMA TI C NE T Net working for I ndustr y
Dokumentations-CD 07/2001 „S IMATI C NET Manual Collection“
Schlüsseldisket te (für die Produkt e DP - 5613, FMS-5613 und S7-5613)
Software-Produktschein und - V er trag
Zusätzlich enthalten die Produkt e 6GK1713- ... folgende Komponenten:
Ei ne der folgenden Baugruppen:
CP 5613
CP 5614
CP 5613 FO
CP 5614 FO
Produkti nformation/Installati onsanl eit ung dieser Baugr uppe
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 15
CD „SIMATIC NET Industrial Communication PC/Windows“
Die CD „SIMATI C NET Industrial Comm unic ation PC/Windows“ ent hält folgende
Komponenten für CP 5613/CP 5614:
Produkt „ CP 5613/CP 5614 ( DP - Base)
zum Betrieb des CP der DP -Base-Progr am m ierschnittstell e unter Windows NT
und Windows 2000.
Pro du kt DP - 5613/Window s“
zum DP-Mast er-Betrieb eines CP mit der DP-Li b-Programmierschnit t stel le un-
ter Windows NT und Wi ndows 2000 (kompatibel zur DP- Schnittstelle des
CP 5412 (A2)).
P rodukt „FM S - 5613/Window s“
zum FMS-Master-Betrieb des CP unter Windows NT und Windows Professi o-
nal.
Produkt „ S 7- 5613/Window s“
zum S7- B etrieb des CP unt er Windows NT und Windows 20 00 ( k ompatibel zur
S7-Sc hnittstelle des CP 5412 (A2) ) und die P r ojek tierungs-Sof tware
SIMATIC NCM PC.
In allen Produkten enthalten und automati sch mitinstalli er t werden:
Projekti er ungs-Software SI M ATIC NCM PC
Software zum FDL- B etri eb des CP unt er Windows NT und Wi ndows 2000
(kom pati bel zur FDL-Schnittstell e des CP 5412 (A2)) ab Produktversion 2. 0
Software zur Unter stützung der PG- Funkti onalität (Unter stützung von
STE P 5/STEP 7) unter Windows NT und W indows 2000 ab Produk tversi on 2.0
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
16 S79220-A5814-X-01-7437
3 Voraussetzungen und Einschränkungen
3.1 Vo raussetzungen und Einschränkungen für die Hardware
PROFIBUS- Netzwerkkarten
Für den Bet rieb können eine oder m ehrere PROFIBUS-Karten verwendet werden.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 17
3.2 Voraussetzungen und Einschränkungenr die Software
Betriebssysteme
Folgende Bet riebssysteme der Firma Microsoft werden unterstüt z t:
Windows 2000
Windows 2000 Professional M ultil anguage m it dem Service- P ac k 1
Windows 2000 Server Multilanguage mit dem Servi c e- P ac k 1
Windows NT
Windows NT Version 4.0 Wor k station mit dem Servic e- P ac k 6a
Windows NT Version 4.0 Server mit dem Servic e- P ac k 6a
Für Freigaben weit er er S ervice- P acks wend en S ie sic h bitt e an Ihren Siem ens-
Ansprechpartner.
Echtzeitanforderungen
Windows 2000 und Windows NT sind k eine Echtz eitbetri ebssysteme. Ec htzeit an-
forderungen k önnen daher nicht erfüllt werden.
Dadurch kann es bei spi elsweise vorkommen, dass beim Star ten von Programm en
oder Lesen von Dat eien Ihre Anwendung mehrere 100 ms lang nicht ausgeführ t
wird.
Wenn Si e nac hfol gend aufgeführte Hinweise befolgen unter stützen diese Maß-
nahm en die Optimi er ung Ihres Systems Richt ung ec htzeitähnlichem Verhalten:
Genügend Haupt sp eicher , so dass Wi ndows nur selten auf die Auslager ungs-
datei zugreifen muss.
Kei ne intensiven Disketten-, Festpl atten- oder CD-Laufwerkszugrif fe, wi e z . B.
das Start en von großen P r ogr ammen.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
18 S79220-A5814-X-01-7437
4 CP 5613/CP 5614 (DP-Base)
4.1 Ausgangssituation nach der Installation
Auf Festplatte kopierte Daten
Nachfolgend fi nden S ie eine Übersi c ht der für Sie zur Programmierung wichtigen
Verzeichnisse, di e im Inst allationsverzeichnis (z. B. C:\SIEMENS\SIMATIC.NET)
Ihres PC angelegt werden:
Verzeichnis Bemerkung
CP5613_CP5614 Pr oduk ti nformation (l iesmich. txt, readme. txt),
Inf ormati on und Funkti onen z ur Dei nstallati on
CP5613_CP5614\prog Informationen für DP-Programmierer
CP5613_CP5614\examples Beispielprogramme
CP5613_CP5614\ databa se Datenbas en für Beispi elpr ogr amme
CP5613_CP5614\ logf iles Bericht sdateien, di e von Di agnoseprogram men
erzeugt wurden.
CP5613_CP5614\diagnose Diagnoseprogramme
Vorsicht
Löschen Sie die in diesem V er z eic hnis abgel egten Dateien nicht, da die Funkti -
onsfähigkeit anderer P r ogr amme beeintr äc htigt werden könnte.
Zur Deinstallation des Produk ts verwenden Sie gegebenenfall s das von Win-
dows NT/W indows 2000 hier für vorgesehene Systemprogr amm (Star t-Leiste Start
Einstellungen Syst emst euerung Software ).
Hinweis
Beachten Sie bitte, dass der gleichzeitige Einsatz der DP-5613/Windows-Schnitt-
stelle und der DP-Base-Programmierschni ttstelle, die im Produkt
„CP 5613/CP 5614 (DP-Base)“ enthalten ist, auf ei nem CP nicht möglich ist.
Bei de P r oduk te können zwar parallel instal liert werden, aber es dürfen nur Pro-
gramme auf einem CP gl eic hz eitig betri eben werden, die eine dieser Schnit tstell en
benutzen.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 19
4.2 Start des einfachen Beispielprogramms
Zweck des Beispielprogramms „ExamEasy
Neben der Einarbeitung für DP -Pr ogr ammierer k ann das ei nfache Beispi elpro-
gramm auc h v er wendet werden, um die Kommunikation mit ei nem DP-Sl av e z u
testen.
Es setzt einen DP-Sl av e mit mi ndestens ei nem Ei ngangs- und Ausgang sbyt e vor -
aus. Im mitgel ieferten Beispiel-STEP 7-Proj ekt Ex amEasy ist der Slav e als
ET 200B auf Teilnehm er adr esse 3 projek ti ert , die Datenüber tragungsgesch windig-
kei t bet r ägt 1,5 Mbit/s.
Auch wenn mehr er e CP 5613 oder CP 5614 vorhanden sind, ver wendet das Pro-
gramm immer den Zugangspunkt „ CP _L2_1:“.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
20 S79220-A5814-X-01-7437
Vorgehensweise
Gehen Sie wi e fol gt beschrieben vor, um das Beispielprogr am m "Exam E asy" z u
starten:
Schritt Beschreibung
1 St ellen Sie das zum B eispi elprogr amm passende ST E P 7- Projekt
ExamEasy ein.
2 Wenn der anzusprechende Slave keine ET 200B mit der Teil nehm er -
adresse 3 ist oder die Dat enüber tragungsgeschwindi gk eit nicht
1,5 Mbit/s beträgt, dann passen Sie bitt e das STEP 7-Projekt ExamEa-
sy an Ihre Konfigurat ion an.
3Starten Sie das Programm „Exam Easy“ (Start-Leiste Start Simatic
SIMATIC NET CP5613_CP5614 Examp les Easy).
4 Das aktuelle Eingangs- und Ausgangsbyte werden in ei ner DOS-Box
angezeigt.
5Wenn Si e jetzt ei nen ander en Wert für das Ausgangsbyt e eingeben
und die Ei ngabetaste drück en, wird der neue A usgang swert über nom-
m en und das akt uelle Eingangs- und Ausgang sbyt e angez eigt .
Bei einer leer en Ei ngabe wir d das Ausgangsbyte beibehalten und das
aktuelle Eingangs- und Ausg angsbyte angez eigt .
6 Tippen Sie „ q“ und die Eingabet aste, um das Progr amm zu beenden.
Hinweis 1
Die Quellen zum Beispielprogramm finden Sie im Unterverzeichnis
„CP5613_CP5614\Examples\Easy“ Ihres Installati onsverzeic hnisses.
Hinweis 2
Das Beispiel programm belegt den DP-RAM-Poi nter exklusiv. Di e Schnittstell e er-
laubt nicht den parallelen Betri eb einer zweiten DP-Anwendung falls der Pointer
v on den A pplik ationen ni c ht wechselseitig freigegeben wir d.
Ergebnisse
Im Fehlerfall gibt das Progr amm Meldetext e aus.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 21
4.3 Star t de s aus hr l i ch en B ei spielpr o gr am m s
Zweck des Beispielprogramms „ExamComp“
Neben der Einarbeitung für DP -Pr ogr ammierer k ann das ausf ühr liche B eispi elpro-
gramm auc h v er wendet werden, um die Kommunikation mit bi s zu drei DP-Slave
zu testen.
Auch wenn mehr er e CP 5613 oder CP 5614 vorhanden sind, ver wendet das Pro-
gramm immer den Zugangspunkt „ CP _L2_1:“.
Es setzt als Konfigurati on die dr ei folgenden Slaves voraus, wobei aber einer oder
zwei weggel as sen werden können:
Slave-
Adresse Konfiguration Projektiert als
3 1 Eingangsbyte, 1 A usgangsbyte ET 200 B 8DI/DO
4 1 Eingangsbyte, 1 A usgangsbyte ET 200 B 8DI/DO
6 Ein beli ebiger Norm-Slav e
Die ak tuell e Konfigur ation di eses Slaves
wird mit der Funktion DP_get _ac tual _cfg
ausgelesen.
ET 200 M IM153
Die Datenübert r agungsge schwindi gk eit betr ägt 1,5 Mbit/s.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
22 S79220-A5814-X-01-7437
Vorgehensweise
Gehen Sie wi e fol gt beschrieben vor, um das Beispielprogr am m ExamComp“ zu
starten:
Schritt Beschreibung
1 St ellen Sie das zum B eispi elprogr amm passende ST E P 7- Projekt
ExamComp als zu verwendendes STE P 7-Pr ojekt ein.
2 Wenn die Proj ektier ung nicht zu den anz usprechenden S laves oder zu
der tatsächlic hen Datenübert r agungsg eschwindi gk eit passt, dann pas-
sen Sie bitte das ST EP 7-Projekt ExamComp an Ihre Konfiguration an.
3Star ten Sie das Bei spi elpr ogr amm „ExamCom p“ (St ar t-Leiste Start
Simat ic SIMATIC NET CP5613_CP 5614 E xampl es
Complete).
4 Das Programm bietet verschi edene M odi z ur A uswahl an. Wählen Sie
einen M odus oder eine beli ebige Kom bination dieser Modi aus (z. B.
„12“ f ür den gleichz eitigen Betrieb der Modi 1 und 2).
5Das Programm kommuniziert jetzt über die ausgewählt en M odi mit den
entsprechenden Slaves. Drücken Sie wiederholt die Ei ngabetaste, um
den aktuellen Status anzuzeigen.
6 Tippen Sie „ q“ und die Eingabet aste, um das Progr amm zu beenden.
Hinweis 1
Die Quellen zum Beispielprogramm finden Sie im Unterverzeichnis
„CP5613_CP5614\Examples\Complete“ Ihres Installationsverzeic hnisses.
Hinweis 2
Das Beispiel programm belegt den DP-RAM-Poi nter exklusiv. Di e Schnittstell e er-
laubt nicht den parallelen Betri eb einer zweiten DP-Anwendung falls der Pointer
v on den A pplik ationen ni c ht wechselseitig freigegeben wir d.
Ergebnisse
Für jeden der dr ei Sl aves werden die aktuell en Daten ausgegeb en bz w. T exte im
Fehlerfall.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 23
4.4 Star t de s „Fas t Lo gi c“-Beispielprogram ms
Zweck des Beispielprogramms „ExamFast“
Mit dem Beispiel programm „ExamFast“ wi rd die „Fast Logic“-Funktionalität des DP-
Masters erklärt . Sie lernen die Funktionen DP_f ast_logic_on, DP_fast_l ogic _off
und den Um gang mi t F ast- Logic-Sem aphor en k ennen.
Wenn m ehr er e CP 5613 oder CP 5614 v or handen si nd, kann bei Pr ogr ammstart
der zu ver wendende CP ausge wählt werden. Als Fast-Logic-ID wird immer die I D 2
verwendet.
Es setzt als Konfigurati on die z wei folgenden Slaves voraus:
Slave Kon fi gu rat ion Projekti ert als
1 1 Eingangsbyte, 1 A usgangsbyte ET 200 B 8DI/8DO, Adresse 3
2 1 Eingangsbyte, 1 A usgangsbyte ET 200 B 8DI/8DO, Adresse 4
Die Datenübert r agungsge schwindi gk eit betr ägt 1,5 Mbit/s.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
24 S79220-A5814-X-01-7437
Vorgehensweise
Gehen Sie wi e fol gt beschrieben vor, um das Beispielprogr am m ExamFast“ zu
starten:
Schritt Beschreibung
1 Stellen Sie bitte das zum Beispielprogramm passende STEP 7-Projekt
ExamFast al s zu verwendendes STE P 7- B eispielpr ojekt ein.
2 Wenn die Proj ektier ung nicht zu den anz usprechenden S laves oder zu
der tatsächlic hen Datenübert r agungsg eschwindi gk eit passt, dann än-
dern Sie bitte das STEP 7-Projekt Ex amFast.
3Star ten Sie das Bei spi elpr ogr amm „ExamFast“ (Start- Leiste Start
Simat ic SIMATIC NET CP5613_CP 5614 E xampl es
FastLogic).
4 Das Programm fordert den Benutzer auf, das Fast-Logic-Ereigni s zu
provozieren. Um das Fast-Logic-Ereignis auszul ösen, muss für den
Sl av e mit A dr esse 3 im Ei ngangsbyt e 0 das Bit 1 auf „1“ gesetzt wer-
den.
5 Das Programm k ommuniziert jetzt zykli sch mit den ausgewählt en S la-
v es. Dr üc k en Si e wiederhol t die Eingabet aste, um den aktuellen St atus
anzuzeigen.
6 Tippen Sie „ q“ und die Eingabet aste, um das Progr amm zu beenden.
Hinweis 1
Die Quellen zum Beispielprogramm finden Sie im Unterverzeichnis
„CP5613_CP5614\Examples\F astLogic “ Ihr es Installati onsverzeic hnisses.
Hinweis 2
Das Beispiel programm belegt den DP-RAM-Poi nter exklusiv. Di e Schnittstell e er-
laubt nicht den parallelen Betri eb einer zweiten DP-Anwendung falls der Pointer
v on den A pplik ationen ni c ht wechselseitig freigegeben wir d.
Ergebnisse
Es werden di e ak tuell en Sl av e-Zustände und eventuell aufgetretene Fast-Logic-
Ereigni sse ausgegeben. I m Fehlerf all werden Texte ausgegeb en.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 25
4.5 Start des Transfer-Beispielprogrammsr CP 5614
Zweck des Beispielprogramms „Transfer“
Neben der Einarbeitung für DP-Programmierer kann das Transfer-Beispiel-
programm v er wendet werden, um die Kommunikation mit mehrer en DP - Sl av es und
einem über geor dneten Master z u testen. Wenn mehr er e CP 5613 oder CP 5614
v or handen si nd, kann bei Pr ogr ammstart der zu v erwendende CP ausgewählt wer-
den.
Erläute r ung der Transfer-Funk tionalität
CP 5614 eignet sich für hi er ar c hisch aufgebaute Netz e. Dabei arbeit et der M aster -
Teil des CP 5614 mit „ unterlagerten“ Aktor en und S ensoren über ein eigenes Bus-
segment . Das Slav e-Modul des CP 5614 ist über ein separat es Bussegment an ei-
ner Lei tstation angeschlossen.
Ei ne oft benötigte Funktionali tät ist die Weit erleitung v on A ktor - und S ensordat en
an das Leitsystem. Die Software, die dies leistet, wird im folgenden Tr ansfer-Soft-
ware genannt.
Aktor Sensor
PROFIBUS DP (II)
PROFIBUS DP (I)
RS485
CP 5614
RS485
Slave
Master
Leitsystem
Transfer-
Software
PC
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
26 S79220-A5814-X-01-7437
Transferprogramm
Mit einem Transf er-Konfi gurationsprogramm kann f estgelegt werden, welche Dat en
der Aktoren bzw. Sensoren an das Leitsystem weitergeleit et werden (siehe Kapi-
tel 4.6).
Das mitgelieferte Beispiel (STEP 7-Proj ekt und Transfer-Konfigurati onsdatei) setzt
einen S lave ET 200B und ei nen CP 5614 v or aus.
Slave Kon fi gu rat ion Projekti ert als
1 1 Eingangsbyte, 1 A usgangsbyte ET 200 B 8DI/8DO, Adresse 3
2 2 Eingangsbyte, 2 A usgangsbyte Sl av e- M odul CP 5614, Adresse 10
Die Datenübert r agungsge schwindi gk eit betr ägt 1,5 Mbit/s.
Das Transf er pr ogr am m ar beitet mit der Datei „transfer.tr a“ und dem STEP 7-
Projekt „Ex am ples“ (Datenbank „pc st_transfer.xdb“). In „transfer.t r a“ ist ein Daten-
transfer v on einem ET 200B Ei ngangsbi t auf ein Ausgangsbit konf iguri er t. A ußer-
dem ist ein Datentr ansfer v om Slave- M odul des CP 5614 Bit 0 bi s 6 auf einen
ET 200B ab Bi t 1 projek tiert.
Hinweis
Falls Ihre DP- Um gebung v on diesem Beispiel abweic ht, m üssen Sie mit SIM ATIC
NCM PC oder STEP 7 V5.1 SP2 ein passendes STEP 7-Projekt erstellen. Die
Sl av e- Ei genschaften des CP 5614 sind in der Dat ei „Sam ple.GS D“ voreingestell t.
Falls Sie für den CP 5614 ei ne ander e A nz ahl Ei n- /Ausgabe-Por ts def inieren
m öc hten, editieren Sie bitte diese Datei oder er stellen eine neue GSD-Datei für
den CP 5614.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 27
Vorgehensweise
Gehen Sie wi e fol gt beschrieben vor, um das Beispielprogr am m „Tr ansfer“ zu
starten:
Schritt Beschreibung
1 Stellen Sie bitte das zum Beispielprogramm passende STEP 7-Projekt
„Exam ples“ (Dat enbank pc st_transfer.xdb“ ) ein.
2Star ten Sie das Bei spi elpr ogr amm „Transfer“ (Start-Leiste Start
Simat ic SIMATIC NET CP5613_CP 5614 E xampl es
Transfer5614).
3Das Programm läuft in einer DOS-Box und modifiziert di e Eingabeda-
ten des Sl av e- M oduls des CP 5614. Am ET 200B sehen Sie, wie das
CP 5614 Sl av e- M odul Werte hochz ählt.
4 Tippen Sie „ q“ und die Eingabet aste, um das Progr amm zu beenden
Hinweis 1
Die Quellen zum Beispielprogramm finden Sie im Unterverzeichnis
„CP5613_CP5614\Examples\TRANSFER5614“ Ihres Installations verze ichnisses .
Hinweis 2
Das Beispiel programm belegt den DP-RAM-Poi nter exklusiv. Di e Schnittstell e er-
laubt nicht den parallelen Betri eb einer zweiten DP-Anwendung falls der Pointer
v on den A pplik ationen ni c ht wechselseitig freigegeben wir d.
Ergebnisse
Am ET 200B k önnen Si e das erste Eingabebit per Sc halter ver änder n ( Wert 0
oder 1). Dieses Eingabebit wir d v om Tr ansfer pr ogr amm auf das erste Ausgangsbit
(LED) über tragen.
Im CP 5614- Sl av e- M odul ist ein Zähl er realisier t. 7 Bit des Zählerstands werden
v om Tr ansfer pr ogr am m auf die LEDs, Bit 1-7 des ET 200B übertragen.
Das Transf er pr ogr am m über trägt all e k onfigurier ten Daten zyklisch all e 10 ms.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
28 S79220-A5814-X-01-7437
4.6 K on fi gur a ti on d es Tr a nsf er s für da s CP 56 1 4 Tr ansf er-
Beispielprogramm
Zweck des Werkzeugs „Transfer-Configuration“
Mi t dem Werk z eug k ann k onfigurier t werden, welche E ingabe-, Ausgabe- oder Di-
agnosedaten z wischen den ange schlossenen S laves und dem überlager ten Mas-
ter in beide Richtungen übert r agen werden.
All e Zugriffsadressen beginnen m it 0, d. h. das niederwertigste B it oder By te eines
Slave oder des Master-Moduls ist Bit bzw. Byte 0.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 29
Vorgehensweise
Gehen Sie wie folgt beschri eben vor, um das Werkzeug „Transfer-Konfi gurati on“
zu start en:
Schritt Beschreibung
1Start en Sie das Werkzeug „Transfer-Konf iguration“ (Start-Leiste Start
Simati c SIMATIC NET CP5613_CP5614 Transfer5614-
Configuration).
2 Wählen Sie die z u bearbei tende Datei für die Abl age der Tr ansfer - Liste
oder erzeugen S ie eine neue Dat ei.
3Tragen S ie im Fenster Transfer-Konfi gur ation Ihre Daten ein. Im
Fenster Transfer-Liste werden di e Daten nochmals i n Kurzform und al s
Übersicht angezeigt.
In der Regel wird ein Ausgang (Quell e auf der link en S eite) mit einem
Ei ngang ( Ziel, auf der r ec hten Seite) ver k nüpft .
4 Nach F er tigstell ung der Transfer- Liste speic her n Si e diese ab.
Ergebnisse
Im Bil d oben sehen Sie die Konfi gur ation für das Bei spi elprogr amm:
Bi t 0 von Sl av e ET 200B mit der Adr esse 3 wird auf seinen Ausgang kopiert . Die
Bi ts 0-6 des Slave-Moduls (Adresse 127) werden auf Bit 1-7 des ET 200 B kopiert.
Die LE Ds von ET 200 B bli nk en gem äß der Zähleransteuerung des Sl ave-Moduls.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
30 S79220-A5814-X-01-7437
5 DP-5613/Windows
5.1 Eigenschaften
Eigenscha ften von DP-5613/Windows
Mi t „DP - 5613/W indows“ wird die vom CP 5412 (A2) bek annte
DP-Lib-Programmierschnittstelle für den DP-Master-Betrieb auch für den CP 5613
und CP 5614 zur V erfügung gestellt . Diese sol l f ür Neuentwic k lungen nicht mehr
benutzt werden; verwenden Sie stattdessen die OP C-Schnittstell e.
Beacht en S ie auch, dass der Paral lelbet rieb di eser Sc hnittstelle mi t der im Produkt
„CP 5613/CP 5614 (DP-Base)“ enthaltenen DP-Base-Programmierschnitt stell e
nicht möglich ist.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 31
5.2 Prüfung und Konfiguration von DP-5613/Windows
Übersicht
Nach der I nstallati on der S oft ware und der Baugr uppe so wie der K onfi gur ation der
DP-Base-Programmierschnit t stelle erfahren Sie hier, wi e Si e die Baugruppe f ür
den Betr ieb von DP-5613/W indows konf igurieren können.
Hinweis
Das Produkt DP - 5613/Windows enthält die DP-Li b-Pr ogr ammierschni ttstelle und
einige Programm e z um Test der Funktionali tät dieser Schni tt stelle.
Beacht en S ie bitte, dass der gleichzeiti ge Ei nsatz dieser Sc hnitt stelle und der
DP-Base-Programmierschnitt stelle, die im Produkt „CP 5613/CP 5614 (DP-Base)“
enthalten ist, auf einem CP nicht möglic h ist.
Bei de P r oduk te können zwar parallel instal liert werden, aber es dürfen nur Pro-
gramme auf einem CP gl eic hz eitig betri eben werden, die eine dieser Schnit tstell en
benutzen.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
32 S79220-A5814-X-01-7437
5.3 Ausgangssituation nach der Installation bei DP
Auf Festplatte kopierte Daten
Nachfolgend fi nden S ie eine Übersi c ht der für Sie zur Programmierung wichtigen
Verzeichnisse, di e im Inst allationsverzeichnis (z. B. c:\SIEMENS\SIMATIC.NET) Ih-
res PC angelegt werden:
Verzeichnis Bemerkung
opc2 OPC- S erver, I nform ationen und Beispiele
Vorsicht
Löschen Sie die in diesem V er z eic hnis abgel egten Dateien nicht, da die Funkti -
onsfähigkeit anderer P r ogr amme beeintr äc htigt werden könnte.
Zur Deinstallation des Produk ts verwenden Sie gegebenenfall s das von
Windows NT/Windows 2000 hi erfür v or gesehene Systemprogramm (St ar t-Leiste
Start Einstellungen Systemsteuerung Software).
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 33
6 FMS-5613/Windows
6.1 Eigenschaften
Eigenscha ften von FMS-5613
Mi t „FM S - 5613/W indowswird die vom CP 5412 (A2) bekannt e
FMS-Programmierschnittstelle mit ihren wesentlichen Eigenschaften auch für den
CP 5613 und CP 5614 zur V erfügung gestellt. Diese soll für Neuentwic kl ungen
nicht mehr benutzt werden; verwenden Sie statt dessen die OPC-Schnittstell e.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
34 S79220-A5814-X-01-7437
6.2 Ausgangssituation nach der Installation
Auf Festplatte kopierte Daten
Nachfolgend fi nden S ie eine Übersi c ht der für Sie zur Programmierung wichtigen
Verzeichnisse, di e im Inst allationsverzeichnis (z. B. c:\SIEMENS\SIMATIC.NET) Ih-
res PC angelegt werden:
Verzeichnis Bemerkung
opc2 OPC- S erver, I nform ationen und Beispiele
Vorsicht
Löschen Sie die in diesem V er z eic hnis abgel egten Dateien nicht, da die Funkti -
onsfähigkeit anderer P r ogr amme beeintr äc htigt werden könnte.
Zur Deinstallation des Produk ts verwenden Sie gegebenenfall s das von
Windows NT/Windows 2000 hi erfür v or gesehene Systemprogramm (St ar t-Leiste
Start Einstellungen Systemsteuerung Software).
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 35
7 S7-5613/Windows
7.1 Eigenschaften
Eigenschaften von S7-5613
Mi t „S 7- 5613/Windows“ wird die vom CP 5412 (A2) bekannte S7-Schnittstelle mit
einigen Er weiterungen auch für den CP 5613 und CP 5614 zur Verfügung gestel lt.
Diese soll für Neuent wic k lungen nicht mehr benutzt werden; verwenden Si e statt-
dessen di e OPC-Schnit t stelle.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
36 S79220-A5814-X-01-7437
7.2 Ausgangssituation nach der Installation
Auf Festplatte kopierte Daten
Nachfolgend fi nden S ie eine Übersi c ht der für Sie zur Programmierung wichtigen
Verzeichnisse, di e im Inst allationsverzeichnis (z. B. c:\SIEMENS\SIMATIC.NET) Ih-
res PC angelegt werden:
Verzeichnis Bemerkung
opc2 OPC- S erver, I nform ationen und Beispiele
Vorsicht
Löschen Sie die in diesem V er z eic hnis abgel egten Dateien nicht, da die Funkti -
onsfähigkeit anderer P r ogr amme beeintr äc htigt werden könnte.
Zur Deinstallation des Produk ts verwenden Sie gegebenenfall s das von
Windows NT/Windows 2000 hi erfür v or gesehene Systemprogramm (St ar t-Leiste
Start Einstellungen Systemsteuerung Software).
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 37
8 PG-Betrieb mit STEP 5/STEP 7
Keine Projektierung
Für das Arbeit en im PG-Betrieb mit STE P 5/STE P 7 ist keine Projektier ung nöti g.
Es genügt im Programm „PG/PC-Schnittstel le einstellen“ die Busparam eter einzu-
stellen.
Weitere Informationen entnehmen Sie bitte den Beschrei bungen z u
STEP 5/STEP 7.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
38 S79220-A5814-X-01-7437
9 FAQ (Frequently Asked Questions)
9.1 FAQ zu Kommunikation seigenschaften des Prod ukts
9.1.1 Welche Software-Versionen gibt es, und wie unterscheiden sie
sich?
Software-Version V1.0
Was ist neu? Passende
Dokumentation
Basisversion für CP 5613
Nicht unterstützt:
DPC1, DP C2
• FDL
Fast Logic
Mehrere CP 5613/CP 5614 parall el
Mehrere A nwendungsprogramme benutzen ei-
nen CP 5613/CP 5614 gleichzeitig.
User-Watchdog
Sl av e- Ei genschaften des CP 5614
STEP 7
Online-F unktionen des SIM ATIC NCM PC oder
STEP 7 V5.1 SP2
DP-Master Klasse 2 (Di agnose)
Installationsanleitung,
Ausgabe 1, 1999
Programmierschnitt-
stelle, Ausgabe 1, 1999
Software-Version V1.1
Wie V1.0
Unterst ützt zusätzli ch:
Slav e-F unktionen und Transf er-Mechanismus des
CP 5614
Installationsanleitung,
Ausgabe 1, 1999
Programmierschnittstel-
le, Ausgabe 1, 1999
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 39
Software-Version V1.2
Was ist neu? Passende
Dokumentation
Unterstützt:
Sl av e- Ei genschaften des CP 5614
Fast Logic
User-Watchdog f ür DP-Master (nic ht für
Slave-Funktionen)
Mehrere CP 5613/CP 5614 parall el
Mehrere A nwendungsprogramme benutzen
einen CP 5613/CP 5614 gleic hzeiti g.
Nicht unterstützt:
DPC1, DP C2
• FDL
User-Watchdog für Slave-Funktionen
STEP 7
DP-Master Klasse 2 (Di agnose)
Installationsanleitung,
Ausgabe 2, 1999
Programmierschnittstelle,
Ausgabe 2, 1999
Software-Version V2.0
Was ist neu? Passende
Dokumentation
Unterstützt:
Sl av e- Ei genschaften des CP 5614
Fast Logic
User-Watchdog f ür DP-Master (nic ht für Sla-
ve-Funktionen)
Bi s zu vier CP 5613/CP 5614 parallel
Mehrere A nwendungsprogramme benutzen
einen CP 5613/CP 5614 gleic hzeiti g.
DPC1 (Ver si on 1.13, wie bei CP 5412 ( A 2)
ab V5.0)
DPC2
• FDL
• S7
Unterstützung von STEP 7, Version 5.0, ab
Serv ice- P ack 3 oder höher
Unterstützung der P G-Funktionali tät mit
STE P 5 und STEP 7
Nicht unterstützt:
User-Watchdog für Slave-Funktionen
DPC1 (Alarme vollständig nach Norm V1.14)
DP-Master Klasse 2 (Di agnose)
Installationsanleitung,
Ausgabe 3, 1999
DP-Base-Programmier-
schnit tstell e, Ausgabe 3,
1999
DP-Master-Programmier-
schnit tstell en, Ausgabe 5,
1999
FDL-Programmierschnitt-
stelle, Ausgabe 3, 1999
S7-Programmierschnitt-
stelle, Ausgabe 5, 1999
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
40 S79220-A5814-X-01-7437
Software-Version V2.1
Was ist neu? Passende
Dokumentation
Unterstützt:
• FMS
Äqui distanzm odus - Die Äquidistanzpar ame-
ter m üssen in STEP 7/NCM V5. 1 eingestellt
werden.
Nicht unterstützt:
User-Watchdog f. Slave-Funktionen
DPC1 (Alarme vollständig nach Norm V1.14)
DP-Master Klasse 2 (Di agnose)
FMS-
Programmierschnittstelle,
Ausgabe 5
Software-Version V6.0
Was ist neu? Passende
Dokumentation
Unterstützt:
Neue Projekti er ung mi t SIMA TI C NCM PC oder
STEP 7 V5.1 SP2
Nicht unterstützt:
User-Watchdog f. Slave-Funktionen
DPC1 (Alarme vollständig nach Norm V1.14)
Anl eitung „PC- Stationen mit
SIM ATIC NCM PC projekti e-
ren“
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 41
9.2 Fragen zu technischen Daten
9.2.1 Fragen zu technischen Daten der Software-Produkte
Mit welchen Kommunikationspartnern ka nn das Produkt betrieben werden?
DP-Mast er des CP 5613/ CP 5614
Der DP-Master des CP 5613/CP 5614 kann mit all en zertifizierten DP-Slaves be-
trieben werden.
DP-Slave d es CP 5614
Der DP-Slav e des CP 5614 kann mit allen zertifizi ert en DP-Master-Stati onen be-
trieben werden.
Welches Mengengerüst wird für DP unte rstützt?
Maximale Länge der DP - Ei ngangsdaten: 244 Byte pro Sl av e
Maxim ale Länge der DP-Ausgangsdaten: 244 Byte pro Slav e
Maximale Länge der DP - Diagnosedaten: 244 Byte pro Slav e
Anzahl DP-Slaves: 124
Herleitung:
Theoreti sches Maximum (St ationsadressen 0-127) 128
Ei ne A dr esse ist durc h den CP 5613/ CP 5614 belegt -1
Adresse 127 i st für Br oadc ast r eserv iert -1
Adresse 0 für DP-Master Klasse 2 reserv ieren (empfohlen) -1
Adresse 126 für Knotentaufe r eserv ieren ( em pfohlen) -1
Ergebnis 124
Maximale Anz ahl gleic hz eiti ger
DPC1-Auftr äge ( r ead/writ e): einer pro Sl av e
Maximale Anz ahl gleic hz eiti ger
DPC2-Ver bindungen (r ead/writ e) : 48
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
42 S79220-A5814-X-01-7437
Welches Mengengerüst wird für FMS unterstützt?
Maximale Anzah l von FMS-Anwendungsp rogrammen: 5
Nachfolgende Tabelle nennt die maximale Anzahl von F MS-Verbi ndungen in
Abhängi gk eit der Anz ahl der Cr edits:
Anzahl der Credits maximal e Anzahl FMS-Verbindung en
140
220
SAPI FMS erl aubt den Betrieb von zwei CP 5613.
Welches Mengengerüst wird für FDL unterstützt?
Maximal 118 unbearbeit ete F DL- Requests können zwischen zwei Stationen unter-
wegs s ein .
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 43
Welches Mengengerüst wird für S7 unterstützt?
Für S 7 ist die m aximale Anzahl gleic hz eiti g betriebener A nwendungsprogramme
sowie di e m aximale Anzahl gleichz eitiger S7-Verbindungen defi nier t.
Maximale Anzahl von S7-Anwendungsprogrammen.
Es können bis zu 10 S7- A nwendungs pr ogr am me gleichz eitig betri eben wer-
den, d. h. es werden insgesamt bis zu 10 Anmeldungen mit „s7-i nit()“ unter-
stützt.
In nachfol gender Tabelle wird dieser Sachver halt durc h zwei Beispielkom bina-
tionen dargestellt:
Anzahl Anwendungs-
programme Anzahl der Anmeldungen mit s7-init()
je Anwend un gsprogramm
10 1
52
Maximale Anzahl gleichzeitiger S 7- V erbi ndung en
Die maximale Anzahl von S7-Verbindungen ist abhängig von:
PDU-Größe
Anzahl der Cr edits
Die nac hfolgende Tabelle nennt die m aximale Anzahl v on off enen
S7-Ver bindungen unt er den oben genannten Bedingungen:
PDU-G röß e Anzahl S 7- V erbi ndung en
bei Credi t 1 Anzahl S7-Verbindungen
bei Credi t 2
112 50 35
240 50 35
480 50 35
960 30 15
Welche Kommunikationsprotokolle werden unterstützt?
Si ehe V er si onstabelle, Kapitels 9.1.1.
Kann STEP 7 auch mit dem CP 5613/CP 5614 betrieben werden?
Si ehe V er si onstabelle zu Beginn des Kapit els 9.1.1.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
44 S79220-A5814-X-01-7437
Kann STEP 5 auch mit dem CP 5613/CP 5614 betrieben werden?
Si ehe V er si onstabelle zu Beginn des Kapit els 9.1.1.
Parallelbetrieb von Protokollen
Es können m aximal 2 Protokolle parallel betrieben werden, z. B. PROFIBUS- DP
und PROFI B US -F M S.
Ab we lche r Version werde n mehrere Baugruppen parallel unterstützt?
Si ehe V er si onstabelle zu Beginn des Kapit els 9.1.
Sind für die CP 5613/CP 5614-Produkt Lizenze n erforderlich?
Für die Produkte DP-5613, FMS-5613 und S7-5613 sind Lizenzen erforderlich.
Für die Tr eiber und Software zum DP-Betrieb des CP 5613 und CP 5614 über di e
DP-Base-Programmierschnittstelle ist keine Li zenz erforderlich. Für den reinen
FDL-B etrieb ist ebenfalls keine Lizenz erfor derli c h.
Kann der CP sich an die vorhandenen Busparameter dynamisch anpassen, wenn
beim Anlauf das Netz schon von anderen PROFIBUS-Mas te r n benutzt wird?
Der DP-Sl ave-T eil des CP 5614 kann sic h an die B usparameter des angeschlos-
senen Netz es anpa s sen.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 45
9.2.2 Fragen zu den technischen Daten des CP 5613/CP 5614
Welche m axi male Performance er r eicht der C P?
Eigenschaft Größe
Datenrate Proz essabbil d v om PC aus lesen 3 kbyt e/ms
Datenrate Proz essabbil d v om PC aus schreiben 8 kbyt e/ms
Mi ttl er e Si gnallauf z eit vom Slave 50 mikr osec + Buslaufzeit
Maximale Signall aufzeit vom Slave 100 mikrosec + B usl aufzeit
Welche Datenübertragungsgeschwindigkeiten werde n unterstützt?
9,6 kbit/s
19,2 kbit/s
45,45 kbit/s
93,75 kbit/s
187,5 kbit/s
500,0 kbit/s
1,5 Mbit/s
3,0 Mbit/s
6,0 Mbit/s
12,0 Mbit/s
Wie viele CP 5613/CP 5614 können parallel betrieben werden?
Bi s zu vier B augr uppen CP 5613/CP 5614 können paral lel bet rieben werden.
Der CP 5613/CP 5614 funktioniert nicht auf einem Celsius 620 Rechner mit
Tyan 100 Motherboard
Ab dem Hardware-Stand 03 (Mitte 2000) ist dieses Probl em behoben.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
46 S79220-A5814-X-01-7437
Der CP 5613/CP 5614 funktioniert nicht auf einem SNI Scenic 860 Rechner mit
D1127 Motherboard unter Windows NT
Auf diesem Rechner ist im BIOS standar dmäßig „Plug and Play“ als Bet riebssys-
temeinstellung aktiviert. Da Windows NT die „Plug and Play“-Funktionalit ät nicht
unterstützt , müssen Sie im BIOS die Ei nstellung von „ P &P OS“ auf „no“ setz en.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 47
10 Hinweise zur CE-Kennzeichnung von
SIMATIC NET-Produkten
Produktbezeichnung
SIM ATIC NET, CP 5613 C79458-L800 0- A 77
SIM ATIC NET, CP 5614 C79458-L800 1- A 77
SIM ATIC NET, CP 5613 FO A5E00047996
SIM ATIC NET, CP 5614 FO A5E00047997
EMV-Richtlinie
Die obigen SIMATIC NET-Produkte erfüllen die Anforderungen f olgender
EG-Richtlinie:
Ric htlini e 89/336/EWG „Elektromagnetische Vert r äglichk eit
Einsatzbereich
Die P r oduk te si nd ausgel egt für den Ei nsatz in folgenden Bereichen:
Ei nsatz ber eich Anforder ungen an
Störaussendung Störfestigkeit
Wohnbereich, Geschäfts- und G ewer-
beberei c h so wie K leinbet ri ebe EN 50081-1 : 1992 EN 50082-1 : 1997
Industriebereich EN 50081-2 : 1993 EN 50082-2 : 1995
Aufbaurichtlinien beachten
Die P r oduk te erfüllen die Anforderungen, wenn Sie bei Installati on und Betri eb die
Aufbauri c htlini en und Si c her heitshinweise einhalt en, die auf diesem Blatt “Hinweise
zur CE- K ennz eichnung” sowie i n folgender Dokum entation beschrieben ist:
SIM ATIC NET, PROFIBUS- Netze, Handbuch
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
48 S79220-A5814-X-01-7437
Konformitätserklärung
Die EG- K onformitätserkl är ung wir d gem äß den obengenannt en E G-Richtli nien für
die z uständigen Behör den z ur V erfügung gehalten bei :
Si em ens Aktiengesellschaft
Bereich Automatisierungs- und Antriebstechnik
Industrielle Komm unik ation (A&D PT 2)
Postfach 4848
D-90327 Nürnberg
Maschinenrichtlinie
Das Produkt ist weit er hin eine Komponente nac h A r tikel 4(2) der
EG- M aschinenrichtli nie 89/392/EWG.
Nach der Maschinenrichtli nie sind wir verpflichtet darauf hinz uweisen, dass das
bezei c hnete Produk t ausschließlich zum Einbau in eine Maschine bestim m t ist.
Bevor das Endprodukt in Betrieb genom men wi r d, muss si c her gestellt sei n, dass
es mit der Richtli nie 89/392/EWG konform i st.
Hinweis für Australien
Die P r oduk te erfüllen die Anforderungen der Nor m A S/NZS 3548.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 49
11 Glossar
BIOS Basic
Input
Output
System – Unter BIOS wird der Teil der „Sof tware
v er standen, der die Ver bindung z wischen“ Har dware und den Treibern
des Betriebssystems herstellt. Das BIOS dient zur Abstrahierung der
zugrunde li egenden Har dware, die zugehör ige Soft ware i st in einem
EPRO M hinterl egt.
Wichtige Bestandt eile sind beispielswei se der Lader für den Boot-
Sekt or , das (Hardware-) SETUP zur Festlegung der Har dwarekonfigu-
ration und zur Einstellung der Uhrzeit.
booten PC-Neustart
COM P ROFIBUS Confi
g
uration Mana
g
er for Process Field Bus – Bisheri
g
es Pro
g
ramm
zur Er z eugung von Datenbasen, die di e Anl agenbeschreibung ent hal-
ten.
COM PROF I B US wi rd ab DP-, FMS- oder S7-5613-Produktversion
V6.0 dur c h eine P r ojek tierung mit dem Software-Werkzeug SIMATIC
NCM PC oder das separat erhält liche STEP 7 V5.1 SP 2 abgel öst.
CP Communicati on Processor – Kommunik ationsbaugrup-
pe/Net zwerkkarte für den Einbau in Rechner oder Automati si erungs-
systeme.
CP 5613 FO Kommunikationsprozessor für PROFI B US, P CI-K art e m it eigenem
Prozessor mit Fi ber-Optik-Schnittstell e.
CP 5614 FO Kommunikationsprozessor für PROFI B US, wie CP 5613, aber mit zu-
sätzl ichem Slave-Modul und –Anschl us s. A usge stattet mit einer Fi ber -
Opti c - und einer elek trischen Sc hnittstelle.
CP 5613 Kommunikationsprozessor für PROFI B US, P CI-K art e m it eigenem
Prozessor
CP 5614 Kommunikationsprozessor für PROFI B US, wie CP 5613, aber mit zu-
sätzl ichem Slave-Modul und –Anschl us s
DIN Deut sches In stitut fü r Normung
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
50 S79220-A5814-X-01-7437
DLL Dynamic Link Li br ar y – Sammlung von Funktionen, die m ehr er en
Program men zur Verf ügung z u stehen, aber nur einmal in den Spei -
cher geladen werden (Windows)
DOS-BOX Konsolenfenster, MS-DOS-Eingabeaufforderung
DP Dezentrale Peripherie – Ein-/Aus
g
an
g
sbau
g
rupp en, di e ab
g
esetzt von
der CPU (Zentral einheit der Steuerung) eingesetzt werden. Die Verbin-
dung zwischen dem A utomatisierungsgerät und der Dez entralen Peri-
pheri e erfolgt über das Bussystem PROFIBUS - DP.
DPRAM Dual Port Random Access Mem or y (Dual-Port- RA M ) – Gestattet den
gleichz eitigen Zugriff von zwei Rechnereinheiten (CP und CPU) auf
einen S peicher ber eic h ( RA M).
E/A Eingangs/Ausgang s-Per ipherie eines Automatisierungsgerät s
EN 50170 PROFIBUS
FDL Fieldbus Data Link – Schicht 2 des ISO-Referenzm odells bei
PROFI B US ; sie besteht aus Fieldbus Link Control (FCL) und Medium
Access Control (MAC)
FMS Fieldbus Message Spec ifi c ation – Obere Teil schicht von Schi c ht 7
des ISO- Referenzm odells bei P ROFIB US; si e umfasst di e Funkti onen
Prot ok ollmaschine, Generierung der PDUs sowie Codi er ung/Decodie-
rung und Interpretation der P r otokolldat eneinheit.
GSD-Datei Gerätestammdaten – enthält Eigenschaf ten eines DP-Slave für di e
Projekti er ung. Die GSD-Dat ei enthält die genaue B eschreibung der
Sl av e- Funkti onalität. Daher wir d für den CP 5614 nur ein Beispi el mi t-
gelief ert , das an die eigentli c he A nwendung angepasst wer den muss.
Hardware-
Ressourcen Der vom CP 5613/CP 5614 benötigte Int er r upt und die Speic her ber ei-
che werden vom PCI-BIO S im Anlauf automati sch ver geben.
IK PI Katalog der SIMATIC-NET-Produkte (IK = Industrial Communication,
PI = Process Interf aces)
IRQ Interrupt Request – Unterbr ec hungsanforder ung.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
S79220-A5814-X-01-7437 51
ISO International Standard Organiz ation – Internationale Or ganisation mit
Si tz in Genf z ur Sc haffung allgem einer Normen, v or all em auf dem
Gebiet des Datenübertr agungsberei c hs.
LED Light Emitting Di ode – Leuchtdiode
MPI Multi Point Interface – Mehrpunktfähige Schnittstelle für SIMATIC S7
NCM SIMATIC Network Configuration Manager – Pr ojektierungs-Software
für SIMATIC NET- K ommunikati onsprozes sore n.
Overflow Überl auf, Über schreit ung des zulässigen Maximalwerts
PC Personal Computer
PCI Peripher al Com puter Interf ac e – PC-Kartenstandar d
PG Programmiergerät für die P r oduktfamilie SIMATIC der Si em ens AG;
wird ei ngesetz t zum Programmieren, z ur Pr ojek tierung, bei der War-
tung und im S ervice.
PNO PROFIBUS Nutzer-Organisation
PROFIBUS Process Field Bus – Ein Feldbus nach EN 50170 Vol. 2 PROFI B US
(DIN 19245; fr üher er Nam e: SINEC L2) .
S7 Protokoll zur Komm unikation mit einer SIMATIC S7
SELV Safety Extra Low Vol tage – Sicherheit s-Kleinspannung
SIMATIC NCM PC SIMAT I C Network Configuration Manager für P C – Projektierungs-
Software f ür SIMATIC NET-PC- K ommunikati onsprozessoren.
SIMATIC S7 Autom atisierungs steuer ung S IMATIC S7 von Siem ens
SPS Speicherprogrammierbare Steuerung
Token Der Tok en ist ein „Senderecht“, das bei mehr er en M aster n im
PROFIBUS-Netz umläuft.
Produktinf ormat ion CP (DP-Base), DP-, FMS- und S7-5613/ W indows
Produktinformation/Product Information CP (DP-Base), DP-Base, DP-, FMS- und S7-5613/Windows
52 S79220-A5814-X-01-7437
12 Stichwortverzeichnis
A
Autorisierungs-Hotline............................11
B
Beispielprogramm...................... 19, 21, 23
C
Custom er S uppor t..................................11
D
Datenübertragungsgeschwindigkeiten....45
DP-5613/Windows..................................30
E
Echtzeitanforderungen ...........................17
Eigenschaften
DP-5613.............................................30
FMS-5613...........................................33
S7-5613..............................................35
F
FMS-5613/Windows...............................33
M
Mengengerüst........................................41
P
Performance..........................................45
Projektierung
DP
STEP 7-Projekt....................20, 22, 24
Werkzeuge.........................................15
S
S7-5613/Windows..................................35
T
Technical S uppor t..................................11
Transfer
Beispielprogramm...............................25
konfigurieren.......................................28
V
Versionen
Software.............................................38
Verzeichnis
database.......................................18, 32
diagnose.............................................18
examples............................................18
include................................................32
lib.......................................................32
logfiles................................................18
prog....................................................18
sample ...............................................32
Verzeichnisstruktur
CP-5613.............................................18
DP-5613.......................................32, 34
S7-5613........................................32, 36
W
Windows 2000 .......................................17
Windows NT ..........................................17
53
SIMAT IC NET
Product Information
Release 07/2001
CP 5613 (DP-Base)
CP 5614 (DP-Base)
CP 5613 FO (D P-Bas e)
CP 5614 FO (D P-Bas e)
DP-5613/Windows
FMS-5613/Windows
S7-5613/Windows
6GK1561-3AA00
6GK1561-4AA00
6GK1561-3FA00
6GK1561-4FA00
6GK1713-5DB60-3AA
0
6GK1713-5FB60-3AA
0
6GK1713-5CB60-3AA
0
The following information is in English
S79220-A5814-X-01-7437
© SIEMENS AG 2001
Subject to change
Si em ens Aktiengesellschaft
English
S79220-A5814-X-01-7437
Copyright Siemens AG 2001, All rights reserved
The reproduction, transmission or use of this document or its contents
is not permitted without express written authority. Offenders will be
li able for dam a
g
es. All ri
g
hts, i ncludin
g
ri
g
hts created b y paten t
g
rant
or registrat ion of a utility or design, are reserved.
Disclaimer
We hav e checked the contents of this manual for agreement with the
hardware and software described. Since deviations cannot be
precluded entirely, we cannot
g
uarantee full a
g
reement. However, the
data in this manual are reviewed regularly and any necessary
corrections included in subsequent editions. Suggestions for
improvement are welcome.
Siemens AG
Bereich Automatisierungs- und Antriebstechnik
Geschäftsgebiet Industrie-Automatisierungssysteme
Postfach 48 48, D-90327 Nürnberg
S79220-A5814-X-01-7437
© Siemens AG 2001
Technical data subject to change.
Siemens Aktiengesellschaft Printed in the Federal Republic of Germany 54
Classification of Safety-Related Notices
This document c ontains noti c es which you shoul d observe to ensure your own per son al
safety, as wel l as to protect the pr oduct and c onnec ted equi pm ent. These notices are
highlight ed in the manual by a warning triangl e and ar e m arked as follows accor ding t o
the level of danger:
!Danger
indicates that death or sev ere personal injury will result if proper pr ec autions are not
taken.
!Warning
indicates that death or sev ere personal injury can result if pr oper pr ec autions are not
taken.
!Caution
with a warning triangle indi c ates that minor personal injur y can resul t if proper
precaut ions are not taken.
Caution
without a warni ng triangle indicates that dam age to property c an r esul t if proper
precaut ions are not taken.
Notice
indicates that an undesi r able resul t or status can occur if the relevant notic e is ignored.
Note
highlight s important information on the product, usi ng the product, or part of t he
documentation that is of particular im por tance and that will be of benef it to the user.
Product Information/Product Information CP (DP-Base), DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 55
Trademarks
SIMATIC, SIMATIC NET, SINEC and SIMA TI C NET Networking for Industry ® ar e
regi ster ed trademar k s of Si em ens AG .
Third parties using for their own purposes any ot her names i n this document whic h r efer
to t r adem ar k s might infringe upon the right s of the trademark owners.
Safety Instructions Regarding your Product
Before you use the product descri bed her e, read the saf ety instr uc tions below thoroughly.
Qualified Personnel
Only qualifi ed per sonnel shoul d be allowed to i nstall and work on this equi pm ent.
Qualif ied persons are defi ned as persons who are aut hor ized to commission, to ground,
and to t ag ci r c uits, equipment , and systems in acc or danc e with established safety
pract ices and standards.
Correct Usage of Hardware Products
Pl ease note the following r egar ding t he c or r ect usage of har dware products:
Caution
This devi c e and its component s may only be used for the applications described in the
catalog or the t ec hnic al descripti on, and only in connec tion wit h devi c es or com ponents
from other manufac turers which have been approv ed or recommended by Siem ens.
This product c an only function corr ectly and safely if it i s transported, stor ed, set up, and
installed correctl y, and oper ated and maint ained as recom mended.
Before you use the supplied sample pr ogr am s or progr am s you have written yourself,
m ak e cert ain that no injur y to persons nor damage to equipm ent can result in y our pl ant
or process.
EU Di r ectiv e: Do not start up until you have established that the mac hine on whic h y ou
intend to run this component complies with the di r ective 89/392/EEC.
Product Information/Product Information CP (DP-Base), DP-, FMS- und S7-5613/Windows
56 S79220-A5814-X-01-7437
Correct Usage of Software Products
Pl ease note the following r egar ding t he c or r ect usage of software products:
Caution
This software may only be used for the applicati ons descri bed in the cat alog or the
technical descripti on, and only in connec tion wit h software products, dev ices, or
components fr om other m anufacturers which have been approved or recommended by
Siemens.
Before you use the supplied sample pr ogr am s or progr am s you have written yourself,
m ak e cert ain that no injur y to persons nor damage to equipm ent can result in y our pl ant
or process.
Prior to Startup
Before putti ng the product int o oper ation, note the following warni ng:
Caution
Prior to start up y ou must observe the instr uc tions in t he rel ev ant docum entation. For
ordering data of t he doc um entation, please refer to catalogs or cont ac t your loc al
Si em ens representative.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 57
Contents
1 Introduction...............................................................................................................59
2 Components of the Product.....................................................................................64
3 Req uirements and Restrict io ns ...............................................................................66
3.1 Requir ements and Restrictions for the Har dware ............................................66
3.2 Requir ements and Restrictions for the S oft ware..............................................67
4 CP 5613/CP 5614 (DP - Base) .....................................................................................68
4.1 Situa t io n Fo l lowing Installation........................................................................68
4.2 Star t in g the S i mp le Sample Prog r am ..............................................................69
4.3 Starting the Com plete Sample Program..........................................................71
4.4 Star ting the “F ast Logic” Sample P r ogr am ......................................................73
4.5 Star ting the Transfer Sample P r ogr am for the CP 5614 ...................................75
4.6 Configuring the Transfer for the CP 5614 Transfer Sample Pr ogr am...............78
5 DP-5613/Windows.....................................................................................................80
5.1 Properties.......................................................................................................80
5.2 Checking and Configuri ng DP - 5613/W indows.................................................81
5.3 Situation Following Installation wi th DP...........................................................82
6 FMS-5613/Windows ..................................................................................................83
6.1 Properties.......................................................................................................83
6.2 Situa t io n Fo l lowing Installation........................................................................84
7 S7-5613/Windows .....................................................................................................85
7.1 Properties.......................................................................................................85
7.2 Situa t io n Fo l lowing Installation........................................................................86
8 PG Mode with STEP 5 / STEP 7................................................................................87
9 F AQ (Frequen tl y Asked Quest ions).........................................................................88
9.1 FAQs about the Communications Propert ies of t he Product............................88
9.1. 1 Which software versions exist and how do they differ from each other? ..........88
9.2 Questions on the Tec hnic al S pec ificati ons......................................................91
9.2. 1 Questions on the Tec hnic al S pec ificati ons of the Software Produc ts...............91
9.2. 2 Questions on the Tec hnic al S pec ificati ons of the CP 5613/CP 5614................95
10 Notes on th e CE Mark of SIMATI C NET P roduct s....................................................97
11 Glossary....................................................................................................................99
12 Index .....................................................................................................................102
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
58 S79220-A5814-X-01-7437
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 59
1 Introduction
SIMATIC NET CP 5613 and CP 5614 Communications Processors
Thank y ou for deci ding to buy the SIMATIC NET CP 5613/CP 5614. You hav e
purchased a pr oduc t with innovative feat ur es all owing ex tremely fast S7, DP and
FMS access and simple installation.
Purpose of this Document
To prov ide you with inf ormati on on the produc t. This document suppl em ents the
HTML doc um entation “I ndustr ial Comm unic ation for PG/PC” .
Validity of the Product Information/ Installation Instructions
This document is valid for the following hardware v er si ons:
Name Hardw are V ersion
CP 5613> 4
CP 5614> 4
CP 5613 FO> 2
CP 5614 FO> 2
Product Documentation
You wil l find informati on on the use of t his product in the following sources:
Relevant paper doc um entation
The online hel p integrated i n the soft ware (F1 key)
Text and PDF files on the SIMATIC NET CD
HTML Doc um ent “Industrial Communic ation for PG/ P C”
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
60 S79220-A5814-X-01-7437
Overview of the Documentation
The docum entation for this product is struct ur ed as follows:
Hardw are ( communicati on s modules)
Pro du ct In format ion/Installat io n Inst ructions
describes the install ation of the CP 5613/CP 5614 communic ations modules.
Sof tw are ( S IMATIC NET Products)
Readme Files
Pro du ct In format ion
provides inf ormati on on the produc t.
Installation Instructions for the Software
describes the install ation of the SIMATIC NET pr oduc ts on the PG /PC.
HTM L Do cumen t “Indust rial Communication for PG/ P C”
contains the f ollowing topi c s:
Basics of industrial communicati on with OPC
Commissioning the product wit h utilities
Configuration of the installed products
OPC pr ogr amming and the sample programs
SIMATIC NET CD
The ent ir e S IMATIC NET documentation is available on the CDs fr om
SIMATIC NET:
Product CD 07/2001 “ SIM ATIC NET Networking f or Industry ®
(CD supplied)
Documentation CD 07/2001 “SI MATI C NET M anual Collection”
(CD supplied)
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 61
Automation and Drives, Service & Support
Serv ice & Support f r om A&D is available round t he cl oc k worldwide.
The languages spoken are G erman and English.
Frenc h, Italian, and Spani sh are also spoken on the authoriz ation hotline.
Technical Support Authorization Hot line
Europe and A frica (Nuremberg)
Mo. to Fr. 7:00 to 17:00 (local time, GMT +1)
Phone: +49 - (0) 180 - 5050 - 222
Fax: +49 - (0) 180 - 5050 - 223
E-mail: techsupport@ad.siemens.de
Europe and A frica (Nuremberg)
Mo. to Fr. 7:00 to 17:00 (local time, GMT +1)
Phone: +49 - (0) 911 - 895 - 7200
Fax: +49 - (0) 911 - 895 - 7201
E-mail: authorization@nbgm.siemens.de
America ( Johnson City)
Mo. to Fr. 8:00 to 19:00 (local time, GMT -5)
Phone: +1 - (0) 423 - 262 - 2522
Fax: +1 - (0) 42 3 - 26 2 - 2231
E-mail: simatic.hotline@sea.siemens.com
Asia and Australia (S ingapore )
Mo. to Fr. 8:30 to 17:30 (local time, GMT +8)
Phone: +65 - (0) 740 - 7000
Fax: +65 - (0) 740 - 7001
E-mail: simatic.hotline@sae.siemens.com.sg
SIMATIC Premium Hotline
Worldwide (Nuremberg )
Workdays
0:00 to 24: 00 (local time, GMT +1)
Phone: +49 - (0) 911 - 895 - 7777
Fax: +49 - (0) 911 - 895 - 7001
E-mail: techsupport@ad.siemens.de
Fast callback
guaranteed within a m aximum of two hours
(charged, only wi th the SIMATIC Card)
Johnson Cit y Nuremberg
SingaporeSingapore
Service & S up po rt
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
62 S79220-A5814-X-01-7437
Service & Support on the Internet
On t he Worl d Wide Web, you will find the very latest inform ation on the entire
SIM ATIC product range, for example, answers to fr equentl y asked questions
(FA Qs), tips and trick s, software updates, and u ser informati on.
In addition to t his fr ee inform ation, you can also order t he following, for whic h a
charge is made:
Manuals
Software products
Sample appli c ation program s
These are charged to the SIM ATIC CARD.
Int er net address:
http://www.ad.siemens.de/support
You can also form ulate a question f or the SIMATIC Knowledge Manager that will
find the solution in the knowledge dat abase.
If y ou are working in an area without an online connection, part of the fr ee
inform ation area is avail able on the “SIMATIC Customer Support Knowledge Base”
CD.
Note
If y ou telephone, please hav e the f ollowing inf ormati on av ailable:
Manufacturer and type of your computer
Your operati ng system v er si on
Your BIOS versi on
Ot her m odules i nsert ed in your PC
Software Version
You can display the ver si on of t he SIM ATIC NET PC software products in t he
Start menu.
Fo r exampl e, with Version 6.0 Build 1400, you will see the entry “SIMATI C
NET- P C- S oft ware V6. 0 B uild 1400” (taskbar S t art Control Panel
Software SIMATI C NET- P C-So ftware V6. 0 Build 1400).
Version of the CP
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 63
Who to Contact
If y ou cannot find answers to tec hnical questions on the soft ware i n the sources
listed above, please contact your l oc al Si em ens office.
You will find the addresses:
in the “README.RTF” in the main folder of the SIMATI C NET CD
on the I nternet (http://www.ad.siemens.de/net)
in our catalog IK PI
Training for SIMATIC NET
Who to Contact about Training Courses:
Siemens AG
Trainings-Center für Automatisierungs- und Antriebstechnik
A&D PT 49 Kursbüro
Östliche Rheinbrück enstr e 50
76181 Karlsruhe
Germany
Phone: +49 - ( 0) 721 - 595 - 2917
Fax: +49 - ( 0) 721 - 595 - 6087
Internet: http://www.ad.siemens.de/training
Certification
The produc ts and systems l isted in t his document are manufactured and mar k eted
using a qual ity managem ent system complyi ng with DIN ISO 9001 and cert ifi ed by
DQS ( c ertificate registration no. 2613) . T he DQS certificate is recogni z ed in all
IQ Net countries (Reg. No. 2613).
Standards and A pprov als
The CP 5613, CP 5613 FO, CP 5614, and CP 5614 FO meet the requi r em ents of
the CE m ar k. CSA and UL approv als have also been obtai ned.
For m or e detailed informati on on the approvals and standards, refer to the
Appendi x Notes on the CE Mark of SIMATI C NET Products”.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
64 S79220-A5814-X-01-7437
2 Components of the Product
Check List
Pl ease check that you have received all the c om ponents:
Product Informati on CP (DP-Base), DP-5613, FMS-5613, S7-5613
Install ation Instruct ions for all SIM ATIC NET software products
Descripti on “ A dv anc ed PC Configur ati on” (mi gr ation manual)
Product CD 07/2001 “ SIM ATIC NET Net working for Industr y®
Documentation CD 07/2001 “SI MATI C NET Manual Collec tion”
Key diskette (for the products DP-5613, FMS-5613 and S7-5613)
Software product c er tif icate and contract
The produc ts 6GK1713-... also contain the following c om ponents:
One of the f ollowing modules:
CP 5613
CP 5614
CP 5613 FO
CP 5614 FO
Product Information/Installation Instructions for this module
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 65
“SIMATIC NET Industrial Commun ica tion PC/Windows” CD
The CD “SIM ATIC NET Industri al Communi c ation PC/Wi ndows” contains the
following components f or t he CP 5613/CP 5614:
The produ ct “CP 5613/CP 5614 (DP-Base)”
for operating the CP of the DP-Base programming interface under Windows NT
and Windows 2000.
The product “DP-5613/Windows”
for the DP master mode of a CP with the DP-Lib programm ing interf ac e under
Windows NT and Wi ndows 2000 (compatibl e with the DP interface of the
CP 5412 (A2)).
The product “FMS-5613/Windows”
for the FMS master mode of t he CP under W indows NT and Windows
Professional.
The product “S7-5613/Windows”
for S7 operati on of t he CP under W indows NT and Windows 20 00 ( c ompatibl e
with t he S 7 interface of t he CP 5412 (A2) ) and the configurati on soft ware
SIMATIC NCM PC.
The f ollowing com ponents are incl uded in all the products and are instal led
automatically:
SIMATIC NCM PC configuration software
Software f or operati ng the CP in the FDL mode under Windows NT and
Windows 20 00 ( c ompatible with the F DL interface of the CP 5412 (A2)), product
v er si on 2.0 or hi gher .
Software to support PG functionalit y (support of STEP 5/STEP 7) under
Windows NT and Wi ndows 2000, product ver si on 2.0 or higher.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
66 S79220-A5814-X-01-7437
3 Requirements and Restrictions
3.1 R eq uir ement s an d R estrictio ns for th e Har dw a re
PR OFI BUS Network Cards
Duri ng oper ati on, one or m or e PROFIBUS c ar ds can be used.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 67
3.2 R eq uir ement s an d R estrictio ns for th e Softwar e
Operating Systems
The f ollowing Mi c r osoft operati ng systems are supported:
Windows 2000
Windows 2000 Professional M ultil anguage with Service Pac k 1
Windows 2000 Server Multilanguage with S ervice Pac k 1
Windows NT
Windows NT Version 4.0 Wor k station with Serv ic e P ac k 6a
Windows NT Version 4.0 Server wit h Servic e P ack 6a
For inform ation on approvals of other service pac k s, please contac t your Si em ens
representative.
Real-Time Requirements
Windows 2000 and Windows NT are not real-time operating system s. Real- time
requi r em ents cannot t her efore be met.
As a result, it is possible that when starting progr am s or reading files, your
application is not executed for several 100 ms.
The points bel ow will help you to optimize y our system and to achieve r eaction
times approaching those of a real-time system:
You should have enough mem or y so that W indows only seldom needs to use
the page f ile.
Avoid long access to di sket tes, hard disks or a CD, as i s the c ase when star ti ng
lar ge pr ogr am s.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
68 S79220-A5814-X-01-7437
4 CP 5613/CP 5614 (DP-Base)
4.1 Situation Following Installation
Data Copied to the Hard Disk
Bel ow, you will fi nd an ov erview of the folder s created i n the installation folder (for
example, c:\SIEMENS\SIMATIC.NET) of your PC that are rel evant for
programming:
Folder Note
CP5613_CP5614 Pr oduc t Information (l iesmich. txt, readme. txt),
inform ation and instructions on uninstalli ng
CP5613_CP5614\ pr og I nformation for DP progr ammers
CP5613_CP5614\ examples Sample program s
CP5613_CP5614\ databa se Database s for sample program s
CP5613_CP5614\ logf iles Log files created by the diagnosti c pr ogr am s.
CP5613_CP5614\ diagnose Diagnostic pr ogr am s
Caution
Do not delete files stored i n this folder sinc e this coul d im pair the functi onality of
other pr ogr ams.
If y ou want to uni nstall the product, use the system pr ogr am pr ov ided by
Windows NT/Windows 2000 (t askbar St art Settings Control Panel
Add/Remove Programs).
Note
Please note that it is not possi ble t o use the DP-5613/Windows int erfac e and the
DP-Base programming interface included in the product “CP 5613/CP 5614 (DP-
Base)” on one CP at the same tim e.
Al though it is possible to install both products at the same time, you c an only run
programs that use one of these interfaces at the same time on one CP.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 69
4.2 Starting the Simple Sample Program
Purpose of the “ExamEasy” Sample Progra m
Apart from familiar iz ing DP programm er s with the program, the sim ple sample
program can also be used to test c ommunicati on with a DP slave.
To use this function, you must have a DP slave with at least one i nput and out put
byte. In the supplied ExamEasy sam ple STE P 7 project, the slav e is confi gur ed as
an ET 200B at node addres s 3; the data transmission rate is 1.5 Mbps.
Even if you have more than one CP 5613 or CP 5614, t he pr ogr am always uses
the acc ess point CP _L2_1:”.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
70 S79220-A5814-X-01-7437
Procedure
Follow the steps outlined below to start the “ExamEasy” sample pr ogr am :
Step Description
1 Set the STEP 7 project Exam E asy f or t he sample program.
2 If the slave you want t o addr ess is not an ET 200B at node address 3
or you do not oper ate at 1.5 Mbps, adapt the ExamEasy STEP 7
proj ec t to your configurati on.
3Star t the “ExamEasy” progr am ( taskbar Start Simatic
SIMATIC NET CP5613_CP5614 Examples Easy).
4 The c ur r ent input and output byte are di spl ay ed in a DOS box.
5 If you now ty pe in and ent er a different value f or the out put byte, the
new output val ue is adopted and the curr ent input and output byte
displayed.
If y ou make a blank entry, the out put byte is retained and the current
input and output byte is display ed.
6 Ty pe “ q” and pr ess the enter k ey to quit the progr am .
Note 1
The source f iles for the sam ple pr ogr am ar e in the
“CP5613_CP5614\Examples\Easy” folder of your installation folder.
Note 2
The sam ple pr o
g
ram occ upies the DP - RA M pointer exclusivel
y
. The interface does
not allow parallel operati on of a second DP application i f the pointer is not
alternat ely r eleased by t he applications.
Results
If an er r or occ ur s, the program di spl ay s a message.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 71
4.3 Starting the Complete Sample Program
Purpose of the “ExamComp” Sa mple Program
Apart from familiar iz ing DP programm er s with the program, the com pr ehensive
sample program can al so be used to test c ommunicati on with up to three DP
slaves.
Even if you have more than one CP 5613 or CP 5614, t he pr ogr am al ways uses
the acc ess point CP _L2_1:”.
It assumes a conf iguration with the f ollowing three slav es, one or two of which can
be omi tt ed:
Slave
address Configuration Configured as
3 1 Input byt e, 1 out put byte ET 200 B 8DI/DO
4 1 Input byt e, 1 out put byte ET 200 B 8DI/DO
6 Any standar d sl ave
The cur r ent configurati on of t his slave is
read out with the DP_get_ac tual _cfg
function.
ET 200 M IM153
The dat a transmi ssion rate is 1.5 Mbps.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
72 S79220-A5814-X-01-7437
Procedure
Follow the steps outlined below to start the “ExamComp” sam ple pr ogr am:
Step Description
1 Set the STEP 7 project Exam Com p that matc hes the sample program
as the STE P 7 project to be used.
2 If the configur ation does not mat c h the slav es you want to addr es s or
the actual data transmission rate, adapt the ExamComp STE P 7
proj ec t to your configurati on.
3Star t the “ExamComp” sample program (taskbar S t art Simatic
SIMATIC NET CP5613_CP5614 Examples
Complete).
4 The pr ogr am pr ov ides various modes for selec tion. Sel ect a mode or
any combinati on of t hese modes (for example, “12” for simult aneous
operation of modes 1 and 2).
5The progr am now communicates using the selec ted modes wit h the
correspondi ng sl aves. Press the enter k ey to display the cur r ent status.
6 Ty pe “ q” and pr ess the enter k ey to quit the progr am .
Note 1
The source f iles for the sam ple pr ogr am ar e in the
“CP5613_CP5614\Examples\Complete” folder of your installation folder.
Note 2
The sam ple pr o
g
ram occ upies the DP - RA M pointer exclusivel
y
. The interface does
not allow parallel operati on of a second DP application i f the pointer is not
alternat ely r eleased by t he applications.
Results
The cur r ent data are displayed for each of t he three sl aves or a message if an err or
occurs.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 73
4.4 Starting the “Fast Logic” Sample Program
Purpose of the “ExamFast” Sample Program
The “ExamFast” sampl e pr ogr am explains the “F ast Logic functionali ty of the DP
m aster . You will get to know the functions DP_fast_l ogic _on, DP_fast_logi c _off and
how to handle F ast- Logic semaphores.
If several CP 5613 or CP 5614 m odules exi st, you c an sel ec t t he CP to be used
when you start the program . I D 2 is always used as the Fast Logic ID.
It assumes a conf iguration with the f ollowing two sl aves:
Slave Configuration Configured as
1 1 Input byt e, 1 out put byte ET 200 B 8DI/8DO, address 3
2 1 Input byt e, 1 out put byte ET 200 B 8DI/8DO, address 4
The dat a transmi ssion rate is 1.5 Mbps.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
74 S79220-A5814-X-01-7437
Procedure
Follow the steps outlined below to start the “ExamFast” sample program:
Step Description
1 Set the STEP 7 project ExamFast that matc hes the sample program as
the STEP 7 sam ple projec t t o be used.
2 If the configur ation does not mat c h the slav es you want to addr es s or
the actual data transmission rate, adapt the ExamFast ST EP 7 projec t .
3Star t the “ExamFast” sample program (t askbar S t art Simatic
SIMATIC NET CP5613_CP5614 Examples
FastLogic).
4 The pr ogr am pr om pts the user to prov ok e the Fast Logi c ev ent. To
trigger the F ast Logic ev ent, bit 1 in input byte 0 of the slave with
address 3 m ust be set to “1”.
5The progr am now communicates cyclically with the selected slav es.
Press the enter k ey to display the current status.
6 Ty pe “ q” and pr ess the enter k ey to quit the progr am .
Note 1
The source f iles for the sam ple pr ogr am ar e in the
“CP5613_CP5614\Examples\FastLogic” fo lder of your installation folder.
Note 2
The sam ple pr o
g
ram occ upies the DP - RA M pointer exclusivel
y
. The interface does
not allow parallel operati on of a second DP application i f the pointer is not
alternat ely r eleased by t he applications.
Results
The cur r ent slave states and any Fast Logic ev ents that occurr ed ar e displ ay ed. If
an error oc c ur r ed, texts are display ed.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 75
4.5 Starting the Transfer Sample Program for the CP 5614
Purpose of the “Transfer” Sample Program
Apart from familiar iz ing DP programm er s, the T r ansfer sample program can be
used to test t he c ommunicati on with more than one DP sl av e and a higher - lev el
m aster . If several CP 5613 or CP 5614 m odules exist, y ou can select the CP to be
used when you start the pr ogr am .
Explanation of the Transfer Functi onality
The CP 5614 is suitable for hier ar c hic ally struct ur ed networks. The master sect ion
of t he CP 5614 oper ates wi th “subordi nate” actuator s and sensors on it s own bus
segment . The slave m odule of the CP 5614 is attached to a contr olling stati on v ia a
separate bu s segment .
One f unc tion that is oft en r equir ed is the passing on of actuator and sensor data to
the control system. The soft ware that provides this func tionality is known as the
Transfer software.
Actuator Senso
r
PROFIBUS DP (II)
PROFIBUS DP (I)
RS485
CP 5614
RS485
Slave
Master
Control
system
Transfer
software
PC
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
76 S79220-A5814-X-01-7437
Transfer Program
With a transfer configurat ion progr am, y ou can specify which data from the
actuators or sensors are pas sed on to the cont r ol system (see Section 4.6).
The sam ple suppl ied (STE P 7 project and transf er configuration fil e) was wri tten for
a slave ET 200B and a CP 5614.
Slave Configuration Configured as
1 1 Input byt e, 1 out put byte ET 200 B 8DI/8DO, address 3
2 2 i nput bytes, 2 output bytes S lave m odule CP 5614, address 10
The dat a transmi ssion rate is 1.5 Mbps.
The t r ansfer program works wi th the “ transfer .tr a” file and the STEP 7 project
“Exam ples” (dat abase “pcst_transfer.xdb”) . A data transf er fr om an ET 200B input
bit to an output bit is confi gur ed in the “transfer.tr a” file. A data tr ansfer from the
slave module of the CP 5614 bits 0 to 6 to an ET 200B starti ng at bit 1 is also
configured.
Note
If y our DP env ir onm ent is differ ent f r om the one r equir ed for this exam ple, cr eate a
suitable STEP 7 proj ect with SIMATIC NCM PC or STEP 7 V5.1 SP2. The slave
propert ies of t he CP 5614 are set in the “Sampl e.G S D” file. If you want to define a
differ ent number of input/out put ports for the CP 5614, please edit this file and
creat e a new GSD file for the CP 5614.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 77
Procedure
Follow the steps outlined below to start the “Tr ansfer” sample pr ogr am :
Step Description
1 Please set the ST EP 7 projec t “Examples” that matches the sam ple
program (database “pcst_t r ansfer.xdb”).
2Star t the “Transfer” sample program (taskbar Start
Simat ic SIMATIC NET CP5613_CP 5614 E xampl es
Transfer5614).
3The progr am r uns i n a DOS box and modifi es the input data of t he
slave module of the CP 5614. On the ET 200B, you can see how the
CP 5614 slave module increments the va lues.
4 Ty pe “ q” and pr ess the enter k ey to quit the progr am .
Note 1
The source f iles for the sam ple pr ogr am ar e in the
“CP5613_CP5614\Examples\TRANSFER5614” folder of your installation folder.
Note 2
The sam ple pr o
g
ram occ upies the DP - RA M pointer exclusivel
y
. The interface does
not allow parallel operati on of a second DP application i f the pointer is not
alternat ely r eleased by t he applications.
Results
On t he ET 200B , you c an m odify the first i nput bit (value 0 or 1). This i nput bit is
transferr ed to the first output bit (LE D) by the transfer pr ogr am.
A count er is implement ed in the CP 5614 sl ave modul e. 7 bit s of the counter
readi ng ar e transferred to the LEDs, bits 1-7 of the ET 200B by the transfer
program.
The t r ansfer program transfers all the configured dat a c y cli c ally ev er y 10 ms.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
78 S79220-A5814-X-01-7437
4.6 Configuring the Transfe r for the CP 5 614 Transfer
Sample Program
Purpose of the “Transfer Configuration” Tool
Using the tool, y ou can confi gur e whic h input, output or diagnosti c data is
transferr ed between the att ac hed sl av es and the higher- lev el m aster in both
directions.
All ac c ess addresses begin with 0, in other words, the lowest order bit or byte of a
slave or the master m odule is bi t or byte 0.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 79
Procedure
Follow the steps outlined below to start the “Tr ansfer Configurati on” tool:
Step Description
1Star t the “Transfer Confi gur ation” tool (taskbar St art Si matic
SIMATIC NET CP5613_CP5614 Transfer5614-Configuration).
2 Select the file for storing the transfer list or c r eate a new file.
3Enter y our data in the transfer c onfigurati on window. A short form of the
data is display ed as an overvi ew in the transfer list window.
Generally, an out put (source on t he left - hand si de) is li nk ed to an input
(desti nati on on the ri ght-hand side) .
4 Save the transf er list when it is compl ete.
Results
The fi gur e above illustr ates the confi gur ation for the sam ple pr ogr am :
Bi t 0 of the sl av e ET 200B with address 3 is copied to it s output. Bits 0-6 of the
slave module (addr ess 127) are copied to bits 1-7 of the ET 200 B.
The LEDs of the ET 200 B flash in time with the counter addressi ng of the sl av e
module.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
80 S79220-A5814-X-01-7437
5 DP-5613/Windows
5.1 Properties
Prope rties of DP-56 13/Windows
With “DP-5613/W indows”, the DP- Lib programming interface known from the
CP 5412 (A2) is available for the DP master mode for the CP 5613 and CP 5614.
This should no longer be used for new dev elopments; instead, y ou shoul d use the
OPC in te rfa ce .
You should al so note that parallel operation of this i nt erface with the DP-Base
programming int erface in the product “CP 5613/CP 5614 (DP-Base)” is not
possible.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 81
5.2 Checking and Configuring DP-5613/Windows
Overview
Now that you have installed the software and the module and configured the DP
Base programming interf ac e, t his section explains how you can confi gur e the
m odule for DP-5613/Windows operation.
Note
The produc t DP-5613/W indows contains the DP - Lib progr amming int erface and
several programs for testing the functionality of this interface.
Please note that it is not possi ble t o use this i nt erface and the DP-Base
programming int erface included i n the product “CP 5613/CP 5614 (DP-Base)” on
one CP at the sam e time.
Al though it is possible to install both products at the same time, you c an only run
programs that use one of these interfaces at the same time on one CP.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
82 S79220-A5814-X-01-7437
5.3 Situation Following Installation with DP
Data Copied to the Hard Disk
Bel ow, you will fi nd an ov erview of the folder s created i n the installation folder (for
example, c:\SIEMENS\SIMATIC.NET) of your PC that are rel evant for
programming:
Folder Note
opc2 OPC server, information, and samples
Caution
Do not delete files stored i n this folder sinc e this coul d im pair the functi onality of
other pr ogr ams.
If y ou want to uni nstall the product, use the system pr ogr am pr ov ided by
Windows NT/Windows 2000 (t askbar St art Settings Control Panel
Add/Remove Programs).
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 83
6 FMS-5613/Windows
6.1 Properties
Prope rties of FMS-5613
With “FMS- 5613/W indows”, the essential proper ti es of the FMS pr ogr amming
interface known from the CP 5412 (A2) ar e also availabl e for the CP 5613 and
CP 5614. This shoul d no longer be used for new development s; instead, you
should use t he OPC interface.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
84 S79220-A5814-X-01-7437
6.2 Situation Following Installation
Data Copied to the Hard Disk
Bel ow, you will fi nd an ov erview of the folder s created i n the installation folder (for
example, c:\SIEMENS\SIMATIC.NET) of your PC that are rel evant for
programming:
Folder Note
opc2 OPC server, information, and samples
Caution
Do not delete files stored i n this folder sinc e this coul d im pair the functi onality of
other pr ogr ams.
If y ou want to uni nstall the product, use the system pr ogr am pr ov ided by
Windows NT/Windows 2000 (t askbar St art Settings Control Panel
Add/Remove Programs).
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 85
7 S7-5613/Windows
7.1 Properties
Properties of S7-5613
With "S7-5613/Wi ndows”, the S 7 interf ac e known fr om the CP 5412 (A2) is
av ailable wit h c ert ain ex tensions for the CP 5613 and CP 5614. Thi s should no
longer be used for new development s; instead, you should use the OPC int erfac e.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
86 S79220-A5814-X-01-7437
7.2 Situation Following Installation
Data Copied to the Hard Disk
Bel ow, you will fi nd an ov erview of the folder s created i n the installation folder (for
example, c:\SIEMENS\SIMATIC.NET) of your PC that are rel evant for
programming:
Folder Note
opc2 OPC server, information, and samples
Caution
Do not delete files stored i n this folder sinc e this coul d im pair the functi onality of
other pr ogr ams.
If y ou want to uni nstall the product, use the system pr ogr am pr ov ided by
Windows NT/Windows 2000 (t askbar St art Settings Control Panel
Add/Remove Programs).
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 87
8 PG Mode with STEP 5 / STEP 7
No Conf iguration
To work i n the PG mode with STEP 5/STEP 7, no configur ation i s necessary. All
that is necessary is to set t he bus parameters in the “S et PG/ P C Int erface”
program.
For m or e detailed informati on, refer to the descriptions of STEP 5/STEP 7.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
88 S79220-A5814-X-01-7437
9 FAQ (Frequently Asked Questions)
9.1 FAQs about the Communications Properties of the
Product
9.1.1 Which software versions exist and how do they differ from each
other?
Software version V1.0
What' s New? Relevan t
Documentation
Basic version for CP 5613
Not supported:
DPC1, DP C2
• FDL
Fast Logic
Use of m or e than one CP 5613/CP 5614 at the
same time
Use of one CP 5613/CP 5614 by several
application programs at the same time
User watchdog
Sl av e pr oper ties of t he CP 5614
STEP 7
Online functions of SIMAT IC NCM PC or STEP
7 V5.1 SP2
DP master cl ass 2 (diagnostics)
Installation Instructions,
rel ease 1, 1999
Programming Interface,
rel ease 1, 1999
Software version V1.1
As V1.0
Also supp orted:
Sl av e functions and transfer mec hanism of the
CP 5614
Installation Instructions,
rel ease 1, 1999
Programming Interface,
rel ease 1, 1999
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 89
Software version V1.2
What' s New? Relevan t
Documentation
Supported:
Sl av e pr oper ties of t he CP 5614
Fast Logic
User watchdog for DP master ( not f or sl av e
functions)
Use of m or e than one CP 5613/CP 5614 at
the same time
Use of one CP 5613/CP 5614 by several
application programs at the same time
Not supported:
DPC1, DP C2
• FDL
User watchdog for sl av e functions
STEP 7
DP master cl ass 2 (diagnostics)
Installation Instructions,
rel ease 2, 1999
Programming Interface,
rel ease 2, 1999
Software version V2.0
What' s New? Relevant
Documentation
Supported:
Sl av e pr oper ties of t he CP 5614
Fast Logic
User watchdog for DP master ( not f or sl av e
functions)
Up to f our CP 5613/CP 5614 modules at the
same time
Use of one CP 5613/CP 5614 by several
application programs at the same time.
DPC1 (version 1. 13, as for CP 5412 (A2)
V5.0 or higher )
DPC2
• FDL
• S7
Support of STEP 7, version 5.0, f r om servi c e
pack 3 onwards
Support of PG functionalit y with STE P 5 and
STEP 7
Not supported:
User watchdog for sl av e functions
DPC1 (alarm s fully c om pliant with the V1.14
standard)
DP master cl ass 2 (diagnostics)
Installation Instructions,
rel ease 3, 1999
DP-Base Programming
Int erfac e, release 3, 1999
DP-Master Programming
Int erfac e, release 5, 1999
DP-Base Programming
Int erfac e, release 3, 1999
S7 program m ing int erf ac e,
rel ease 5, 1999
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
90 S79220-A5814-X-01-7437
Software version V2.1
What' s New? Relevan t
Documentation
Supported:
• FMS
Constant scan time m ode - t he c onstant tim e
scan param eters m ust be set in STE P 7/NCM
V5.1.
Not supported:
User watchdog for sl av e functions
DPC1 (alarm s fully c om pliant with the V1.14
standard)
DP master cl ass 2 (diagnostics)
FMS Programming Interface,
rel ease 5
Software version V6.0
What' s New? Relevant
Documentation
Supported:
New configuration with SIM ATIC NCM PC or
STEP 7 V5.1 SP2
Not supported:
User watchdog for sl av e functions
DPC1 (alarm s fully c om pliant with the V1.14
standard)
"Conf iguring PC Stations wi th
SIM ATIC NCM PC” m anual
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 91
9.2 Questions on the Technical Specifications
9.2.1 Questions on the Technical Specifications of the Software
Products
With which c ommunication partners ca n the product be operate d?
DP master o f the CP 5613/CP 5614
The DP m aster of t he CP 5613/CP 5614 can be operated with all certif ied DP
slaves.
DP slave of the CP 5614
The DP sl av e of t he CP 5614 can be operated with all c ertified DP m aster stations.
What are the data lengths supported for DP?
Maximum length of the DP input dat a: 244 bytes per slave
Maximum length of the DP output data: 244 by tes per slave
Maximum length of the DP diagnostic data: 244 bytes per slave
Num ber of DP sl av es: 124
Calculation:
Theoreti c al m aximum ( station addresses 0-127) 128
One addres s i s used by the CP 5613/ CP 5614 -1
Address 127 i s reserved for broadcast -1
Reserve address 0 f or DP m aster Class 2 (recommended) -1
Reserve address 126 f or node initi aliz ation (rec ommended) -1
Result 124
Maximum number of simultaneous
DPC1 j obs (read/writ e) : one per slave
Maximum number of simultaneous
DPC2 connecti ons (read/writ e) : 48
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
92 S79220-A5814-X-01-7437
What are the data lengths supported for FMS?
Maximum number of FMS applicati on pr ogr am s: 5
The f ollowing t able shows the maximum number of F M S connections
depending on the number of credi ts:
Number of Credits Maximum Number of FMS Connections
140
220
SAPI-FMS allows the operation of two CP 5613 modules.
How many reque sts are supported for FDL?
A maxim um of 118 unpr oc essed FDL requests can be in transit bet ween two
stations.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 93
What is the maximum number of applications and connections supporte d for
S7?
For S 7, t he m aximum num ber of applicati on pr ogr am s operat ing simultaneousl y
and the max im um num ber of sim ultaneous S7 connect ions is defined.
Maximum Number of S7 Applic ation Progr am s
Up to 10 S7 applic ation program s can be operated at the sam e time; in other
words, a total of up to 10 logons with “s7-ini t()” are supported.
The f ollowing t able illustrates this based on two sampl e c om binations:
Numb er of Application
Programs Number of Logons with s7-ini t() per
Application Program
10 1
52
Maximum number of simul t aneous S 7 connect io ns
The maximum number of S7 connections depends on the following:
PDU size
Number of cr edits
The f ollowing t able lists the m ax imum number of open S7 c onnec tions under
the conditi ons li sted above.
PDU Size Numb er of S 7 Connect io ns
for Credit 1 Number of S7 Connectio ns
for Credit 2
112 50 35
240 50 35
480 50 35
960 30 15
Which communications protocols ar e supported?
See version table, Secti on 9.1. 1.
Can STEP 7 also be operated with the CP 5613/CP 5614 ?
Refer to the versi on table at the beginning of Secti on 9.1.1.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
94 S79220-A5814-X-01-7437
Can STEP 5 also be operated with the CP 5613/CP 5614 ?
Refer to the versi on table at the beginning of Secti on 9.1.1.
Parallel Opera tion of Protocols
A maxim um of two protocols can be operat ed at the same time, for
ex am ple P ROF IBUS DP and PROFIBUS FMS.
From wh ich version onwards ar e multiple modules supported?
Refer to the versi on table at the beginning of Secti on 9.1.
Are product licenses required for the CP 5613/CP 5614?
Licenses are required for the products DP-5613, FMS-5613 and S7-5613.
For the driv er s and software for DP operati on with the CP 5613 and CP 5614 via
the DP B ase program m ing interface no license i s necessary. A license i s al so not
required for purely FDL operation.
Can the CP adapt itself to existing bus parameters dynamically if the network is
alread y being used by other PROFIBUS masters when it is started up?
The DP sl av e secti on of the CP 5614 can adapt itself to the bus parameters of the
att ac hed network.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 95
9.2.2 Questions on the Technical Specifications of the CP 5613/CP 5614
What is the maximum performance that the CP can achieve?
Property Value
Data rate reading the process image f r om the
PC 3 Kbytes/ms
Data rate writi ng the proc ess image from the
PC 8 Kbytes/ms
Average signal pr opagati on time 50 µs + bus propagat ion time
Maximal signal pr opagati on time of slave 100 µs + bus propagat ion t im e
Which data transmission rates are supporte d?
9. 6 Kbps
19.2 Kbps
45. 45 Kbps
93. 75 Kbps
187.5 Kbps
500.0 Kbps
1.5 Mbps
3.0 Mbps
6.0 Mbps
12.0 Mbps
How many CP 5613/CP 5614 modules can be operated at the same time?
Up to f our CP 5613/CP 5614 m odules can be operated at the same tim e.
The CP 5613/CP 5614 does not work on a Celsius 620 computer with
Tyan 100 motherboard
This problem has been fixed from hardware version 03 (mid 2000).
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
96 S79220-A5814-X-01-7437
The CP 5613/CP 5614 does not work on an SNI Scenic 860 computer with D1127
motherboard under Windows NT
On t his computer, “Plug and Pl ay is activated as the default operating system
setting i n the BIOS. Si nc e Windows NT does not support “ P lug and Play
functionality, you must set “P&P OS” to “no in the BIOS.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 97
10 Notes on the CE Mark of SIMATIC NET
Products
Product Name :
SIM ATIC NET, CP 5613 C79458-L800 0- A 77
SIM ATIC NET, CP 5614 C79458-L800 1- A 77
SIM ATIC NET, CP 5613 FO A5E00047996
SIM ATIC NET, CP 5614 FO A5E00047997
EMC Directi ve
The SIMA TI C NET pr oduc ts l isted above m eet t he r equir em ents of the following
directive:
89/336/ E E C “ El ec tromagnetic Compatibilit y
Area of Application
The produc ts are designed for use in t he following areas:
Area of A pplic ation Requir ements
Noise emission Noise immunity
Househol d, comm er ci al, light industr y EN 50081-1 : 1992 EN 50082-1 : 1997
Industry EN 50081-2 : 1993 EN 50082-2 : 1995
Inst allatio n G uidelines
The produc t meet s the requi r em ents provi ding y ou adhere to the guideli nes for
install ati on and safet y described i n this Section “Notes on the CE Mark” and i n the
following document ation:
SIM ATIC NET, PROFIBUS Networks, manual
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
98 S79220-A5814-X-01-7437
Conformity Certificates
The EU c onformity certificates are avail able for the relevant authorities accor ding to
the EU dir ec tive and are kept at t he following address:
Si em ens Aktiengesellschaft
Bereich Automatisierungs- und Antriebstechnik
Industrielle Komm unik ation (A&D PT 2)
Postfach 4848
D-90327 Nürnberg
Germany
Directive on Machines
The produc t remains a component in complianc e with Artic le 4(2) of the EU
dir ec tive on machi nes 89/392/EEC.
According to the directive on machines, we are obli ged to point out that the product
described is intended solely for installation in a machine. Before the final product
can be put into operati on, it must be tested to ensure t hat it c onforms with the
dir ec tive 89/ 392/EE C.
Note for Australia
The produc ts meet the requirem ents of the AS/NZS 3548 standard.
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 99
11 Glossary
BIOS Basic
Input
Output
System – BIOS means the part of the sof tware
that c r eates a l ink between the hardware and the driver s of the
operating system. The BIOS is used to abstract the underlying
hardware, the corr espondi ng soft ware i s stored on an EP ROM.
Impor tant component s i nc lude, for exam ple, the loader for the boot
sector, the (hardware) SE TUP for stipulating the hardware
configuration and for sett ing the tim e.
COM P ROFIBUS Configuration Manager for Process Field Bus – previous program f or
creat ing dat abases containi ng a descripti on of t he system.
COM P ROFIB US will be r eplac ed from DP, FMS or S7- 5613 pr oduc t
v er si on V 6.0 and higher by configur ation with the SIMATIC NCM PC
configuration tool or STEP 7 V5. 1 SP 2.
CP Communicati ons Proc essor – communications modul e/network car d
for i nstallation in comput er s or progr ammabl e contr ollers.
CP 5613 FO Communications processor for PROFIBUS, PCI card with it s own
processor and a f iber- optic port.
CP 5614 FO Communicati ons proces sor for PROFI B US, same f unctions as the
CP 5613 but with additional slave m odule and attac hm ent. Equi pped
with a fi ber - optic and an electric al por t.
CP 5613 Communications processor for PROFIBUS, PCI card with it s own
processor
CP 5614 Communicati ons proces sor for PROFI B US, same f unctions as the
CP 5613 but with additional slave m odule and attac hm ent
DIN Deut sches In stitut fü r Normung (German Standar ds Instit ute)
DLL Dynam ic Link Li br ar y – group of functi ons availabl e to mor e than one
program but that are only loaded in memory onc e (W indows)
DOS-BOX Console window, MS-DOS prompt
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
100 S79220-A5814-X-01-7437
DP Distributed Peripheral I/Os – input/ output modul es used in a
distr ibut ed c onfigurati on. T he pr ogr ammable cont r oller and distr ibuted
I/Os are connected vi a the PROFIB US - DP bus system.
DPRAM Dual Port Random Access Mem or y (Dual-Port RAM) – allows
simultaneous acces s by t wo computer units (CP and CPU) to one
m em ory ar ea ( RAM).
EN 50170 PROFIBUS
FDL Fieldbus Data Link – Layer 2 of the ISO refer enc e m odel in
PROFIBUS; it consists of Fieldbus Link Control (FCL) and Medium
Access Control (MAC)
FMS Fieldbus Message Spec ifi c ation – upper subl ay er of Layer 7 of the
ISO reference m odel in P ROFIB US. It incl udes the functi ons: pr otocol
m ac hine, generati on of PDUs and coding/dec oding and int er pr etati on
of t he pr otocol dat a unit.
GSD file Fil e c ontaining the pr oper ties of a DP slave required for configur ati on.
The G S D file contains an exact descripti on of t he sl av e functionali ty.
For this reason, only one ex am ple is supplied with the CP 5614 that
m ust be adapted to the actual applicati on.
Hardware
resources The interrupt and m em ory ranges required by the CP 5613/CP 5614
are assigned automatic ally by the P CI-B IO S during start up.
I/O Peripheral Inputs/Output s of a programm able c ontroller
IK PI Catalog of SIMATI C NET pr oduc ts
IRQ Interrupt Request
ISO Internat ional Standard Or ganiz ation – International organizati on
based in Geneva responsible for formulating general standards,
particular ly in the area of dat a transmission.
LED Light Emitting Diode
MPI Multi Point Interface for SI MATIC S7
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
S79220-A5814-X-01-7437 101
NCM SIMATIC Network Configuration Manager for PC – Configuration
software f or SIMA TI C NET c ommunicati ons proces sors.
Overflow When the maximum permi tt ed v alue is exceeded
PC Personal Computer
PCI Peripher al Com puter Interface
PG Program m ing devic e belonging to the SIM ATIC product f amil y fr om
Si em ens AG; PGs are used for programm ing, confi gur ing,
m aintenance, and serv ice.
PLC Program mable Logic Controller
PNO PROFIB US Users Organization
PROFIBUS Process Field Bus – a fi eldbus complying with EN 50170 Vol. 2
PROFI B US (DIN 19245; previousl y : SINEC L2).
S7 Prot oc ol for communication with a SIM ATIC S7 PLC
SELV Safety Extra Low Voltage
SIMATIC NCM PC SIMAT I C Network Configuration Manager for P C – Confi gur ati on
software f or SIMA TI C NET P C communic ations processor s.
SIMATIC S7 SIM ATIC S7 process control system from Si em ens
Token The t ok en is the “ right to send” that is passed around the PRO FI B US
network when there is m or e than one master .
Product Information CP (DP-Base), DP, FMS and S7-5613/Window s
Product Information/Product Information CP (DP-Base), DP-Base, DP, FMS and S7-5613/Windows
102 S79220-A5814-X-01-7437
12 Index
A
Authorization hotline...............................61
C
Configuration
DP
STEP 7 project.....................70, 72, 74
tools ...................................................65
Custom er S uppor t..................................61
D
Data transmissi on rates ..........................95
DP-5613/Windows..................................80
F
Folder
database.......................................68, 82
diagnose.............................................68
examples............................................68
include................................................82
lib.......................................................82
logfiles................................................68
prog....................................................68
sample ...............................................82
Folder struc ture
CP-5613.............................................68
DP-5613.......................................82, 84
S7-5613........................................82, 86
N
Numeric data.........................................91
P
Performance..........................................95
Properties
DP-5613.............................................80
FMS-5613 ..........................................83
S7-5613..............................................85
R
Real- time requir em ents..........................67
S
Sampl e program ........................ 69, 71, 73
T
Technical S uppor t..................................61
Transfer
configuring..........................................78
sample program .................................75
V
Versions
Software.............................................88
W
Windows 2000 .......................................67
Windows NT ..........................................67
Anhang OP C- S er v er für S IMA TIC NET
Produkti nformation/Product Information OPC-Server für SIMATIC NET
C79000-Z8974-C75-01 A-1
Anhang „OPC-Server für SIMATIC NET“
Inhaltsverzeichnis
1 Hinweise zur Installation............................................................................................ 2
1.1 OPC Cli ent-Setup für DCOM-Betrieb................................................................2
2 Hinweise zu Protokollen ............................................................................................3
2.1 DP-Protokoll.....................................................................................................4
2.2 FMS-Protokoll ..................................................................................................5
2.3 S7-Protokoll......................................................................................................6
2.4 SEND/RECEIVE-Protokoll................................................................................7
3 Hinweise zu OPC........................................................................................................8
4 Hinweise zum OPC-Scout.......................................................................................... 9
Anhang OP C- S er v er für S IMA TIC NET
Produkti nformation/Product Information OPC-Server für SIMATIC NET
A-2 C79000-Z8974-C75-01
1 Hinweise zur Installation
1.1 OPC Client- Setup für DCOM-Betrieb
DCOM-Betrieb
Für den DCO M-Bet r ieb muss auf dem Cli ent -Rechner eine Mini mal-I nstallati on
durchgeführ t werden. Dabei werden di e benöti gten und von der O P C- Foundation
bereitgestel lten Komponenten und der OP C-Scout i nstalliert und registr iert.
Nach der Instal lation muss der DCO M-Bet r ieb eingeric htet werden. Beachten Sie
dazu das entsprechende Kapitel im Handbuch „ Industriel le Kommunikati on mit
PG/PC“ bz w. die HTM L- Onl ine- Hilfe.
Vorgehensweise
Gehen Sie bitte wie folgt z ur Instal lat ion der S oftware für den OPC-Client- Rec hner
vor:
Schritt Beschreibung
1 St ar ten Sie Ihr en Rec hner mit M ic r osoft Windows 2000 oder Win-
dows NT 4. 0.
2 Melden Sie sich als Admi nistr ator bei Ihr em
Wi ndows-System an.
3 Legen Sie di e S IMATIC NE T-CD in I hr CD- ROM-Laufwerk ein.
4 Verlassen Sie das Install ati onsprogramm, falls es v on der CD automa-
tisch ausgeführ t wird.
5 Wechsel n S ie in das Verzeichnis „\sw\opc_cl ient \di sk1" auf der
SIMATIC NET-CD.
6 St ar ten Sie das Programm „S etup. exe“ .
7 Geben S ie den Namen des Rechners an, auf dem der OPC- S er ver ge-
startet werden soll.
8 Nach erfol gr eicher Instal lat ion müssen Sie die DCOM - K onfi gur ati on
wie im Handbuc h beschrieben einstel len.
Anhang OP C- S er v er für S IMA TIC NET
Produkti nformation/Product Information OPC-Server für SIMATIC NET
C79000-Z8974-C75-01 A-3
2 Hinweise zu Protokollen
Zur Benutzung
In diesem K apit el werden für einzelne Pr otokoll e Hinweise gegeben.
Prot ok olle für die k eine weit er en Hinweise zu geben sind, er scheinen i n diesem
Kapi tel nicht.
Anhang OP C- S er v er für S IMA TIC NET
Produkti nformation/Product Information OPC-Server für SIMATIC NET
A-4 C79000-Z8974-C75-01
2.1 DP-Protokoll
Watchdog
Die mit Watchdog Ti meout“ in der Pr ojekti er ung eingestellte Zei t (Default - Wert
6000 Millisekunden) wird in den CP als Watc hdog- Zei t gel aden.
Gegebenenfalls muss diese Zeit noc h er höht werden, um das Auslösen des
Watc hdog wegen vom B etriebssystem ver ur sacht er Unterbrec hungen z u ver hin-
dern.
Anhang OP C- S er v er für S IMA TIC NET
Produkti nformation/Product Information OPC-Server für SIMATIC NET
C79000-Z8974-C75-01 A-5
2.2 FMS-Protokoll
Viele Verbindungen und große O bj ektverzeichnisse
Der OPC-Server baut die not wendigen F MS-Verbindungen unmi ttelbar nach dem
Ei nfügen des ersten It ems ei ner V er bindung auf. Fügt man Items, die vielen Ver -
bindungen z ugeor dnet sind, in eine Gr uppe ein, so müssen nacheinander viel e
Verbindungen aufgebaut werden.
Im Normalfall umfasst der Ver bindungsaufbau auch das Laden des Obj ek tver-
zei c hnisses vom Partnergerät. Dieser Vorgang nimmt in Abhängigkeit von der
Projekt ierung des Partnergeräts erhebl iche Zei t i n A nspruch, so dass unter Um-
ständen die Über wachungszeit ei ner V er bindung ablaufen k ann. Das hat zur Fol -
ge, dass der OPC-S er ver diese Verbindung wieder abbaut und die Ver bindung
nic ht benutz t werden kann.
In diesem Fal l sollten di e Obj ek tverzeichnisse der Partner ger äte unabhängi g vom
OPC- B etrieb i n der P r ojektierung festgelegt werden.
Beacht en S ie jedoch, dass Sie nac h Ä nder ungen der P r ojektierung des Part ner ge-
räts, die das Objekt ver z eichnis betreffen, das projekt ierte Objektverzeichnis auf
den aktuellen St and br ingen müssen.
Aufba u von asymmetrischen FMS-Verbindungen
Zu den asymmetri schen FMS-Verbindungen zähl t man Verbi ndungen mit den
Verbindungsattr ibut en I-D (I ist akt iver Par tner), I - O (I ak ti ver P ar tner) und D- O (D
aktiver P ar tner). Sie werden als asymmetrisch bezei c hnet, da an diesen Verbin-
dungen zwei St ati onen tei lnehmen, deren Roll e beim Ver bindungsaufbau unter -
schiedli c h ist. Während bei dem am häufi gsten benutzt en V er bindungstyp D- D je-
der der beiden Endstat ionen die Verbindung ak ti v zu der ander en S tation aufbau-
en kann, ist die Rol le des aktiven Ver bindungsaufbaus bei der I-D Ver bindung nur
dem I-Par tner zugeor dnet. B er üc k si c htigt man diese Rollenvertei lung bei der Pr o-
jek ti er ung nicht, so kann u. U. der V er bindungsaufbau mi sslingen.
Anhang OP C- S er v er für S IMA TIC NET
Produkti nformation/Product Information OPC-Server für SIMATIC NET
A-6 C79000-Z8974-C75-01
2.3 S7-Protokoll
Variablentypen
Folgender Var iablenty p wir d nic ht von allen Automat isier ungsgerät en unterstüt z t
und ist deshal b über den S 7- OPC-S er ver gr undsätz lich nicht anwendbar:
Bit-Arrays z. B. DB5,X0.2,3
Anhang OP C- S er v er für S IMA TIC NET
Produkti nformation/Product Information OPC-Server für SIMATIC NET
C79000-Z8974-C75-01 A-7
2.4 SEND/RECEIVE-Protokoll
Direk tzugriff auf S5-Pe ripherie
Wi rd über das SEND/RECEIVE-Protokoll ein Ausgang der S5-Peripherie direkt
beschrieben, so wi r d dieser Wert bei dem näc hsten Zyklus der S5 durc h das Pro-
zessabbild wieder über schrieben. Dieses Verhalten i st in den S 5-
Hantierungsbausteinen begr ündet.
Dauerhaft e V er änder ungen der A usgänge per Direktzugriff sind nur über S c hr eib-
zugriffe auf das Prozessabbil d ( B er eich A ) möglich.
Anhang OP C- S er v er für S IMA TIC NET
Produkti nformation/Product Information OPC-Server für SIMATIC NET
A-8 C79000-Z8974-C75-01
3 Hinw eise zu OPC
Parallelnutzung
Innerhalb eines OPC-Client s muss j eweils eine V er si on der OPC-S pez ifikati on
durchgängig benutz t werden. Der Mischbetr ieb von Sc hnit tstel len unt er schiedli c her
Versionen ist nicht z ulässig.
OPC Automation Interface 2.0
Das OPC Aut omati on Inter face 2. 0 wir d in einer von Siemens erstel lt en, geteste-
ten und fr eigegebenen Ver si on installiert.
Ak tivieren von „nur schreibbaren“ OPC-Items
Akt ive O P C- Items werden durch den OP C- S er ver beobac htet. Dazu setzt der
OPC- S er ver Leseauft r äge über das Netz ab. Werden jedoch Leseauft r äge auf nur
schreibbare SEND/RECEIVE-Vari ablen durchgeführt , so baut das Partnergerät di e
Verbindung ab und erst nach einiger Z eit wieder auf. „Nur schreibbare“ OPC-Items
dürfen deshalb nicht akt iviert werden.
Anhang OP C- S er v er für S IMA TIC NET
Produkti nformation/Product Information OPC-Server für SIMATIC NET
C79000-Z8974-C75-01 A-9
4 Hinw eise zum OPC-Scout
Performance
Der OP C- S c out i st ein Cli ent, der als Werkzeug z um Test und zur Inbet r iebnahme
vor gesehen i st. Bei Bet r ieb mit sehr vi elen Var iablen ergeben si c h je nach Leis-
tung des Rechners und ver wendetem Pr otokoll erhebli c he Reak ti onszeiten.
Werte generieren
Es ist nicht mögli c h, über die Scout -F unkti on „Werte generieren“ Arrays zu be-
schreiben oder negati ve Werte z u gener ieren.
Browsing
Es können mit dem O P C-Scout beim Browsi ng maximal 256 Item-Einträge in ei -
ner Ebene angezeigt werden.
Ak tivieren von „nur schreibbaren“ OPC-Items
Akt ive O P C- Items werden durch den OP C- S er ver beobac htet. Werden Leseauf-
träge auf „nur schreibbare“ V ar iablen durchgeführt , so bauen manc he P ar tnerge-
räte die Ver bindung ab und erst nac h einiger Zei t wieder auf. Eini ge P ar tnergeräte
reagi er en jedoch negati v auf solche A uftr äge. Deshalb dürfen „nur schreibbare“
Variablen nie aktivi ert werden. Im OPC-Scout erreicht m an dies, indem man diese
Variabl en in eine ni c ht akti ve G r uppe einfügt.
Anhang OP C- S er v er für S IMA TIC NET
Produkti nformation/Product Information OPC-Server für SIMATIC NET
A-10 C79000-Z8974-C75-01
Appendix O P C S er v er for S IMA TIC NET
Produkti nformation/Product Information OPC Server for SIMATIC NET
C79000-Z8974-C75-01 A-11
Appendix “OPC Server for SIMATIC NET”
Contents
1 Notes on Installation ................................................................................................12
1.1 OPC Client Setup for DCOM Operation..........................................................12
2 Notes on Protocols...................................................................................................13
2.1 DP Protocol....................................................................................................14
2.2 FMS Protocol .................................................................................................15
2.3 S7 Protocol.....................................................................................................16
2.4 SEND/RECEIVE Protocol...............................................................................17
3 Notes on OPC ...........................................................................................................18
4 Notes on the OPC Scout..........................................................................................19
Appendix O P C S er v er for S IMA TIC NET
Produkti nformation/Product Information OPC Server for SIMATIC NET
A-12 C79000-Z8974-C75-01
1 Notes on Installation
1.1 OPC Client Setup for DCOM Operation
DCOM Operation
For DCOM operati on, a mini mum install ati on is requi r ed on the cli ent comput er .
This involves install ing and registering t he r equired c omponents provided by the
OPC Foundation and t he OPC Sc out.
Foll owing install ation, DCOM operati on must be set up. For mor e infor mati on,
refer to the r elevant to chapt er in t he “ Industrial Comm unicati on with PG /PC”
m anual or the section i n the HT M L online hel p.
Procedure
To instal l t he soft ware for the OP C c lient c omputer, fol low the steps outl ined
below:
Step Description
1 St ar t your c omputer wit h M icr osoft Wi ndows 2000 or Windows NT 4.0.
2 Log on as administrat or with the Windows system.
3 Insert the SI M A TIC NE T CD i n y our CD- ROM drive.
4 Exit the i nstallat ion progr am if it is started automatically fr om the CD.
5 Go to the fol der \sw\opc _c lient\di sk1” on the SI M A TIC NE T CD.
6 St ar t the “ S etup.exe” pr ogr am.
7 Enter the name of the computer on which the OPC Server will be
started.
8 When you have c omplet ed the i nstallation, y ou must then set the
DCOM c onfi gur ati on as descri bed in t he manual.
Appendix O P C S er v er for S IMA TIC NET
Produkti nformation/Product Information OPC Server for SIMATIC NET
C79000-Z8974-C75-01 A-13
2 Notes on Protocols
Purpose
This chapter c ontai ns notes on some of the pr otocols.
Prot oc ols not requiring any special notes are not listed i n thi s chapt er .
Appendix O P C S er v er for S IMA TIC NET
Produkti nformation/Product Information OPC Server for SIMATIC NET
A-14 C79000-Z8974-C75-01
2.1 DP Protocol
Watchdog
The t ime set wit h “ Watchdog Ti meout” in the c onfi gur ati on ( defaul t 6000
milliseconds) is l oaded on the CP as the watchdog t ime.
In som e si tuations, it is necessary to increase this time to pr event the watchdog
timi ng out due to interrupti ons caused by the oper ati ng system.
Appendix O P C S er v er for S IMA TIC NET
Produkti nformation/Product Information OPC Server for SIMATIC NET
C79000-Z8974-C75-01 A-15
2.2 FMS Protocol
Large Numbers of Connections and Large Object Dictionaries
The O P C S er ver establishes the requir ed FMS c onnec ti ons i mmediat ely after the
fi r st it em of a connecti on is added. I f you add items to a gr oup and they are
assi gned to a l ot of connec ti ons, a lot of connecti ons must be establ ished one after
the ot her .
Normal ly, connection establ ishm ent al so i nvolves loading the object di c tionary
from t he par tner device. Depending on t he c onfi gur ati on of the par tner device, thi s
can tak e a c onsi der able t ime and it is quite possi ble t hat a connecti on will time out.
If thi s happens, the OPC Ser ver terminates the c onnec ti on and the connec ti on
cannot be used.
In t his case, the object di c tionaries of the part ner devices should be included i n the
loc al confi gur ati on independent of OP C oper ati on.
Rem ember , however, that if any c hanges are made t o the configurati on of the
partner device that involve the object di c ti onar y , the locally confi gur ed object
dic ti onar y must also be updated.
Establishing Asymmetrical FMS Connections
The asymmetr ical FMS c onnec ti ons i nc lude t he c onnec ti ons with the connecti on
att r ibut es I- D ( I i s act ive partner), I- O (I is active partner) and D- O (D is active
partner ) . They ar e c alled asym metrical because the two stati ons that tak e par t i n
communi c ati on on these connect ions have different r oles duri ng establishment.
Whi le either of the end stati ons can establi sh the c onnec ti on ac ti vely to the par tner
on the most common type of connect ion (D- D) , the r ole of active connec ti on
establishm ent on an I- D c onnec ti on is reserved only for t he I part ner . If these
differing roles are not taken into ac c ount when defining t he c onfigur ati on,
connect ion establi shment may fail .
Appendix O P C S er v er for S IMA TIC NET
Produkti nformation/Product Information OPC Server for SIMATIC NET
A-16 C79000-Z8974-C75-01
2.3 S7 Protocol
Variable Types
The following variabl e type is not supported by all progr ammable controll er s and
cannot therefor e be used vi a the S7 O P C S er ver :
Bi t array s for example, DB5, X0.2,3
Appendix O P C S er v er for S IMA TIC NET
Produkti nformation/Product Information OPC Server for SIMATIC NET
C79000-Z8974-C75-01 A-17
2.4 SEND/RECEIVE Protocol
Direct Access to the S5 I/O
If an S 5 output is written directl y usi ng the SEND/RECEIVE pr otocol, thi s val ue
will be overwritten by the process im age in the next cycle. This behavior can be
att r ibut ed to the S 5 handling blocks.
Making permanent c hanges to the outputs using di r ec t access is possible only by
writing t o the process image (Q area) .
Appendix O P C S er v er for S IMA TIC NET
Produkti nformation/Product Information OPC Server for SIMATIC NET
A-18 C79000-Z8974-C75-01
3 Notes on OPC
P arallel Use
Wi thi n an OPC client, one version of the OPC Spec ificati on must be used for all
funct ions. A mixture of int er faces of di fferent ver si ons i s not per mit ted.
OPC Automation Interface 2.0
The O P C A utomation I nterface 2.0 is installed i n a ver si on c r eated, tested and
rel eased by Siemens.
Activating “Write-Only” OPC Items
Act ive O P C it ems are monitor ed by the OP C S er ver by the server sendi ng r ead
jobs over t he network. I f, however , the server attempts to read write-only
SEND/ RE CE IVE var iables, the par tner t er minat es the c onnec ti on and establishes
it agai n only after a c er tai n ti me. “Wr it e- only” OPC items must t her efore not be
activated.
Appendix O P C S er v er for S IMA TIC NET
Produkti nformation/Product Information OPC Server for SIMATIC NET
C79000-Z8974-C75-01 A-19
4 Notes on the OPC Scout
Performance
The O P C S c out i s a cli ent i ntended as a tool for testi ng and c ommissioni ng. When
operating wit h large number s of variables, l ong r eac ti on times can result
depending on the perfor manc e of the c omputer and t he pr otocol you use.
Generating Values
It is not possibl e to writ e to array s or t o gener ate negat ive val ues with the
“Gener ate Values” Scout funct ion.
Browsing
When browsing with the OP C scout , a maxi mum of 256 entr ies can be di spl ay ed
at one level .
Activating “Write-Only” OPC Items
Act ive O P C it ems are monitor ed by the OP C S er ver . If the server attempts to read
“writ e- only” var iables, some par tners terminat e the connection and establ ish it
again only after a c er tai n ti me. Some partner devices, however, react negatively t o
such jobs. “Wri te-only” var iables must therefor e never be ac ti vated. Y ou c an
achi eve thi s i n the OP C S c out by adding these variabl es to an inacti ve gr oup.
Appendix O P C S er v er for S IMA TIC NET
Produkti nformation/Product Information OPC Server for SIMATIC NET
A-20 C79000-Z8974-C75-01