MKSERIES HIGH PERFORMANCE PC BOARD MOUNTING FILTERS SPECIFICATIONS INTRODUCTIONS 1. Maximum leakage current each line-to-ground @ 115VAC 60Hz: 2uA @ 250VAC 50Hz: 5uA 2. Hipot rating (one minute) line-to-ground: 2250VDC line-to-line: 1450VDC 3. Operating frequency: 50/60Hz 4. Rated voltage: 115/250VAC 1. Applications for UL 544 & UL 2601 health care equipment. 2. Direct PC board mounting for easy installation. COMPONENTS ELECTRICAL SCHEMATIC 1 L COMMON MODE (L-G) IN 50 OHM SYSTEM CURRENT FREQUENCY-MHz TYPE RATING .15 .50 1.0 5.0 10 01MK4EM 1A 15 30 35 35 20 03MK4EM 3A 15 25 30 25 15 06MK4EM 6A 10 20 20 20 15 10MK4EM 10A 10 20 20 20 15 DIFFERENTIAL MODE (L-L) IN 50 OHM SYSTEM 01MK4EM 1A 2 30 45 45 45 03MK4EM 3A 2 25 45 45 40 06MK4EM 6A 3 15 35 45 40 10MK4EM 10A 3 15 35 45 40 L' L I N E 30 7 7 7 7 Cx L O A D Cx L N' N SERIES DIMENSIONS 25 25 25 25 PART NO. 01MK4E 03MK4E 06MK4E 10MK4E 0.18 +0 4.5 -0.5 MECHANICAL CONSTRUCTION DIMENSIONS IN INCHES/mm A B C 0.65 16.5 0.03 0.8 0.04 1.1 0.79 0.047 0.06 20.0 1.2 1.5 1.3 0.004 33 0.1 B 0.8 SUGGESTED MOUNTING PITCH IN P.C. BOARD 1.10 0.15 0.02 3.85 0.5 0.4 0.02 MK4EM 10.2 0.5 1.3 0.02 33.0 0.5 0.4 0.02 41.5 10.2 0.1 1.63 0.8 0.02 20.3 0.5 A 0.40 0.004 C UNIT: 7-21 20.3 0.1 MINIMUM INSERTION LOSS IN dB 0.4 0.004(2X) 10.15 0.1 0.1 L (mH) 10 2.6 28.0 Cx (uF) 10.15 0.5 PART NO. 01MK4EM 03MK4EM 06MK4EM 10MK4EM V D E INCH mm