ABB Entrelec SENSOR / CAPTEUR Issued: 2002.04.12 Emis le : 10, Rue Ampere Commercial reference Order code Modification : 1 69680 Chassieu, FRANCE reference commerciale Reference de commande Date : 2002.11.27 Tel : +33 (0)4 72 22 17 22 ESM1000C 1SBT191000R0003 Fax : +33 (0)4 72 22 19 35 Page 1/2 Measuring electronic sensor of d.c., a.c., pulsating currents with a galvanic insulation between primary and secondary circuits. Capteur electronique de mesure de courants d.c., a.c., impulsionnels, avec isolation galvanique entre circuits primaire et secondaire. CONNECTOR / CONNECTEUR MOLEX ref. 5045-03-A TERMINAL MARKING / REPERAGE SORTIES 1 : +Va 2: M 3 : -Va General tolerance : 1 mm Tolerance generale : 1 mm GENERAL DESCRIPTION DESCRIPTION GENERALE Coated electronic circuit Self extinguishing plastic case Direction of the secondary current : A primary current flowing in the direction of the arrow results in a positive output current on M terminal. Circuit electronique enrobe Boitier en matiere isolante auto-extinguible Sens du courant secondaire : Un courant primaire circulant dans le sens de la fleche engendre un courant secondaire sortant par la borne M. Protections : -Of the measuring circuit against short-circuits -Of the measuring circuit against opening Protections : -Du circuit de mesure contre les court-circuits -Du circuit de mesure contre l'ouverture UL file E166814, industrial control equipment UL508, open type Dossier UL E166814, equipement de controle industriel UL508, montage en coffret Instructions de montage et d'utilisation suivant notre catalogue Instructions for use and mounting according to our catalogue C_ES_7.doc The caracteristics detailed in this leaflet are subject to change without prior notice. Les caracteristiques detaillees dans cette brochure sont susceptibles d'evoluer sans notification prealable. ABB Entrelec SENSOR / CAPTEUR Issued: 2002.04.12 Emis le : Order code Modification : 1 Reference de commande Date : 2002.11.27 1SBT191000R0003 Page 2/2 10, Rue Ampere 69680 Chassieu, FRANCE Tel : +33 (0)4 72 22 17 22 Fax : +33 (0)4 72 22 19 35 Commercial reference reference commerciale CHARACTERISTICS CARACTERISTIQUES Nominal primary current (IPN) Courant primaire nominal (IPN) A r.m.s. (A eff.) : 1000 Measuring range (IP max) Plage de mesure (IP max) A peak (A crete) : 1500 Max. measuring resistance (RM max) Resistance de mesure max. (RM max) : 25 (@IPmax / 24V (5%)) Min. measuring resistance (RM min) Resistance de mesure min. (RM min) :0 (@IPN / 24V (5%)) Not measurable overload Surcharge non mesurable A peak (A crete) : 10000 Turn ratio (NP/NS) Rapport de transformation (NP/NS) Secondary current (IS) at IPN Courant secondaire (IS) a IPN mA : 200 Accuracy at IPN Precision a IPN % : 0.5 (@ +25C) Accuracy at IPN Precision a IPN % : 1 (-20C ... +70C) Offset current (IS0) Courant residuel (IS0) mA : 0.25 (@ +25C) Linearity Linearite % : 0.1 Thermal drift coefficient Coefficient de derive thermique mA/C : 0.01 Delay time Temps de retard S :1 di/dt correctly followed di/dt correctement suivi A/ s : 100 Bandwidth Bande passante kHz : 0 ... 100 (-1dB) No-load consumption current (IA0) (Consumption = IA0 + I S) Courant de consommation a vide (IA0) (Consommation = IA0 + IS) mA : 15 Voltage drop (e) Tension de dechet (e) V :2 Secondary resistance (RS) Resistance secondaire (RS) : 44 Dieletric strength Rigidite dielectrique kVr.m.s. (kV eff.) :3 ESM1000C Primaire / Secondaire Primary / Secondary (10ms/h) : 1/5000 (-20C ... +70C) (@ +70C) (50Hz, 1min) Supply voltage Tension d'alimentation V d.c. : 15 ... 24 (5%) Mass Masse Kg : 0.600 Operating temperature Temperature de service C : -20 ... +70 Storage temperature Temperature de stockage C : -40 ... +85 Temperature of primary conductor in contact with the sensor Temperature du conducteur primaire en contact avec le capteur C : 100 Particularities Particularites High magnetic immunity Immunite magnetique elevee C_ES_7.doc The caracteristics detailed in this leaflet are subject to change without prior notice. Les caracteristiques detaillees dans cette brochure sont susceptibles d'evoluer sans notification prealable.