Typical Applications
ADTECH
Analog-Digital Technology, Inc.
The Adtech DCA series alarms accept standard process DC current or DC voltage
input signals and provide relay contact outputs.
The basic input range is 1-50 mA (i.e., 4-20 mA), or any voltage of 0-1.25 mV DC
to 0-250 VDC (i.e., 1-5 VDQ and output contacts are rated at 10 amps, 30 VDC,
or 250 VAC resistive.
They provide a cost-effective way of protecting equipment for over- and/or under-
current or voltage conditions.
The DCA 114 single alarm has a DPDT output. The DCA 115 dual alarm has a
SPDT output per each setpoint.
A 24 VDC at 35 mA DC output is provided as standard for loop transmitters.
Integral dual color LEDs provide green indication for normal conditions and red
indication on alarm per setpoint independent of relay coil power.
The alarms are furnished as standard with the relay power fail-safe (i.e., relay coil
energized) regardless of highand/br low-alarm configurations. You may specify
the relays to be non-fail-safe (i.e., relay coil de-energized) or any combination at
no extra cost.
The DCA 114 and DCA 115 are supplied with a fixed dead band of 0.5% of span,
as standard. They are optionally supplied with adjustable dead band of I to 100%
of input span. Ten-turn calibrated dials are offered as an option for both the
setpoint and dead band at a nominal extra cost and are mounted in the
"wide-line” (2.75" wide) enclosure.
An adjustable time delay of 1-30 seconds may also be provided as an option. This
is useful to prevent false alarms due to signal transient noise-interference.
DC Current/Voltage
Alarms
Model Nos. DCA 114 Single,
DCA 115 Dual
Limit detector of DC
voltage/current inputs
Tank-filling applications with
dead band feature
Contact inputs to
annunciators, lights, and
horns
High-/low-alarm or window
monitor
Alarm and/or shutdown of
process variables
Machine and process
protection
On/off controller
Features
DC Current Inputs: 1 mA to 50 mA DC: (i.e., 4-20 mA DC)
DC Voltage Inputs: 1.25 mV to 250 VDC: (i.e. 1-5 VDC)
High Input Impedance: 1.0 megohms minimum
Zero-Based Inputs: Current and voltage
Repeatability: ±0.1 % of span
Universal Relay Action: Fail-safe or non-fail-safe for high
and low trip
Contact Status: LED indication: green--normal; red--alarm
Adjustable Dead Band: 1-100% of input span--optional
Adjustable Time Delay: 1-30 seconds--optional
Calibrated Set Point and Dead Band: Ten turn--optional
Connections/Dimensions
Represented by:
Input/Output
Ordering Information
Model number
Model number
Input signal
High and/or low relay action
Relay action, F.S. or non-F.S.
Prime power with option no,
Input/output/control(s) options
Housing and miscellaneous
options
Please refer to the Housing and/or
Option Section for more specific
and detailed information.
Power
Performance
Mechanical
Options
Information subject to change without notice.
Printed in U.S.A. A092
ADTECH
Input Signals
*Any: 1 to 50 mA DC span
(i.e., 4-20 mA DC--Z in 20 ohms)
*Any: 1.25 mV to 250 VDC span
(i.e., 1-5, 0-5, 0-10 VDC--
Z in 1 megohm min.)
*Zero suppression/elevation
to 85% of span.
Repeatability: ±0.1 % of span
Trip Point Stability: Zero and span
±0.004%/˚F typical, ±0.01%/˚F maximum
for a 50˚F change from ambient
* Trip Adjustment: 0-100% of span
continuously adjustable; blind set:
infinite resolution
Fixed Dead Band: Factory set at 0.5% of
span
Note: All accuracies are given as a percentage of span.
* Ten-turn dials:
±
0.5% accuracy,
±
0.05% resolution
* Adjustable Dead Band: 1-100% of span
continuously adjustable; blind set: infinite
resolution
Power Supply Effect: ±0.05% for a
±10% power variation
Isolation: Input/output/power 1,500 VAC,
50/60 Hz, for AC & isolated DC powered units
Response Time: Less than 200 milliseconds
Temperature Range: 0˚ to 140˚F (-18˚ to 60˚C)
operating; -40˚ to 185˚F (-40˚ to 85˚C) storage
Option Number Description
O 26& O 28 Setpoint ten-turn calibrated dials: single and dual
O 27 & O 29 Dead band ten-turn calibrated dials: single and dual
O 30 & O 31 Adjustable time delay: single and dual
O 34 DPDT output: dual
O 40 & O 41 Hermetically sealed relays: single and dual
O 46S & O 46D Adjustable blind set dead band: single and dual
H 10 & H 11 Thin- and wide-line conduit mounting plate and terminal cover
H 13B, H 14B, H 15B NEMA 4, 7, and 12 enclosures
115VAC: 50/60 Hz, 0.7PF (Standard) 48 VDC: Isolated (Option P3)
12 VDC: Isolated (Option P8) 125 VDC: Isolated (105-140 VDQ (Option P4)
24 VDC: Non-isolated (Option PI) 230 VAC: 50/60 Hz, 0.7 PF (Option P5)
24 VDC: Isolated (Option P2)
Note: All units 3 watts maximum, and a
±
10% power variation unless noted.
Electrical Classification: General purpose
Connection: Barrier terminal strip (3/8" spacing, No. 6 screws)
Controls: Multiturn trip set controls; optional time delay and dead band controls, and internal
zero span controls
Mounting: Surface mounting standard. See Housings Section for options.
Weight: Net Unit: 2.6 pounds (1.18 kilograms); Shipping: 3.0 pounds (1.36 kilograms)
Output Signals
Standard: DCA 114 one set DPDT contact**
DCA 115 two SPDT contacts**
** Rated 10 amps at 30 VDC or
250 VAC resistive.
24 VDC at 35 mA DC two-wire transmitter excitation
Optional: DPDT dual alarms: (Option O 34).
Hermetically sealed 2 amp at 28 VDC or 115
VAC resistive: (Option O 40 single,
Option O 41 dual)
Note: With Option 0 34, the "wide-line"
(2.75" wide) housing is supplied.