AGENCY APPROVALS - IAL/IUL/IEL
Voltage
Frequency
(Hz) Phase
Min.
Poles TC OL UL/CSA
VDE
(amps)
UL 1077 & CSA
(AIC)
VDE
(AIC)
65 DC - 1 1 1 .02-100 .10-70 U2, 7500 4000
65(4) DC - 1 1 1 .02-100 - U2, 3000 -
65(4) DC - 1 1 1 .02-50 - U2, 5000 -
65 DC - 2** 2 1 101-150 - U2, 7500 -
80 DC - 1 1 1 .02-70 .10-50 U2, 7500 4000
80 DC - 1 1 1 70.1-100 - U2, 5000 -
80 DC - 2 1 1 101-150 - U1, 10000 -
80 DC - 3 1 0 251-300 - U2, 7500 -
125 DC - 2 1 0 .02-100 - U2, 5000 -
250 DC - 2+ 1 0 .02-50 - U1, 5000 -
300 DC - 3++ 1 0 .02-50 .10-50 U2, 1000 5000
125 50/60 1 1 1 0 .02-70 - U2, 5000 -
125 50/60 1 1 1 1 .02-100 - U1, 3000 -
125(5) 50/60 1 1 1 1 .02-100 - U3, 1500 -
120/240 50/60 1 2 2 1 .02-100 - U1, 2000 -
125/250(5) 50/60 1 2 only 1 1 .02-100 - U3, 1500 -
240 50/60 1&3 1 1 0 .02-70 - U1, 2000 -
240 50/60 3 2 1 1 .02-100 - U2, 2000 -
250 50/60 3 1 1 1 .02-50 .10-100 U2, 3000 2000
250 50/60 3 1 1 1 .02-50 .10-100 C2, 5000(1) 2000
250 50/60 1 1 1 1 .02-50 .10-100 C2, 5000(2) 2000
250 50/60 3 2 1 0 .02-80 .10-100 U1, 1000 2000
250 50/60 3 1 1 0 .02-60 .10-100 U1, 5000 2000
250(5) 50/60 3 3 only 1 1 .02-100 - U3, 2000 -
277 50/60 1 1 1 1 .02-50 - U2, 2000 -
277 50/60 1&3 1 2 1 .02-50 - C2, 5000(1) -
240/415 50/60 3 2 2 0 .02-50 .10-50 U2, 2000 2000
240/415 50/60 1 2 2 0 .02-50 .10-50 C2, 5000(1) 2000
277/480 50/60 3 2 2 1 .02-30 - U2, 2000 -
277/480 50/60 3 2 2 1 .02-50 - U2, 1200 -
277/480 50/60 3 2 1 1 .02-30 - C2, 5000(3) -
277480 50/60 1&3 2 1 0 .02-50 - C2, 5000(3) -
480 50/60 1&3 2 1 1 .02-30 - C2, 5000(3) -
480 50/60 3 2 1 0 .02-50 - C2, 5000(3) -
250 400 1&3 1 2 1 .02-50 - U2, 1500 -
AGENCY APPROVALS - CEL/CELP (COMMUNICATIONS)
Voltage
Frequency
(Hz) Phase
Min.
Poles UL/CSA
VDE
(amps)
UL 489A
(AIC)
VDE
(AIC)
65 DC - 1 .05-50 - 7500 -
65 DC - 2** 101-150 - 50000 -
80 DC - 1 .05-100 - 50000 -
80 DC - 2** 101-200 - 10000 -
80 DC - 3** 201-250 - 10000 -
125 DC - 1 .05-70 - 5000 -
80 DC - 1 15.1-125 - 10000 -
General notes:
• All supplementary protectors are of the overcurrent (OC) type
• The family of protectors has been evaluated for end use application for use groups
(UG) A, B, C and D
• The terminals (FW) are suitable for factory wiring only (0)
• The maximum voltage ratings for which the protectors have been tested are shown in
the chart
• The current is the amperage range that the protectors have been tested
• The tripping current (TC) for all of the protectors is either either “1” (in the range of
125% to 135% of ampere rating) or “2” (more than 135% of ampere rating)
• The overload rating (OL) – designates whether the protector has been tested for
general use or motor starting applications.
0 – tested at 1.5 times amp rating for general use
1 – tested at 6 times AC rating or 10 times DC rating for motor starting
• The short circuit current rating (SC) – The short circuit rating in amperes following a
letter and number designating the test conditions and any calibration following the
short circuit test is defined below:
C – Indicates short circuit test was conducted with series overcurrent protection
U – Indicates short circuit test was conducted without series overcurrent protection
1 – Indicates a recalibration was not conducted as part of the short circuit testing
2 – Indicates a recalibration was performed as part of the short circuit testing
3 – Indicates recalibration was performed along with the dielectric and voltage
withstand for “Suitable for Further Use” rating
AGENCY APPROVALS - IULD (DUST SEALED)
Voltage
Frequency
(Hz) Phase
Min.
Poles TC OL UL/CSA
VDE
(amps)
UL 1077 & CSA
(AIC)
VDE
(AIC)
250 50/60 1&3 1 1 1 .02-100 - C2, 5000(3) -
277 50/60 1 1 1 1 .02-30 - C2, 5000(3) -
Notes:
** Paralleled poles; + 2 poles in series; ++ 3 poles in series; (1) With 125 A max. series fuse; (2) Series
combination with 209 or 229 series (100 A max.); (3) With 100 A max. series fuse; (4) With blocked vent
construction (5) Non-standard construction. “Fit for further use” approval
IAL/IUL/IEL/IDL/LEL/LELHP SPECIFICATIONS
AGENCY APPROVALS - LEL/LELHP
Voltage
Frequency
(Hz) Phase
Min.
Poles UL/CSA
VDE
(amps)
UL489
(AIC)
VDE
(AIC)
65 DC - 1 .05-50 - 7500 -
65 DC - 2** 101-150 - 50 000 -
65 DC - 3** 175-200 - 50000 -
80 DC - 1 .05-100 .10-100 10000 2000
80 DC - 1 .05-100 - 50000 -
80 DC - 2** 125-150 125-150 10000 2000
80 DC - 3** 175-200 151-200 10000 2000
125 DC - 1 .05-70 .05-70 5000 3000
125/250 DC - 2 .05-50 - 5000 -
125 50/60 1&3 1 .05-40 - 10000 -
125 50/60 1&3 1 .05-50 .10-50 5000 2000
120/240 50/60 1 2 .05-70 .10-50 5000 2000
240 50/60 1&3 1 .05-20 - 5000 -
AGENCY APPROVALS - CELHP
80 DC - 4 400 - 10000 AIC
(UL489A)
-
AGENCY APPROVALS - IDL/IDLP (MARINE)
Voltage
Frequency
(Hz) Phase
Min.
Poles TC OL UL/CSA
VDE
(amps)
UL 1077 & CSA
(AIC)
VDE
(AIC)
48 DC - 1 1 1 .02-100 - U1, 5000 -
48 DC - 2** 1 1 101-150 - U1, 5000 -
65 DC - 1 1 1 .02-60 - U1, 1000 -
80 DC - 1 1 1 .02-100 - U2, 1500 -
125 50/60 1 1 1 1 .02-100 - U 1, 1500 -
250 50/60 1 2 1 1 .02-100 - U2, 1500 -
250 50/60 1&3 1 1 1 .02-60 - U1, 1000 -
AGENCY APPROVALS - IULQ (TAPPED COIL)
Voltage
Frequency
(Hz) Phase
Min.
Poles TC OL UL/CSA
VDE
(amps)
UL 1077 & CSA
(AIC)
VDE
(AIC)
125/250 50/60 1 1 1 1 2/1-30/15 - C2, 5000(1) -
http://airpax.sensata.com/ IAL/CEL/LEL Series - Operating Characteristics 150
IAL Series - Specications
IAL Series
164