3RHP Series AC Control
• 100K-cycle UL508 Endurance Rating for Enhanced Reliability
• 40 and 50A output
• V oltage rati ngs to 600 VAC
• Lifetime 2 million o per ation s at full loa d
• LE D input status indicator
• Wire, lug or quick connect t erminati o n
• Industry Standard DP cont actor mounting
PRODUCT SELECTION (by control voltage and output rating)
Control Voltage 40A 280 VAC 50A 280 VAC 40A 600 VAC 50A 600 VAC
20-26 VAC 3RHP2840E 3RHP2850E 3RHP6040E 3RHP6050E
100-130 VAC 3RHP2840F 3RHP2850F 3RHP6040F 3RHP6050F
208-240 VAC 3RHP2840G 3RHP2850G 3RHP6040G 3RHP6050G
OUTPUT SPECIFICATIONS (voltage)
Description 280 VAC 600 VAC
Operating Voltage (47-63Hz) [Vrms] 24-280 48-600
Maximum Off-State Leakage Current per channel 0.05 mA @ 240 VAC 0.06 mA @ 480 VAC
OUTPUT SPECIFICATIONS (current)
Description 40A 50A
Maximum Load Current per phase @ 40°C [Arms] (1) 40A Resistive 50A Resistive
Power terminals 1/4" Quick Connect and 10x32 binder
head screws 1/4" Quick Connect and box lugs
Wire Size 8-14 AWG 6-14 AWG
INPUT SPECIFICATIONS
Description SUFIX E SUFIX F SUFIX G
Coil Voltage [50/60 Hz] 20-26 VAC 100-130 VAC 208-240 VAC
Min. Turn-On Voltage 20 VAC 100 VAC 208 VAC
Min. Turn-Off Voltage 12 VAC 24 VAC 48 VAC
Coil Power Consumption, inrush. 56 VA @ 24 VAC 56 VA @ 120 VAC 56 VA @ 220 VAC
Coil Power Consumption, sealed. 6.6 VA @ 24 VAC 6.6 VA @ 120 VAC 6.6 VA @ 220 VAC
GENERAL SPECIFICATIONS
Description Parameters
Dielectric Strength, Input to Output 4000 Vrms
Dielectric Strength, Input/Output to ground 2500 Vrms
Contacts (2) Three Normally Open
Ambient Operating Temperature Range (3) -20 to 65 °C
Ambient Storage Temperature Range -40 to 100 °C
Max. Turn-On Time 50/60 Hz 20 ms / 16.6 ms
Max. Turn-Off Time 50/60Hz 40 ms / 32 ms
Maximum Number of Operations 30 per Minute
Lifetime Number of Operations @ Rated Current (4) > 2 Million
Weight (typical) 1.19 lbs (540 g)
Screw Torque (input/Output) 40A 4.4-5 in lb (0.5-0.6 Nm) / 15-18 in lb (1.7-2.1 Nm)
Screw Torque (input/Output) 50A 4.4-5 in lb (0.5-0.6 Nm) / 20-25 in lb (2.2-2.9 Nm)
GENERAL NOTES
(1) See Derating curves for additional operating conditions.
(2) The RHP includes a Solid State Relay , therefore electrical isolation is not provided.
(3) The RHP includes over temperature protection for the solid state relay.
(4) 40°C ambient temperature, 30 oper ations/min, max imum voltage control.
Obsolete
MECHANICAL SPECIFICATIONS
THERMAL DERATE INFORMATION
Obsolete
TYPICAL ELECTRICAL CONNECTIONS
AGENCY APPROVALS
UL/cUL UL508, E116950 Rev.063011
EN60950-1-2006
Obsolete
ACCESSORIES
Obsolete
Obsolete
ANNEX - ENVIROMENTAL INFORMATION
Obsolete