https://www.phoenixcontact.com/us/products/2308108
09/03/2014Page1/5
Universal current transducer-MCR-SL-CUC-100-U-2308108
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Universal current transducer, for measuring DC, AC, and distorted currents, 0 ... 100 A input current, 0 ... 10 V
output
The MCR-SL-CUC-100-I is illustrated
Product Features
Variable mounting on DIN rail and mounting plate
Compact dimensions also enable distributed use
Simple connection technology thanks to COMBICON plug-in connection terminal blocks
Universal current measurement, no shunt required
3-way isolation
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 300.0 GRM
Custom tariff number 90303310
Country of origin China
Technical data
Dimensions
Width 90 mm
Height 33.8 mm
Depth 85 mm
Ambient conditions
Ambient temperature (operation) -40 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20
Input data
https://www.phoenixcontact.com/us/products/2308108
09/03/2014Page2/5
Universal current transducer-MCR-SL-CUC-100-U-2308108
Technical data
Input data
Input current range 0 A ... 100 A
Overload capacity 6 x IIN
Frequency measuring range 20 Hz ... 6000 Hz (0 Hz)
Connection method Cable design: 32 mm diameter
Output data
Output name Voltage output
Voltage output signal 0 V ... 10 V
Load/output load voltage output ≥ 10 kΩ
Switching output
Output name No switching output
Power supply
Nominal supply voltage 24 V DC
Supply voltage range 20 V DC ... 30 V DC
Max. current consumption 30 mA
Connection data
Conductor cross section solid min. 0.25 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 12
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Stripping length 10 mm
General
Maximum transmission error <± 1 % (of final value)
Temperature coefficient, typical 0.02 %/K (0 ... 60°C)
0.04 %/K (-40 ... 65°C)
Linearity error <± 1 % (From the range end value)
Step response (10-90%) 150 ms
Surge voltage category III
Pollution degree 2
Rated insulation voltage 300 V AC
Color green
Housing material Frianyl B63 V0 GV30
Conformance CE-compliant
https://www.phoenixcontact.com/us/products/2308108
09/03/2014Page3/5
Universal current transducer-MCR-SL-CUC-100-U-2308108
Technical data
General
UL, USA / Canada UL/C-UL listed UL 508
Classifications
eCl@ss
eCl@ss 4.0 27200303
eCl@ss 4.1 27200303
eCl@ss 5.0 27200303
eCl@ss 5.1 27210902
eCl@ss 6.0 27210902
eCl@ss 7.0 27210902
eCl@ss 8.0 27210902
ETIM
ETIM 3.0 EC002475
ETIM 4.0 EC002048
ETIM 5.0 EC002475
UNSPSC
UNSPSC 6.01 30211506
UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 39121008
Approvals
Approvals
Approvals
UL Listed / cUL Listed / cULus Listed
Ex Approvals
Approvals submitted
https://www.phoenixcontact.com/us/products/2308108
09/03/2014Page4/5
Universal current transducer-MCR-SL-CUC-100-U-2308108
Approvals
Approval details
UL Listed
cUL Listed
cULus Listed
Drawings
Dimensioned drawing
90
Ø32 33,8
70
Circuit diagram
IN 1.3
1.4
1.2
1.1
GND
OUTU
NC
+24VDC
ADC
µC
DAC
U
https://www.phoenixcontact.com/us/products/2308108
09/03/2014Page5/5
Universal current transducer-MCR-SL-CUC-100-U-2308108
Schematic diagram
A
B
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com