Product datasheet
Characteristics
RE17LCBM
off-delay timing relay - control - 1 s..100 h -
24..240 V - solid state output
Main
Range of product Zelio Time
Product or component type Modular timing relay
Discrete output type Solid state
Width 17.5 mm
Component name RE17L
Time delay type C
Time delay range 1...10 h
1...10 min
10...100 h
1...10 s
6...60 min
6...60 s
0.1...1 s
Nominal output current 0.7 A
Complementary
Control type Selector switch on front panel
[Us] rated supply voltage 24...240 V AC at 50/60 Hz
Voltage range 0.85...1.1 Us
Supply frequency 50...60 Hz (+/- 5 %)
Release of input voltage 7 V
Control signal pulse width 0.05 s typical
Insulation resistance 100 MOhm at 500 V DC conforming to IEC 60664-1
[Uimp] rated impulse withstand voltage 5 kV (1.2/50 µs)
Power on delay < 100 ms
Connections - terminals Screw terminals, clamping capacity: 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12 (solid) without cable
end
Screw terminals, clamping capacity: 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14 (solid) without cable
end
Screw terminals, clamping capacity: 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14 (flexible) with cable end
Screw terminals, clamping capacity: 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16 (flexible) with cable end
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Jul 11, 2019
1
Tightening torque 0.6...1 N.m conforming to IEC 60947-1
Dielectric strength 2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
Housing material Self-extinguishing
Repeat accuracy +/- 0.5 % conforming to IEC 61812-1
Temperature drift +/- 0.05 %/°C
Voltage drift +/- 0.2 %/V
Setting accuracy of time delay +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Reset time 350 ms on de-energisation typical
On-load factor 100 %
Power consumption in VA 0...3 VA at 240 V AC
Power consumption in W <= 1.5 W at 240 V DC
Breaking capacity 0.5 A AC/DC conforming to UL
0.7 A AC/DC at 20 °C
Operating frequency 10 Hz
Maximum output current 20 A <= 10 ms
Minimum switching current 10 mA
Leakage current < 5 mA
Maximum switching voltage 250 V AC
Voltage drop 4 V 3-wire
8 V 2-wire
Electrical durability 100000000 cycles
Marking CE
Creepage distance 4 kV/3 conforming to IEC 60664-1
Safety reliability data MTTFd = 353.8 years
B10d = 320000
Mounting position Any position in relation to normal vertical mounting plane
Mounting support 35 mm DIN rail conforming to EN/IEC 60715
Product weight 0.068 kg
Environment
Immunity to microbreaks <= 20 ms
Derating factor 5 mA/°C
Standards EN 61000-6-1
EN 61000-6-2
2004/108/EC
EN 61000-6-3
2006/95/EC
IEC 61812-1
EN 61000-6-4
Product certifications CSA
GL
cULus
Ambient air temperature for storage -30...60 °C
Ambient air temperature for operation -20...60 °C
IP degree of protection IP20 (terminal block) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP50 (front panel) conforming to IEC 60529
Vibration resistance 20 m/s² (f = 10...150 Hz) conforming to IEC 60068-2-6
Shock resistance 15 gn (duration = 11 ms) conforming to IEC 60068-2-27
Relative humidity 93 % without condensation conforming to IEC 60068-2-30
Electromagnetic compatibility Electrostatic discharge immunity test, in contact at 6 kV conforming to IEC 61000-4-2 level 3
Electrostatic discharge immunity test, in air at 8 kV conforming to IEC 61000-4-2 level 3
Susceptibility to electromagnetic fields, 80 MHz to 1 GHz at 10 V/m conforming to IEC 61000-4-3
level 3
Electrical fast transient/burst immunity test, capacitive connecting clip at 1 kV conforming to IEC
61000-4-4 level 3
Electrical fast transient/burst immunity test, direct at 2 kV conforming to IEC 61000-4-4 level 3
1.2/50 µs shock waves immunity test, differential mode at 1 kV conforming to IEC 61000-4-5 level 3
1.2/50 µs shock waves immunity test, common mode at 2 kV conforming to IEC 61000-4-5 level 3
2
Conducted RF disturbances, 0.15...80 MHz at 10 V conforming to IEC 61000-4-6 level 3
Voltage dips and interruptions immunity test, 1 cycle at 0 % conforming to IEC 61000-4-11
Voltage dips and interruptions immunity test, 25/30 cycles at 70 % conforming to IEC 61000-4-11
Conducted and radiated emissions conforming to EN 55022 class B
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1650 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
End of Life Information
Product end of life instructions Available
3
Product datasheet
Dimensions Drawings
RE17LCBM
Width 17.5 mm
4
Product datasheet
Connections and Schema
RE17LCBM
Internal Wiring Diagram
5
Product datasheet
Connections and Schema
RE17LCBM
Wiring Diagram
6
Product datasheet
Technical Description
RE17LCBM
Function C : Off-Delay Relay with Control Signal
Description
After power-up and closing of the control contact C, the output R closes. When control contact C re-opens, timing T starts. At the end of the timing
period, the output(s) R revert(s) to its/their initial state. The second output can be either timed or instantaneous.
Function: 1 Output
Function: 2 Outputs
2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
7
Product datasheet
Technical Description
RE17LCBM
Legend
Relay de-energised
Relay energised
Output open
Output closed
C Control contact
G Gate
R Relay or solid state output
R1/R2 2 timed outputs
R2 inst.The second output is instantaneous if the right position is selected
T Timing period
Ta - Adjustable On-delay
Tr - Adjustable Off-delay
U Supply
8