1
New Product
Digital Timer
H5CZ
Easy to Use and Easy to Read.
Basic Features
Character height of 10 mm for better readability.
Operation is simplified by the Up/Down Keys for each digit on 4-digit.
Safety and Reliability
Power supply circuit and input circuits are isolated for safety and reliability.
Set value limit function prevents unexpected operation of output devices
caused by setting mistakes.
Output counter function helps in managing the service life of the Timer or
the load.
Other Features
Models with instantaneous contact output.
Waterproof, dust-proof structure (UL508 Type 4X and IP66).
Key protection.
Features
Basic Features
Better Readability
Character Height of 10 mm with a Wide Viewing Angle.
The Easiest Operation
Operation is simplified by the Up/Down
Keys for each digit on 4-digit.
Safety and Reliability
Isolated Power Supply and Input Circuits *1
Power supply circuit and input circuits are isolated for safety and
reliability.
Previous non-isolated timers had wiring restrictions and could be damaged if
wired incorrectly. The H5CZ removes these worries.
*1. H5CZ with 100 to 240-VAC specifications.
Set Value Limit
You can set an upper limit for the set value to prevent unexpected
operation of output devices caused by setting mistakes.
Output Counter
The output counter counts the number of times the output turns ON
(alarm display, count monitoring, count in increments of 1,000). This
counter is useful in managing the service life of the Timer or the load.
Other Features
Models with Instantaneous Contact Output
Models with instantaneous contact outputs have been added for use
with self-holding circuits and as auxiliary relays. These models are
also convenient when replacing analog timers.
Waterproof, Dust-proof Structure (UL508 Type
4X and IP66)
Worry-free application is possible in locations subject to water.
Note: When the Y92S-29 Waterproof Packing is used.
Key Protection
Select from any of seven protection patterns. Use the best one for the
application.
New Modes
Modes, such as a stopwatch mode (Mode S), have been added.
Select any of 15 modes.
Refer to Safety Precautions on page 29. For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
10 mm (actual size) Clear
Confirmation
Easy to read from the top,
bottom, and sides.
V+V
Output terminal on PLC
or other device
AC power
supply *2
Input terminal
0-V terminal
COM terminal
Forget These
Worries with the
H5CZ
Stabilized DC
power supply
*2. The AC power supply ground is on the commercial power supply side.
Worry-free operation is
achieved with the H5CZ
by restricting the time
that can be set.
H5CZ
2
Model Number Structure
Model Number Legend
H5CZ-L @@@
–––
123
Ordering Information
List of Models
Note: The functions that are provided depend on the model. Check detailed specifications before ordering.
*A time-limit DPDT output can also be used.
Type Time specifications Operating modes External
connections Inputs Outputs Supply voltage Models
H5CZ
0.001 to 9.999 s
0.01 to 99.99 s
0.1 to 999.9 s
1 to 9999 s
1 s to 99 min 59 s
0.1 to 999.9 min
1 to 9999 min
1 min to 99 h 59 min
0.1 to 999.9 h
1 to 9999 h
Timer Mode
A: Signal ON Delay I
A-1: Signal ON Delay II
A-2: Power ON Delay I
A-3: Power ON Delay II
b: Repeat cycle 1
b-1: Repeat cycle 2
d: Signal OFF Delay
E: Interval
F: Cumulative
Z:
ON/OFF-duty-adjustable flicker
S: Stopwatch
Twin Timer Mode
toff: Flicker OFF Start 1
ton: Flicker ON Start 1
toff-1: Flicker OFF Start 2
ton-1: Flicker ON Start 2
8-pin socket
Signal, Reset
(NPN inputs)
Contact output
(time-limit
SPDT)
100 to 240 VAC H5CZ-L8
12 to 24 VDC/
24 VAC H5CZ-L8D
Timer Mode
A-2: Power ON Delay I
b: Repeat cycle 1
E: Interval
Z:
ON/OFF-duty-adjustable flicker
Twin Timer Mode
toff: Flicker OFF Start 1
ton: Flicker ON Start 1
None
Contact output
(time-limit SPDT
+ instantaneous
SPDT)
Models with
instantaneous
contact outputs
*
100 to 240 VAC H5CZ-L8E
12 to 24 VDC/
24 VAC H5CZ-L8ED
1. External Connections 2. Output type
*Can be used as a time-limit DPDT output.
3. Supply voltage
Symbol Meaning
8 8-pin socket
Symbol Meaning
None Contact output (time-limit SPDT)
EContact output (time-limit
SPDT + instantaneous SPDT) *
Symbol Meaning
None 100 to 240 VAC 50/60 Hz
D 12 to 24 VDC/24 VAC 50/60 Hz
H5CZ
3
Accessories (Order Separately)
Soft Cover
Hard Cover
Flush Mounting Adapter
Waterproof Packing
Connection Sockets
Terminal Covers for P3G-08 Back-connecting Sockets
Models Page
Y92A-48F1 9
Models Page
Y92A-48 9
Models Page
Y92F-30 9
Models Page
Y92S-29 9
Models Type Remarks Page
P2CF-08 Front Connecting
Socket ---
10P2CF-08-E
Front Connecting
Socket
(Finger-safe Type)
Round crimp terminals cannot be used on Finger-safe
Sockets. Use forked crimp terminals.
P3G-08 Back Connecting Socket A Y92A-48G Terminal Cover can be used with the
Socket to create a finger-safe construction.
Models Page
Y92A-48G 10
H5CZ
4
Specifications
Ratings
*1. Do not use the output from an inverter as the power supply. The ripple must be 20% maximum for DC power.
*2. Inrush current will flow for a short time when the power supply is turned ON.
Inrush Current (Reference Values)
*3. The display is lit only when the power is ON. Settings and changes are not possible if the power supply is not ON.
H5CZ Digital Timers
Item Models H5CZ-L8@
Ratings
Power supply
voltage *1 100 to 240 VAC 50/60 Hz
12 to 24 VDC/24 VAC 50/60 Hz
Operating voltage
fluctuation range 85% to 110% of rated supply voltage (90% to 110% at 12 to 24 VDC)
Power consumption Approx. 6.2 VA at 100 to 240 VAC, Approx. 5.1 VA/2.4 W at 24 VAC/12 to 24 VDC *2
Mounting method Flush mounting, Surface mounting, DIN track mounting
External connections 8-pin socket
Degree of protection IEC IP66, UL508 Type 4X (indoors) for panel surface only and when Y92S-29 Waterproof Packing is used
4 digits
Digits
Time ranges 0.001 s to 9.999 s, 0.01 s to 99.99 s, 0.1 s to 999.9 s, 1 s to 9999 s, 1 s to 99 min 59 s
0.1 m to 999.9 min, 1 min to 9999 min, 1 min to 99 h 59 min, 0.1 h to 999.9 h, 1 h to 9999 h
Timer mode Elapsed time (Up), Remaining time (Down) (selectable)
Inputs
Input signals Signal, Reset
(no inputs on models with instantaneous contact outputs)
Input method
No-voltage Input
ON impedance: 1 kΩ max. (Leakage current: 12 mA when 0 Ω)
ON residual voltage: 3 V max.
OFF impedance: 100 kΩ min.
Signal, reset Minimum input signal width: 1 or 20 ms (selectable, same for all input)
Reset system Power reset (depending on output mode), External reset, Manual reset, Automatic reset (depending on output mode)
Power reset Minimum power-opening time: 0.5 s (except for A-3, b-1, F, ton-1, and toff-1 mode)
Reset voltage 10% max. of rated supply voltage
Sensor waiting time 250 ms max. (Control output is turned OFF and no input is accepted during sensor waiting time.)
Output
Output modes
A: Signal ON Delay I, A-1: Signal ON Delay II, A-2: Power ON Delay I, A-3: Power
ON Delay II, b: Repeat Cycle 1, b-1: Repeat Cycle 2, d: Signal OFF Delay, E:
Interval, F: Cumulative, Z: ON/OFF-duty-adjustable flicker, S: Stopwatch, toff:
Flicker OFF Start 1, ton: Flicker ON Start 1, toff-1: Flicker OFF Start 2, ton-1:
Flicker ON Start 2
Models with Instantaneous Contact Outputs
A-2: Power ON Delay I, b: Repeat Cycle 1,
E: Interval, Z: ON/OFF-duty-adjustable
flicker, toff: Flicker OFF Start 1, ton: Flicker
ON Start 1
One-shot output time 0.01 to 99.99 s
Control output
5 A at 250 VAC/30 VDC, resistive load (cos =1)
Minimum applied load: 10 mA at 5 VDC (failure level: P, reference value)
Contact materials: AgSnIn
Display method *3 LCD; Present value: 10-mm-high characters
Set value: 6-mm-high characters
Memory backup EEPROM (overwrites: 100,000 times min.) that can store data for 10 years min.
Operating temperature range -10 to 55°C (-10 to 50°C if counters are mounted side by side) (with no icing or condensation)
Storage temperature range -25 to 70°C (with no icing or condensation)
Operating humidity range 25% to 85%
Front panel color Light gray (5Y7/1)
Voltage Applied voltage Inrush current (peak value) Time
100 to 240 VAC 264 VAC 5.3 A 0.4 ms
12 to 24 VDC/24 VAC 26.4 VAC 6.4 A 1.4 ms
26.4 VDC 4.4 A 1.7 ms
H5CZ
5
Characteristics
Applicable Standards
*The following safety standards apply to H5CZ.
cUL (Listing): Applicable when an OMRON P2CF (-E) Socket is used.
cUR (Recognition): Applicable when any other socket is used.
I/O Functions
For details, refer to the timing charts on page 16 and page 25.
*The H5CZ-L8E@ does not have an input.
Approved safety standards
UL508/Listing, UL50 Type 4X for indoor use (enclosure rating), CSA C22.2 No. 14 *,
conforms to EN61812-1 (Pollution degree 2/overvoltage category III)
B300 PILOT DUTY
1/4 HP 120 VAC, 1/3 HP, 240 VAC, 5 A resistive load
VDE0106/P100
CCC: Pollution degree 2, Overvoltage category II
EMC
(EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC mains: EN55011 Group 1 class A
(EMS) EN61812-1
Immunity ESD: IEC61000-4-2
Immunity RF-interference: IEC61000-4-3
Immunity Burst: IEC61000-4-4
Immunity Surge: IEC61000-4-5
Immunity Conducted Disturbance: IEC61000-4-6
Immunity Voltage Dip/Interruption: IEC61000-4-11
Inputs *
Start signal Normally functions to start timing.
In modes A-2 and A-3, disable timing. In mode S, starts and stops timing.
Reset
Resets present value. (In elapsed time mode, the present value returns to 0; in remaining time mode,
the present value returns to the set value.)
Count inputs are not accepted and control output turns OFF while reset input is ON.
Reset indicator is lit while reset input is ON.
Outputs Control output (OUT) Outputs take place according to designated operating mode when timer reaches corresponding set value.
*Refer to Life-test Curve.
Accuracy of operating time
and setting error (including
temperature and voltage
influences)
Power-ON start: ±0.01% ±50 ms max. (See note)
Signal start: ±0.005%±0.03 ms max. (See note)
If the set value is within the sensor waiting time at startup the control
output of the H5CZ will not turn ON until the sensor waiting time passes.
Note: The values are based on the set value.
Insulation resistance
100 MΩ min. (at 500 VDC) between current-carrying terminal and
exposed non-current-carrying metal parts, and between non-continuous
contacts
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and
non-current-carrying metal parts
2,000 VAC, 50/60 Hz for 1 min between power supply and input circuits
for all models except H5CZ-@D
2,000 VAC, 50/60 Hz for 1 min between control output, power supply,
and input circuits
1,000 VAC, 50/60 Hz for 1 min between non-continuous contacts
Impulse withstand voltage
5 kV (between power terminals) for 100 to 240 VAC, 1 kV for 24 VAC/12
to 24 VDC
5 kV (between current-carrying terminal and exposed non-current-
carrying metal parts) for 100 to 240 VAC 1.5 kV for 24 VAC/12 to 24 VDC
Noise immunity
±1.5 kV (between power terminals) and ±600 V (between input
terminals), square-wave noise by noise simulator (pulse width: 100 ns/
1 µs, 1-ns rise)
Static immunity Malfunction: 8 kV
Destruction: 15 kV
Vibration
resistance
Destruction 10 to 55 Hz with 0.75-mm single amplitude each in three directions for
2 h each
Malfunction 10 to 55 Hz with 0.35-mm single amplitude each in three directions for
10 min each
Shock
resistance
Destruction 300 m/s2 in three directions, three cycles
Malfunction 100 m/s2 in three directions, three cycles
Life
expectancy
Mechanical 10,000,000 operations min. (under no load at 1,800 operations/h and
ambient temperature of 23°C)
Electrical 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800
operations/h and ambient temperature of 23°C) *
Weight Approx. 105 g (Timer only)
Life-test Curve (Reference
Values)
A maximum current of 0.15 A can be switched at
125 VDC (cosφ =1) and a maximum current of 0.1
A can be switched if L/R is 7 ms. In both cases, a
life of 100,000 operations can be expected.
DC30V L/R=7ms
AC250V/DC30V
cos
φ
=1
AC250V cos
φ
=0.4
0 1 2 3 4 5
1,000
500
100
50
10
Switching operations (× 10
4
)
Load current (A)
H5CZ
6
Connections
Block Diagram
Note: Basic insulation is provided between the power supply circuit and the input circuits. However, basic insulation is not provided in the
H5CZ-@D.
Terminal Arrangement
Confirm that the power supply meets specifications before use.
Note: Do not connect unused terminals as relay terminals.
Input Circuits
Signal and Reset Input
Input Connections
The inputs are no-voltage (closed or open). (The H5CZ-L8E@ does not have an input.)
No-voltage Inputs (NPN Inputs)
H5CZ-L8/-L8D H5CZ-L8E/-L8ED
Open Collector Voltage Output Contact Input DC Two-wire Sensor
Output circuit
(See note.)
Internal control
circuit
Display circuit
Key switch circuit
Input circuits
Power supply
circuit
(Basic insulation)
(Basic insulation)
4
3
2
1 8
7
6
5
0V
Signal
Reset
Internal circuit
Contact
output
(-) (+)
Terminals 1 and 2 of the H5CZ-L8D
are connected internally.
4
3
2
18
7
6
5
(–) (+)
Internal circuit Internal circuit
Instantaneous
contact output
OUT1
Time-limit
contact output
OUT2
OUT1 can also be used as a time-limit
contact output.
Internal
circuit
IN
+14 V
1 kΩ
No-voltage Inputs (NPN Inputs)
134
PLC or
sensor
Note: Operate with transistor ON
0 V for inputs
Reset input
Signal input
Sensor
0 V for inputs
Reset input
Signal input
134
Note: Operate with transistor ON Note: Operate with contacts ON.
0 V for inputs
Reset input
Signal input
1 3 4
Note: Operate with transistor ON
0 V for inputs
Reset input
Signal input
134
Applicable Two-wire Sensor
Leakage current: 1.5 mA max.
Switching capacity: 5 mA min.
Residual voltage: 3.0 VDC max.
Operating voltage: 10 VDC
No-voltage Input Signal Levels
Note: The DC voltage must be 30 VDC max.
No-contact
input
Short-circuit level Transistor ON
Residual voltage: 3 V max.
Impedance when ON: 1 kΩ max.
(The leakage current is approx. 12 mA when the
impedance is 0 Ω.)
Open level Transistor OFF
Impedance when OFF: 100 kΩ min.
Contact input Use contacts which can adequately switch 5 mA at 10 V
H5CZ
7
Nomenclature
10 mm 6 mm
12
3
2
8
9
5
4
6
7
11
10
1
Display Section
1. Key Protect Indicator
2. Control Output Indicator
Front View
Character Size
for Present
Value Display
Character Size
for Set Value
Display
3. Reset Indicator
Operation Key
Switches
8. Mode Key
(Changes modes and setting items)
9. Reset Key
(Resets present value and output)
10. Up Keys 1 to 4
11. Down Keys 1 to 4
12. Key-protect Switch
6. Set Value Display (Sub-display)
(Character height: 6 mm)
7. Set Value 1, 2 Indicator
4. Present Value Display (Main display)
(Character height: 10 mm)
5. Time Unit Indicators
(If the time range is 0 min, 0 h, 0.0 h, or 0 h
0 min, these indicators flash to indicate
timing operation.)
OFF
(Disabled)
ON
(Enabled)
(Default setting)
H5CZ
8
Dimensions (unit: mm)
Digital Timers
Digital Timers
H5CZ-L8@ (Flush Mounting/Surface Mounting Models)
63.7 14.2
6
44.8×44.8
48×48
Panel Cutouts
Panel cutouts areas shown below. (according
to DIN43700).
Note: 1. The mounting panel thickness
should be 1 to 5 mm.
2. To allow easier operation, it is
recommended that Adapters be
mounted so that the gap between
sides with hooks is at least 15 mm
(i.e., with the panel cutouts
separated by at least 60 mm).
3. It is possible to horizontally mount
Timers side by side. Attach the
Flush Mounting Adapters so that
the surfaces without hooks are on
the sides of the Timers. (However,
if Timers are mounted side by side,
water resistance will be lost.)
60 min.
60 min.
45+0.6
0
45+0.6
0
15 min.
A
A=(48n-2.5)
With Y92A-48F1 attached.
A={48n-2.5+(n-1)×4}
With Y92A-48 attached.
A = (51n - 5.5)
n Units mounted side-by-side
+1
–0
+1
–0
+1
–0
Dimensions with Flush Mounting Adapter
H5CZ-L8@ (Adapter and Waterproof Packing Ordered Separately)
58
48 84.87.5
(51)
Y92F-30 (order separately)
Flush Mounting Adapter P3G-08 (order
separately)
Back-connecting
Socket
PanelY92S-29 (order separately)
Waterproof Packing
H5CZ
-L8@
P2CF-08(-E) (order separately)
Front Connecting Socket
92.3 90
*
Dimensions with Front Connecting Socket
*These dimensions vary with the type of DIN track (reference value).
H5CZ
9
Accessories (Order Separately)
Protecting the Timer in Environments Subject to Oil
The Waterproof Packing will deteriorate, harden, and shrink
depending on the application environment. To ensure maintaining the
IP@6, UL Type 4X waterproof level, periodically replace the
Waterproof Packing. The periodic replacement period will depend on
the application environment. You must confirm the proper
replacement period. Use 1 year or less as a guideline. If the
Waterproof Packing is not replaced periodically, the waterproof level
will not be maintained.
It is not necessary to mount the Waterproof Packing if waterproof
construction is not required.
Note:
Depending on the operating environment, the condition of
resin products may deteriorate, and may shrink or become
harder. Therefore, it is recommended that resin products are
replaced regularly.
The H5CZ's panel surface is water-resistive (IP@6, UL Type 4X)
and so even if drops of water penetrate the gaps between the keys,
there will be no adverse effect on internal circuits. If, however, there
is a possibility of oil being present on the operator's hands, use the
Soft Cover. The Soft Cover ensures protection equivalent to IP54
against oil. Do not, however, use the H5CZ in locations where it
would come in direct contact with oil.
Soft Cover
Y92A-48F1
Hard Cover
Y92A-48
Flush Mounting Adapter
Y92F-30
Order this Flush Mounting Adapter separately
if it is required.
Waterproo
f
Pack
i
ng
Y92S-29 Order this Waterproof Packing
separately if it is required.
The Waterproof Packing can be used
to achieve IP66 protection.
H5CZ
10
Connection Sockets
Front-connecting Sockets
Note: Round crimp terminals cannot be used on Finger-safe Sockets. Use forked crimp terminals.
Back-connecting Sockets
Note: A Y92A-48G Terminal Cover can be used with the Socket to create a finger-safe construction.
Terminal Covers for P3G-08 Back-connecting Sockets
Note: The Terminal Cover can be used with a Back-mounting Socket (P3G-08) to create a finger-safe construction.
Model Dimensions Terminal arrangement
and internal connections
Mounting hole
dimensions
P2CF-08
(Top View)
Note: The Socket can
also be mounted
to DIN track.
P2CF-08-E
(Finger Safe Terminal)
Model Dimensions Terminal arrangement
and internal connections
P3G-08
(Bottom View)
Model Dimensions
Y92A-48G
4
70 max.
Two, 4.5-dia. holes
Eight, M3.5 x 7.5 sems screws 7.8
20.3 max.
4.5
3
50 max.
35.4
6 5 4 3
7 8 1 2
40±0.2
Two, M4 or 4.5-dia. holes
1278
4365
P2CF-08-E
10A250VAC
RESISTIVE
4
70 max.
Two, 4.5-dia. holes
Eight, M3.5 x 7.5 set screws 7.8
21.5 max.
20.3
19
4.5
35.4
1.3
3
5
50 max.
40±0.2
27 dia
4.9 17
45
45
6543
7812
Y92A-48G UP
P C
34
Twelve, 6.4 dia
47.7×47.7 48×48
27.6
24.6
16.5
47.4
H5CZ
11
Optional Products for Track Mounting
Note: Order Spacers in increments of 10.
1
35
±0.3
7.3
±0.15
27
±0.15
4.5
15 25 2510 15 (5) *
1025 25
1,000 (500) ** The values shown in parentheses are for the PFP-50N.
Mounting Track
PFP-100N
PFP-50N
15 25 25 1,000
4.5
25 25 1510 1
242735±0.3
16
1.5
29.2
10
Mounting Track
PFP-100N2
4.8
1.3
35.5 35.3
1.8
1
1.8
10
6.2
M4 spring washer
50
11.5
M4 x 8 pan
head screw
10
End Plate
PFP-M
5
16
12
44.3 34.8
16.5
Spacer
PFP-S
H5CZ
12
Timer
Operating Procedures
Setting Procedure Guide
Settings for Timer Operation *
Use the following settings.
Settings for Twin Timer Operation *
Refer to page 22.
*At the time of delivery, the H5CZ is set to the Timer configuration. Refer to page 25 for information on switching models.
Operating Procedures for Timer Function
Run mode
Power ON
Function setting mode
Set the time range using the keys.
Set the timer mode using the keys.
Set the output mode using the keys.
Set the input signal width using the keys.
Set the function (instantaneous or time-limit operation) for the instantaneous output (output 1)
using the Keys.
Set each digit for the output time using the corresponding keys.
For details, refer to the Time Range List.
(If the one-shot output time is set to 0.00, is displayed.)
*1. If the mode is switched to the function setting mode during operation, operation will continue.
*2. Changes made to settings in function setting mode are enabled for the first time when the mode is changed to run mode.
Also, when settings are changed, the timer is reset (time initialized and output turned OFF).
Display Set Value
Time Range List
0.01 s to 99.99 s
(default setting)
0.1 s to 999.9 s
1 s to 9999 s
0 min 01 s to
99 min 59 s
0.1 min to
999.9 min
1 min to
9999 min
0 h 01 min to
99 h 59 min
0.1 h to 999.9 h
1 h to 9999 h
0.001 s to
9.999 s
~
Time range
Timer mode
Output modes
One-shot
Output time
Input signal
width
Instantaneous/
time-limit
To next page From next page
(DOWN) (UP)
(1ms) (20ms)
(A-1) (A-2) (A-3) (b-1) (b) (d) (E) (F) (S) (Z) (A)
(0.01s) (99.99s) (Output hold)
Note:
Displayed for modes A, A-1, A-2, A-3, b, b-1 and S only.
Note:
Only modes A-2, b, E, and Z can be selected for models with instantaneous
contact outputs.
Note:
Displayed only for models with instantaneous contact outputs.
3 s min. *2
3 s min. *1
The characters displayed in reverse video are the default settings.
(Instantaneous) (Time-limit)
• Change to Function Setting Mode.
Note:
Not displayed for models with instantaneous contact outputs.
Function setting mode
……
20ms 1ms
2c 1c1c
down up
z a-1 a a-2
99.99 0.01 hold
hold
a-3 b b-1 d e f s
For details on operations in run mode, refer to page 15.
H5CZ
13
Timer
*1
To previous
page
From previous
page
Output ON
count alarm
set value/
monitor value
Key protect
level
Set value
upper limit
(KP-1) (KP-2) (KP-3) (KP-4) (KP-5) (KP-6) (KP-7)
Instantaneous
output 1
(OUT1) ON
count alarm
set value
Instantaneous
output 2
(OUT2) ON
count alarm
set value
(9999 x 1000 times)
(0 x 1000 times)
(9999 x 1000 times)
(0 x 1000 times)
Note: The monitor value is only displayed.
It cannot be set.
Output ON
count alarm
set value
Output ON
count monitor
value
(9999 x 1000 times)
(0 x 1000 times)
Note: The monitor value is only displayed.
It cannot be set.
Note: The monitor value is only displayed.
It cannot be set.
Instantaneous
output 1
(OUT1) ON
count monitor
value
Instantaneous
output 2
(OUT2) ON
count monitor
value
(9999)(1)
99990
99990
99990
9999
kp-2
kp-1 kp-3 kp-4 kp-5 kp-6 kp-7
1
• Models without Instantaneous Contact Outputs
• Models with Instantaneous Contact Outputs
Function setting mode
Set the digits for the set value limit using the corresponding keys.
Set the key protect level using the keys.
*1. Set each digit for the output time using the corresponding keys.
~
~
~
H5CZ
14
Timer
Explanation of Functions
Operating Procedures for Timer Function
Time Range (timr)
Set the range to be timed in the range 0.001 s to 9,999 h.
Timer Mode (timm)
Set either the elapsed time (UP) or remaining time (DOWN) mode.
In UP mode, the elapsed time is displayed, and in DOWN mode, the
remaining time is displayed.
Output Mode (outm)
Set the output mode.
The possible settings are A, A-1, A-2, A-3, b, b-1, d, E, F, Z and S.
(For details on output mode operation, refer to “Timing Charts” on
page 16.)
Output Time (otim)
When using one-shot output, set the output time for one-shot output
(0.01 to 99.99 s).
One-shot output can be used only if the selected output mode is A,
A-1, A-2, A-3, b, b-1 or S.
If the output time is set to 0.00, hold is displayed, and the output is
held.
Input Signal Width (iflt)
Set the minimum signal input width (20 ms or 1 ms) for signal and
reset inputs.
The same setting is used for all external inputs (signal and reset
inputs).
If contacts are used for the input signal, set the input signal width to
20 ms.
Processing to eliminate chattering is performed for this setting.
Key Protect Level (kypt)
Set the key protect level.
Refer to “Key Protect Level” on page 28.
Instantaneous/Time-limit (otmd)
Set the contact output to time-limit SPDT + instantaneous SPDT or
time-limit SPDT operation.
Set Value Upper Limit (sl-h)
Set the upper limit for the set value when it is set in Run Mode.
The limit can be set to between 1 and 9999.
This setting does not apply to the ON duty in Z mode.
Output ON Count Alarm Set Value (on-a)
Set the alarm value for the output ON count.
The limit can be set to between 0 x 1000 (0 times) and 9999 x 1000
(9,999,000 times). Only the underlined values are set. The alarm will
be disabled if 0 is set.
If the total ON count of the output exceeds the alarm set value, e3 will
be displayed on the Timer to indicate that the output ON count alarm
value was exceeded. Refer to “Self-diagnostic Function” on page
28 for information on the e3 display.
ON Count Alarm Set Values for Outputs 1 and 2 (OUT1
and OUT2) (on1a and on2a)
Set the ON count alarm values for the outputs 1 and 2.
The limit can be set to between 0 x 1000 (0 times) and 9999 x 1000
(9,999,000 times). Only the underlined values are set. The alarm will
be disabled if 0 is set.
If the total ON count of instantaneous output 1 or 2 exceeds the alarm
set value, e3 will be displayed on the Timer to indicate that the output
ON count alarm value was exceeded. Refer to “Self-diagnostic
Function” on page 28 for information on the e3 display.
Output ON Count Monitor Value (on-c)
The monitor value is only displayed. It cannot be set.
The output ON count will be 1,000 times the displayed value.
ON Count Monitor Values for Outputs 1 and 2 (OUT1 and
OUT2) (on1c and on2c)
The monitor value for output 1 or 2 is only displayed. It cannot be set.
The output ON count will be 1,000 times the displayed value.
H5CZ
15
Timer
Operation in Run Mode
Operating Procedures for Timer Function
Present value
Set value
Present value
ON duty ratio
Present value
Cycle time
Set each digit for the output time using the corresponding keys.
Note: H5CZ-L8E@ Precautions
Set the Timer’s set value before using the Timer in a self-holding circuit.
Set each digit for the output time using the corresponding keys.
(The keys for the 4th digit cannot be used.)
Set each digit for the output time using the corresponding keys.
When Output Mode Z Is Selected
H5CZ
16
Timer
Timing Charts
Operating Procedures for Timer Function
Models without Instantaneous Contact Outputs Either one-shot output or sustained output can be selected.
Mode A: Signal ON delay 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
The control output is controlled using a sustained or
one-shot time period.
Note: Output is instantaneous when setting is 0.
Mode A-1: Signal ON delay 2 (Timer resets when power comes ON.)
Basic operation Detailed operation
Timing starts when the start signal goes ON, and
resets when the start signal goes OFF.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
The control output is controlled using a sustained or
one-shot time period.
Note: Output is instantaneous when setting is 0.
Mode A-2: Power ON delay 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
Timing starts when the reset input goes OFF.
The start signal disables the timing function.
The control output is controlled using a sustained or
one-shot time period.
Note: Output is instantaneous when setting is 0.
Mode A-3: Power ON delay 2 (Timer does not reset when power comes ON.)
Basic operation Detailed operation
Timing starts when the reset input goes OFF.
The start signal disables the timing function.
The control output is controlled using a sustained or
one-shot time period.
Note: Output is instantaneous when setting is 0.
Power
Output
*
Start signal
inputTiming
Power
Start signal
tt
Reset
Control output
Set value
0
Set value
UP
DOWN
0
Timing diagram
Power
Output
Start signal
input Timing
t
0
0
Power
Start signal
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
Timing
t
0
0
Power
Start signal
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
Timing
Sustained
ttt
0
0
Power
Start signal
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
H5CZ
17
Timer
Mode b: Repeat cycle 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact
output type).
Sustained Output
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The control output is turned ON when time is up.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact
output type).
One-shot Output
Mode b-1: Repeat cycle 2 (Timer does not reset when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact
output type).
Sustained Output
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The control output is turned ON when time is up.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact
output type).
One-shot Output
Power
Output
*
Start signal
inputTiming Timing Timing Timing
0
0
Power
Start signal
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
*
Start signal
inputTiming Timing Timing Timing
tt
0
0
Power
Start signal
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
*
Start signal
inputTiming Timing Timing
Timing Sustained Timing
0
0
Power
Start signal
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
*
Start signal
inputTiming Timing Timing
Timing Sustained Timing
tt tt
0
0
Power
Start signal
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
H5CZ
18
Timer
Mode d: Signal OFF delay (Timer resets when power comes ON.)
Basic operation Detailed operation
*Start signal input is enabled during timing.
The control output is ON when the start signal is ON
(except when the power is OFF or the reset is ON).
The timer resets when the time is up.
Note: Output functions only during start signal input
when setting is 0.
Mode E: Interval (Timer resets when power comes ON.)
Basic operation Detailed operation
*Start signal input is enabled during timing.
Timing starts when the start signal comes ON.
The timer resets when the time is up.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Output is disabled when the setting is 0.
Mode F: Cumulative (Timer does not reset when power comes ON.)
Basic operation Detailed operation
Start signal enables timing (timing is stopped when the
start signal is OFF or when the power is OFF).
A sustained control output is used.
Note: Output is instantaneous when setting is 0.
When the H5CZ is used with power start in mode F (i.e.,
cumulative operation with output on hold), there will be
a timer error (approximately 100 ms each time the
H5CZ is turned ON) due to the characteristics of the
internal circuitry. Use the H5CZ with signal start if timer
accuracy is required.
Mode Z: ON/OFF-duty-adjustable flicker (Timer resets when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (ON at start).
While the start signal is ON, the timer starts when power
comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output
type).
Output
*
Start signal
inputTiming
Power
0
0
Power
Start signal
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
*
Start signal
inputTiming
0
0
Power
Start signal
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
Start signal
inputTiming Sustained Timing
0
0
Power
Start signal
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
*
Start signal
inputTiming
(cycle time)
Timing
ON duty
(%)
Timing
(cycle time)
Timing
ON duty
(%)
Power
Start signal
Reset
Control output
Cycle time
ON duty setting
(%) ON time
0
Cycle time
ON duty setting
(%) ON time
UP
DOWN
0
Timing diagram
H5CZ
19
Timer
Mode S: Stopwatch (Timer resets when power comes ON.)
Basic operation Detailed operation
The signal starts and stops timing.
The display is held and timing is continued if the reset
is received during timing operation.
The timer resets if the reset is received when the
timing operation is stopped.
Note: Output is instantaneous when setting is 0.
Power
Start signal
input
Reset
Display
(for elapsed
time) * flashes
*
Timing
RST
9999
Set time
0
Set time
0
UP
DOWN
Power
Start signal
Reset
Timing diagram
Output
H5CZ
20
Timer
Models with Instantaneous Contact Outputs Either one-shot output or sustained output can be selected.
Note: H5CZ-L8E@ Precautions
Set the Timer’s set value before using the Timer in a self-holding circuit.
Mode A-2: Power ON delay (Timer resets when power comes ON.)
Basic operation Detailed operation
The Timer starts when the power comes ON or when
the reset input goes OFF.
Note: Output is instantaneous when setting is 0.
Mode b: Repeat cycle 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
The Timer starts when the power comes ON or when
the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms.
Time-limit
output
Power
Timing
Instantaneous
output
t-a
Reset Key
Time-limit
contacts, NC
Time-limit
contacts, NO
Instantaneous
contacts, NC
Instantaneous
contacts, NO
t t-a t-aRt Rtt
t = Set time, Rt = Reset time (0.5 s min.), t – a < t (Indicates the time is less than the set time.)
Power
Instantaneous
output
Time-limit
output
Power
t (time) t (time) t (time) t (time)
t-a t-a t-aRt Rtttt t-at-attt
Reset Key
Time-limit
contacts, NC
One-shot Output
Time-limit
contacts, NO
Time-limit
contacts, NC
Instantaneous
contacts, NC
Time-limit
contacts, NO
Instantaneous
contacts, NO
t = Set time, Rt = Reset time (0.5 s min.), t – a < t (Indicates the time is less than the set time.)
Power
Sustained Output
H5CZ
21
Timer
Note: H5CZ-L8E@ Precautions
Set the Timer’s set value before using the Timer in a self-holding circuit.
Mode E: Interval (Timer resets when power comes ON.)
Basic operation Detailed operation
The Timer starts when the power comes ON or when
the reset input goes OFF.
Note: Output is not instantaneous when setting is 0.
Mode Z: ON/OFF-duty adjustable flicker (Timer resets when power comes ON.)
Basic operation Detailed operation
The Timer starts when the power comes ON or when
the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms.
Instantaneous
output
Time-limit
output
Power
Timing
t-a
Reset Key
Time-limit
contacts, NC
Time-limit
contacts, NO
Instantaneous
contacts, NC
Instantaneous
contacts, NO
t t-a t-aRt Rtt
t = Set time, Rt = Reset time (0.5 s min.), t – a < t (Indicates the time is less than the set time.)
Power
Timing (cycle time) Timing (cycle time)
Timing
(ON duty) (ON duty)
Timing
Instantaneous
output
Time-limit
output
Power
t-a t-aRt Rt
ttt-a t-a
dty dty dty dty
t-a
t = Set time, dty = ON duty time, Rt = Reset time (0.5 s min.), t – a < t (Indicates the time is less than the set time.)
Reset Key
Time-limit
contacts, NC
Time-limit
contacts, NO
Instantaneous
contacts, NC
Instantaneous
contacts, NO
Power
H5CZ
22
Twin Timer
Setting Procedure Guide
Operating Procedures for Twin Timer Function
To switch to twin timer operation, use the procedure given below. For details, refer to page 27.
Hold down for 1 s min.
Hold down for 1 s min.
Timer
Press the or Key to
switch to a Twin Timer.
Twin timer
Run mode
Power ON Timer/twin timer
selection mode
1
+
1
+
tim
Step1
Switching to a Twin Timer
twn
Run mode
Power ON
Function setting mode
From next pageTo next page
(1 ms)(20 ms)
3 s min. *2
3 s min. *1
Step2
(DOWN)(UP)
OFF time
range
ON time
range
Timer mode
Twin timer
output mode
Input signal
width
( ) ( ) ( ) ( )
Flicker
OFF start 1
Flicker
On Start 1
Flicker
OFF start 2
Flicker
On Start 2
Note: Not displayed for models with instantaneous contact outputs.
Note: Only Flicker OFF Start 1 or Flicker ON Start 1 can be selected for the H5CZ-L8E@.
20ms
up down
1ms
toff ton tof1 ton1
……
……
For details, refer to Time Range List.
For details, refer to Time Range List.
The characters displayed in reverse video are the default settings.
• Change to Function Setting Mode.
Function setting mode
Set the OFF time range using the keys.
Set the ON time range using the keys.
Set the timer mode using the keys.
Set the twin timer output mode using the keys.
Set the input signal width using the keys.
*1. If the mode is switched to the function setting mode during operation, operation will continue.
*2. Changes made to settings in function setting mode are enabled for the first time when the mode is changed to run mode.
Also, when settings are changed, the timer is reset (time initialized and output turned OFF).
Display Set Value
Time Range List
0.01 s to 99.99 s
(default setting)
0.1 s to 999.9 s
1 s to 9999 s
0 min 01 s to
99 min 59 s
0.1 min to
999.9 min
1 min to
9999 min
0 h 01 min to
99 h 59 min
0.1 h to 999.9 h
1 h to 9999 h
0.001 s to
9.999 s
For details on operations in run mode, refer to page 24.
H5CZ
23
Twin Timer
~
~
~
Set the function (instantaneous or time-limit operation) for the instantaneous output (output 1)
using the Keys.
(KP-1) (KP-2) (KP-3) (KP-4) (KP-5) (KP-6) (KP-7)
(9999 x 1000 times)
(0 x 1000 times)
(9999 x 1000 times)
(0 x 1000 times)
(9999 x 1000 times)
(0 x 1000 times)
Note: The monitor value is only displayed.
It cannot be set.
Note:
The monitor value is only displayed.
It cannot be set.
Note:
The monitor value is only displayed.
It cannot be set.
To previous
page
From previous
page
Function setting mode
Set the digits for the set value limit using the corresponding keys.
Set the key protect level using the keys.
Set value
upper limit 1
Set the digits for the set value limit using the corresponding keys.
Set value
upper limit 2
Key protect
level
Output ON
count alarm
set value/
monitor value
Output ON
count alarm
set value
Output ON
count monitor
value
Instantaneous
output 1
(OUT1) ON
count alarm
set value
Instantaneous
output 2
(OUT2) ON
count alarm
set value
Instantaneous
output 1
(OUT1) ON
count monitor
value
Instantaneous
output 2
(OUT2) ON
count monitor
value
• Models without Instantaneous Contact Outputs
• Models with Instantaneous Contact Outputs
*1. Set the digits for the output ON alarm set value using the corresponding
keys.
*1
Note: Displayed only for models with instantaneous contact outputs.
(Instantaneous) (Time-limit)
Instantaneous/
time-limit
(9999)(1)
99990
99990
99990
9999
kp-2
kp-1 kp-3 kp-4 kp-5 kp-6 kp-7
1
(9999)(1)
99991
2c1c1c
H5CZ
24
Twin Timer
Explanation of Functions
Operating Procedures for Twin Timer Function
OFF Time Range (oftr)
Set the time range for the OFF time in the range 0.000 s to 9,999 h.
ON Time Range (ontr)
Set the time range for the ON time in the range 0.001 s to 9,999 h.
Timer Mode (timm)
Set either the elapsed time (UP) or remaining time (DOWN) mode.
In UP mode, the elapsed time is displayed, and in DOWN mode, the
remaining time is displayed.
Twin Timer Output Mode (totm)
Set the output mode.
Set either flicker OFF start or flicker ON start. (For details on output
mode operation, refer to "Timing Charts" on page 25.)
Input Signal Width (iflt)
Set the minimum signal input width (20 ms or 1 ms) for signal and
reset inputs.
The same setting is used for all external inputs (signal and reset
inputs).
If contacts are used for the input signal, set the input signal width to
20 ms.
Processing to eliminate chattering is performed for this setting.
Key Protect Level (kypt)
Set the key protect level.
Refer to “Key Protect Level” on page 28.
Operation in Run Mode
Operating Procedures for Twin Timer Function
Present Value and OFF Set Time
The present value is displayed in the main display and the OFF set
time is displayed in the sub-display. Set the OFF time.
Present Value and ON Set Time
The present value is displayed in the main display and the ON set
time is displayed in the sub-display. Set the ON time.
Present value
OFF set time
Present value
ON set time
Note: 1. The display will automatically show the OFF set time when the OFF time is being timed and the ON set time when the ON time is being timed.
Note: 2. H5CZ-L8E@ Precautions
Set the Timer’s set value before using the Timer in a self-holding circuit.
Set the digits for the OFF set time using the corresponding keys.
Set the digits for the OFF set time using the corresponding keys.
H5CZ
25
Twin Timer
Timing Charts
Operating Procedures for Timer Function
Models without Instantaneous Contact Outputs
Mode toff: Flicker OFF start 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output
type).
Mode ton: Flicker OFF start 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (ON at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output
type).
Mode toff-1: Flicker OFF start 2 (Timer does not reset when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output
type).
Power
Output
*
Start signal
inputTiming
OFF
Timing
ON
Timing
OFF
Timing
ON
ON time
OFF time
0
OFF time
ON time
0
UP
DOWN
Power
Start signal
Reset
Control output
Timing diagram
Power
Output
*
Start signal
inputTiming
ON
Timing
OFF
Timing
ON
Timing
OFF
0
0
ON time
OFF time
OFF time
ON time
UP
DOWN
Power
Start signal
Reset
Control output
Timing diagram
Power
Output
*
Start signal
input
Timing
OFF
Timing
ON
Timing
OFF
(a + b = ON time)
ab
0
0
ON time
OFF time
OFF time
ON time
UP
DOWN
Power
Start signal
Reset
Control output
Timing diagram
H5CZ
26
Twin Timer
Models with Instantaneous Contact Outputs
Note: H5CZ-L8E@ Precautions
Set the Timer’s set value before using the Timer in a self-holding circuit.
Mode ton-1: Flicker ON start 2 (Timer does not reset when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (ON at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output
type).
Mode toff: Flicker OFF start 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
The Timer starts when the power comes ON or when
the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the ON time and OFF time to at least 100
ms.
Mode ton: Flicker ON start 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
The Timer starts when the power comes ON or when
the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the ON time and OFF time to at least 100
ms.
Timing
ON
Timing
OFF
Timing
ON
(a + b = OFF time)
ab
Power
Output
*
Start signal
input
0
0
ON time
OFF time
OFF time
ON time
UP
DOWN
Power
Start signal
Reset
Control output
Timing diagram
Ton timeToff timeTon timeToff time
Instantaneous
output
Time-limit
output
Power
t-a t- bt-a Rt Rt t-off t-on t-off t-b t-a t-off t-on t-off
t-on = ON time, t-off = OFF time, Rt = Reset time (0.1 s min.), t – a < t-off and t – b < t-on
(
Indicates the time is less than the set time.
)
Reset Key
Time-limit
contacts, NC
Time-limit
contacts, NO
Instantaneous
contacts, NC
Instantaneous
contacts, NO
Power
Toff time
Ton time
Toff time
Ton time
Instantaneous
output
Time-limit
output
Power
t-b t-a t-bRt Rtt-on t-off t-on t-a t-bt-on t-off t-on
t-on = ON time, t-off = OFF time, Rt = Reset time (0.1 s min.), t – a < t-off and t – b < t-on
(Indicates the time is less than the set time.)
Reset Key
Time-limit
contacts, NC
Time-limit
contacts, NO
Instantaneous
contacts, NC
Instantaneous
contacts, NO
Power
H5CZ
27
Timer/Twin Timer Selection Mode (Configuration Selection)
Select whether the H5CZ is used as a timer or a twin timer in timer/twin timer selection mode.
1
+
1
twn
1
1
tim
KeyKey
1 s min.
*1. When the mode is changed to timer/twin timer selection mode, the present value is reset and output turns OFF.
Timing operation is not performed in timer/twin timer selection mode.
*2. Setting changes made in timer/twin timer selection mode are enabled when the mode is changed to run mode.
If settings are changed, the HC5Z is automatically reset (present value initialized, output turned OFF).
Power ON
Timer/Twin
timer selection
Caution
Run mode
Timer/Twin Timer
Selection Mode
*2 *1
To change the mode to timer/twin timer selection mode,
hold down the key for 1 s min. with the key held
down. The key must be pressed before the key. If the
key is pressed first, the mode will not change.
Select either timer operation or twin timer operation using the
keys.
Note: The H5CZ is factory-set for timer operation.
H5CZ
28
Key Protect Level
When the key-protect switch is set to ON, it is possible to prevent setting errors by prohibiting the use of certain operation keys by specifying the
key protect level (KP-1 to KP-7).
The key protect indicator is lit while the key-protect switch is set to ON.
*Changing mode to Timer/Twin Timer Selection Mode or Function Setting Mode.
Self-diagnostic Function
The following displays will appear if an error occurs.
*1. This includes times when the life of the EEPROM has expired.
*2. The normal display and e3 will appear alternately.
When the Reset Key is pressed, e3 will no longer be displayed even if the alarm set value is exceeded. (Monitoring is possible, however, because the Timer will
continue without clearing the output ON count.)
Level Meaning
Details
Changing mode*
Switching display
during operation
Reset Key
Up/down key
KP-1
(default setting) Invalid Valid Valid Valid
KP-2 Invalid Valid Invalid Valid
KP-3 Invalid Valid Valid Invalid
KP-4 Invalid Valid Invalid Invalid
KP-5 Invalid Invalid Invalid Invalid
KP-6 Invalid Invalid Valid Valid
KP-7 Invalid Invalid Invalid Valid
Main display Sub-display Error Output status Correction method Set value after reset
e1 Not lit CPU OFF Either press the reset key or
reset the power supply. No change
e2 Not lit Memory error (RAM) OFF Reset the power supply. No change
e2 sum Memory error EEPROM *1 OFF Reset Key Factory setting
e3 *2 No change Output ON count alarm set
value exceeded No change Reset Key No change
* Factory-set to OFF
*
OFF
(Disabled)
ON
(Enabled)
Key protect indicator
H5CZ
29
Safety Precautions for All H5CZ Series (Common)
Do not allow pieces of metal, wire clippings, or fine
metallic shavings or fillings from installation to enter
the product. Doing so may occasionally result in
electric shock, fire, or malfunction.
Minor injury due to explosion may occasionally occur.
Do not use the Timer where subject to flammable or
explosive gas.
Fire may occasionally occur. Tighten the terminal
screws to the rated torque.
P2CF Socket terminals: 4.4 lb-in (0.5 N m)
Minor injury due to electric shock may occasionally
occur. Do not touch any of the terminals while power
is being supplied. Be sure to mount the terminal cover
after wiring.
The life expectancy of the output relay varies
considerably according to its usage. Use the output
relay within its rated load and electrical life
expectancy. If the output relay is used beyond its life
expectancy, its contacts may become fused or there may be a
risk of fire. Also, be sure that the load current does not exceed
the rated load current and when using a heater, be sure to use a
thermal switch in the load circuit.
Minor electric shock, fire, or malfunction may
occasionally occur. Do not disassemble, modify, or
repair the Timer or touch internal components.
The panel surface of the H5CZ is water-resistant (conforming to
NEMA4, IP66, UL Type 4X (Indoor Use Only). To protect the
internal circuits from water penetration through the space between
the H5CZ and operating panel, waterproof packing is included.
Attach the Y92F-30 Adapter with sufficient pressure with the
reinforcing screws so that water does not penetrate the panel.
When mounting the Timer to a panel, tighten the two mounting
screws alternately, a little at a time, so as to keep them at an equal
tightness. If the panel screws are tightened unequally, water may
enter the panel.
Store the Timer at the specified temperature. If the Time has been
stored at a temperature of less than -10°C, allow the Time to stand
at room temperature for at least 3 hours before use.
Mounting the Timer side-by-side may reduce the life expectancies
of internal components.
Use the Timer within the specified ranges for the ambient operating
temperature and humidity.
Do not use in the following locations:
Locations subject to sudden or extreme changes in
temperature.
Locations where high humidity may result in condensation.
Do not use the Timer outside of the rated ranges for vibration,
shock, water exposure, and oil exposure.
Do not use this Timer in dusty environments, in locations where
corrosive gasses are present, or in locations subject to direct
sunlight.
Install the Timer well away from any sources of static electricity,
such as pipes transporting molding materials, powders, or liquids.
Internal elements may be destroyed if a voltage outside the rated
voltage range is applied.
Be sure that polarity is correct when wiring the terminals.
Separate the Timer from sources of noise, such as devices with
input signals from power lines carrying noise, and wiring for I/O
signals.
Do not connect more than two crimp terminals to the same
terminal.
Up to two wires of the same size and type can be inserted into a
single terminals.
Use the specified wires for wiring. Applicable Wires: AWG 18 to
AWG 22, solid or twisted, copper.
Install a switch or circuit breaker that allows the operator to
immediately turn OFF the power, and label it to clearly indicate its
function.
Approximately 14 V is output from the input terminals. Use a
sensor that contains a diode.
Use a switch, relay, or other contact so that the rated power supply
voltage will be reached within 0.1 seconds. If the power supply
voltage is not reached quickly enough, the Timer may malfunction
or outputs may be unstable.
Use a switch, relay, or other contact to turn the power supply OFF
instantaneously. Outputs may malfunction and memory errors may
occur if the power supply voltage is decreased gradually.
When changing the set value during a timing operation, the output
will turn ON if the set value is changed as follows because of the
use of a constant read-in system:
Elapsed time (UP) mode: Present value Set value
Remaining time (DOWN) mode: Elapsed time Set value (The
present value is set to 0.)
When in the remaining time mode, the amount the set value is
changed is added to or subtracted from the present value.
Operation with a set value of 0 will vary with the output mode. Refer
to the timing charts on page 16.
Do not use organic solvents (such as paint thinners or benzine),
strong alkali, or strong acids. They will damage the external finish.
Confirm that indications are working normally, including the LCD.
The indicator LCD, and resin parts may deteriorate more quickly
depending on the application environment, preventing normal
indications. Periodic inspection and replacement are required.
The waterproof packing may deteriorate, shrink, or harden
depending on the application environment. Periodic inspection and
replacement are required.
CAUTION
Precautions for Safe Use
It is recommended that the
space between the screw
head and the Adapter be 0.5
to 1 mm.
0.5 to 1 mm
Input0V
Sensor
Diode
H5CZ
30
H5CZ models with a 24-VDC/12 to 24-VDC power supply use a
transformer-free power supply method in which the power supply
terminals are not isolated from the signal input terminals. If a non-
isolating DC power supply is used, unwanted current paths may
occasionally burn or destroy internal components depending on
the wiring. Always check the wiring sufficiently before use.
An inrush current of approx. 10 A will flow for a short time when the
power supply is turned ON. If the capacity of the power supply is
not sufficient, the Timer may not start. Be sure to use a power
supply with sufficient capacity.
Maintain voltage fluctuations in the power supply within the
specified operating voltage range.
When turning the power ON and OFF, input signal reception is
possible, unstable, or impossible as shown in the diagram below.
To allow for the startup time of peripheral devices (sensors, etc.),
the Timer starts timing operation between 200 to 250 ms after
power is turned ON. For this reason, in operations where timing
starts from power ON, the time display will actually start from 249
ms. If the set value is 249 ms or less, the time until output turns ON
will be a fixed value between 200 and 250. The present value
display will start from 250 ms. (Normal operation is possible for set
values of 250 ms or more.) In applications where a set value of 249
ms or less is required, use start timing with signal input.
Inrush current generated by turning ON or OFF the power supply
may deteriorate contacts on the power supply circuit. Turn ON or
OFF to a device with the rated current of more than 10 A.
Make sure that all settings are appropriate for the application.
Unexpected operation resulting in property damage or accidents
may occur if the settings are not appropriate.
Do not leave the Timer for long periods at a high temperature with
output current in the ON state. Doing so may result in the
premature deterioration of internal components (e.g., electrolytic
capacitors).
EEPROM is used as backup memory when the power is
interrupted. The write life of the EEPROM is 100,000 writes.
The EEPROM is written at the following times:
When the power supply is turned OFF
When switching from Timer/Twin Timer Selection Mode or
Function Setting Mode to Run Mode
Dispose of the product according to local ordinances as they apply.
When conforming to EMC standards, refer to the information
provided in this datasheet for cable selection and other conditions.
This is a class A product. In residential areas it may cause radio
interference, in which case the user may be required to take
adequate measures to reduce interference.
Basic insulation is provided between the power supply and input
terminals. (No insulation is provided between the power supply and
input terminals for the H5CZ-L8D.)
Basic insulation is provided between power supply and output
terminals, and between input and output terminals.
When double insulation or reinforced insulation is required, apply
double insulation or reinforced insulation as defined in IEC 60664
that is suitable for the maximum operating voltage with clearances
or solid insulation.
Connect the input and output terminals to devices that do not have
any exposed charged parts.
Precautions for Correct Use
Input Impossible
200ms 5ms0 to 50 ms 0 to 500 ms
Possible
Unstable
Unstable Impossible
Power
supply
ON
OFF
Conformance to EN/IEC Standards
Warranty and Application Considerations
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or
other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER
ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET
THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS,
OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,
INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE
MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of
products in the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with
your OMRON representative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Authorized Distributor:
In the interest of product improvement,
specifications are subject to change without notice.
© OMRON Corporation 2009 All Rights Reserved.
OMRON Corporation Industrial Automation Company
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
Contact: www.ia.omron.com
Tokyo, JAPAN
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 Cat. No. L116-E1-01
Printed in Japan
0709
CSM_6_1_0614
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
Y92A-48F1