https://www.phoenixcontact.com/us/products/2688064
09/03/2014Page1/6
I/O module-AXL AI 8-2688064
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Axioline analog input module, 8 inputs: 0 - 10V, ±10V, 0 - 20mA, 4 - 20mA, ±20mA, 2-wire connection method
(including bus base module and connectors)
Product description
The module is designed for use within an Axioline station.
It is used to acquire analog voltage and current signals. 
Product Features
8 analog, bipolar input channels for the connection of either voltage or current signals
Connection of sensors in 2-wire technology
Voltage ranges: 0V ... 10V, ±10V, 0V ... 5V, ±5V
Current ranges: 0mA ... 20mA, 4mA ... 20mA, ±20mA
Device rating plate stored
Diagnostic and status indicators
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 240.0 GRM
Custom tariff number 85389091
Country of origin Germany
Technical data
Dimensions
Width 53.6 mm
Height 126.1 mm
Depth 54 mm
Note on dimensions The depth is valid when a TH35-7.5 DIN rail is used (according to
EN60715).
Ambient conditions
https://www.phoenixcontact.com/us/products/2688064
09/03/2014Page2/6
I/O module-AXL AI 8-2688064
Technical data
Ambient conditions
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 5 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Connection data
Designation AxiolineF connector
Connection method Push-in technology
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 1.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 16
Stripping length 8 mm
General
Weight 204 g
Note on weight specifications with connectors and bus base module
Mounting type DIN rail
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Test section 5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1 min
5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Electrostatic
discharge (ESD) EN61000‑4‑2/IEC61000‑4‑2 Criterion B; 6 kV contact
discharge, 8 kV air discharge
Noise immunity test in accordance with EN 61000-6-2 Electromagnetic
fields EN61000‑4‑3/IEC61000‑4‑3 Criterion A; Field intensity: 10 V/m
Noise immunity test in accordance with EN 61000-6-2 Fast transients
(burst) EN61000‑4‑4/IEC61000‑4‑4 Criterion B, 2kV
Noise immunity test in accordance with EN 61000-6-2 Transient surge
voltage (surge) EN61000‑4‑5/IEC61000‑4‑5 Criterion B; supply lines DC:
±0.5 kV/±0.5 kV (symmetrical/asymmetrical); ±1 kV to shielded I/O cables
Noise immunity test in accordance with EN 61000-6-2 Conducted
interference EN61000‑4‑6/IEC61000‑4‑6 Criterion A; Test voltage 10 V
Noise emission test according to EN 61000-6-3 Radio interference
properties EN 55022 Class B
https://www.phoenixcontact.com/us/products/2688064
09/03/2014Page3/6
I/O module-AXL AI 8-2688064
Technical data
General
Mechanical tests Vibration resistance in acc. with EN60068-2-6/IEC60068-2-6 5g
Shock in acc. with EN60068-2-27/IEC60068-2-27 25g, 11 ms period, half-
sine shock pulse
Continuous shock according to EN60068-2-27/IEC60068-2-27 10g
Interfaces
Designation AxiolineFlocal bus
Connection method Bus base module
Transmission speed 100 MBit/s
Axioline potentials
Communications power UBus 5 V DC (via bus base module)
Current consumption from UBus typ. 105 mA
max. 130 mA
Supply of analog modules UA24 V DC
Current consumption from UAtyp. 35 mA
max. 45 mA
Analog inputs
Number of inputs max. 8 (Differential inputs, voltage or current can be chosen separately)
Connection method Push-in technology
2-wire (shielded, twisted pair)
Input name Analog inputs
A/D conversion time 2 µs
Resolution A/D 16 bit
Limit frequency (3 dB) 30 Hz
12 kHz (in fast mode)
Type of protection Transient protection of inputs
Protective circuit/component Suppressor diode
Data formats IB IL, S7-compatible
Measured value representation 16 bits (15 bits + sign bit)
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Voltage input signal 0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
https://www.phoenixcontact.com/us/products/2688064
09/03/2014Page4/6
I/O module-AXL AI 8-2688064
Technical data
Analog inputs
Precision 0.1 % (of measuring range final value for active mean-value generation
and 30 Hz filter)
Filtering RFI filtering / passive TP 1st order
Input filter 30 Hz, 12 kHz and mean-value generation (can be parameterized)
Number of inputs 8 (differential inputs, current)
Type of protection Overload protection
Protective circuit/component No; ±5.2VDC, maximum, Imax = 50mA
Open circuit response Going to 0mA; open-circuit detection from 4 mA ... 20 mA
Number of inputs 8 (differential inputs, voltage)
Type of protection Overload protection
Protective circuit/component ±30 V DC, maximum
Open circuit response Goes to 0V
Classifications
eCl@ss
eCl@ss 4.0 27240405
eCl@ss 4.1 27240405
eCl@ss 5.0 27242201
eCl@ss 5.1 27242601
eCl@ss 6.0 27242601
eCl@ss 7.0 27242601
eCl@ss 8.0 27242601
ETIM
ETIM 3.0 EC001599
ETIM 4.0 EC001596
ETIM 5.0 EC001596
UNSPSC
UNSPSC 6.01 43172015
UNSPSC 7.0901 43201404
UNSPSC 11 39121311
UNSPSC 12.01 39121311
UNSPSC 13.2 39121311
Approvals
Approvals
https://www.phoenixcontact.com/us/products/2688064
09/03/2014Page5/6
I/O module-AXL AI 8-2688064
Approvals
Approvals
UL Listed / cUL Listed / BSH / RINA / DNV / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
BSH
RINA
DNV
cULus Listed
Drawings
https://www.phoenixcontact.com/us/products/2688064
09/03/2014Page6/6
I/O module-AXL AI 8-2688064
Dimensioned drawing
53,6 54
122,4
126,1
Connection diagram
U1+
I1+
U1–
I1–
U2+
I2+
U2–
I2–
U
U
I
I
Connection for voltage and current measurement
Connection diagram
U1+
I1+
U1–
I1–
U2+
I2+
U2–
I2–
P
I
+24V
GND
Passive pressure sensor at a differential current input
Connection diagram
U1+
I1+
U1–
I1–
U2+
I2+
U2–
I2–
P
U
+24V
GND
Differential voltage input with active 3-wire transmitter
Block diagram
D
UA
E1
E2
8x
AI 1...8
U
24 V
ANA
UBus
Local bus
m
C
U/I
#
U
REF
Supervisor
FE
M
U
X
8:1
Internal wiring of the terminal points
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com