Operating Instructions • 11/2016
Vibrating Switches
SITRANS LVL200E
RELAY (DPDT)
2*7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
3
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-16112833840-EN-161128
Contents
1 About this document
1.1 Function ........................................................................................................................... 5
1.2 Target group ..................................................................................................................... 5
1.3 Symbols used................................................................................................................... 5
2 For your safety
2.1 Authorised personnel ....................................................................................................... 6
2.2 Appropriate use ................................................................................................................ 6
2.3 Warning about incorrect use ............................................................................................. 6
2.4 General safety instructions ............................................................................................... 6
2.5 Safety label on the instrument .......................................................................................... 7
2.6 EU conformity ................................................................................................................... 7
2.7 SIL conformity .................................................................................................................. 7
2.8 Safety instructions for Ex areas ........................................................................................ 7
3 Product description
3.1 Conguration .................................................................................................................... 8
3.2 Principle of operation........................................................................................................ 9
3.3 Adjustment ....................................................................................................................... 9
3.4 Storage and transport..................................................................................................... 10
3.5 Accessories.................................................................................................................... 10
4 Mounting
4.1 General instructions ....................................................................................................... 12
4.2 Mounting instructions ..................................................................................................... 15
5 Connecting to power supply
5.1 Preparing the connection ............................................................................................... 18
5.2 Connection procedure .................................................................................................... 18
5.3 Wiring plan, single chamber housing.............................................................................. 19
6 Setup
6.1 General information ........................................................................................................ 21
6.2 Adjustment elements ...................................................................................................... 21
6.3 Function table ................................................................................................................. 22
7 Maintenanceandfaultrectication
7.1 Maintenance .................................................................................................................. 24
7.2 Rectify faults ................................................................................................................... 24
7.3 Exchanging the electronics ............................................................................................ 25
7.4 How to proceed if a repair is necessary .......................................................................... 25
8 Dismount
8.1 Dismounting steps.......................................................................................................... 26
8.2 Disposal ......................................................................................................................... 26
9 Supplement
9.1 Technical data ................................................................................................................ 27
9.2 Dimensions .................................................................................................................... 34
9.3 Trademark ...................................................................................................................... 37
4*7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
Safety instructions for Ex areas
TakenoteoftheExspecicsafetyinstructionsforExapplications.
These instructions are attached as documents to each instrument
with Ex approval and are part of the operating instructions manual.
Editing status: 2016-11-18
5
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
1 About this document
1.1 Function
This operating instructions manual provides all the information you
need for mounting, connection and setup as well as important instruc-
tionsformaintenanceandfaultrectication.Pleasereadthisinforma-
tion before putting the instrument into operation and keep this manual
accessible in the immediate vicinity of the device.
1.2 Target group
This operating instructions manual is directed to trained specialist
personnel. The contents of this manual should be made available to
these personnel and put into practice by them.
1.3 Symbols used
Information, tip, note
This symbol indicates helpful additional information.
Caution: If this warning is ignored, faults or malfunctions can result.
Warning: If this warning is ignored, injury to persons and/or serious
damage to the instrument can result.
Danger: If this warning is ignored, serious injury to persons and/or
destruction of the instrument can result.
Ex applications
This symbol indicates special instructions for Ex applications.
SIL applications
This symbol indicates instructions for functional safety which must be
taken into account particularly for safety-relevant applications.
List
The dot set in front indicates a list with no implied sequence.
→ Action
This arrow indicates a single action.
1 Sequence of actions
Numbers set in front indicate successive steps in a procedure.
Battery disposal
This symbol indicates special information about the disposal of bat-
teries and accumulators.
6*7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
2 For your safety
2.1 Authorised personnel
All operations described in this operating instructions manual must
be carried out only by trained specialist personnel authorised by the
plant operator.
During work on and with the device the required personal protective
equipment must always be worn.
2.2 Appropriate use
The SITRANS LVL200E is a sensor for point level detection.
Youcannddetailedinformationabouttheareaofapplicationin
chapter "Product description".
Operational reliability is ensured only if the instrument is properly
usedaccordingtothespecicationsintheoperatinginstructions
manual as well as possible supplementary instructions.
For safety and warranty reasons, any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer. Arbi-
traryconversionsormodicationsareexplicitlyforbidden.
2.3 Warning about incorrect use
Inappropriate or incorrect use of the instrument can give rise to
application-specichazards,e.g.vesseloverllordamagetosystem
components through incorrect mounting or adjustment.
2.4 General safety instructions
This is a state-of-the-art instrument complying with all prevailing
regulations and guidelines. The instrument must only be operated in a
technicallyawlessandreliablecondition.Theoperatorisresponsible
for the trouble-free operation of the instrument.
During the entire duration of use, the user is obliged to determine the
compliance of the necessary occupational safety measures with the
current valid rules and regulations and also take note of new regula-
tions.
The safety instructions in this operating instructions manual, the na-
tional installation standards as well as the valid safety regulations and
accident prevention rules must be observed by the user.
For safety and warranty reasons, any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer. Arbi-
traryconversionsormodicationsareexplicitlyforbidden.
The safety approval markings and safety tips on the device must also
be observed.
7
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
2.5 Safety label on the instrument
The safety approval markings and safety tips on the device must be
observed.
2.6 EU conformity
ThedevicefullsthelegalrequirementsoftheapplicableEUguide-
lines.ByaxingtheCEmarking,weconrmsuccessfultestingofthe
product.
2.7 SIL conformity
SITRANSLVL200Efullstherequirementstofunctionalsafetyac-
cordingtoIEC61508orIEC61511.Youndfurtherinformationinthe
Safety Manual "SITRANS LVL200".
2.8 Safety instructions for Ex areas
PleasenotetheEx-specicsafetyinformationforinstallationandop-
eration in Ex areas. These safety instructions are part of the operating
instructions manual and come with the Ex-approved instruments.
8*7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
3 Product description
3.1 Conguration
The scope of delivery encompasses:
SITRANS LVL200E point level switch
Documentation
This operating instructions manual
Safety Manual "Functional safety (SIL)" (optional)
Ex-specic"Safety instructions" (with Ex versions)
Ifnecessary,furthercerticates
The SITRANS LVL200E consists of the components:
Housing lid
Housing with electronics
Processttingwithtuningfork
1
2
3
Fig. 1: SITRANS LVL200E
1 Housing lid
2 Housing with electronics
3 Processtting
Thetypelabelcontainsthemostimportantdataforidenticationand
use of the instrument:
Article number
Serial number
Technical data
Article numbers, documentation
SILidentication(withSILratingexworks)
Scope of delivery
Constituent parts
Type label
9
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
3.2 Principle of operation
SITRANS LVL200E is a point level sensor with tuning fork for point
level detection.
It is designed for industrial use in all areas of process technology and
can be used in liquids.
Typicalapplicationsareoverllanddryrunprotection.Thesmall
tuning fork allows use in all kinds of tanks and vessels. Thanks to its
simple and rugged measuring system, SITRANS LVL200E is virtually
unaectedbythechemicalandphysicalpropertiesoftheliquid.
Itfunctionsevenunderdicultconditionssuchasturbulence,airbub-
bles, foam generation, buildup, strong external vibration or changing
products.
Function monitoring
The electronics module of SITRANS LVL200E continuously monitors
the following criteria via frequency evaluation:
Strong corrosion or damage on the tuning fork
Loss of vibration
Linebreaktothepiezodrive
If a malfunction is detected or in case of power failure, the electron-
icstakesonadenedswitchingcondition,i.e.therelaydeenergises
(safe state).
Thetuningforkispiezoelectricallyenergisedandvibratesatits
mechanicalresonancefrequencyofapprox.1200Hz.Thepiezosare
xedmechanicallyandarehencenotsubjecttotemperatureshock
limitations. The frequency changes when the tuning fork is covered
by the medium. This change is detected by the integrated electronics
module and converted into a switching command.
SITRANS LVL200E is a compact instrument, i.e. it can be oper-
ated without external evaluation system. The integrated electronics
evaluates the level signal and outputs a switching signal. With this
switching signal, a connected device can be operated directly (e.g. a
warning system, a pump etc.).
Thedataforpowersupplyarespeciedinchapter"Technical data".
3.3 Adjustment
Withthefactorysetting,productswithadensity≥0.7g/cm³
(0.025lbs/in³)canbedetected.Theinstrumentcanbeadaptedto
products with lower density.
Ontheelectronicsmoduleyouwillndthefollowingdisplayand
adjustment elements:
Signal lamp for indication of the switching condition (green/red)
DIL switch for sensitivity adjustment
Mode adjustment for selection of the switching condition (A/B)
Application area
Functional principle
Voltage supply
10 *7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
3.4 Storage and transport
Your instrument was protected by packaging during transport. Its
capacity to handle normal loads during transport is assured by a test
based on ISO 4180.
The packaging of standard instruments consists of environment-
friendly, recyclable carton material. The sensing element is additional-
ly protected with a cardboard cover. For special versions, PE foam or
PE foil is also used. Please dispose of the packaging material through
specialised recycling companies.
Transport must be carried out in due consideration of the notes on the
transport packaging. Nonobservance of these instructions can cause
damage to the device.
The delivery must be checked for completeness and possible transit
damage immediately at receipt. Ascertained transit damage or con-
cealed defects must be appropriately dealt with.
Up to the time of installation, the packages must be left closed and
stored according to the orientation and storage markings on the
outside.
Unless otherwise indicated, the packages must be stored only under
the following conditions:
Not in the open
Dry and dust free
Not exposed to corrosive media
Protected against solar radiation
Avoiding mechanical shock and vibration
Storage and transport temperature see chapter "Supplement -
Technical data - Ambient conditions"
Relative humidity 20 … 85 %
3.5 Accessories
Screwedangesareavailableindierentversionsaccordingtothe
following standards: DIN 2501, EN 1092-1, BS 10, ASME B 16.5,
JIS B 2210-1984, GOST 12821-80.
Youcanndadditionalinformationinthesupplementaryinstructions
manual "Flanges according to DIN-EN-ASME-JIS".
The electronics module SW E60 is a replacement part for level switch-
es SITRANS LVL200E.
Youcanndinformationintheoperatinginstructionsmanualofthe
electronics module.
For connecting the sensors with a separator to voltage supply or sig-
nal processing, the sensors are also available with plug connectors.
The following plug connectors are available:
M12 x 1
ISO 4400
Packaging
Transport
Transport inspection
Storage
Storage and transport
temperature
Flanges
Electronics module
Plug connector
11
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
Harting HAN 7D
Harting HAN 8D
Amphenol-Tuchel
12 *7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
4 Mounting
4.1 General instructions
Make sure that all parts of the instrument coming in direct contact
with the process, especially the sensor element, process seal and
processtting,aresuitablefortheexistingprocessconditions,such
as process pressure, process temperature as well as the chemical
properties of the medium.
Youcanndthespecicationsinchapter"Technical data" and on the
nameplate.
In general, SITRANS LVL200E can be installed in any position. The
instrument only has to be mounted in such a way that the tuning fork
is at the height of the desired switching point.
The tuning fork has lateral markings (notches) that indicate the
switching point with vertical mounting. The switching point applies
to water in conjunction with the basic setting of the density switch
≥0.7g/cm³(0.025lbs/in³).WhenmountingSITRANSLVL200E,
make sure that this marking is at the height of the requested switch-
ing point. Keep in mind that the switching point of the instrument will
shiftifthemediumhasadensityotherthanwater-wateris1g/cm³
(0.036lbs/in³).Forproducts≤0.7g/cm³(0.025lbs/in³)and≥0.5g/
cm³(0.018lbs/in³)thedensityswitchmustbesetto≥0.5g/cm³.
Keepinmindthatfoamswithadensity≥0.45g/cm³(0.016lbs/in³)
are detected by the sensor. This can lead to erroneous switchings,
particulary when the sensor is used for dry run protection.
Suitability for the process
conditions
Switching point
13
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
2
3
14
Fig. 2: Vertical mounting
1 Switching point approx. 13 mm (0.51 in)
2 Switching point with lower density
3 Switching point with higher density
4 Switching point approx. 27 mm (1.06 in)
1
Fig. 3: Horizontal mounting
1 Switching point
1
2
Fig. 4: Horizontal installation (recommended mounting position, particularly for
adhesive products)
1 Switching point
2 Marking with screwed version, facing up
Inthecaseofangeversions,theforkisalignedasfollows.
14 *7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
1
Fig.5:Forkpositionwithangeversions
1 Markingwithangeversion,facingup
Use the recommended cables (see chapter "Connecting to power
supply") and tighten the cable gland.
You can give your instrument additional protection against moisture
penetration by leading the connection cable downward in front of the
cableentry.Rainandcondensationwatercanthusdraino.Thisap-
plies mainly to outdoor mounting as well as installation in areas where
high humidity is expected (e.g. through cleaning processes) or on
cooled or heated vessels.
Fig. 6: Measures against moisture ingress
Caution:
Do not hold SITRANS LVL200E on the tuning fork. Particularly with
angeortubeversions,thetuningforkcanbedamagedjustbythe
weight of the instrument. Transport coated instruments very carefully
and avoid touching the tuning fork.
Remove the packaging or the protective cover just before installation.
Theprocessttingmustbesealedifthereisgaugeorlowpressurein
the vessel. Before use, check if the seal material is resistant against
the measured product and the process temperature.
Moisture
Transport
Pressure/Vacuum
15
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
Themax.permissiblepressureisspeciedinchapter"Technical
data" or on the type label of the sensor.
The vibrating level switch is a measuring instrument and must be
treated accordingly. Bending the vibrating element will destroy the
instrument.
Warning:
The housing must not be used to screw the instrument in! Applying
tightening force can damage internal parts of the housing.
Use the hexagon above the thread for screwing in.
Metric threads
In the case of instrument housings with metric thread, the cable
glands are screwed in at the factory. They are sealed with plastic
plugs as transport protection.
You have to remove these plugs before electrical connection.
NPT thread
In the case of instrument housings with self-sealing NPT threads, it is
not possible to have the cable entries screwed in at the factory. The
free openings for the cable glands are therefore covered with red dust
protection caps as transport protection.
Prior to setup you have to replace these protective caps with ap-
proved cable glands or close the openings with suitable blind plugs.
4.2 Mounting instructions
SITRANSLVL200Ehasadenedthreadstartingpoint.Thismeans
that every SITRANS LVL200E is in the same fork position after being
screwed in. Remove therefore the supplied seal from the thread of
SITRANS LVL200E. This seal is not required when using a welded
socket with O-ring in front.
Keep in mind that this welded socket is not suitable for coated instru-
ment versions.
Screw SITRANS LVL200E completely into the welded socket. The
later position can be determined already before welding. Mark the
appropriate position of the welded socket. Before welding, unscrew
SITRANS LVL200E and remove the rubber ring from the welded
socket. The welded socket has a marking (notch). Weld the socket
with the notch facing upward, or in case of pipelines (DN 32 up to
DN50),alignedwiththedirectionofow.
Handling
Cable entries - NPT
thread
Cable glands
Welded socket
16 *7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
1
Fig. 7: Marking on the welded socket
1 Marking
Incaseofhorizontalmountinginadhesiveandviscousproducts,
the surfaces of the tuning fork should be vertical in order to reduce
builduponthetuningfork.Onthescrewedversionyouwillnda
marking on the hexagon. With this you can check the position of the
tuning fork when screwing it in. When the hexagon touches the seal,
thethreadcanstillbeturnedbyapprox.halfaturn.Thisissucientto
reach the recommended installation position.
Inthecaseofangeversions,theforkisalignedwiththeangeholes.
When used in adhesive and viscous products, the tuning fork should
protrude into the vessel to avoid buildup. For that reason, sockets
forangesandmountingbossesshouldbeavoidedwhenmounting
horizontally.
IfSITRANSLVL200Eismountedinthellingstream,unwantedfalse
measurement signals can be generated. For this reason, mount
SITRANS LVL200E at a position in the vessel where no disturbances,
e.g.fromllingopenings,agitators,etc.,canoccur.
This applies particularly to instrument types with long extension tube.
Fig.8:Inowingmedium
To make sure the tuning fork of SITRANS LVL200E generates as little
resistanceaspossibletoproductow,mountthesensorsothatthe
surfaces are parallel to the product movement.
Adhesive products
Inowingmedium
Productow
17
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
Duetotheeectsofagitators,equipmentvibrationorsimilar,the
level switch can be subjected to strong lateral forces. For this reason,
do not use an overly long extension tube for SITRANS LVL200E,
but check if you can mount a level switch on the side of the vessel in
horizontalposition.
Extreme vibration caused by the process or the equipment, e.g.
agitators or turbulence in the vessel, can cause the extension tube of
SITRANS LVL200E to vibrate in resonance. This leads to increased
stress on the upper weld joint. Should a longer tube version be neces-
sary, you can provide a suitable support directly above the tuning fork
to secure the extension tube.
This measure applies mainly to applications in Ex areas category 1G
or WHG. Make sure that the tube is not subject to bending stress due
to this measure.
Fig. 9: Lateral suppot of SITRANS LVL200E
Instruments with enamel coating should be treated very carefully and
shocks should be avoided. Unpack SITRANS LVL200E directly before
installation. Insert SITRANS LVL200E carefully into the vessel open-
ing and avoid touching any sharp vessel parts.
The second seal of the gas-tight leadthrough (option) prevents an
uncontrolled leakage of the medium. The service life of the gas-tight
leadthrough depends on the chemical resistance of the materials.
See "Technical data".
Caution:
If it is determined (e.g. via an error message from SITRANS LVL200E)
that medium has already penetrated into the vibrating element, the
instrument must be exchanged immediately.
Agitators
Enamel coating
Gas-tight leadthrough
18 *7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
5 Connecting to power supply
5.1 Preparing the connection
Always keep in mind the following safety instructions:
Warning:
Connect only in the complete absence of line voltage.
The electrical connection must only be carried out by trained
personnel authorised by the plant operator.
Alwaysswitchopowersupply,beforeconnectingordisconnect-
ing the instrument.
Note:
Install a separating facility for the instrument which is easy to access.
The separating facility must be marked for the instrument (IEC/
EN 61010).
Inhazardousareasyoumusttakenoteoftherespectiveregulations,
conformityandtypeapprovalcerticatesofthesensorsandpower
supply units.
Connect the voltage supply according to the connection diagrams.
The electronics module with relay output is designed in protection
class I. To maintain this protection class, it is absolutely necessary
that the earth conductor be connected to the inner earth conductor
terminal. Keep the general installation regulations in mind. Take note
ofthecorrespondinginstallationregulationsforhazardousareaswith
Ex applications.
Thedataforpowersupplyarespeciedinchapter"Technical data".
The instrument is connected with standard three-wire cable without
screen. If electromagnetic interference is expected which is above the
test values of EN 61326 for industrial areas, screened cable should
be used.
Use cable with round cross-section. A cable outer diameter of
5…9mm(0.2…0.35in)ensuresthesealeectofthecablegland.
Ifyouareusingcablewithadierentdiameterorcross-section,
exchange the seal or use a suitable cable gland.
Inhazardousareas,useonlyapprovedcableconnectionsforSI-
TRANS LVL200E.
Take note of the corresponding installation regulations for Ex applica-
tions.
Cover all housing openings conforming to standard according to
EN 60079-1.
5.2 Connection procedure
With Ex instruments, the housing cover may only be opened if there is
no explosive atmosphere present.
Proceed as follows:
Note safety instructions
Take note of safety
instructions for Ex
applications
Voltage supply
Connection cable
Connection cable
for Ex applications
19
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
1. Unscrew the housing lid
2. Loosen compression nut of the cable gland and remove blind
plug
3. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) of insulation from the ends of the individual wires
4. Insert the cable into the sensor through the cable entry
5. Open the terminals with a screwdriver
6. Insert the wire ends into the open terminals according to the wir-
ing plan
7. Tighten the terminals with a screwdriver
8. Check the hold of the wires in the terminals by lightly pulling on
them
9. Tighten the compression nut of the cable entry gland. The seal
ring must completely encircle the cable
10. Screw the housing lid back on
Theelectricalconnectionisnished.
5.3 Wiring plan, single chamber housing
The following illustrations apply to the non-Ex as well as to the Ex-d
version.
3
5
1
2
4
20-250V AC
20-72V DC
A
B
LN
12 345678
0,5 g / cm3
0,7 g / cm3
3 4 5 6 7 8
+
SW E60R
Fig. 10: Electronics and terminal compartment, single chamber housing
1 Control lamp
2 DIL switch for mode adjustment
3 DIL switch for switching point adaptation
4 Ground terminal
5 Connection terminals
Electronics and terminal
compartment
20 *7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
We recommend connecting SITRANS LVL200E in such a way that
the switching circuit is open when there is a level signal, line break or
failure (safe state).
Information:
The relays are always shown in non-operative condition.
1
2
3
123456
+
L1
-
N
78
Fig. 11: Wiring plan, single chamber housing
1 Relay output
2 Relay output
3 Voltage supply
Wiring plan
21
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
6 Setup
6.1 General information
Theguresinbracketsrefertothefollowingillustrations.
Inthebasicsetting,productswithadensity≥0.7g/cm³(0.025lbs/in³)
can be detected. For products with lower density, you have to set the
switchto≥0.5g/cm³(0.018lbs/in³).
Ontheelectronicsmoduleyouwillndthefollowingdisplayand
adjustment elements:
Control lamp for indication of the switching condition (1)
DIL switch for mode adjustment - A/B (2)
DIL switch for sensitivity adjustment (3)
Note:
Always immerse the tuning fork of SITRANS LVL200E in a liquid to
test its function. Do not test the function of SITRANS LVL200E with
your hand. This can damage the sensor.
6.2 Adjustment elements
12345678
1
2
3
Fig. 12: Oscillator SWE60R - Relay output
1 Control lamp (LED)
2 DIL switch for mode adjustment
3 DIL switch for sensitivity adjustment
Control lamp for indication of the switching status
green=relayenergized
red=relaydeenergized
red(ashing)=failure
With the mode adjustment (A/B) you can change the switching
condition of the relay. You can set the required mode according to the
"Function table"(A-max.detectionoroverowprotection,B-min.
detection or dry run protection).
Function/Conguration
Signal lamp (1)
Mode adjustment (2)
22 *7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
With this DIL switch (3) you can set the switching point to liquids
havingadensitybetween0.5and0.7g/cm³(0.018and0.025lbs/
in³).Withthebasicsetting,liquidswithadensityof≥0.7g/cm³(0.025
lbs/in³)canbedetected.Inliquidswithlowerdensity,youmustset
theswitchto≥0.5g/cm³(0.018lbs/in³).Thespecicationsforthe
positionoftheswitchingpointrelatetowater-densityvalue1g/cm³
(0.036lbs/in³).Inproductswithadierentdensity,theswitchingpoint
will shift in the direction of the housing or tuning fork end depending
on the density and type of installation.
Note:
Keepinmindthatfoamswithadensity≥0.45g/cm³(0.016lbs/in³)
are detected by the sensor. This can lead to erroneous switchings,
particulary when the sensor is used for dry run protection.
6.3 Function table
The following table provides an overview of the switching conditions
depending on the set mode and the level.
Level Switching status Control lamp
Mode A
Overowprotec-
tion 53 4
(8)(6) (7)
Relayenergized Green
Mode A
Overowprotec-
tion 53 4
(8)(6) (7)
Relay deener-
gized
Red
Mode B
Dry run protection 53 4
(8)(6) (7)
Relayenergized Green
Mode B
Dry run protection 53 4
(8)(6) (7)
Relay deener-
gized
Red
Failure of the sup-
ply voltage
(mode A/B)
any
53 4
(8)(6) (7)
Relay deener-
gized
O
Sensitivity adjustment (3)
23
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
Level Switching status Control lamp
Fault any
53 4
(8)(6) (7)
Relay deener-
gized
ashesred
24 *7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
7 Maintenanceandfaultrectication
7.1 Maintenance
If the instrument is used properly, no special maintenance is required
in normal operation.
7.2 Rectify faults
The operator of the system is responsible for taking suitable meas-
ures to rectify faults.
SITRANSLVL200Eoersmaximumreliability.Nevertheless,faults
can occur during operation. These may be caused by the following,
e.g.:
Sensor
Process
Voltage supply
Signal processing
Therstmeasuretotakeistochecktheoutputsignal.Inmanycases,
thecausescanbedeterminedthiswayandthefaultsquicklyrectied.
Error Reason Removal
SITRANS LVL200E signals "cov-
ered" without being submerged
(overllprotection)
SITRANS LVL200E signals "uncov-
ered" when being submerged (dry
run protection)
Operating voltage too low Check operating voltage
Electronics defective Press the mode switch. If the instru-
ment then changes the mode, the
vibrating element may be covered
with buildup or mechanically dam-
aged. Should the switching function
in the correct mode still be faulty, re-
turn the instrument for repair.
Press the mode switch. If the in-
strument then does not change the
mode, the electronics module may
be defective. Exchange the electron-
ics module.
Unfavourable installation location Mount the instrument at a location in
thevesselwherenodeadzonesor
air bubbles can form.
Buildup on the vibrating element Check the vibrating element and the
sensor for buildup and remove the
buildup if there is any.
Wrong mode selected Set the correct mode with the mode
switch(overowprotection,dryrun
protection). Wiring should be carried
out according to the closed-circuit
principle.
Reaction when malfunc-
tion occurs
Causes of malfunction
Faultrectication
Checking the switching
signal
25
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
Error Reason Removal
Signallampashesred Error on the vibrating element Check if the vibrating element is
damaged or extremely corroded.
Interference on the electronics mod-
ule
Exchanging the electronics module
instrument defective Exchange the instrument or send it
in for repair
Depending on the reason for the fault and the measures taken, the
steps described in chapter "Set up" may have to be carried out again.
7.3 Exchanging the electronics
If the electronics module is defective, it can be replaced by the user.
In Ex applications only an electronics module with respective Ex ap-
proval may be used.
Youcanndalltheinformationyouneedtocarryoutanelectronics
exchange in the handbook of the new electronics module.
In general, all electronics modules of series SW60 can be inter-
changed.Ifyouwanttouseanelectronicsmodulewithadierent
signaloutput,youcarryoutthecompletesetup.Youndtheneces-
sary, suitable operating instruction on our homepage.
Note:
Keep in mind that enamelled instrument versions need special
electronics modules. These electronics modules are called SW60E or
SW60E1.
7.4 How to proceed if a repair is necessary
If it is necessary to repair the instrument, please contact Siemens
MilltronicsProcessInstrumentsInc.Youndthelocationsonour
homepage "www.siemens.com/processautomation".
Reaction after fault recti-
cation
26 *7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
8 Dismount
8.1 Dismounting steps
Warning:
Before dismounting, be aware of dangerous process conditions such
as e.g. pressure in the vessel, high temperatures, corrosive or toxic
products etc.
Take note of chapters "Mounting" and "Connecting to power supply"
and carry out the listed steps in reverse order.
With Ex instruments, the housing cover may only be opened if there is
no explosive atmosphere present.
8.2 Disposal
The instrument consists of materials which can be recycled by spe-
cialised recycling companies. We use recyclable materials and have
designed the parts to be easily separable.
WEEE directive 2002/96/EG
This instrument is not subject to the WEEE directive 2002/96/EG and
the respective national laws. Pass the instrument directly on to a spe-
cialised recycling company and do not use the municipal collecting
points. These may be used only for privately used products according
to the WEEE directive.
Correctdisposalavoidsnegativeeectsonhumansandtheenviron-
ment and ensures recycling of useful raw materials.
Materials: see chapter "Technical data"
If you have no way to dispose of the old instrument properly, please
contact us concerning return and disposal.
27
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
9 Supplement
9.1 Technical data
Note for approved instruments
The technical data in the respective safety instructions are valid for approved instruments (e.g. with
Exapproval).Thesedatacandierfromthedatalistedherein,forexampleregardingtheprocess
conditions or the voltage supply.
General data
Material 316L corresponds to 1.4404 or 1.4435
Materials, wetted parts
Ʋ Processtting-thread 316L, Alloy C22 (2.4602)
Ʋ Processtting-ange 316L, 316L with Alloy C22 (2.4602) coating, steel enam-
elled, 316L with ECTFE coating, 316L with PFA coating
ƲProcess seal Klingersil C-4400
ƲTuning fork 316L, Alloy C22 (2.4602), Alloy C4 (2.4610) enamelled
ƲExtension tube: ø 21.3 mm (0.839 in) 316L, Alloy C22 (2.4602), Alloy C22 (2.4602) enamelled,
316L with ECTFE coating, 316L with PFA coating
Materials, non-wetted parts
ƲAluminium die-cast housing Aluminium die-casting AlSi10Mg, powder-coated - basis:
Polyester
ƲStainless steel housing, electropol-
ished
316L
ƲSeal between housing and housing lid Silicone SI 850 R, NBR silicone-free
ƲGround terminal 316L
ƲCable gland PA, stainless steel, brass
ƲSealing, cable gland NBR
ƲBlind plug, cable gland PA
ƲTemperature adapter (optional) 316L
Second Line of Defense (optional)1)
ƲThe Second Line of Defense (SLOD)
is a second level of the process
separation in the form of a gas-tight
feedthrough in the lower part of the
housing, preventing product from
penetrating into the housing.
ƲSupporting material 316L
ƲGlass potting Borosilicate glass - Schott no. 8421
ƲContacts 1.4101
ƲHelium leak rate < 10-6 mbar l/s
ƲPressure resistance PN 64
1) or gas-tight leadthrough
28 *7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
Sensor length (L)
Ʋ316L, Alloy C22 (2.4602) 80 … 6000 mm (3.15 … 236.2 in)
ƲAlloy C22 (2.4602) enamelled 80 … 1500 mm (3.15 … 59.06 in)
Ʋ316L, ECTFE coated 80 … 3000 mm (3.15 … 118.1 in)
Ʋ316L, PFA coated 80 … 4000 mm (3.15 … 157.48 in)
Tube diameter ø 21.3 mm (0.839 in)
Weight
ƲInstrument weight (depending on
processtting)
approx. 0.8 … 4 kg (0.18 … 8.82 lbs)
ƲTube extension approx.920g/m(9.9oz/ft)
Layer thickness
ƲEnamel approx. 0.8 mm (0.031 in)
ƲECTFE approx. 0.5 mm (0.02 in)
ƲPFA approx. 0.5 mm (0.02 in)
Surface quality
ƲStandard Ra < 3 µm (1.18-4 in)
ƲHygienic version (3A) Ra < 0.8 µm (3.15-5 in)
ƲHygienic version (3A) Ra < 0.3 µm (1.18-5 in)
Processttings
ƲPipe thread, cylindrical (DIN 3852-A) G¾, G1
ƲAmerican pipe thread, conical
(ASME B1.20.1)
¾ NPT, 1 NPT
ƲFlanges DIN from DN 25, ASME from 1"
Ʋ hygienicttings Slotted nut DN 40 PN 40, Clamp 1" DIN 32676
ISO 2852/316L, Clamp 2" DIN 32676 ISO 2852/316L,
conus DN 25 PN 40, Tuchenhagen Varivent DN 50
PN 10
Max.torque-processtting
ƲThread G¾, ¾ NPT 75 Nm (55 lbf ft)
ƲThread G1, 1 NPT 100 Nm (73 lbf ft)
Torque for NPT cable glands and Conduit tubes
ƲAluminium/Stainless steel housing max. 50 Nm (36.88 lbf ft)
Gas-tight leadthrough (optional)
ƲLeakage rate < 10-6 mbar l/s
ƲPressure resistance PN 64
High voltage test (enamel) max. 5 KV
Output variable
Output Relayoutput(DPDT),2oatingspdts
Switching voltage
ƲMin. 10 mV
ƲMax. 253 V AC, 253 V DC
29
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
Switching current
ƲMin. 10 µA
ƲMax. 3 A AC, 1 A DC
Breaking capacity
ƲMin. 50 mW
ƲMax. 750 VA AC, 54 W DC
If inductive loads or stronger currents are switched
through, the gold plating on the relay contact surface will
be permanently damaged. The contact is then no longer
suitable for switching low-level signal circuits.
Contact material (relay contacts) AgNi (Au plated) or AgSnO (Au plated)
Modes (switchable)
ƲAMax.detectionoroverow/overllprotection
ƲB Min. detection or dry run protection
Accuracy (according to DIN EN 60770-1)
Reference conditions and actuating variables according to DIN EN 61298-1
ƲAmbient temperature +18 … +30 °C (+64 … +86 °F)
ƲRelative humidity 45 … 75 %
ƲAir pressure 860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
ƲProduct temperature +18 … +30 °C (+64 … +86 °F)
ƲProduct density 1g/cm³(0.036lbs/in³)(water)
ƲProduct viscosity 1 mPa s
ƲSuperimposed pressure 0 kPa
ƲSensor installation Vertically from top
ƲDensity selection switch ≥0.7g/cm³
Measuring accuracy
Deviation ± 1 mm (0.04 in)
30 *7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
Inuenceoftheprocesstemperatureontheswitchingpoint
1
3
4
2
10 ( 25/64")
8 ( 5/16")
6 ( 15/64")
4 ( 5/32")
2 ( 5/64")
-2 (-5/64")
-4 (-5/32")
-6 (-15/64")
-8 (-5/16")
-10 (-25/64")
0
0°C
(32 °F)
100°C
(212 °F)
150°C
(302 °F)
200°C
(392 °F)
250°C
(482 °F)
50°C
(122 °F)
Fig.29:Inuenceoftheprocesstemperatureontheswitchingpoint
1 Shifting of the switching point in mm (in)
2 Process temperature in °C (°F)
3 Switching point at reference conditions (notch)
4 Tuning fork
Inuenceoftheproductdensityontheswitchingpoint
1
2
4
3
5
6
1,2
(0,043)
1
(0,036)
0,8
(0,029)
0,6
(0,022)
1,4
(0,051)
1,6
(0,058)
1,8
(0,065)
2
(0,072)
2,2
(0,079)
2,4
(0,087)
10 ( 25/64")
8 ( 5/16")
6 ( 15/64")
4 ( 5/32")
2 ( 5/64")
-2 (-5/64")
-4 (-5/32")
-6 (-15/64")
-8 (-5/16")
-10 (-25/64")
0
Fig.30:Inuenceoftheproductdensityontheswitchingpoint
1 Shifting of the switching point in mm (in)
2 Product density in g/cm³ (lb/in³)
3 Switchposition≥0.5g/cm³(0.018lb/in³)
4 Switchposition≥0.7g/cm³(0.025lb/in³)
5 Switching point at reference conditions (notch)
6 Tuning fork
31
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
Inuenceoftheprocesspressuretotheswitchingpoint
1
2
3
4
12
(174,1)
38
(551,1)
25
(362,6)
51
(739,7)
64
(928,2)
10 ( 25/64")
8 ( 5/16")
6 ( 15/64")
4 ( 5/32")
2 ( 5/64")
-2 (-5/64")
-4 (-5/32")
-6 (-15/64")
-8 (-5/16")
-10 (-25/64")
0
Fig.31:Inuenceoftheprocesspressuretotheswitchingpoint
1 Shifting of the switching point in mm (in)
2 Process pressure in bar (psig)
3 Switching point at reference conditions (notch)
4 Tuning fork
Repeatability 0.1 mm (0.004 in)
Hysteresis approx. 2 mm (0.08 in) with vertical installation
Switching delay approx.500ms(on/o)
Measuring frequency approx.1200Hz
Ambient conditions
Ambient temperature on the housing -40 … +70 °C (-40 … +158 °F)
Storage and transport temperature -40 … +80 °C (-40 … +176 °F)
Process conditions
Measured variable Limit level of liquids
Process pressure -1 … 64 bar/-100 … 6400 kPa (-14.5 … 928 psig)
The process pressure is dependent on the process
tting,forexampleClamporange(seethefollowing
diagrams)
Maximum allowable operating pressure 100 bar/10000 kPa (1450 psig) or 1.5 times process
pressure
The function of the instrument is ensured up to an
operating pressure of 100 bar/10000 kPa (1450 psig)
at a maximum process temperature of +50 °C (+122 °F)
(only with threaded versions).
Processtemperature(threadorange
temperature)
ƲSITRANS LVL200E of 316L/Alloy C22
(2.4602)
-50 … +150 °C (-58 … +302 °F)
32 *7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
Processtemperature(threadorange
temperature) with temperature adapter
(option)
ƲSITRANS LVL200E of 316L/Alloy C22
(2.4602)
-50 … +250 °C (-58 … +482 °F)
ƲSITRANS LVL200E enamelled -50 … +200 °C (-58 … +392 °F)
ƲSITRANS LVL200E with ECTFE
coating
-50 … +150 °C (-58 … +302 °F)
ƲSITRANS LVL200E with PFA coating -50 … +250 °C (-58 … +482 °F)
200 °C
(392 °F)
250 °C
(482 °F)
-50 °C
(-58 °F)
-40 °C
(-40 °F)
0 °C
(32 °F)
40 °C
(104 °F)
70 °C
(158 °F)
50 °C
(122 °F)
100 °C
(212 °F)
150 °C
(302 °F)
1
23
Fig. 32: Ambient temperature - Process temperature
1 Process temperature in °C (°F)
2 Ambient temperature in °C (°F)
3 Temperature range with temperature adapter
1
2
-50 °C
(-58 °F)
0°C
(32 °F)
50°C
(122 °F)
100°C
(212 °F)
150°C
(302 °F)
200°C
(392 °F)
250°C
(482 °F)
20
(290)
-1 (-14,5)
40
(580)
64
(928)
Fig.33:Processtemperature-Processpressurewithswitchposition≥0.7g/cm³(sensitivityswitch)
1 Process pressure in bar (psig)
2 Process temperature in °C (°F)
33
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
1
2
-50 °C
(-58 °F)
0°C
(32 °F)
50°C
(122 °F)
100°C
(212 °F)
150°C
(302 °F)
200°C
(392 °F)
250°C
(482 °F)
20
(290)
-1 (-14,5)
40
(580)
64
(928)
Fig.34:Processtemperature-Processpressurewithswitchposition≥0.5g/cm³(sensitivityswitch)
1 Process pressure in bar (psig)
2 Process temperature in °C (°F)
Viscosity - dynamic 0.1 … 10000 mPa s (requirement: with density 1)
Flow velocity max. 6 m/s (with a viscosity of 10000 mPa s)
Density 0.7…2.5g/cm³(0.025…0.09lbs/in³);0.5…2.5g/cm³
(0.018…0.09lbs/in³)byswitchingover
Vibration resistance
ƲInstrument housing 1gat5…200HzaccordingtoEN60068-2-6(vibration
with resonance)
ƲSensor 1gwith5…200HzaccordingEN60068-2-6(vibration
at resonance) with sensor length up to 50 cm (19.69 in)
Withasensorlength>50cm(19.69in)youhavetox
the extension tube with a suitable support. See mounting
instructions.
Electromechanical data
Cable entry/plug (dependent on the version)
ƲSingle chamber housing 1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm),
1xblindplugM20x1.5;attached1xcableentry
M20 x 1.5
or:
1 x cable entry ½ NPT, 1 x blind plug ½ NPT, 1 x cable
entry ½ NPT
or:
1xplugM12x1;1xblindplugM20x1.5
Screw terminals for wire cross-section up to 1.5 mm² (AWG 16)
Adjustment elements
Mode switch
ƲAMax.detectionoroverow/overllprotection
ƲB Min. detection or dry run protection
Density changeover switch
Ʋ ≥0.5g/cm³ 0.5…2.5g/cm³(0.018…0.09lbs/in³)
34 *7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
Ʋ ≥0.7g/cm³ 0.7…2.5g/cm³(0.025…0.09lbs/in³)
Voltage supply
Operating voltage 20…253VAC,50/60Hz,20…72VDC(at
U >60 V DC, the ambient temperature can be max.
50 °C/122 °F)
Power consumption max. 8 VA (AC), 1,5 W (DC)
Electrical protective measures
Protection rating IP 66/IP 67 (NEMA Type 4X)
Overvoltage category III
Protection class I
Approvals
Dependingontheversion,instrumentswithapprovalscanhavedierenttechnicaldata.Forthese
instruments, please note the corresponding approval documents. They are included in the scope of
delivery.
9.2 Dimensions
SITRANS LVL200E
125 mm (4 59/64")
~ 116 mm (4 9/16")
ø 84 mm (3 5/16")
M20x1,5M20x1,5/
½ NPT
~ 59 mm
(2 21/64") ø 80 mm
(3 5/32")
112 mm (4 13/32")
M20x1,5/
½ NPT
21
Fig. 35: Housing versions
1 Aluminium housing
2 Stainless steel housing, electropolished
35
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
SITRANS LVL200E
G3/4A, 3/4"NPT
G1A, 1"NPT
L
L
L
L
L
32 (G3/4A, 3/4"NPT)
41 (G1A, 1"NPT)
45
123
18,5 mm
(0.73")
57 mm
(2.24")
50 mm
(1.97")
ø 33,7 mm
(1.33")
36 mm
(1.42")
19 mm
(0.75")
50 mm
(1.97")
L
6
ø 21,3 mm
(0.84")
Fig. 36: SITRANS LVL200E
1 Thread
2 Clamp
3 Cone DN 25
4 Slotted nut DN 40
5 Flange
6 Tuchenhagen Varivent
L = Sensor length, see chapter "Technical data"
36 *7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
SITRANS LVL200E, options
34 mm
(1.34")
178 mm (7.01")
1 2
Fig. 37: Options
1 Gas-tight leadthrough
2 Temperature adapter
37
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
9.3 Trademark
All the brands as well as trade and company names used are property of their lawful proprietor/
originator.
Notes
38 *7ML19985KW01*SITRANS LVL200E - Operating Instructions
33840-EN-161128
Notes
39
*7ML19985KW01* SITRANS LVL200E - Operating Instructions
33840-EN-161128
Siemens Canada Limited
PD PA PI LW
1954 Technology Drive
P.O. Box 4225
Peterborough, ON
K9J 7B1, Canada
email: techpubs.smpi@siemens.com
www.siemens.com/processautomation
Subject to change without prior notice
*7ML19985KW01* Rev. 0.0