Three Phase RFI Power Line Filters for High Noise Applications
The AYC series filters are designed for 3-phase, four-wire,
WYE wiring applications. These cost-effective filters help
better protect electronic equipment in industrial
applications.
The series offers filtering up to 180 amps maximum and is
used in 3-phase, noisy industrial applications such as
frequency converters. The AYC series is designed to
comply with International Standards including EN133200
and UL 1283.
16
Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
AYC Series
AYC Series
CORCOM Product Guide
Electrical Schematic
LINE LOAD
A
B
C
N
GND
A
B
C
N
GND
Specifications
Maximum leakage current, each line-to-ground
16A
25/36A
63
80/110/150A
180A
Hipot rating (one minute):
line-to-ground 1850 VDC
line-to-line 1850 VDC
line-to-neutral 1450 VDC
Operating frequency: 50/60 Hz
Operating voltage (max.): 480 VAC
Rated current:
16AYC10B 16A 80AYC10B 80A
25AYC10B 25A 110AYC10B 110A
36AYC10B 36A 150AYC10B 150A
63AYC10B 63A 180AYC10B 180A
Typical insertion loss in dB:
Line-to-ground in 50 ohm circuit
Current Frequency-MHz
Rating .01 .05 .1 .5 1 5 10 30
16A 23 66 82 88 82 79 55 21
25A 26 68 83 93 88 68 45 4
36A 18 61 78 96 91 71 49 7
63A 11 57 72 90 86 68 44 4
110A 10 51 60 88 84 74 50 12
150A* 0 50 57 82 79 75 51 7
150A 1 51 55 85 82 84 51 11
180A 3 53 55 97 89 81 56 20
Line-to-line in 50 ohm circuit
Current Frequency-MHz
Rating .01 .05 .1 .5 1 5 10 30
16A 21 32 54 90 86 73 72 47
25A 23 33 60 100 95 87 70 38
36A 25 37 51 94 87 69 58 17
63A 27 45 41 84 77 63 61 43
110A 27 35 39 75 72 51 44 31
150A* 28 37 42 74 67 52 45 30
150A 28 40 42 73 66 51 44 31
180A 30 41 50 70 64 49 42 26
*150AYC10B-95 only
UL Recognized AYC10B
Resistor location for reference only.Resistor location for reference only.
120 VAC 60Hz:
62mA
68mA
74mA
74mA
111mA
250 VAC 50Hz:
106mA
118mA
128mA
129mA
192mA
Case Dimensions
Part No. ABCDE
± .078
(max) (max) (max) (max) ± 0.2
16AYC10B 6.69 4.37 2.56 4.92 2.76
170.0 111.0 65.0 125.0 70.0
25AYC10B 9.96 5.08 2.52 5.71 4.53
246.0 129.0 64.0 145.0 115.0
36AYC10B 10.35 5.08 2.52 5.71 4.53
263.0 129.0 64.0 145.0 115.0
63AYC10B 10.89 5.08 2.52 5.71 4.53
279.0 129.0 64.0 145.0 115.0
80/110/150 12.09 5.55 5.55 6.10 4.53
AYC10B 307.0 141.0 141.0 155.0 115.0
180AYC10B 15.71 5.55 5.55 6.10 3.25
399.0 141.0 141.0 155.0 82.5
Ground Terminals
Part Numbers
16AYC10B 110AYC10B
25AYC10B 150AYC10B
36AYC10B 150AYC10B-95
63AYC10B 180AYC10B
80AYC10B
Type (qty.) Torque
16AYC10B
Ground Terminals M5 (2) 51 - 55 in. lb.
Phoenix Contacts VDFK4 (8) 5.3 (min.)
Accepts 12 AWG stranded wire. Strip length 0.315
25AYC10B
Ground Terminals M5 (2) 51 - 55 in. lb.
Phoenix Contacts VDFK6 (8) 13.3 (min.)
Accepts 10 AWG stranded wire. Strip length 0.354
36AYC10B
Ground Terminals M5 (2) 54 - 58 in. lb.
Phoenix Contacts HDFK10 (8) 13.3 (min.)
Accepts 8 AWG stranded wire. Strip length 0.433
63AYC10B
Ground Terminals M6 (2) 54 - 58 in. lb.
Phoenix Contacts HDFK16 (8) 17.7 (min.)
Accepts 6 AWG stranded wire. Strip length 0.630
80/110/150AYC10B
Ground Terminals M10 (2) 56 - 60 in. lb.
Phoenix Contacts HDFK50 (8) 53.1 (min.)
Accepts 1 AWG stranded wire. Strip length 0.945
150AYC10B-95
Ground Terminals M10 (2) 56 - 60 in. lb.
Phoenix Contacts HDFK95 (8) 132 (min.)
Accepts 0 AWG stranded wire. Strip length 1.063
Three Phase RFI Power Line Filters for High Noise Applications (Continued)
Case Styles
17
Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
RFI Power Line Filters
AYC Series
CORCOM Product Guide
16, 25, 36, 63 AYC10B
80, 110, 150AYC10B / -95
180 AYC10B
BD
E
A
C
BD
E
A
C
BD
A
C
EE