SPECIFICATION CONTROL DRAWING CMC-0553 TITLE WIRE, RADIATION-CROSSLINKED, MODIFIED FLEXIBLE ETFE-INSULATED, Date Revision NORMAL WEIGHT, GENERAL PURPOSE, 600 VOLT 28-Mar-11 N1 This specification sheet forms a part of the latest issue of Raychem Specification 80. CONDUCTOR - NICKEL-COATED COPPER PRIMARY INSULATION - RADIATION-CROSSLINKED, MODIFIED FLEXIBLE ETFE COLOR - LIGHT GREEN JACKET - RADIATION-CROSSLINKED, MODIFIED FLEXIBLE ETFE TABLE |. CONSTRUCTION DETAILS DIAMETER OF FINISHED WIRE STRANDED PART NUMBER Moe oO RANGING. CONDUCTOR Ae oe rANCE DIAMETER MAXIMUM (AWG) | (number x AWG) (in.) AT 20C (in.) WEIGHT MINIMUM | MAXIMUM | (ohms/1000 ft.) (lbs/1000 ft.) CMC-0553-8-* 8 133 x 29 158 173 694 216 + 008 70.8 CMC-0553-6-* 6 133 x 27 198 217 436 267 + 010 107. CMC-0553-4-* 4 133 x 25 250 274 275 325 + .010 170. CMC-0553-2-* 2 665 x 30 320 340 AT7 407 + .016 261. CMC-0553-1-* 1 817 x 30 360 380 144 453 4.016 309. CMC-0553-0-* 0 1045 x 30 395 425 113 504 + .016 429, CMC-0553-00-* 00 1330 x 30 440 475 089 553+ 016 530. CMG-0553-000-* 000 1665 x 30 500 540 O71 630 + .016 634. CMC-0553-0000-* | 0000 2109 x 30 565 605 056 698 + .016 765. PART NUMBER 1 CMC-0553-8-* CMC-0553-6-* CMC-0553-4-* CMC-0553-2-* CMC-0553-1-* CMC-0553-0-* CMC-0553-00-* CMC-0553-000-* CMC-0553-0000-* TABLE II. PERFORMANCE DETAILS BEND TESTING MANDREL DIAMETER WEIGHT (inch) (+ 3%) (Ib) (+ 3%) CROSSLINKING PROOF TEST CROSSLINKING PROOF TEST 3.00 4,00 4.00 4.00 5.00 4.00 6.00 6.00 8.00 6.00 8.00 6.00 10.0 8.00 10.0 8.00 10.0 8.00 Users should evaluate the suitability of this product for their application. Specifications are subject to change without notice. TE Connectivity also reserves the right to make changes in materials or processing, which clo not affect compliance with any specification, without notification to Buyer. 4/ COLORS AND COLOR CODE DESIGNATORS SHALL BE IN ACCORDANCE WITH MIL-STD-681. OTHER CODES AND SUFFIXES MAY BE ADDED TO THE PART NUMBER. AS NECESSARY, TO CAPTURE ANY ADDITIONAL RE QUIREMENTS IMPOSED BY THE PURCHASE ORDER. Page 1 of 3 The TE logo, Te Connectivity and Raychem are trademarks. TE Connectivity Wire & Cable =- 501 Oakside Avenue DIMENSIONS ARE IN INCHES, AND UNLESS OTHERWISE DESIGNATED ARE NOMINAL.. , mf TE Redwood City, CA 94063-3800 Phone: 1-800-227-8816 THIS SPECIFICATION SHEET TAKES PRECEDENCE OVER DOCUMENTS REFERENCED HEREIN. TE Connectivity oy as0-367 6907 REFERENCED DOCUMENTS SHALL BE OF THE ISSUE IN EFFECT ON DATE OF INVITATION FOR BID. page 3 is for intemal use only& TE | sPpeCIFICATION CONTROL DRAWING | Pece203 [yr fo TE Connectivity CMC-0553 WIRE RATINGS AND ADDITIONAL REQUIREMENTS TEMPERATURE RATING: 200C Maximum continuous conductor temperature VOLTAGE RATING: 600 volts (rms) at sea level CONCENTRICITY: 70% (minimum) CROSSLINKING PROOF TEST: 300 + 3C for 7 hours IDENTIFICATION AND COLOR STRIPING DURABILITY: 125 cycles (250 strokes) (minimum), 500 g weight INSULATION ELONGATION AND TENSILE STRENGTH: Elongation, 125% (minimum) Tensile Strength, 3000 Ibffin? (minimum) INSULATION FLAWS: Primary Insulation, Spark Test, 1.5 kV (rms) at 3 kHz Impulse Dielectric Test, 6.0 kV (peak) Finished Wire, Spark Test, 3.0 kV (rms) at 3 kHz Impulse Dielectric Test, 8.0 kV (peak) INSULATION THICKNESS: AWG 8-4, = .008 inch (minimum) for primary insulation .012 inch (minimum) for outer jacket AWG 2 - 0000, .010 inch (minimum) for primary insulation -.015 inch (minimum) for outer jacket JACKET COLOR: White preferred SECANT MODULUS: (Test per ASTM D 882) 4.0 x 104 Ibf/in? (maximum) 2% strain, 2 inch jaw separation, 0.2 inch/minute SHRINKAGE: 200 + 3C for 6 hours, .25 inch (maximum) in 12 inches VOLTAGE WITHSTAND (Post Environmental): 2500 volts (rms), 60 Hz PART NUMBER: The * in the part numbers on page 1 shall be replaced by a color code designator. 1/ Example: AWG 2, white: CMC-0553-2-9 PRODUCT IDENTIFICATION: Mark outer jacket in a contrasting color at 12 inch (nominal) intervals with the following: " CMC-0553-AWG-06090 " i/ See footer section on page 1