Output Output Output Input Current @ Full Load Inrush Current Max. Model
Power max. Voltage nom. Current max. 115 V AC 230 V AC 115 V AC 230 V AC Number
300 W 24 V DC 12 A 4.6 A 2.4 A 35.0 A 70.0 A TIS300-124RED
300 W 48 V DC 6 A 4.6 A 2.4 A 35.0 A 70.0 A TIS300-148RED
600 W 24 V DC 24 A 9.5 A 4.7 A 70.0 A 80.0 A TIS600-124RED
600 W 48 V DC 12 A 9.5 A 4.7 A 70.0 A 80.0 A TIS600-148RED
With this option a parallel operation of up to five units is possible. Decoupling diodes and current share lines allow to
build true N + 1 redundant systems with active current sharing for all units. This function also includes an alarm relay
to signal a single unit failure.
This option is available as standard for TIS300 and TIS600 models. A combination with other options is not possible.
For this option standard output connector is not used.
Output Output Output Input Current @ Full Load Inrush Current Max. Model
Power max. Voltage nom. Current max. 115 V AC 230 V AC 115 V AC 230 V AC Number
75 W 12 V DC 6.0 A 1.2 A 0.6 A 16.5 A 33.0 A TIS75-112
75 W 24 V DC 3.0 A 1.2 A 0.6 A 16.5 A 33.0 A TIS75-124
75 W 48 V DC 1.5 A 1.2 A 0.6 A 16.5 A 33.0 A TIS75-148
150 W 24 V DC 6.0 A 2.4 A 1.2 A 35.0 A 70.0 A TIS150-124
150 W 48 V DC 3.0 A 2.4 A 1.2 A 35.0 A 70.0 A TIS150-148
300 W 24 V DC 12.0 A 4.6 A 2.4 A 35.0 A 70.0 A TIS300-124
300 W 48 V DC 6.0 A 4.6 A 2.4 A 35.0 A 70.0 A TIS300-148
500 W 24 V DC 20.0 A - 2.4 A - 70.0 A TIS500-124
600 W 24 V DC 24.0 A 9.5 A 4.7 A 70.0 A 80.0 A TIS600-124
600 W 48 V DC 12.0 A 9.5 A 4.7 A 70.0 A 80.0 A TIS600-148
Output Output Output Input Current @ Full Load Inrush Current Max. Model
Power max. Voltage nom. Current max. 115 V AC 230 V AC 115 V AC 230 V AC Number
150 W 24 V DC 6 A 2.4 A 1.2 A 35.0 A 70.0 A TIS150-124SIG
150 W 48 V DC 3 A 2.4 A 1.2 A 35.0 A 70.0 A TIS150-148SIG
300 W 24 V DC 12 A 4.6 A 2.4 A 35.0 A 70.0 A TIS300-124SIG
300 W 48 V DC 6 A 4.6 A 2.4 A 35.0 A 70.0 A TIS300-148SIG
600 W 24 V DC 24 A 9.5 A 4.7 A 70.0 A 80.0 A TIS600-124SIG
600 W 48 V DC 12 A 9.5 A 4.7 A 70.0 A 80.0 A TIS600-148SIG
NOTES:
1. DC Auxiliary rails available for TIS300 - maximum power 15 watts, and TIS600 - maximum power 25 watts.
Call technical sales for details.
Output Output Output Input Current @ Full Load Inrush Current Max. Model
Power max. Voltage nom. Current max. 115 V AC 230 V AC 115 V AC 230 V AC Number
300 W 24 V DC 12 A 4.6 A 2.4 A 35.0 A 70.0 A TIS300-124UDS
600 W 24 V DC 24 A 9.5 A 4.7 A 70.0 A 80.0 A TIS600-124UDS
Output Voltage & Current Ratings
Models With Built-In Redundancy Module - Option RED
Models With Built-In DC UPS Module - Option UDS
Models With Built-In Signals Module - Option SIG
Redundancy Module - Option RED
DIN-Rail Power Industrial Power Supplies 75-600 Watts TIS Series www.xpplc.com
Tel: +33 (0)820 801 401 Tel: +41 (0)56 483 34 00
FCH