CE Marked - LVD & EMC
DIN Rail Mounting
Rugged for Industrial Use
Regulated and Low Ripple
High Efficiency
Optional Built-In UPS Module
Wall Mount Bracket Available
(All specifications are typical at nominal input, full load and +25 °C unless otherwise stated)
Input Voltage 93-132 V/187-264 V AC User selectable
187-264 V AC only TIS500 model
Input Frequency 47-63 Hz
Inrush Current See Table
Input Current See Table
Earth Leakage Current 300 µA typ. 75 W, 150 W & 600 W units, 600 µA typ. 300 W units
Hold Up Time 30 ms minimum
Output Voltage See Table
Output Adjustment 12 V models: 12-14 V DC, 24 V models: 24-28 V DC, 48 V models: 48-52 V DC
Line Regulation ±0.2%
Load Regulation ±1% 75 W and 150 W models, ±0.5% 300 W and 600 W models for load
variation between 10 and 90%
Ripple & Noise <50 mV p-p 20 MHz band width
Overload Protection 110% typically into constant current mode
Overvoltage Protection At 140% V out nominal
Temperature Coefficient ±150 ppm max
Efficiency >85%
Operating Temperature -25 °C to +70 °C derate at 2%/°C above +50 °C
Storage Temperature -25 °C to +85 °C
Relative Humidity 95%
Isolation 3000 V AC input to output, 1 minute
2000 V AC input to case, 1 minute
500 V AC output to case, 1 minute
Safety Class Class 1 (IEC536)
EMI/RFI EN55022, EN555011 Class B conducted EMI
Safety Approvals EN60950, IEC950, UL1950 (File No. E181381)
Immunity To EN61000-4 sections -2, -3, -4, -6 and -8
MTBF 75 W & 150 W >750,000hrs, 300 W & 600 W >370,000 hrs to MIL-HBK217F
Switching Frequency 67 kHz (100kHz TIS 75 W models)
Industrial Power Supplies
TIS SERIES 75-600 Watts
Specification
Tel: +44 (0)118 984 5515 Tel: +49 (0)700 9977 1000
UK D
Output Output Output Input Current @ Full Load Inrush Current Max. Model
Power max. Voltage nom. Current max. 115 V AC 230 V AC 115 V AC 230 V AC Number
300 W 24 V DC 12 A 4.6 A 2.4 A 35.0 A 70.0 A TIS300-124RED
300 W 48 V DC 6 A 4.6 A 2.4 A 35.0 A 70.0 A TIS300-148RED
600 W 24 V DC 24 A 9.5 A 4.7 A 70.0 A 80.0 A TIS600-124RED
600 W 48 V DC 12 A 9.5 A 4.7 A 70.0 A 80.0 A TIS600-148RED
With this option a parallel operation of up to five units is possible. Decoupling diodes and current share lines allow to
build true N + 1 redundant systems with active current sharing for all units. This function also includes an alarm relay
to signal a single unit failure.
This option is available as standard for TIS300 and TIS600 models. A combination with other options is not possible.
For this option standard output connector is not used.
Output Output Output Input Current @ Full Load Inrush Current Max. Model
Power max. Voltage nom. Current max. 115 V AC 230 V AC 115 V AC 230 V AC Number
75 W 12 V DC 6.0 A 1.2 A 0.6 A 16.5 A 33.0 A TIS75-112
75 W 24 V DC 3.0 A 1.2 A 0.6 A 16.5 A 33.0 A TIS75-124
75 W 48 V DC 1.5 A 1.2 A 0.6 A 16.5 A 33.0 A TIS75-148
150 W 24 V DC 6.0 A 2.4 A 1.2 A 35.0 A 70.0 A TIS150-124
150 W 48 V DC 3.0 A 2.4 A 1.2 A 35.0 A 70.0 A TIS150-148
300 W 24 V DC 12.0 A 4.6 A 2.4 A 35.0 A 70.0 A TIS300-124
300 W 48 V DC 6.0 A 4.6 A 2.4 A 35.0 A 70.0 A TIS300-148
500 W 24 V DC 20.0 A - 2.4 A - 70.0 A TIS500-124
600 W 24 V DC 24.0 A 9.5 A 4.7 A 70.0 A 80.0 A TIS600-124
600 W 48 V DC 12.0 A 9.5 A 4.7 A 70.0 A 80.0 A TIS600-148
Output Output Output Input Current @ Full Load Inrush Current Max. Model
Power max. Voltage nom. Current max. 115 V AC 230 V AC 115 V AC 230 V AC Number
150 W 24 V DC 6 A 2.4 A 1.2 A 35.0 A 70.0 A TIS150-124SIG
150 W 48 V DC 3 A 2.4 A 1.2 A 35.0 A 70.0 A TIS150-148SIG
300 W 24 V DC 12 A 4.6 A 2.4 A 35.0 A 70.0 A TIS300-124SIG
300 W 48 V DC 6 A 4.6 A 2.4 A 35.0 A 70.0 A TIS300-148SIG
600 W 24 V DC 24 A 9.5 A 4.7 A 70.0 A 80.0 A TIS600-124SIG
600 W 48 V DC 12 A 9.5 A 4.7 A 70.0 A 80.0 A TIS600-148SIG
NOTES:
1. DC Auxiliary rails available for TIS300 - maximum power 15 watts, and TIS600 - maximum power 25 watts.
Call technical sales for details.
Output Output Output Input Current @ Full Load Inrush Current Max. Model
Power max. Voltage nom. Current max. 115 V AC 230 V AC 115 V AC 230 V AC Number
300 W 24 V DC 12 A 4.6 A 2.4 A 35.0 A 70.0 A TIS300-124UDS
600 W 24 V DC 24 A 9.5 A 4.7 A 70.0 A 80.0 A TIS600-124UDS
Output Voltage & Current Ratings
Models With Built-In Redundancy Module - Option RED
Models With Built-In DC UPS Module - Option UDS
Models With Built-In Signals Module - Option SIG
Redundancy Module - Option RED
DIN-Rail Power Industrial Power Supplies 75-600 Watts TIS Series www.xpplc.com
Tel: +33 (0)820 801 401 Tel: +41 (0)56 483 34 00
FCH
The option Signal module (SIG) provides three functions:
• Remote ON/OFF • AC-Powerfail signal (PF) • DC-OK signal
The power supply can be controlled by remote ON/OFF signal. If pin 1 and 2 are connected together unit is ON, with
disconnection unit is OFF. AC-Powerfail and DC-OK signals are available via isolated relay contacts.
Please note option SIG is not available for TIS75 models.
Models TIS300124-UDS and TIS600124-UDS are equipped to build an uninterruptible DC-UPS system.
Additional to the standard 24 V DC output power supplies they provide a professional battery management system to charge and
monitor an external battery. In case of a power failure the battery is switched automatically and without any interruption to the
DC-output. If mains power is available again the battery is switched off. The hold-up time is limited only by battery capacity and
load. Charge current and voltage can be adjusted to values as required by battery type. Power fail and low battery alarm signals
are available via two independent relay contacts. During normal operation the battery status is monitored by periodically loading
the battery for short time. If a cell resistance is high there is a relay alarm available. The battery is fully protected under any
operational conditions. The power supply is short circuit protected even with battery-backup operation, however for safety
reasons the battery should be fused with a fast blow fuse.
Battery mode can be activated by connection of Con1-Pin 7 and 8.
Complete external battery modules (7 Ah standard) are available on request - Contact Technical Sales
TECHNICAL DATA UDS TIS300-124UDS TIS600-124UDS
Adjustment range of charging current 0.15 ... 1.5 A 0.25 ... 2.5 A
Charging current (factory set) at 1.2 A 2.4 A
Adjustment range charge voltage at charging current <50 mA 26.5 ... 28.5 V
Holding current for charged battery at voltage 27.3 V (factory set) <50 mA
Overload or short circuit during battery operation system switches off
AC-Powerfail signal Vin <93 V AC and <187 V AC closed relay A
Low battery signal battery voltage below 22 V ±0.5 closed relay B
During battery charge operation output current reduction by 1.4 x charge current
DC-UPS-module
Uninterruptible DC-System - Option UDS
Signal Module - Option SIG
Tel: +44 (0)118 984 5515 Tel: +49 (0)700 9977 1000
UK D
TIS75
Case Material: Steel & to IP20
Internal Fuse: 4 A Slow Blow
Weight: 480g approx.
TIS150
Case Material: Steel & to IP20
Internal Fuse: 4 A Slow Blow
Weight: 800g approx.
TIS300
Case Material: Steel & to IP20
Internal Fuse: 6.3 A Slow Blow
Weight: 1400g approx.
TIS500/600
Case Material: Steel & to IP20
Internal Fuse: 12 A Slow Blow
Weight: 2000g approx.
TIS500 Dimensions in brackets
Models Order code A B C D E F G
TIS75 MK075 50.0 25.0 135 150.6 4.6 7.5
TIS150 MK150 145.0 20.0 105.0 135 150.6 4.6 7.5
TIS300 MK300 145.0 20.0 105.0 135 150.6 4.6 7.5
TIS500 MK500 145.0 20.5 105.0 150 160.0 4.6 7.5
TIS600 MK600 190.0 37.5 115.0 198 213.2 4.6 7.5
Mechanical Details
Wall Mounting Kit
DIN-Rail Power Industrial Power Supplies 75-600 Watts TIS Series www.xpplc.com
Tel: +33 (0)820 801 401 Tel: +41 (0)56 483 34 00
FCH Rev 1.0