SITOP power supply
SITOP PSU400M
Manual
SITOP PSU400M 24 V/20 A
6EP1536
-3AA00
SITOP PSE400M
6EP1566
-3AA00
05.2018
C98130
-A7601-A1-5-7629
Overview
Safety instructions
1
Description, device design,
dimension drawing
2
Mounting/removal
3
Mounting position, mounting
clearances
4
Installation
5
Technical data
6
Safety, approvals, EMC
7
Ambient conditions
8
Applications
9
Environment
10
Service & Support
11
C98130-A7601-A1-5-7629
05/2018 Subject to change
Copyright © Siemens AG 2018.
All rights reserved
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by
personnel qualified
for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 3
Overview
Description
Figure 1 View of devices
SITOP PSU400M is a power supply for DC link voltages of drive systems. If the power fails,
the energy of the flywheel mass and in the DC link capacitors is used to maintain the 24 V
supply for the electronics. As a consequence, axes can be stopped or retracted in a
controlled fashion. This can prevent expensive workpieces from being destroyed.
The key benefits of the product include:
Rated input voltage 600 V DC
Operating voltage range 200 (300) - 900 V DC
High degree of efficiency up to 95 %
Output voltage can be adjusted in the range 24 - 28.8 V
Ambient temperature -25 ... 70 °C (derating from 60 °C)
Brief overload capability of 150% for 5 s/min (extra power)
No lateral mounting clearances are required
Selectable short-circuit behavior
Soft characteristic for parallel switching can be selected
integrated signaling contact for "24 V O.K."
Display of the operating state using 3 LEDs
Overview
SITOP PSU400M
4 Manual, 05.2018, C98130-A7601-A1-5-7629
Adjustable starting delay for operation on the DC link of SINAMICS converters
Hot plug-in is possible when using the 6EP1566-3AA00 ballast as voltage rise limiter. A
filter is integrated in the ballast to improve the EMC of power supply PSU400M (only
applicable for product version 1).
Ordering data
The following device versions are available:
Regulated SITOP PSU400M power supply
Type
Order number
Input 600 V DC
Output 24 V DC / 20 A
6EP1536-3AA00
SITOP PSE400M voltage rise limiter
Type
Order number
Input 600 V DC
Output 600 V DC
6EP1566-3AA00
Accessories
Type
Order number
Device identification labels 20 mm × 7 mm, pastel
turquoise
3RT1900-1SB20
Validity
This manual provides information on the following products:
SITOP PSU400M
Article No.: 6EP1536-3AA00
Product State: 2
Changes with respect to the previous version (PS 1):
modified input voltage range and derating of the output current, see Figure 6-1 Derating
input range for product version 1 (Page 32), Figure 6-2 Derating input range for product
version 2 (Page 32)
Voltage rise limiter SITOP PSE400M
Article No.: 6EP1566-3AA00
Product State: 2
Changes with respect to the previous version (PS 1):
renamed from PSU400M to PSE400M
no integrated EMC filter
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 5
Table of contents
Overview................................................................................................................................................. 3
1 Safety instructions ................................................................................................................................... 7
2 Description, device design, dimension drawing........................................................................................ 9
2.1 Device description ..................................................................................................................... 9
2.1.1 PSU400M .................................................................................................................................. 9
2.1.2 Voltage rise limiter .................................................................................................................. 10
2.2 Connections and terminal designation.................................................................................... 11
2.2.1 PSU400M ................................................................................................................................ 11
2.2.2 Voltage rise limiter .................................................................................................................. 12
2.3 Potentiometer .......................................................................................................................... 13
2.4 Operating displays and signaling ............................................................................................ 14
2.5 Selector switch ........................................................................................................................ 15
2.6 Block diagram ......................................................................................................................... 17
2.6.1 PSU400M ................................................................................................................................ 17
2.6.2 Voltage rise limiter .................................................................................................................. 18
2.7 Dimensions and weight ........................................................................................................... 19
3 Mounting/removal ................................................................................................................................. 21
4 Mounting position, mounting clearances ................................................................................................ 23
4.1 Standard mounting position .................................................................................................... 23
4.2 Other mounting positions ........................................................................................................ 24
5 Installation ............................................................................................................................................ 27
5.1 Line-side connection ............................................................................................................... 27
5.2 Output-side connection ........................................................................................................... 29
6 Technical data ...................................................................................................................................... 31
6.1 Input ........................................................................................................................................ 31
6.2 Output ..................................................................................................................................... 35
6.3 Efficiency ................................................................................................................................. 38
6.4 Closed-loop control ................................................................................................................. 38
6.5 Protection and monitoring ....................................................................................................... 39
6.6 MTBF ...................................................................................................................................... 39
6.7 Mechanical system ................................................................................................................. 39
6.8 Accessories ............................................................................................................................. 40
6.9 Dimension drawing ................................................................................................................. 40
Table of contents
SITOP PSU400M
6 Manual, 05.2018, C98130-A7601-A1-5-7629
7 Safety, approvals, EMC ........................................................................................................................ 41
7.1 Safety ..................................................................................................................................... 41
7.2 Test voltage ............................................................................................................................ 42
7.3 Approvals ............................................................................................................................... 43
7.4 EMC ....................................................................................................................................... 43
8 Ambient conditions ................................................................................................................................ 45
9 Applications .......................................................................................................................................... 47
9.1 Parallel connection to increase the power rating ................................................................... 47
9.2 Parallel connection for redundancy ....................................................................................... 49
9.3 Series connection for increased voltage ................................................................................ 50
9.4 Overload protection in the 24 V output circuit ........................................................................ 51
9.5 Protection against longer failure of the power supply voltage ............................................... 52
10 Environment ......................................................................................................................................... 55
11 Service & Support ................................................................................................................................. 57
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 7
Safety instructions
1
WARNING
Correct handling of the devices
When operating electrical devices, it is inevitable that certain components will carry
dangerous voltages.
Therefore, failure to handle the units properly can result in death or serious physical injury
as well as extensive property damage.
Only appropriately qualified personnel may work on or in the vicinity of this equipment.
Perfect, safe, and reliable operation of this equipment is dependent on proper
transportation, storage, installation and mounting.
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again.
If this instruction is not observed, touching live parts can result in death or serious injury.
Safety instructions
SITOP PSU400M
8 Manual, 05.2018, C98130-A7601-A1-5-7629
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 9
Description, device design, dimension drawing
2
2.1
Device description
2.1.1
PSU400M
SITOP PSU400M is a primary-clocked power supply for connection to DC supply voltages
(e.g. to the DC link voltage of drive systems). An electronically regulated DC voltage that can
be set via a potentiometer is available at the output of the device. The output of the device is
isolated, no-load proof and short-circuit proof. The LED display indicates the operating
status. The operating state of the device can be processed via the signaling contact.
DC input
DC output
Signaling contact
24 - 28.8 V potentiometer
Indicator lights (24 V O.K., OVERLOAD, SHUTDOWN)
A/B/C selector switch
DIN rail slider
Natural convection
Clearance above/below
Figure 2-1 6EP1536-3AA00 design
Description, device design, dimension drawing
2.1 Device description
SITOP PSU400M
10 Manual, 05.2018, C98130-A7601-A1-5-7629
2.1.2
Voltage rise limiter
The 6EP1566-3AA00 voltage rise limiter is used as ballast for the PSU400M 24 V/20 A
power supply.
A filter is integrated in the ballast to improve the EMC of power supply PSU400M (only
applicable for product version 1).
It is not permissible that a 6EP1566-3AA00 ballast device is connected in parallel or in series
with a second ballast device.
DC input
DC output
DIN rail slider
Convection
Clearance above/below
Figure 2-2 6EP1566-3AA00 design
Description, device design, dimension drawing
2.2 Connections and terminal designation
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 11
2.2
Connections and terminal designation
2.2.1
PSU400M
The input terminals can be used to establish the connection to the supply voltage. Output
terminals are used to connect to the loads to be supplied (see Section Installation
(Page 27)).
The operating state of the device can be processed via the signaling contact (function
and contact rating, see Chapter Operating displays and signaling (Page 14)).
Connections and terminal designations 6EP1536-3AA00
Line input 600 V DC: "+", "-" One screw terminal each
Line input PE 1 screw terminal
output "+" 2 screw terminals
output "–" 2 screw terminals
Output PE 1 screw terminal
signaling contacts 13, 14 One screw terminal each
*1)
Do not subject the end stop to higher loads
Figure 2-3 Terminal data for 6EP1536-3AA00
Description, device design, dimension drawing
2.2 Connections and terminal designation
SITOP PSU400M
12 Manual, 05.2018, C98130-A7601-A1-5-7629
2.2.2
Voltage rise limiter
Connections and terminal designations 6EP1566-3AA00
DC input: "+", "-" One screw terminal each
Line input PE 1 screw terminal
DC output: "+", "-" One screw terminal each
line output PE 1 screw terminal
Figure 2-4 Terminal data for 6EP1566-3AA00
Description, device design, dimension drawing
2.3 Potentiometer
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 13
2.3
Potentiometer
The potentiometer on the front of the device is used to adjust the output voltage. The
output voltage is set to 24 V in the factory, and can be adjusted in the range 24 - 28.8 V; for
example, to compensate voltage drops across long supply lines to the connected load.
Figure 2-5 Potentiometer
NOTICE
Thermal overload possible
When adjusting the output voltage to > 24 V, the output current must be derated by 4 %/V,
or the permissible ambient temperature must be taken into account with 3 °C/V.
Note
It is only permissible to use an
insulated screwdriver when actuating the potentiometer.
For notes on actuating the potentiometer (screwdriver, torque), see Chapter Figure 2-3
Terminal data for 6EP1536-3AA00 (Page 11).
Description, device design, dimension drawing
2.4 Operating displays and signaling
SITOP PSU400M
14 Manual, 05.2018, C98130-A7601-A1-5-7629
2.4
Operating displays and signaling
6EP1536-3AA00 (24 V/20 A)
Operating display LED green, lit for "24 V O. K."
LED flashing green: During the wait time for a delayed start with selector switch C in the "ON"
position
Yellow LED lit for overload condition (U
out
< 20 V ± 0.5 V)
Red LED lit for latching shutdown as a result of overload (only for selector switch B in the "ON"
position)
LED red flashing for prewarning and latching shutdown as a result of overtemperature
Signaling contact Relay contact (NO contact, contact rating (isolated): 30 V AC/0.5 A, DC 60 V/0.3 A, DC 30 V/1 A)
for "24 V O. K."
Signaling
6EP1536-3AA00 (24 V/20 A)
LED green (5.1) off
Signaling contact (3), contacts 13-14 open (quiescent posi-
tion)
No supply voltage
Green LED (5.1) lit
Signaling contact (3), contacts 13-14 closed
Normal operation, output voltage > 20 V ± 0.5 V
Green LED (5.1) flashing
Signaling contact (3), contacts 13-14 open (quiescent posi-
tion)
Output voltage = 0 V during delayed start
Yellow LED (5.2) lit
Signaling contact (3), contacts 13-14 open (quiescent posi-
tion)
Overload (Uout < 20 V ± 0.5 V)
Green LED (5.1) lit and red LED (5.3) flashing
Signaling contact (3), contacts 13-14 open (quiescent posi-
tion)
Prewarning due to overtemperature, device switches off
after approx. 10 s and latches in this condition. (reset possi-
ble after approx. 3 min with power OFF/ON)
Red LED (5.3) lit
Signaling contact (3), contacts 13-14 open (quiescent posi-
tion)
Latching shutdown due to overload
Red LED (5.3) flashing
Signaling contact (3), contacts 13-14 open (quiescent posi-
tion)
Shutdown due to overtemperature → reset using power
OFF/ON after approx. 3 min
Description, device design, dimension drawing
2.5 Selector switch
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 15
2.5
Selector switch
Figure 2-6 Selector switch
The different operating modes can be selected using selector switch . You can choose
one of the following modes:
(A)
Parallel or single mode
(B)
Selectable overload response, constant current characteristic or latching shutdown
(C)
Delayed start
Description, device design, dimension drawing
2.5 Selector switch
SITOP PSU400M
16 Manual, 05.2018, C98130-A7601-A1-5-7629
Switch
ON
OFF
A
influences the output
characteristic
in the load range
Parallel operation:
"Soft" characteristic curve (see Figure 6-7 Out-
put characteristic parallel operation (Page 37))
for the parallel operation of two or more devic-
es: The output voltage falls with increasing
output current (namely, also for the overcurrent
pulse!).
This means that for full output current the high-
est output voltage can normally no longer be
attained.
Single operation:
Delivery state
"Hard" characteristic curve (see Figure 6-6
Output characteristic single operation
(Page 36)) for normal operation (single opera-
tion): The output voltage is independent of the
output current.
B
influences the output
characteristic
in the overload range
Latching shutdown:
If the output current rises above the rated value
and above the current limit, the device reduces
the output voltage (see Figure 6-8 Output char-
acteristic latching shutdown (Page 37)). If the
output voltage falls below 20 V, the device
shuts down latching, the red LED lights up. This
limit voltage of 20 V is independent of the set
output voltage. The 'Short-time overload cur-
rent' feature is not available in this operating
mode. In order to also be able to charge large
capacitances in this operating mode at the
output, non-latching shutdown is performed
during the first ten seconds after power on.
During these first 10 s, the device responds for
overload as if the switch is "OFF".
Constant current:
Delivery state
If the output current rises above the rated value
and above the current limit, the device reduces
the output voltage. The yellow LED lights up if
the output voltage falls below 20 V.
C
Start delay 10 s Immediate start
Delivery state
Note
Selector switches may only be activated when the device is switched off.
Description, device design, dimension drawing
2.6 Block diagram
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 17
2.6
Block diagram
2.6.1
PSU400M
Figure 2-7 Block diagram 6EP1536-3AA00
Description, device design, dimension drawing
2.6 Block diagram
SITOP PSU400M
18 Manual, 05.2018, C98130-A7601-A1-5-7629
2.6.2
Voltage rise limiter
Figure 2-8 Block diagram for 6EP1566-3AA00 (product version 1)
Figure 2-9 Block diagram for 6EP1566-3AA00 (product version 2)
Description, device design, dimension drawing
2.7 Dimensions and weight
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 19
2.7
Dimensions and weight
Figure 2-10 Dimension drawing 6EP1536-3AA00
Figure 2-11 Dimension drawing for 6EP1566-3AA00
6EP1536-3AA00 (24 V/20 A)
6EP1566-3AA00
Dimensions (W × H × D) in mm
90 × 125 × 120
70 × 125 × 120
Weight
approx. 1.2 kg
Approx. 0.5 kg
Description, device design, dimension drawing
2.7 Dimensions and weight
SITOP PSU400M
20 Manual, 05.2018, C98130-A7601-A1-5-7629
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 21
Mounting/removal
3
WARNING
Installing the device in a housing or a control cabinet
The SITOP PSU400M power supply is a built-in device. It must be installed in a housing or
control cabinet, to which only qualified personnel have access.
The device can be mounted in a control cabinet on standard mounting rails (see Chapter
Mechanical system (Page 39))
Note
Ballast device 6EP1566
-3AA00 must be mounted so that it is directly to the right of the
PSU400M 24
V/20 A power supply.
The cable from the output of the ballast device to the PSU400M power supply must be as
short as possible for EMC
-related reasons (< 20 cm).
Mounting
To mount the device, position it with the mounting rail guide at the upper edge of the
standard mounting rail and press down to lock it into place. If this is too difficult, press slider
at the same time, as described under "Removal".
Removal
To remove, pull up the slider using a screwdriver and disengage the device at the
bottom edge of the standard mounting rail. Then you can remove the device from the upper
edge of the standard mounting rail.
Mounting/removal
SITOP PSU400M
22 Manual, 05.2018, C98130-A7601-A1-5-7629
Figure 3-1 Mounting/removal
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 23
Mounting position, mounting clearances
4
4.1
Standard mounting position
The device is mounted on standard mounting rails according to EN 60715. The device must
be mounted vertically in such a way that the input terminals and the output terminals are at
the bottom to ensure correct cooling.
A clearance of at least 50 mm should be maintained above and below the device (maximum
depth of the cable duct, 50 mm).
No space is required at the side.
Ballast device 6EP1566-3AA00 must be mounted so that it is to the right of the PSU400M
24 V/20 A power supply.
When mounting the PSU400M together with the ballast device, the same derating curves
apply.
Output current as a function of the ambient temperature and mounting height
Figure 4-1 Output current in the standard mounting position
Figure 4-2 Mounting height derating
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU400M
24 Manual, 05.2018, C98130-A7601-A1-5-7629
4.2
Other mounting positions
For mounting positions that deviate from the standard mounting position, derating factors
(reduction of the output power or the permissible ambient temperature) must be observed in
accordance with the following diagrams.
Ballast device 6EP1566-3AA00 must be mounted so that it is to the right of the PSU400M
24 V/20 A power supply.
When mounting the PSU400M together with the ballast device, the same derating curves
apply.
Note
In the case of mounting positions that deviate from the standa
rd mounting position, reduced
mechanical resistance of the devices against vibration and shock must be expected.
Particularly when installing on a vertically fastened standard mounting rail, additional
measures may be required, e.g. to prevent the device f
rom slipping on the standard
mounting rail.
Figure 4-3 Mounting position (1)
Figure 4-4 Mounting position (2)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 25
Figure 4-5 Mounting position (3)
Figure 4-6 Mounting position (4)
Figure 4-7 Mounting position (5)
Mounting position, mounting clearances
4.2 Other mounting positions
SITOP PSU400M
26 Manual, 05.2018, C98130-A7601-A1-5-7629
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 27
Installation
5
WARNING
Hazard due to electric shock
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again. If this instruction is
not observed, touching live parts can result in death or serious injury.
5.1
Line-side connection
The SITOP PSU400M power supply is designed for connection to a 600 V DC link with an
operating voltage range from 200 (300) - 900 V DC.
Figure 5-1 Line-side connection
The line supply is connected via terminals 600 V DC "+" and "-" and PE (see Figure 5-1 Line-
side connection (Page 27)) and must be implemented according to IEC 60364, EN 50178
and EN 61800-5-1. A protective device (miniature circuit breaker or circuit breaker) and a
disconnection unit for the power supply must be provided.
The device is to be connected to the inverter in parallel after the DC disconnector.
In other applications, a surge arrester and/or an EMC filter may have to be provided.
NOTICE
Hot plug in and hot plug out are not permissible!
Maximum voltage rate of rise of the supply voltage: 1 V/μs
Installation
5.1 Line-side connection
SITOP PSU400M
28 Manual, 05.2018, C98130-A7601-A1-5-7629
Note
Together with the 6EP1566
-3AA00 ballast device to limit the voltage rise, hot plug-
in and hot
plug
-out are permissible.
A filter is integ
rated in the ballast to improve the EMC of power supply PSU400M (only
applicable for product version
1).
Note
A short
-circuit proof supply line must be provided at the input side.
The breaking capacity of the internal fuse at input "+" and "-" is 20 kA; L/R < 2 ms.
The protective conductor of the line supply must be connected at the PE terminal. The cross-
section of the protective conductor cable must be the same as the supply cable.
NOTICE
Country-specific regulations must be observed when installing.
When installed in wind power plants, the device should only be operated in LPZ2, in
accordance with IEC 61400-24.
Installation
5.2 Output-side connection
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 29
5.2
Output-side connection
At its output, the SITOP PSU400M power supply provides an isolated PELV output voltage
(Protected Extra Low Voltage). When connected to the converter DC link, the output must be
grounded at one end. The ground connection should be established outside the device.
Note
The SITOP PSU400M power supply has two protective conductor connections (PE). It is not
permissible th
at the protective conductor is connected to the input, not even capacitively.
The cross
-section of the protective conductor connections (PE) must be the same as the
supply cable.
The output is no-load, overload, and short-circuit proof. If an overload occurs, the electronic
current limiting function limits the output current to a maximum value (see Section Technical
data (Page 31)).
Figure 5-2 Output-side connection
The output voltage is connected via the + and - terminals at the output of the power supply
(see Figure Output-side connection (Page 29)). Ensure that the output cables are
dimensioned correctly for the maximum output current rms value and fused accordingly.
Installation
5.2 Output-side connection
SITOP PSU400M
30 Manual, 05.2018, C98130-A7601-A1-5-7629
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 31
Technical data
6
Note
Technical data apply for a rated input voltage, rated load and 25
°C ambient temperature if
nothing else is specified.
6.1
Input
6EP1536-3AA00 (24 V/20 A)
Input
DC voltage
Rated voltage U
in rated
for DC
600 V
Voltage range for DC
Remark
200 - 900 V (from prod. version 2: 300 - 900 V)
prod. version 1: Starting from approx. 400 V; derating at
200 - 300 V and 820 - 900 V necessary, (see Figure 6-1
Derating input range for product version 1 (Page 32))
prod. version 2: Starting from 340 V, derating at 300 - 400 V
and 824 - 900 V required, (see Figure 6-2 Derating input
range for product version 2 (Page 32), Figure 6-3 Input
voltage ripple (Page 33), Figure 6-4 Voltage rate of rise
(Page 34))
Wide-range input
Yes
Overvoltage strength
Shutdown at Uin > 900 V
Input current for DC at rated value of input voltage 600 V:
Rated value
0.85 A
Inrush current limiting
(25 °C), max.
8 A
I²t, max
0.02 A²·s
Integrated input fuse
Yes, breaking capacity 20 kA; L/R < 2 ms ("+" and "-" input)
Protection in the line feeder cable (IEC 898)
-
Technical data
6.1 Input
SITOP PSU400M
32 Manual, 05.2018, C98130-A7601-A1-5-7629
Uin = 300 - 824 V DC: Rated power (480 W) and Extra Power (150 % for 5 s/min)
Uin = 200 - 300 V DC: Operating range with current derating max. 10 A (2 min. max.)
Uin = 824 - 860 V DC < 1 min permissible (1x in 1 min.)
Uin = 860 - 900 V DC < 10 s permissible (1x in 10 min.)
In the operating range from 824 - 900 V DC, the complete output power (20 A) is available within the
specified times.
Between 824 and 860 V, the output voltage is continuously available, if a linear derating of 1 A per
10 V is taken into consideration.
Uin > 900 V DC: The output voltage is shut down
Uin > 975 V DC can damage the device
Figure 6-1 Derating input range for product version 1
Uin = 400 - 824 V DC: Rated power (480 W) and Extra Power (150 % for 5 s/min)
Uin = 300 - 400 V DC: Operating range with derating (20 A at max. 55°C, 16 A at max. 60°C)
Uin = 824 - 860 V DC: Linear current derating von 1.4 A per 10 V DC
Uin = 860 - 880 V DC: Max. 15 A
Uin = 880 - 900 V DC: Max. 5 A
Uin > 900 V DC: The output voltage is shut down
Uin > 975 V DC can damage the device
Figure 6-2 Derating input range for product version 2
Technical data
6.1 Input
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 33
The permissible ripple (line frequency) of the input voltage for SITOP PSU400M (between
+Uin and -Uin) may be a maximum of 50 Vpp.
Figure 6-3 Input voltage ripple
Voltage gradient of the converter DC link with respect to PE according to "CSM specification"
10 kV/µs 1500 Vpeak max.
Note
It is not permissible that the 6EP1566
-3AA00 ballast device is connected to a converter DC
link (with active front end) (only applicable for product version 1).
Technical data
6.1 Input
SITOP PSU400M
34 Manual, 05.2018, C98130-A7601-A1-5-7629
Figure 6-4 Voltage rate of rise
Hot plug in and hot plug out are not permissible!
Maximum voltage rate of rise of the supply voltage: 1 V/μs
Note
Together with the 6EP1566
-3AA00 ballast device to limit the voltage rise, hot plug-
in and hot
plug
-out are permissible.
6EP1566-3AA00
Rated voltage U
in rated
for DC
600 V
Voltage range
200 - 900 V
Input current for DC at rated value of input voltage 600 V:
Rated value
0.85 A
Technical data
6.2 Output
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 35
6.2
Output
6EP1536-3AA00 (24 V/20 A)
Output
Regulated, isolated DC voltage
Rated voltage U
out rated
DC
24 V
Total tolerance, static ±
3 %
Static line regulation, approx.
0.3 %
Static load regulation, approx.
0.3 %
Residual ripple peak-peak, max.
150 mV
Residual ripple peak-peak, typ.
30 mV
Spikes peak-peak, max. (bandwidth, approx. 20 MHz)
200 mV
Spikes peak-peak, typ. (bandwidth, approx. 20 MHz)
100 mV
Adjustment range
24 - 28.8 V
Output voltage can be adjusted
Yes
Output voltage setting
Via potentiometer
Operating display LED green for 24 V O.K.
LED flashing green for start delay
Signaling Relay contact (NO contact), contact rating (isolated):
30 V AC/0.5 A, 60 V DC/0.3 A, 30 V DC/1 A) for "24 V O.K."
Response when switching on/off
No overshoot of U
out
(soft start)
Starting delay, max.
Remark
0.1 s
10 s can be set using switch C
Voltage rise, typ.
50 ms
Rise time of the output voltage, max.
150 ms
Rated current Iout rated 20 A
Current range
Remark
0 - 20 A
60 ... 70 °C derating: 5.5 % Iout rated/K
Active power output, typ. 480 W
Constant overload current for a short circuit when powering
up, typ.
40 A
Short-time overload current for a short circuit in operation,
typ.
60 A
Duration of the overload capability for an overcurrent condi-
tion caused by a short circuit when powering up.
150 ms
Duration of the overload capability for an overcurrent condi-
tion caused by a short circuit in operation.
25 ms
Can be connected in parallel to increase the power rating
Remark
Yes
Switchable characteristic
Number of devices that can be connected in parallel to in-
crease the power rating, units
2
Technical data
6.2 Output
SITOP PSU400M
36 Manual, 05.2018, C98130-A7601-A1-5-7629
6EP1536-3AA00 (24 V/20 A)
Overload capability (Extra Power)
30 A for 5 s/min
Output characteristic See Figure 6-6 Output characteristic single operation
(Page 36)
6EP1566-3AA00
Rated input voltage U
in rated
:
600 V DC
Voltage range
200 - 900 V DC
Rated input current I
in rated
0.85 A
Figure 6-5 Starting delay/voltage rise
Figure 6-6 Output characteristic single operation
The device supplies a constant output voltage until the current limit is reached.
If overload occurs, the output current is limited and the output voltage lowered.
Technical data
6.2 Output
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 37
Selector switch A closed (parallel operation):
The output voltage decreases with increasing output current.
Figure 6-7 Output characteristic parallel operation
Selector switch B closed (latching shutdown):
The device will be shut down if the overload continues for longer than 100 ms.
A reset is performed by switching the power supply OFF for at least 30 seconds.
Figure 6-8 Output characteristic latching shutdown
Technical data
6.3 Efficiency
SITOP PSU400M
38 Manual, 05.2018, C98130-A7601-A1-5-7629
6.3
Efficiency
6EP1536-3AA00 (24 V/20 A)
Efficiency at U
out rated
, I
out rated
, approx.
95 %
Power loss at U
out rated
, I
out rated
, approx.
25 W
No-load operation power loss, approx.
10 W
Figure 6-9 Efficiency
6.4
Closed-loop control
6EP1536-3AA00 (24 V/20 A)
Dyn. line regulation (U
in rated
±15 %), max.
1.5 %
Dyn. load regulation (I
out
: 10/90/10 %), U
out
± typ.
3 %
Load step regulation time 10 to 90%, typ.
1 ms
Load step regulation time 90 to 10 %, typ. 1 ms
Dyn. load regulation (Iout: 50/100/50 %), Uout ± typ. 0.5 %
Load step regulation time 50 to 100 %, typ.
1 ms
Load step regulation time 100 to 50 %, typ.
1 ms
Regulation time, max.
5 ms
Technical data
6.5 Protection and monitoring
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 39
6.5
Protection and monitoring
6EP1536-3AA00 (24 V/20 A)
Output overvoltage protection
< 33 V
Current limitation, typ.
22 A
Property of the output: short-circuit proof
Yes
Short-circuit protection Optional constant current characteristic approx. 22 A or
latching shutdown
Continuous short-circuit current: rms value, typ.
Remark
22 A
Overload capability 150 % Iout rated up to 5 s/min
Overload / short-circuit display Yellow LED for "overload"
Red LED for "latching shutdown"
Overtemperature protection
LED red flashing for "Shutdown due to overtemperature"
6.6
MTBF
6EP1536-3AA00 (24 V/20 A)
6EP1566-3AA00
Mean Time Between Failures SN29500:> 620,000 h at 40 °C, rated
load, 24 h operation
> 10000000 h
6.7
Mechanical system
6EP1536-3AA00 (24 V/20 A)
6EP1566-3AA00
Connection system
Screw-type terminal
Connections: Line input DC input "+", "-", PE:
1 screw terminal each for 0.05 ... 4
(2.5) mm² solid (finely stranded)
DC input "+", "-", PE:
1 screw terminal each for 0.05 ... 4
(2.5) mm² solid (finely stranded)
Connections: Output "+", "-", PE:
2 screw terminals each for 0.2 - 6
(4) mm² solid (finely stranded)
DC output "+", "-", PE:
1 screw terminal each for 0.05 - 4
(2.5) mm² solid (finely stranded)
Connections: Auxiliary contacts Signaling contact:
2 screw terminals for 0.14 - 1.5 mm² solid
(finely stranded)
-
Width of the housing 90 mm 70 mm
Height of the housing 125 mm 125 mm
Depth of the housing 120 mm 120 mm
Mounting width
90 mm
70 mm
Mounting height
225 mm
225 mm
Technical data
6.8 Accessories
SITOP PSU400M
40 Manual, 05.2018, C98130-A7601-A1-5-7629
6EP1536-3AA00 (24 V/20 A)
6EP1566-3AA00
Weight, approx.
1.2 kg
0.5 kg
Product feature of the housing:
housing that can be lined up next
to one another
Yes Yes
Type of mounting: Wall/panel
mounting
No No
Type of mounting: Rail mounting
Yes
Yes
Type of mounting: S7-300 rail
mounting
No No
Mounting Can be snapped onto standard EN 60715
TH 35-15/7,5 mounting rails
Can be snapped onto standard EN 60715
TH 35-15/7,5 mounting rails
6.8
Accessories
6EP1536-3AA00 (24 V/20 A)
Mechanical accessories
Device identification labels 20 mm × 7 mm, pastel turquoise 3RT1900-1SB20
6.9
Dimension drawing
See Section Dimensions and weight (Page 19)
CAD data that can be downloaded from the Internet:
6EP1536-3AA00
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_00668)
6EP1566-3AA00
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01248)
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 41
Safety, approvals, EMC
7
7.1
Safety
6EP1536-3AA00 (24 V/20 A)
Primary/secondary galvanic isolation
Yes
Electrical isolation SELV output voltage Uout acc. to EN 60950-1 and EN 50178
Protection class Class I
Degree of protection (EN 60529) IP20
Leakage current, typ.
-
Leakage current, max.
-
Test voltage
See Test voltage (Page 42)
Safety, approvals, EMC
7.2 Test voltage
SITOP PSU400M
42 Manual, 05.2018, C98130-A7601-A1-5-7629
7.2
Test voltage
Figure 7-1 Test voltage diagram with auxiliary contact
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
Connect the input terminals with one another
Connect the output terminals, signaling contact and PE with one another
Test (C)
Connect the output terminals and signaling contact with one another and measure with
respect to PE
Table 7- 1 Test voltage
Test time
Prim ↔ sec (A)
Prim ↔ PE (B)
Sec ↔ PE (C)
Type test
60 s
4200 V DC
2200 V DC
700 V DC
Production test
1 s
2200 V DC
2200 V DC
500 V DC
Field test
1 s
2200 V DC
2200 V DC
500 V DC
Remark:
Tripping current for DC measurement: 0 mA
Safety, approvals, EMC
7.3 Approvals
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 43
7.3
Approvals
6EP1536-3AA00 (24 V/20 A)
6EP1566-3AA00
CE marking Yes (2014/35/EU, 2014/30/EU and
2011/65/EU)
Yes (2014/35/EU, 2014/30/EU and
2011/65/EU)
CB approval
Yes
-
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No.
107.1), File E197259
-
Explosion protection
-
-
Marine approvals
DNV GL
-
7.4
EMC
6EP1536-3AA00 (24 V/20 A)
Electrostatic discharge
EN 61000-4-2
8 kV contact, 8 kV air
Electromagnetic fields EN 61000-4-3 80 - 1000 MHz 20 V/m
1000 - 2000 MHz 3 V/m
2000 - 2700 MHz 1 V/m
High-speed transient disturbance vari-
ables (burst)
EN 61000-4-4 4 kV at line supply connections
2 kV at the DC output
Surge voltages EN 61000-4-5 1 kV symmetrical at the line connections (with converter)
6 kV unsymmetrical at the line connections (primary PE)
500 V symmetrical/unsymmetrical at DC output cables
High-frequency fields EN 61000-4-6 20 V; 0.15 - 80 MHz
3 V; 1.0 - 2 GHz
1 V; 2.0 - 2.7 GHz
Magnetic fields
EN 61000-4-8
30 A/m; 50 Hz
Voltage dips
EN 61000-4-11
-
Voltage interruptions
EN 61000-4-11
-
Emitted interference EN 55022 Class A (HF field)
Class A (cable conducted) only in conjunction with 6EP1566-
3AA00 (is only applicable for product version 1)
Line harmonics limit EN 61000-3-2 -
Generic standards
EN61000-6-2
Noise immunity for industrial environments
EN61000-6-3
-
Safety, approvals, EMC
7.4 EMC
SITOP PSU400M
44 Manual, 05.2018, C98130-A7601-A1-5-7629
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 45
Ambient conditions
8
6EP1536-3AA00 (24 V/20 A)
6EP1566-3AA00
Ambient temperature
-25 ... 70 °C for natural convection (self convection)
Tested according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-78 humid heat, constant
EN 60068-2-14 temperature change
Transport and storage temperature -40 ... 85 °C
Tests (packed for shipping) according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-30 humid heat, cyclic
Humidity class
Climatic class 3K3 according to EN 60721, 5 - 95 % no condensation
Degree of pollution
2
Mechanical stressing during operation Tested according to EN 60068-2-6 vibration, test Fc:
3.5 mm deflection in the range 5 - 8.4 Hz
2 g acceleration in the range 8.4 - 150 Hz
Tested according to EN 60068-2-27 shock, test Ea:
acceleration 150 m/s2, test duration 11 ms
Damaging gases Tested according to:
EN 60068-2-42 sulfur dioxide
EN 60068-2-43 hydrogen sulfide
Atmospheric pressure Operation:
1080 - 795 hPa (-1000 - 2000 m)
Operation at installation altitudes of 2000 to 6000 m above sea level:
output power derating of -7.5 % / 1000 m or
reduction of the ambient temperature by 5 K / 1000 m
(see Figure 4-2 Mounting height derating (Page 23))
Overvoltage category:
III up to 2000 m (EN 50178)
II from 2000 m up to 6000 m (EN 50178)
Storage:
1080 - 660 hPa (-1000 - 3500 m)
Ambient conditions
SITOP PSU400M
46 Manual, 05.2018, C98130-A7601-A1-5-7629
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 47
Applications
9
9.1
Parallel connection to increase the power rating
To increase the power rating, power supplies of the same type can be directly connected in
parallel.
The following must be observed:
The cables connected to each power supply at terminals "+" and "-" must have identical
lengths and the same cable cross-sections (or the same impedance) up to a common
external connection point (terminal strip) if possible.
The power supplies connected in parallel must be switched on simultaneously with a
common switch in the line feeder cable (e.g. with the main switch available in control
cabinets).
The output voltages measured in no-load operation for the power supplies that are not yet
connected in parallel should not deviate more than a maximum of 50 mV. This usually
corresponds to the factory setting. If the output voltage is changed, you should connect
the "-" terminals and then, in no-load operation, measure the voltage difference between
the "+" terminals that have not yet been connected. The voltage difference should not
exceed 50 mV.
Figure 9-1 Parallel connection
Applications
9.1 Parallel connection to increase the power rating
SITOP PSU400M
48 Manual, 05.2018, C98130-A7601-A1-5-7629
NOTICE
Protective circuit for the parallel connection of more than two power supplies
When connecting more than two power supplies in parallel, additional measures must be
taken to prevent high reverse currents in the event of a secondary device fault. For this
purpose, a suitable protective circuit (e.g. decoupling diode or DC-capable circuit breaker)
must be installed between each "+" terminal of the power supply and the common
connection point.
Applications
9.2 Parallel connection for redundancy
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 49
9.2
Parallel connection for redundancy
Connecting several 24 V power supplies in parallel for redundancy purposes is required if
especially high demands are placed regarding the availability of a reliable 24 V power
supply.
Using the SITOP PSE202U redundancy module, two power supplies of the same type up to
20 A can be decoupled (Figure 9-2 Redundant configuration with two power supplies and
SITOP PSE202U redundancy module (Page 49)). When one of the devices fails, then the
other automatically takes over the power supply. If one of the power supplies fails, then this
is signaled using an LED on the redundancy module as well as an isolated relay contact.
When dimensioning the system, it must be ensured that n+1 redundant connected power
supplies can handle the total power requirement of the remaining n power supplies.
Note
For a high reliability of the supply, it is recommended that the redundant switched power
supplies are fused separately on the
line-side and, if possible, be connected to different line
supplies.
Figure 9-2 Redundant configuration with two power supplies and SITOP PSE202U redundancy
module
You can find additional information at:
SITOP PSE202U manual (https://support.industry.siemens.com/cs/ww/en/view/42248598)
Applications
9.3 Series connection for increased voltage
SITOP PSU400M
50 Manual, 05.2018, C98130-A7601-A1-5-7629
9.3
Series connection for increased voltage
To achieve an output voltage of 48 V DC, two 24 V SITOP power supplies of the same type
can be connected in series.
Depending on the grounding point of the secondary output voltages, voltages of +48 V,
±24 V or -48 V can be realized.
Note
For additional details, see Catalog KT 10.1 Chapter 15 Technical information and configuring
(see
http://w3app.siemen
s.com/mcms/infocenter/content/en/Pages/order_form.aspx?nodeKey=ke
y_518431&infotype=catalogs
)).
WARNING
SELV is not guaranteed in the case of a fault
When connecting two power supplies in series, the continuous, permissible SELV voltage
of a maximum of 60 VDC according to EN 60950-1 cannot be guaranteed in the case of a
fault.
Figure 9-3 Series connection
Applications
9.4 Overload protection in the 24 V output circuit
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 51
9.4
Overload protection in the 24 V output circuit
If an overload occurs, the electronic current limiting function of the 24 V power supply limits
the output current to a maximum value (see Section Technical data (Page 31)). The output
cables are protected against a thermal overload if they are dimensioned corresponding to
the maximum rms output current, or protected using additional components (for example,
miniature circuit breaker, fuses).
However, a load circuit that fails as a result of overload, for instance, should frequently be
reliably and quickly identified and specifically switched off before the power supply goes into
current-limiting mode (in current-limiting mode, the supply voltage would also be reduced for
all of the remaining 24 V loads).
The SITOP PSE200U selectivity module with 4 outputs (versions with adjustable output
current range for each output from 0.5 - 3 A and 3 - 10 A) is available for this purpose; this
monitors the 24 V branches for overload and short circuit (Figure 9-4 Electronic protection of
24 V loads using the SITOP PSE200U selectivity module (Page 51)). Brief current peaks,
e.g. as a result of a high inrush current, are permitted, and branches with a longer overload
are switched into a no-current condition. This is also ensured for cables in a high-ohmic
condition and for short circuits that slowly develop over time.
When an output fails, the fault is signaled using a group signal contact or as a single channel
signal, and the branch of the module involved is displayed using an LED.
For variants with single-channel signaling, function blocks for evaluation purposes are
available for SIMATIC S7-1200/1500/300/400, for STEP 7 Classic and TIA Portal at no
charge.
You can find additional information at:
Manual SITOP selectivity modules
(https://support.industry.siemens.com/cs/ww/en/view/108989004)
Figure 9-4 Electronic protection of 24 V loads using the SITOP PSE200U selectivity module
Applications
9.5 Protection against longer failure of the power supply voltage
SITOP PSU400M
52 Manual, 05.2018, C98130-A7601-A1-5-7629
9.5
Protection against longer failure of the power supply voltage
Sudden and longer failures of the line supply voltage can result in undefined states and
significant danger as a result of the associated failure of the plant or system control. The
SITOP power supply product portfolio includes various DC-UPS solutions to prevent the
failure of the 24 V power supply voltage.
Power supply failures up into the minutes range can be buffered using the maintenance-free
SITOP UPS500 DC-UPS modules based on capacitors (Figure 9-5 24 V buffering to allow
the saving of process data and controlled shutdown of PCs (Page 52)).
Figure 9-5 24 V buffering to allow the saving of process data and controlled shutdown of PCs
Using the free-of-charge SITOP DC-UPS software tool, DC-UPS systems can be simply
integrated into PC-based automation solutions. This supports further processing of the status
signals and safely running down the PC.
You can find additional information at:
Manual, DC UPS with capacitors
(https://support.industry.siemens.com/cs/ww/en/ps/18042/man)
Applications
9.5 Protection against longer failure of the power supply voltage
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 53
Using DC UPS SITOP UPS1600 and SITOP UPS1100 battery modules, buffer times in the
range of hours can be implemented. Intelligent battery management using Energy Storage
Link automatically detects the UPS1100 energy storage device, and ensures optimum
temperature-controlled charging and continuous monitoring. The UPS1600 can be flexibly
integrated into the widest range of automation applications with its digital inputs/outputs as
well as optional USB interface or Ethernet/PROFINET port.
Figure 9-6 24 V buffering with SITOP UPS1600 to maintain communication, signaling functions,
sensor measured values and position values
For open, PC-based automation systems, configuration and monitoring is realized using the
SITOP UPS Manager PC software, which is available at no charge. This allows PC
responses to the operating states of the DC UPS to be freely selected and offers
comprehensive diagnostic functions.
For TIA-based automation systems, the UPS1600 is engineered using the TIA Portal.
Special function blocks for SIMATIC S7-300/400/1200 and S7-1500 available at no
charge make it easy to integrate operating and diagnostics information into STEP 7 user
programs. Preconfigured UPS faceplates for WinCC visualization can be downloaded at no
charge.
You can find additional information at:
DC UPS SITOP UPS1600/UPS1100 Manual
(https://support.industry.siemens.com/cs/ww/en/view/84977415)
Applications
9.5 Protection against longer failure of the power supply voltage
SITOP PSU400M
54 Manual, 05.2018, C98130-A7601-A1-5-7629
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 55
Environment
10
The devices are in conformance with RoHS.
As a rule, only non-silicon precipitating materials are used.
Disposal guidelines
Packaging and packaging aids can and should always be recycled. The product itself may
not be disposed of as domestic refuse.
Environment
SITOP PSU400M
56 Manual, 05.2018, C98130-A7601-A1-5-7629
SITOP PSU400M
Manual, 05.2018, C98130-A7601-A1-5-7629 57
Service & Support
11
Technical support
Technical support for all IA/DT products can be accessed through the following
communication channels:
Telephone: + 49 (0) 911 895 7222
Internet:
Web form for support request (http://www.siemens.de/automation/support-request)
Technical documentation on the Internet
Operating instructions and manuals for SITOP are available in the Internet:
Operating instructions/manuals (http://www.siemens.com/sitop/manuals)
SITOP power supply homepage
General news about our power supplies is available in the Internet at the SITOP home page:
SITOP (http://www.siemens.com/sitop)
Information material
SITOP information can be downloaded from the Internet:
Information and download center (http://www.siemens.com/sitop-infomaterial)
CAx data
2D/3D data and circuit diagram macros can be downloaded from the Internet:
Siemens image database (http://www.siemens.com/sitop-cax)
Request all CAx data via the CAx download manager:
CAx shopping cart (http://www.siemens.com/cax)
SITOP Selection Tool
Simply and quickly select the optimum the power supply or DC-UPS:
SITOP Selection Tool (http://www.siemens.com/sitop-selection-tool)
Online catalog and ordering system
The online catalog and the online ordering system are available through the Industry Mall
homepage:
Industry Mall (http://www.siemens.com/industrymall/de)
Service & Support
SITOP PSU400M
58 Manual, 05.2018, C98130-A7601-A1-5-7629
Contact persons
If you have any questions regarding the use of our products, then contact the Siemens
contact person in your regional Siemens sales office.
You can find these addresses as follows:
On the Internet (http://www.automation.siemens.com/partner)
Industry Mall (http://www.siemens.com/industrymall/de)