MAP130 AC-DC Series Data Sheet
MCD10115 Rev. 1.3, 05-Feb-10 Page 3 of 4 www.power-one.com
Interface Signals and Internal Protection
PARAMETER CONDITIONS/DESCRIPTION MIN NOM MAX UNITS
Overvoltage Protection Provided on single output units and only MAP130-1012 17.0 22.0
the main output of multiple output units. MAP130-1024 32.0 37.0 VDC
MAP130-4004 6.2 7.4
All other models. 5.5 6.8
Overcurrent Protection All models have inherent short circuit protection. Units will automatically restart at the removal of the fault.
Remote Sense Total voltage compensation for main output cable losses. 250 mV
Logic LO (denotes power fail detected). 0.7 V
Power Fail Warning Logic HI with internal pull-up to output. 10 k⍀
(Note 1) Power Fail trip point, maximum load, decreasing line. 86 94 VAC
Time before regulation dropout, at full load, due to loss of input power. 5 mS
Overtemperature Warning Warning prior to system shutdown due to excessive internal temperatures. 20 mS
(Note 2) Shifts Power Fail signal to a logic LO state.
NOTES: 1) Power Fail not available on MAP130-1012 and MAP130-1024.
2) MAP130-1012 and MAP130-1024 have overtemperature protection, but do not have the warning feature.
Safety, Regulatory, and EMI Specifications
PARAMETER CONDITIONS/DESCRIPTION MIN NOM MAX UNITS
Agency Approvals UL1950.
CSA 22.2 No. 234/950. Approved
EN60950 (TÜV).
Dielectric Withstand Voltage Input to Output, 1 second. 2600 VDC
Electromagnetic FCC CFR title 47 Part 15 Sub-Part B - Conducted B
Interference, EN55022 / CISPR 22 Conducted B Class
EN55022 / CISPR 22 Radiated (Note 1) B
ESD Susceptibility Per EN61000-4-2, level 4 8 kV
Radiated Susceptibility Per EN61000-4-3, level 3 10 V/M
EFT/Burst Per EN61000-4-4, level 3 (Note 2) ±2 kV
Input Transient Protection Per EN61000-4-5 class 3 Line to Line 1 kV
Line to Ground 2
Insulation Resistance Input to output 7 M⍀
Leakage Current Per EN60950 (264 VAC) 700 µA
NOTES: 1) MAP130-1005 meets Class A, radiated.
2) MAP130-1005, MAP130-4003, and MAP130-4010, meet level 2, ±1kV.
Environmental Specifications
PARAMETER CONDITIONS/DESCRIPTION MIN NOM MAX UNITS
Altitude Operating 10K Feet
Non-Operating 40K
Operating Temperature At 100% load: 0 50 °C
Derate linearly above 50°C by 2.5% per °C At 50% load: 70 °C
Storage Temperature -40 85 °C
Temperature Coefficient 0°C to 70°C (after 15 minute warm-up period) ±0.02 ±0.05 %/°C
Relative Humidity Non-Condensing 5 95 %RH
Shock Operating, peak acceleration 20 GPK
Vibration Random vibration, 10Hz to 2kHz, 3 axis 6 GRMS
Options
DESCRIPTION NOTES DIMENSIONS
Cover Add ‘C’ suffix to model number or order part number 412-59586-G separately.
For convection cooled applications with covers, derate output power as follows: 8.50" x 4.50" x 2.40"
Derate all multiple output models and MAP130-1005 to 120 watts. (215.9mm x 114.3mm x 61.0mm)
Derate MAP130-1012 and MAP130-1024 to 140 watts.