General Description
The MAX16046/MAX16048 EEPROM-configurable system
managers monitor, sequence, track, and margin multiple
system voltages. The MAX16046 manages up to twelve
system voltages simultaneously, and the MAX16048 man-
ages up to eight supply voltages. These devices integrate
an analog-to-digital converter (ADC) for monitoring supply
voltages, digital-to-analog converters (DAC) for adjusting
supply voltages, and configurable outputs for sequencing
and tracking supplies (during power-up and power-
down). Nonvolatile EEPROM registers are configurable for
storing upper and lower voltage limits, setting timing and
sequencing requirements, and for storing critical fault
data for readback following failures.
An internal 1% accurate 10-bit ADC measures each input
and compares the result to one upper, one lower, and
one selectable upper or lower limit. A fault signal asserts
when a monitored voltage falls outside the set limits. Up
to three independent fault output signals are configurable
to assert under various fault conditions.
The integrated sequencer/tracker allows precise control
over the power-up and power-down order of up to twelve
(MAX16046) or up to eight (MAX16048) power supplies.
Four channels (EN_OUT1–EN_OUT4) support closed-
loop tracking using external series MOSFETs. Six outputs
(EN_OUT1–EN_OUT6) are configurable with charge-
pump outputs to directly drive MOSFETs without closed-
loop tracking.
The MAX16046/MAX16048 include twelve/eight inte-
grated 8-bit DAC outputs for margining power supplies
when connected to the trim input of a point-of-load
(POL) module.
The MAX16046/MAX16048 include six programmable
general-purpose inputs/outputs (GPIOs). GPIOs are
EEPROM configurable as dedicated fault outputs, as a
watchdog input or output (WDI/WDO), as a manual reset
(MR), or for margin control inputs.
The MAX16046/MAX16048 feature two methods of fault
management for recording information during system
shutdown events. The fault logger records a failure in
the internal EEPROM and sets a lock bit protecting the
stored fault data from accidental erasure.
An I2C or a JTAG serial interface configures the
MAX16046/MAX16048. These devices are offered in a
56-pin 8mm x 8mm TQFN package or a 64-pin 10mm x
10mm TQFP package and are fully specified from -40°C
to +85°C.
Features
oOperates from 3V to 14V
o1% Accurate 10-Bit ADC Monitors 12/8 Inputs
o12/8 Monitored Inputs with 1 Overvoltage/
1 Undervoltage/1 Selectable Limit
o12/8 8-Bit DAC Outputs for Margining or Voltage
Adjustments
oNonvolatile Fault Event Logger
oPower-Up and Power-Down Sequencing
Capability
o12/8 Outputs for Sequencing/Power-Good
Indicators
oClosed-Loop Tracking for Up to Four Channels
oTwo Programmable Fault Outputs and One Reset
Output
oSix General-Purpose Input/Outputs Configurable as:
Dedicated Fault Output
Watchdog Timer Function
Manual Reset
Margin Enable Input
oI2C (with Timeout) and JTAG Interface
oEEPROM-Configurable Time Delays, Thresholds,
and DAC Outputs
o100 Bytes of Internal User EEPROM
o-40°C to +85°C Operating Temperature Range
Applications
Servers
Workstations
Storage Systems
Networking/Telecom
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
________________________________________________________________
Maxim Integrated Products
1
Ordering Information
PART
TEMP RANGE
PIN-PACKAGE
MAX16046ECB+
-40°C to +85°C
64 TQFP-EP*
MAX16046ETN+
-40°C to +85°C
56 TQFN-EP*
MAX16048ECB+
-40°C to +85°C
64 TQFP-EP*
MAX16048ETN+
-40°C to +85°C
56 TQFN-EP*
19-1050; Rev 5; 9/10
For pricing, delivery, and ordering information, please contact Maxim Direct at 1-888-629-4642,
or visit Maxim’s website at www.maxim-ic.com.
+
Denotes a lead(Pb)-free/RoHS-compliant package.
*
EP = Exposed pad.
Pin Configurations appear at end of data sheet.
EVALUATION KIT
AVAILABLE
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
2 _______________________________________________________________________________________
DACOUT1
DACOUT2–
DACOUT11
DACOUT12
MON1
MON2–MON11
MON12
VSUPPLY
VCC
10µF
VCC
+3.3V
GND
A0
µC
SCL
SDA
RESET
FAULT INT
RESET
INT
I/O
WDI
WDO
DBP
EN_OUT1
EN_OUT1–
EN_OUT11
EN_OUT12
EN
MAX16046
GND
OUT
FB
IN
DC-DC
EN
GND
OUT
FB
IN
DC-DC
EN
GND
OUT
FB
IN
DC-DC
EN 1µF
ABP
1µF
Typical Operating Circuit
Selector Guide
PART VOLTAGE-DETECTOR
INPUTS DAC OUTPUTS GENERAL-PURPOSE
INPUTS/OUTPUTS
SEQUENCING
OUTPUTS
MAX16046 12 12 6 12
MAX16048 8 8 6 8
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
_______________________________________________________________________________________ 3
ABSOLUTE MAXIMUM RATINGS
ELECTRICAL CHARACTERISTICS
(VCC = 3V to 14V, TA= -40°C to +85°C, unless otherwise specified. Typical values are at VCC = 3.3V, TA= +25°C.) (Note 1)
Stresses beyond those listed under “Absolute Maximum Ratings” may cause permanent damage to the device. These are stress ratings only, and functional
operation of the device at these or any other conditions beyond those indicated in the operational sections of the specifications is not implied. Exposure to
absolute maximum rating conditions for extended periods may affect device reliability.
VCC to GND ....................……………………………-0.3V to +15V
EN, MON_, SCL, SDA, A0 ........................................-0.3V to +6V
GPIO_, RESET (configured as open drain) to GND.....-0.3V to +6V
EN_OUT1–EN_OUT6 (configured as open drain)
to GND.................................................................-0.3V to +12V
EN_OUT7–EN_OUT12 (configured as open drain)
to GND...................................................................-0.3V to +6V
GPIO_, EN_OUT_, RESET
(configured as push-pull) to GND .........-0.3V to (VDBP + 0.3V)
DBP, ABP to GND .........-0.3V to the lower of 3V or (VCC + 0.3V)
TCK, TMS, TDI.......................................................-0.3V to +3.6V
TDO ..........................................................-0.3V to (VDBP + 0.3V)
DACOUT_.................………………………-0.3V to (VABP + 0.3V)
EN_OUT1–EN_OUT6
(configured as charge pump) ............-0.3V to (VMON1–6 + 6V)
Continuous Current (all pins)............................................±20mA
56-Pin TQFN (derate 47.6mW/°C above +70°C)..........3810mW*
Thermal Resistance
θJA.................................................................................21°C/W
θJC................................................................................0.6°C/W
64-Pin TQFP (derate 43.5mW/°C above +70°C) .......3478.3mW*
Thermal Resistance
θJA.................................................................................23°C/W
θJC...................................................................................1°C/W
Lead Temperature (soldering, 10s) .................................+300°C
Soldering Temperature (reflow) .......................................+260°C
PARAMETER SYMBOL CONDITIONS MIN TYP MAX UNITS
RESET output asserted low 1.4
Operating Voltage Range VCC 314
V
Undervoltage Lockout VUVLO 2.85 V
Undervoltage-Lockout Hysteresis UVLOHYS (Note 2) 50 mV
Supply Current ICC VCC = 14V, VEN = 3.3V, no load on any
output 4.8 6.5 mA
DBP Regulator Voltage VDBP CDBP = 1µF, no load on any output 2.6 2.7 2.8 V
ABP Regulator Voltage VABP CABP = 1µF, no load on any DACOUT_ 2.78 2.88 2.96 V
Boot Time tBOOT VCC > VUVLO 0.8 1.5 ms
Internal Timing Accuracy (Note 3) -5 +5 %
ADC
ADC Resolution 10 Bits
MON_ range set to ‘00’ in r0Fh–r11h 0.65
MON_ range set to ‘01’ in r0Fh–r11h 0.75
ADC Total Unadjusted Error
(Note 4) ADCERR
MON_ range set to ‘10’ in r0Fh–r11h 0.95
% FSR
ADC Integral Nonlinearity ADCINL 0.8 LSB
ADC Differential Nonlinearity ADCDNL 0.8 LSB
ADC Total Monitoring Cycle Time tCYCLE MAX16046, all channels monitored,
no MON_ fault detected (Note 5) 80 100 µs
MON1–MON4 46 100
MON_ Input Impedance RIN MON5–MON12 65 140 k
MON_ range set to ‘00’ in r0Fh–r11h 5.6
MON_ range set to ‘01’ in r0Fh–r11h 2.8ADC MON_ Ranges ADCRNG
MON_ range set to ‘10’ in r0Fh–r11h 1.4
V
*
As per JEDEC 51 Standard, Multilayer Board (PCB).
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
4 _______________________________________________________________________________________
PARAMETER SYMBOL CONDITIONS MIN TYP MAX UNITS
MON_ range set to ‘00’ in r0Fh–r11h 5.46
MON_ range set to ‘01’ in r0Fh–r11h 2.73
ADC LSB Step Size ADCLSB
MON_ range set to ‘10’ in r0Fh–r11h 1.36
mV
VTH_EN_R EN voltage rising 0.525
EN Input-Voltage Threshold VTH_EN_F EN voltage falling 0.487 0.500 0.512 V
EN Input Current IEN -0.5 +0.5 µA
EN Input Voltage Range 0 5.5 V
CLOSED-LOOP TRACKING
Tracking Differential Voltage Stop
Ramp VTRK VINS_ > VTH_PL, VINS_ < VTH_PG 150 mV
Tracking Differential Voltage
Hysteresis 20 %VTRK
Tracking Differential Fault Voltage VTRK_F VINS_ > VTH_PL, VINS_ < VTH_PG 285 330 375 mV
Slew-rate register set to ‘00’ 640 800 960
Slew-rate register set to ‘01’ 320 400 480
Slew-rate register set to ‘10’ 160 200 240
Track/Sequence Slew-Rate Rising
or Falling TRKSLEW
Slew-rate register set to ‘11’ 80 100 120
V/s
Power-good register set to ‘00’,
VMON_ = 3.5V 94 95 96
Power-good register set to ‘01’,
VMON_ = 3.5V 91.5 92.5 93.5
Power-good register set to ‘10’,
VMON_ = 3.5V 89 90 91
INS_ Power-Good Threshold VTH_PG
Power-good register set to ‘11’,
VMON_ = 3.5V 86.5 87.5 88.5
%V
M ON_
Power-Good Threshold
Hysteresis VPG_HYS 0.5 %VTH_PG
Power-Low Threshold VTH_PL INS_ falling 125 142 160 mV
Power-Low Hysteresis VTH_PL_HYS 10 mV
GPIO_ Input Impedance GPIOINR GPIO_ configured as INS_ 75 100 145 k
INS_ to GND Pulldown
Impedance when Enabled INSRPD VINS_ = 2V 100
DAC
DAC Resolution 8 Bits
DACOUT_ range set to ‘11’ 0.8
DACOUT_ range set to ‘10’ 0.6DAC Output Voltage Range DACRNG
DACOUT_ range set to ‘01’ 0.4
V
DACOUT_ range set to ‘11’ 3.137
DACOUT_ range set to ‘10’ 2.353DAC LSB Step Size
DACOUT_ range set to ‘01’ 1.568
mV
ELECTRICAL CHARACTERISTICS (continued)
(VCC = 3V to 14V, TA= -40°C to +85°C, unless otherwise specified. Typical values are at VCC = 3.3V, TA= +25°C.) (Note 1)
MAX16046/MAX16048
ELECTRICAL CHARACTERISTICS (continued)
(VCC = 3V to 14V, TA= -40°C to +85°C, unless otherwise specified. Typical values are at VCC = 3.3V, TA= +25°C.) (Note 1)
PARAMETER SYMBOL CONDITIONS MIN TYP MAX UNITS
TA = +25°C 1.1660 1.2016 1.2060
IDACOUT = ±50µA, mid
code, DACOUT_ range
set to ‘11’
TA = -40°C to
+85°C 1.1900 1.2016 1.2130
TA = +25°C 0.897 0.901 0.905
IDACOUT = ±50µA, mid
code, DACOUT_ range
set to ‘10’
TA = -40°C to
+85°C 0.890 0.901 0.912
TA = +25°C 0.597 0.601 0.605
DAC Center Code Absolute
Accuracy DACACC
IDACOUT = ±50µA, mid
code, DACOUT_ range
set to ‘01’
TA = -40°C to
+85°C 0.592 0.601 0.612
V
Gain Error Any range -0.8 +0.8 %
DAC Output Sink Capability DACSINK Sinking current, IDACOUTMAX = 0.5mA +8 mV
DAC Output Source Capability DACSOURCE Sourcing current, IDACOUTMAX = -0.5mA -8 mV
DAC Output Switch Leakage DACOUT_ switch off -150 +150 nA
DAC Output Capacitive Load (Note 5) 50 pF
DAC Output Settling Time 50 µs
DC 60
DAC Power-Supply Rejection
Ratio DACPSRR 100mV step in 20ns with 50pF load 40 dB
DAC Differential Nonlinearity DACDNL DACOUT_ code from 07h to F8h,
any range -0.6 +0.6 LSB
DAC Integral Nonlinearity DACINL DACOUT_ code from 07h to F8h,
any range -0.9 +0.9 LSB
OUTPUTS (EN_OUT_, RESET, GPIO_)
Output-Voltage Low VOL ISINK = 2mA 0.4 V
Output-Voltage High (Push-Pull) ISOURCE =100µA 2.4 V
1
GPIO1–GPIO4, VGPIO_ = 3.3V 1Output Leakage (Open Drain) IOUT_LKG
GPIO1–GPIO4, VGPIO_ = 5.0V 22
µA
EN_OUT_ Overdrive (Charge
Pump) (EN_OUT1 to EN_OUT6
Only) Volts above VMON_
VOV IGATE_ = 0.5µA 4.6 5.1 5.6 V
EN_OUT_ Pullup Current (Charge
Pump) ICHG_UP During power-up/power-down,
VGATE_ = 1V 4.5 6 µA
EN_OUT_ Pulldown Current
(Charge Pump) ICHG_DOWN During power-up/power-down,
VGATE_ = 5V 10 µA
INPUTS (A0, GPIO_)
Logic-Input Low Voltage VIL 0.8 V
Logic-Input High Voltage VIH 2.0 V
SMBUS INTERFACE
Logic-Input Low Voltage VIL Input voltage falling 0.8 V
Logic-Input High Voltage VIH Input voltage rising 2.0 V
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
_______________________________________________________________________________________ 5
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
6 _______________________________________________________________________________________
ELECTRICAL CHARACTERISTICS (continued)
(VCC = 3V to 14V, TA= -40°C to +85°C, unless otherwise specified. Typical values are at VCC = 3.3V, TA= +25°C.) (Note 1)
PARAMETER SYMBOL CONDITIONS MIN TYP MAX UNITS
VCC shorted to GND, SCL/SDA at 0V or
3.3V -1 +1
Input Leakage Current
-1 +1
µA
Output-Voltage Low VOL ISINK = 3mA 0.4 V
Input Capacitance CIN 5pF
SMBUS TIMING
Serial Clock Frequency fSCL 400 kHz
Bus Free Time Between STOP
and START Condition tBUF 1.3 µs
START Condition Setup Time tSU:STA 0.6 µs
START Condition Hold Time tHD:STA 0.6 µs
STOP Condition Setup Time tSU:STO 0.6 µs
Clock Low Period tLOW 1.3 µs
Clock High Period tHIGH 0.6 µs
Data Setup Time tSU:DAT 200 ns
Output Fall Time tOF 10pF CBUS 400pF 250 ns
Receive 0
Data Hold Time tHD:DAT Transmit 0.3 0.9 µs
Pulse Width of Spike Suppressed tSP 30 ns
JTAG INTERFACE
TDI, TMS, TCK Logic-Low Input
Voltage VIL Input voltage falling 0.55 V
TDI, TMS, TCK Logic-High Input
Voltage VIH Input voltage rising 2 V
TDO Logic-Output Low Voltage VOL_TDO VDBP 2.5V, ISINK = 2mA 0.4 V
TDO Logic-Output High Voltage VOH_TDO VDBP 2.5V, ISOURCE = 200mA 2.4 V
TDO Leakage Current TDO high impedance -1 +1 µA
TDI, TMS Pullup Resistors RJPU Pullup to VDBP 71013k
Input/Output Capacitance CI/O 5pF
JTAG TIMING
TCK Clock Period t11000 ns
TCK High/Low Time t2, t350 500 ns
TCK to TMS, TDI Setup Time t415 ns
TCK to TMS, TDI Hold Time t515 ns
TCK to TDO Delay t6500 ns
TCK to TDO High-Impedance
Delay t7500 ns
EEPROM TIMING
EEPROM Byte Write Cycle Time tWR (Note 6) 10.5 12 ms
Note 1: Specifications are guaranteed for the stated global conditions, unless otherwise noted. 100% production tested at TA= +25°C
and TA= +85°C. Specifications at TA= -40°C are guaranteed by design.
Note 2: VUVLO is the minimum voltage on VCC to ensure the device is EEPROM configured.
Note 3: Applies to RESET, fault, delay, and watchdog timeouts.
Note 4: Total unadjusted error is a combination of gain, offset, and quantization error.
Note 5: Guaranteed by design.
Note 6: An additional cycle is required when writing to configuration memory for the first time.
MAX16046/MAX16048
STOP
CONDITION
REPEATED START
CONDITION
START
CONDITION
tHIGH
tLOW
tRtF
tSU:DAT tSU:STA tSU:STO
tHD:STA
tBUF
tHD:STA
tHD:DAT
SCL
SDA
START
CONDITION
Figure 1. I2C/SMBus Timing Diagram
TCK
t1
t2t3
t4t5
t6
t7
TDI, TMS
TDO
Figure 2. JTAG Timing Diagram
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
_______________________________________________________________________________________ 7
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
8 _______________________________________________________________________________________
VCC SUPPLY CURRENT
vs. VCC SUPPLY VOLTAGE
MAX16046 toc01
VCC (V)
ICC (mA)
13121 2 3 5 6 7 8 9 104 11
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
0
014
TA = +85°C
TA = -40°CTA = +25°C
NORMALIZED MON_ THRESHOLD
vs. TEMPERATURE
MAX16046 toc02
TEMPERATURE (°C)
NORMALIZED MON_ THRESHOLD
756030 45-15 0 15-30
0.992
0.994
0.996
0.998
1.000
1.002
1.004
1.006
1.008
1.010
0.990
-45 90
2.8V RANGE, HALF SCALE,
PUV THRESHOLD
NORMALIZED EN THRESHOLD
vs. TEMPERATURE
MAX16046 toc03
TEMPERATURE (°C)
NORMALIZED EN_ THRESHOLD
756030 45-15 015-30
0.975
0.980
0.985
0.990
0.995
1.000
1.005
1.010
1.015
1.020
1.025
1.030
0.970
-45 90
Typical Operating Characteristics
(VCC = 3.3V, TA= +25°C, unless otherwise noted.)
TRANSIENT DURATION
vs. THRESHOLD OVERDRIVE (EN)
MAX16046 toc04
EN OVERDRIVE (mV)
TRANSIENT DURATION (µs)
10
20
40
60
80
100
120
140
160
0
1 100
NORMALIZED RESET TIMEOUT PERIOD
vs. TEMPERATURE
MAX16046 toc05
TEMPERATURE (°C)
NORMALIZED RESET TIMEOUT
756030 45-15 015-30
0.92
0.94
0.96
0.98
1.00
1.02
1.04
1.06
1.08
1.10
0.90
-45 90
MON_ PUV THRESHOLD OVERDRIVE
vs. TRANSIENT DURATION
MAX16046 toc06
THRESHOLD OVERDRIVE (mV)
TRANSIENT DURATION (µs)
835670175 340 505
20
40
60
80
100
120
140
160
0
10 1000
DEGLITCH = 16
DEGLITCH = 8
DEGLITCH = 4
DEGLITCH = 2
OUTPUT-VOLTAGE LOW
vs. SINK CURRENT
MAX16046 toc07
SINK CURRENT (mA)
OUTPUT-VOLTAGE LOW (V)
541 2 3
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0
06
EN_OUT_
GPIO_
MAX16046/MAX16048
TRACKING MODE WITH
FAST SHUTDOWN
MAX16046 toc13
20ms/div
1V/div
0V
INS4
INS3
INS2
INS1
SEQUENCING MODE
MAX16046 toc14
40ms/div
1V/div
0V
INS4
INS3
INS2
INS1
FET TURN-ON WITH CHARGE PUMP
MAX16046 toc11
20ms/div
VEN_OUT_
10V/div
VSOURCE
2V/div
IDRAIN
1A/div
0V
0V
0V
TRACKING MODE
MAX16046 toc12
20ms/div
1V/div
0V
INS4
INS3
INS2
INS1
Typical Operating Characteristics (continued)
(VCC = 3.3V, TA= +25°C, unless otherwise noted.)
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
_______________________________________________________________________________________
9
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
10 ______________________________________________________________________________________
ADC INL
MAX16046 toc18
INPUT VOLTAGE (DIGITAL CODE)
ADC INL (LSB)
896768512 640256 384128
-0.8
-0.6
-0.4
-0.2
0
0.2
0.4
0.6
0.8
1.0
-1.0
01024
INTERNAL TIMING ACCURACY
vs. TEMPERATURE
MAX16046 toc19
TEMPERATURE (°C)
NORMALIZED SLOT DELAY
756030 45-15 0 15-30
0.96
0.97
0.98
0.99
1.00
1.01
1.02
1.03
1.04
1.05
0.95
-45 90
Typical Operating Characteristics (continued)
(VCC = 3.3V, TA= +25°C, unless otherwise noted.)
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 11
Pin Descriptions
PIN
THIN QFN
MAX16046 MAX16048
NAME FUNCTION
1–8 1–8 MON1–MON8
ADC Monitored Voltage Inputs. Set ADC input range for each MON_ through
configuration registers. Measured values are written to ADC registers and can be read
back through the I2C or JTAG interface.
9–12 MON9–MON12
ADC Monitored Voltage Inputs. Set ADC input range through configuration registers.
Measured values are written to ADC registers and can be read back through the I2C or
JTAG interface.
9–12,
33–36,
53–56
N.C. No Connection. Must be left unconnected.
13 13 RESET Configurable Reset Output
14 14 A0
Four-State SMBus Address. Address sampled upon POR. Connect A0 to ground, DBP,
SCL, or SDA to program an individual address when connecting multiple devices. See
the I2C/SMBus-Compatible Serial Interface section.
15 15 SCL SMBus Serial Clock Input
16 16 SDA SMBus Serial Data Open-Drain Input/Output
17 17 TMS JTAG Test Mode Select
18 18 TDI JTAG Test Data In
19 19 TCK JTAG Test Clock
20 20 TDO JTAG Test Data Out
21, 40 21, 40 GND Ground. Connect all GND connections together.
22 22 GPIO6
23 23 GPIO5
General-Purpose Input/Output. GPIO6 and GPIO5 are configurable as open-drain or
push-pull outputs, dedicated fault outputs, or for watchdog functionality. GPIO5 is
configurable as a watchdog input (WDI). GPIO6 is configurable as a watchdog output
(WDO). These inputs/outputs are also configurable for margining. Use the EEPROM to
configure GPIO5 and GPIO6. See the General-Purpose Inputs/Outputs section.
24 24 EN
Analog Enable Input. Apply a voltage greater than the 0.525V (typ) threshold to enable
all outputs. The power-down sequence is triggered when EN falls below 0.5V (typ) and
all outputs are deasserted.
25–32 25–32 DACOUT1–
DACOUT8
DAC Outputs. DACOUT1–DACOUT8 are the outputs of an internal 8-bit DAC. Set
DACOUT1–DACOUT8 ranges through configuration registers. Connect a DACOUT_ to
an external DC-DC converter for margining. Leave DACOUT_ outputs unconnected, if
unused.
33–36 DACOUT9–
DACOUT12
DAC Outputs. DACOUT9–DACOUT12 are the outputs of an internal 8-bit DAC. Set
DACOUT9–DACOUT12 ranges through configuration registers. Connect a DACOUT_ to
an external DC-DC converter for margining. Leave DACOUT_ outputs unconnected, if
unused.
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
12 ______________________________________________________________________________________
Pin Descriptions (continued)
PIN
THIN QFN
MAX16046 MAX16048
NAME FUNCTION
37 37 ABP
Internal Analog Voltage Bypass. Bypass ABP to GND with a 1µF ceramic capacitor.
ABP powers the internal circuitry of the MAX16046/MAX16048. Do not use ABP to
power any external circuitry.
38 38 VCC Power-Supply Input. Bypass VCC to GND with a 10µF ceramic capacitor.
39 39 DBP
Internal Digital Voltage Bypass. Bypass DBP to GND with a 1µF ceramic capacitor.
DBP supplies power to the EEPROM memory, to the internal logic circuitry, and to the
internal charge pumps when the programmable outputs are configured as charge
pumps. All push-pull outputs are referenced to DBP. Do not use DBP to power any
external circuitry.
41 41 GPIO1
General-Purpose Input/Output 1. Configure GPIO1 as a logic input, a return sense line
for closed-loop tracking, an open-drain/push-pull fault output, or an open-drain/push-
pull output port. Use the EEPROM to configure GPIO1. See the General-Purpose
Inputs/Outputs section.
42 42 GPIO2
General-Purpose Input/Output 2. GPIO2 is configurable as a logic input, a return sense
line for closed-loop tracking, an open-drain/push-pull fault output, or an open-
drain/push-pull output port. GPIO2 is also configurable as a dedicated MARGINUP
input. Use the EEPROM to configure GPIO2. See the General-Purpose Inputs/Outputs
section.
43 43 GPIO3
General-Purpose Input/Output 3. GPIO3 is configurable as a logic input, a return sense
line for closed-loop tracking, an open-drain/push-pull fault output, or an open-
drain/push-pull output port. GPIO3 is also configurable as a dedicated MARGINDN
input. Use the EEPROM to configure GPIO3. See the General-Purpose Inputs/Outputs
section.
44 44 GPIO4
General-Purpose Input/Output 4. GPIO4 is configurable as a logic input, a return sense
line for closed-loop tracking, an open-drain/push-pull fault output, or an open-
drain/push-pull output port. GPIO4 is also configurable as an active-low manual reset,
MR. Use the EEPROM to configure GPIO4. See the General-Purpose Inputs/Outputs
section.
45–50 45–50 EN_OUT1–
EN_OUT6
Output. EN_OUT1–EN_OUT6 are configurable with active-high/active-low logic and with
an open-drain or push-pull configuration. Program the EEPROM to configure
EN_OUT1–EN_OUT6 as a charge-pump output 5V greater than the monitored input
voltage (VMON_ + 5V). EN_OUT1–EN_OUT4 can also be used for closed-loop tracking.
51, 52 51, 52 EN_OUT7–
EN_OUT8
Output. Configure EN_OUT_ with active-low/active-high logic and with an open-drain or
push-pull configuration.
53–56 EN_OUT9–
EN_OUT12
Output. Configure EN_OUT_ with active-low/active-high logic and with an open-drain or
push-pull configuration.
—— EP
Exposed Pad. Internally connected to GND. Connect to GND. EP also functions as a
heatsink to maximize thermal dissipation. Do not use as the main ground connection.
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 13
Pin Descriptions (continued)
PIN
TQFP
MAX16046 MAX16048
NAME FUNCTION
1–7, 10 1–7, 10 MON1–MON8
ADC Monitored Voltage Inputs. Set ADC input range for each IN_ through
configuration registers. Measured values are written to ADC registers and can be
read back through the I2C or JTAG interface.
11–14 MON9–MON12
ADC Monitored Voltage Inputs. Set ADC input range through configuration registers.
Measured values are written to ADC registers and can be read back through the I2C
or JTAG interface.
8, 9, 15, 25,
33, 48,
49, 64
8, 9, 11–15,
25, 33,
38–41, 48,
49, 60–64
N.C. No Connection. Must leave unconnected.
16 16 RESET Configurable Reset Output
17 17 A0
Four-State SMBus Address. Address sampled upon POR. Connect A0 to ground,
DBP, SCL, or SDA to program an individual address when connecting multiple
devices. See the I2C/SMBus-Compatible Serial Interface section.
18 18 SCL SMBus Serial Clock Input
19 19 SDA SMBus Serial Data Open-Drain Input/Output
20 20 TMS JTAG Test Mode Select
21 21 TDI JTAG Test Data In
22 22 TCK JTAG Test Clock
23 23 TDO JTAG Test Data Out
24, 45 24, 45 GND Ground
26, 27 26, 27 GPIO6, GPIO5
General-Purpose Input/Output. GPIO6 and GPIO5 are configurable as open-drain or
push-pull outputs, dedicated fault outputs, or for watchdog functionality. GPIO5 is
configurable as a watchdog input (WDI). GPIO6 is configurable as a watchdog
output (WDO). These inputs/outputs are also configurable for margining. Use the
EEPROM to GPIO5 and GPIO6. See the General-Purpose Inputs/Outputs section.
28 28 EN
Analog Enable Input. Apply a voltage greater than the 0.525V (typ) threshold to
enable all outputs. Power-down sequence triggered when EN falls below 0.5V (typ)
and all outputs are deasserted.
29–32,
34–37
29–32,
34–37
DACOUT1–
DACOUT8
DAC Outputs. DACOUT1–DACOUT8 are the outputs of an internal 8-bit DAC. Set
DACOUT_ ranges through configuration registers. Connect a DACOUT_ to an
external DC-DC converter for margining. Leave DACOUT_ outputs unconnected, if
unused.
38–41 DACOUT9–
DACOUT12
DAC Outputs. DACOUT9–DACOUT12 are the outputs of an internal 8-bit DAC. Set
DACOUT_ ranges range through configuration registers. Connect a DACOUT_ to an
external DC-DC converter for margining. Leave DACOUT_ outputs unconnected, if
unused.
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
14 ______________________________________________________________________________________
Pin Descriptions (continued)
PIN
TQFP
MAX16046 MAX16048
NAME FUNCTION
42 42 ABP
Internal Analog Voltage Regulator Output. Bypass ABP to GND with a 1µF ceramic
capacitor. ABP powers the internal circuitry of the MAX16046/MAX16048 and
supplies power to the internal charge pumps when the programmable outputs are
configured as charge pumps. Do not use ABP to power any external circuitry.
43 43 VCC Power-Supply Input. Bypass VCC to GND with a 10µF ceramic capacitor.
44 44 DBP
Internal Digital Voltage Regulator Output. Bypass DBP to GND with a 1µF ceramic
capacitor. DBP supplies power to the EEPROM memory and the internal logic
circuitry. All push-pull outputs are referenced to DBP. Do not use DBP to power any
external circuitry.
46 46 GPIO1
General-Purpose Input/Output 1. Configure GPIO1 as a TTL input, a return sense
line for closed-loop tracking, an open-drain/push-pull fault output, or an open-
drain/push-pull output port. Use the EEPROM to configure GPIO1. See the General-
Purpose Inputs/Outputs section.
47 47 GPIO2
General-Purpose Input/Output 2. GPIO2 is configurable as a TTL input, a return
sense line for closed-loop tracking, an open-drain/push-pull fault output, or an open-
drain/push-pull output port. GPIO2 is also configurable as a dedicated MARGINUP
input. Use the EEPROM to configure GPIO2. See the General-Purpose
Inputs/Outputs section.
50 50 GPIO3
General-Purpose Input/Output 3. GPIO3 is configurable as a TTL input, a return
sense line for closed-loop tracking, an open-drain/push-pull fault output, or an open-
drain/push-pull output port. GPIO3 is also configurable as a dedicated MARGINDN
input. Use the EEPROM to configure GPIO3. See the General-Purpose
Inputs/Outputs section.
51 51 GPIO4
General-Purpose Input/Output 4. GPIO4 is configurable as a TTL input, a return
sense line for closed loop tracking, an open-drain/push-pull fault output, or an open-
drain/push-pull output port. GPIO4 is also configurable as an active-low manual
reset, MR. Use the EEPROM to configure GPIO4. See the General-Purpose
Inputs/Outputs section.
52–57 52–57 EN_OUT1–
EN_OUT6
Output. EN_OUT1–EN_OUT6 are configurable with active-high/active-low logic and
with open-drain or push-pull configurations. Program the EEPROM to configure
EN_OUT_ with a charge-pump output 5V greater than the monitored input voltage
(VIN_ + 5V). EN_OUT1–EN_OUT4 can also be used for closed-loop tracking.
58, 59 58, 59 EN_OUT7,
EN_OUT8
Output. Configure EN_OUT_ with active-low/active-high logic and with an open-drain
or push-pull configuration.
60–63 EN_OUT9–
EN_OUT12
Output. Configure EN_OUT_ with active-low/active-high logic and with an open-drain
or push-pull configuration.
—— EP
Exposed Pad. Internally connected to GND. Connect to GND. EP also functions as a
heatsink to maximize thermal dissipation. Do not use as the main ground connection.
MAX16046/MAX16048
Functional Diagram
EN
VTH_EN
VOLTAGE
SCALING
AND MUX
10-BIT
ADC (SAR)
ADC
REGISTERS
THRESHOLD
REGISTERS
DIGITAL COMPARATORS
TRACK AND
HOLD
( ) MAX16048 ONLY.
8-BIT DAC DAC
REGISTERS
RAM
REGISTERS
EEPROM
REGISTERS
LOGIC
SEQUENCER
CLOSED-LOOP
TRACKER
I2C SLAVE
INTERFACE JTAG INTERFACE
MON1–
MON12
(MON1–
MON8)
DACOUT1–
DACOUT12
(DACOUT1–
DACOUT8)
RESET
FAULT1
FAULT2
MR
MARGIN
WATCHDOG
TIMER
WDI
GPIO CONTROL
WDO
GPIO1
GPIO2
GPIO3
GPIO4
GPIO5
GPIO6
INS1
INS2
INS3
INS4
EN_OUT1–
EN_OUT12
(EN_OUT1–
EN_OUT8)
EN_OUT1–
EN_OUT4
A0 SDA SCL TMS TCK TDI TDO
MARGINUP
MARGINDN
FAULTPU
GND
VCC
NONVOLATILE
FAULT EVENT
LOGGER
MAX16046
MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 15
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
16 ______________________________________________________________________________________
Register Summary (All Registers 8-Bits Wide)
PAGE REGISTER DESCRIPTION
ADC Conversion Results
(Registers r00h to r17h)
Input ADC conversion results. ADC writes directly to these registers during normal
operation. ADC input ranges (MON1–MON12) are selected with registers r0Fh to r11h.
Failed Line Flags
(Registers r18h to r19h)
Voltage fault flag bits. Flags for each input signal when undervoltage or overvoltage
threshold is exceeded.
GPIO Data
(Registers r1Ah to r1Bh) GPIO state data. Used to read back and control the state of each GPIO.
Extended
DAC Enables
(Registers r1Ch to r1Dh)
DAC output control. Controls whether DAC outputs are high impedance or connected
to the DAC.
Default DAC Registers
(Registers r00h to r0Bh) DAC code registers. Sets the output voltage of each DAC output.
ADC Range Selections
(Registers r0Fh to r11h) ADC input voltage range. Selects the voltage range of the monitored inputs.
DAC Range
(Registers r12h to r14h) DAC range registers. Sets the voltage output range of each DAC output.
RESET and Fault Outputs
(Registers r15h to r1Bh)
RESET and FAULT1FAULT2 output configuration. Programs the functionality of the
RESET, FAULT1, and FAULT2 outputs, as well as which inputs they depend on.
GPIO Configuration
(Registers r1Ch to r1Eh)
General-purpose input/output configuration registers. GPIOs are configurable as a
manual-reset input, a margin disable input, margin-up/margin-down control inputs, a
watchdog timer input and output, logic inputs/outputs, fault-dependent outputs, or as
the feedback/pulldown inputs (INS_) for closed-loop tracking.
Programmable Output
Configuration
(Registers r1Fh to r22h)
Programmable output configurations. Selectable output configurations include: active-
low or active-high, open-drain or push-pull outputs. EN_OUT1–EN_OUT6 are
configurable as charge-pump outputs and EN_OUT1–EN_OUT4 can be configured for
closed-loop tracking.
Overvoltage and
Undervoltage Thresholds
(Registers r23h to r46h)
Input overvoltage and undervoltage thresholds. ADC conversion results are compared
to overvoltage and undervoltage threshold values stored here. MON_ voltages
exceeding threshold values trigger a fault event.
Fault Behavior
(Registers r47h to r4Ch)
Selects how the device should operate during faults. Options include latch-off or
autoretry after fault. The autoretry delay is selectable (r4Fh). Use registers r48h
through r4Ch to select fault conditions that trigger a critical fault event.
Software Enable and Margin
(Register r4Dh)
Use register r4Dh to set the Software Enable bit, to select early warning thresholds
and undervoltage/overvoltage, to enable/disable margining, and to enable/disable the
watchdog for independent/dependent mode.
S eq uenci ng - M od e
C onfi g ur ati on ( Reg i ster s r 50h
to r 5Bh and r 5E h to r 63h)
Assign inputs and outputs for sequencing. Select sequence delays (20µs to 1.6s) with
registers r50h through r54h. Use register r54h to enable/disable the reverse sequence
bit for power-down operation.
Watchdog Functionality
(Register r55h) Configure watchdog functionality for GPIO5 and GPIO6.
Default and
EEPROM
DAC Output Margin Levels
(Registers r66h to r7Dh)
DAC output levels depend on GPIO2 and GPIO3 when configured for margining
functionality. Set registers r66h to r71h for margin up. Set registers r72h to r7Dh for
margin down.
Fault Log Results
(Registers r00h to r0Eh)
ADC conversion results and failed-line flags at the time of a fault. These values are
recorded by the fault event logger at the time of a critical fault.
EEPROM User EEPROM (Registers
r9Ch to rFFh) User-available EEPROM
Note: This data sheet uses a specific convention for referring to bits within a particular address location. As an example, r0Fh[3:0]
refers to bit 3 to bit 0 in register with address 15 decimal.
MAX16046/MAX16048
Detailed Description
Getting Started
The MAX16046 is capable of managing up to twelve
system voltages simultaneously, and the MAX16048
can manage up to eight system voltages. After boot-
up, if EN is high and the Software Enable bit is set to
‘0,’ an internal multiplexer cycles through each input. At
each multiplexer stop, the 10-bit ADC converts the
monitored analog voltage to a digital result and stores
the result in a register. Each time the multiplexer finish-
es a conversion (8.3µs max), internal logic circuitry
compares the conversion results to the overvoltage and
undervoltage thresholds stored in memory. When a
conversion violates a programmed threshold, the con-
version can be configured to generate a fault. Logic
outputs can be programmed to depend on many com-
binations of faults. Additionally, faults are programma-
ble to trigger the nonvolatile fault logger, which writes
all fault information automatically to the EEPROM and
write-protects the data to prevent accidental erasure.
The MAX16046/MAX16048 contain both I2C/SMBus and
JTAG serial interfaces for accessing registers and
EEPROM. Use only one interface at any given time. For
more information on how to access the internal memory
through these interfaces, see the
I
2
C/SMBus-Compatible
Serial Interface
and
JTAG Serial Interface
sections.
Registers are divided into three pages with access con-
trolled by special I2C and JTAG commands.
The factory-default values at POR (power-on reset) for
all RAM registers are ‘0’s. POR occurs when VCC reach-
es the undervoltage-lockout threshold (UVLO) of 2.85V
(max). At POR, the device begins a boot-up sequence.
During the boot-up sequence, all monitored inputs are
masked from initiating faults and EEPROM contents are
copied to the respective register locations. During boot-
up, the MAX16046/MAX16048 are not accessible
through the serial interface. The boot-up sequence can
take up to 1.5ms, after which the device is ready for
normal operation. RESET is low during boot-up and
asserts after boot-up for its programmed timeout period
once all monitored channels are within their respective
thresholds. During boot-up, the GPIOs, DACOUTs, and
EN_OUTs are high impedance.
Accessing the EEPROM
The MAX16046/MAX16048 memory is divided into
three separate pages. The default page, selected by
default at POR, contains configuration bits for all func-
tions of the part. The extended page contains the ADC
conversion results, GPIO input and output registers,
and DAC enable bits. Finally, the EEPROM page con-
tains all stored configuration information as well as
saved fault data and user-defined data. See the
Register Map
table for more information on the function
of each register.
During the boot-up sequence, the contents of the
EEPROM (r0Fh to r7Dh) are copied into the default
page (r0Fh to r7Dh). Registers r00h to r0Bh of the
default page contain the DAC output voltage registers,
and are reset to ‘0’s at POR. Registers r00h to r0Eh of
the EEPROM page contain saved fault data.
The JTAG and I2C interfaces provide access to all
three pages. Each interface provides commands to
select and deselect a particular page:
98h(I2C)/09h(JTAG)—Switches to the extended
page. Switch back to the default page with
99h(I2C)/0Ah(JTAG).
9Ah(I2C)/0Bh(JTAG)—Switches to the EEPROM
page. Switch back to the default page with
9Bh(I2C)/0Ch(JTAG).
See the
I
2
C/SMBus-Compatible Serial Interface
or the
JTAG Serial Interface
section.
Power
Apply 3V to 14V to VCC to power the MAX16046/
MAX16048. Bypass VCC to ground with a 10µF capacitor.
Two internal voltage regulators, ABP and DBP, supply
power to the analog and digital circuitry within the device.
Do not use ABP or DBP to power external circuitry.
ABP is a 2.85V (typ) voltage regulator that powers the
internal analog circuitry and supplies power to the DAC
outputs. Bypass the ABP output to GND with a 1µF
ceramic capacitor installed as close to the device as
possible.
DBP is an internal 2.7V (typ) voltage regulator.
EEPROM and digital circuitry are powered by DBP. All
push-pull outputs are referenced to DBP. DBP supplies
the input voltage to the internal charge pumps when
the programmable outputs are configured as charge-
pump outputs. Bypass the DBP output to GND with a
1µF ceramic capacitor installed as close as possible to
the device.
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 17
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
18 ______________________________________________________________________________________
Enable
To initiate sequencing/tracking and enable monitoring,
the voltage at EN must be above 0.525V and the
Software Enable bit in r4Dh[0] must be set to ‘0.’ To
power down and disable monitoring, either pull EN
below 0.5V or set the Software Enable bit to ‘1.’ See
Table 1 for the software enable bit configurations.
Connect EN to ABP if not used.
If a fault condition occurs during the power-up cycle,
the EN_OUT_ outputs are powered down immediately,
independent of the state of EN. If operating in latch-on
fault mode, toggle EN or toggle the Software Enable bit
to clear the latch condition and restart the device once
the fault condition has been removed.
Table 1. EEPROM Software Enable Configurations
REGISTER/
EEPROM ADDRESS BIT RANGE DESCRIPTION
0
Software Enable bit
0 = Enabled. EN must also be high to begin sequencing.
1 = Disabled (factory default)
1
Margin bit
1 = Margin functionality is enabled
0 = Margin disabled
2
Early Warning Selection bit
0 = Early warning thresholds are undervoltage thresholds
1 = Early warning thresholds are overvoltage thresholds
3
Watchdog Mode Selection bit
0 = Watchdog timer is in dependent mode
1 = Watchdog timer is in independent mode
4Dh
[7:4] Not used
Voltage Monitoring
The MAX16046/MAX16048 feature an internal 10-bit
ADC that monitors the MON_ voltage inputs. An internal
multiplexer cycles through each of the twelve inputs,
taking 100µs (typ) for a complete monitoring cycle.
Each acquisition takes approximately 8.3µs. At each
multiplexer stop, the 10-bit ADC converts the analog
input to a digital result and stores the result in a regis-
ter. ADC conversion results are stored in registers r00h
to r17h in the extended page. Use the I2C or JTAG seri-
al interface to read ADC conversion results. See the
I
2
C/SMBus-Compatible Serial Interface
or the
JTAG
Serial Interface
section for more information on access-
ing the extended page.
The MAX16046 provides twelve inputs, MON1–MON12,
for voltage monitoring. The MAX16048 provides eight
inputs, MON1–MON8, for voltage monitoring. Each
input voltage range is programmable in registers r0Fh
to r11h (see Table 2). When MON_ configuration
registers are set to ‘11,’ MON_ voltages are not moni-
tored or converted, and the multiplexer does not stop at
these inputs, decreasing the total cycle time. These
inputs cannot be configured to trigger fault conditions.
The three programmable thresholds for each monitored
voltage include an overvoltage, an undervoltage, and
an early warning threshold that can be set in r4Dh[2] to
be either an undervoltage or overvoltage threshold. See
the
Faults
section for more information on setting over-
voltage and undervoltage thresholds. All voltage
thresholds are 8 bits wide. The 8 MSBs of the 10-bit
ADC conversion result are compared to these overvolt-
age and undervoltage thresholds.
For any undervoltage or overvoltage condition to be
monitored and any faults detected, the MON_ input
must be assigned to a particular sequence order. See
the
Sequencing
section for more details on assigning
MON_ inputs.
MAX16046/MAX16048
Table 2. Input Monitor Ranges and Enables
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[1:0]
MON1 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON1 is not converted or monitored
[3:2]
MON2 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON2 is not converted or monitored
[5:4]
MON3 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON3 is not converted or monitored
0Fh
[7:6]
MON4 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON4 is not converted or monitored
[1:0]
MON5 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON5 is not converted or monitored
[3:2]
MON6 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON6 is not converted or monitored
[5:4]
MON7 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON7 is not converted or monitored
10h
[7:6]
MON8 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON8 is not converted or monitored
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 19
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
20 ______________________________________________________________________________________
Table 2. Input Monitor Ranges and Enables (continued)
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[1:0]
MON9 Voltage Range Selection*:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON9 is not converted or monitored
[3:2]
MON10 Voltage Range Selection*:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON10 is not converted or monitored
[5:4]
MON11 Voltage Range Selection*:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON11 is not converted or monitored
11h
[7:6]
MON12 Voltage Range Selection*:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON12 is not converted or monitored
*
MAX16046 only
MAX16046/MAX16048
The extended memory page contains the ADC conver-
sion result registers (see Table 3). These registers are
also used internally for fault threshold comparison.
Voltage-monitoring thresholds are compared with the 8
MSBs of the conversion results. Inputs that are not
enabled are not converted by the ADC; they contain the
last value acquired before that channel was disabled.
The ADC conversion result registers are reset to 00h at
boot-up. These registers are not reset when a reboot
command is executed.
Table 3. ADC Conversion Registers
EXTENDED PAGE
ADDRESS BIT RANGE DESCRIPTION
00h [7:0] MON1 ADC Conversion Result (MSB)
[7:6] MON1 ADC Conversion Result (LSB)
01h [5:0] Reserved
02h [7:0] MON2 ADC Conversion Result (MSB)
[7:6] MON2 ADC Conversion Result (LSB)
03h [5:0] Reserved
04h [7:0] MON3 ADC Conversion Result (MSB)
[7:6] MON3 ADC Conversion Result (LSB)
05h [5:0] Reserved
06h [7:0] MON4 ADC Conversion Result (MSB)
[7:6] MON4 ADC Conversion Result (LSB)
07h [5:0] Reserved
08h [7:0] MON5 ADC Conversion Result (MSB)
[7:6] MON5 ADC Conversion Result (LSB)
09h [5:0] Reserved
0Ah [7:0] MON6 ADC Conversion Result (MSB)
[7:6] MON6 ADC Conversion Result (LSB)
0Bh [5:0] Reserved
0Ch [7:0] MON7 ADC Conversion Result (MSB)
[7:6] MON7 ADC Conversion Result (LSB)
0Dh [5:0] Reserved
0Eh [7:0] MON8 ADC Conversion Result (MSB)
[7:6] MON8 ADC Conversion Result (LSB)
0Fh [5:0] Reserved
10h [7:0] MON9 ADC Conversion Result (MSB)*
[7:6] MON9 ADC Conversion Result (LSB)*
11h [5:0] Reserved
12h [7:0] MON10 ADC Conversion Result (MSB)*
[7:6] MON10 ADC Conversion Result (LSB)*
13h [5:0] Reserved
14h [7:0] MON11 ADC Conversion Result (MSB)*
[7:6] MON11 ADC Conversion Result (LSB)*
15h [5:0] Reserved
16h [7:0] MON12 ADC Conversion Result (MSB)*
[7:6] MON12 ADC Conversion Result (LSB)*
17h [5:0] Reserved
*
MAX16046 only
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 21
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
22 ______________________________________________________________________________________
General-Purpose Inputs/Outputs
GPIO1–GPIO6 are programmable general-purpose
inputs/outputs. GPIO1–GPIO6 are configurable as a
manual reset input, a margin disable input, margin-
up/margin-down control inputs, a watchdog timer input
and output, logic inputs/outputs, fault-dependent out-
puts, or as the feedback inputs (INS_) for closed-loop
tracking. When programmed as outputs, GPIOs are
open drain or push-pull. See registers r1Ch to r1Eh in
Tables 4 and 5 for more detailed information on config-
uring GPIO1–GPIO6.
Table 4. General-Purpose IO Configuration Registers
REGISTER/
EEPROM ADDRESS BIT RANGE DESCRIPTION
[2:0] GPIO1 Configuration Register
[5:3] GPIO2 Configuration Register1Ch
[7:6] GPIO3 Configuration Register (LSB)
[0] GPIO3 Configuration Register (MSB)
[3:1] GPIO4 Configuration Register
[6:4] GPIO5 Configuration Register
1Dh
[7] GPIO6 Configuration Register (LSB)
[1:0] GPIO6 Configuration Register (MSB)
1Eh [7:2] Reserved
Table 5. GPIO Mode Selection
CONFIGURATION
BITS GPIO1 GPIO2 GPIO3 GPIO4 GPIO5 GPIO6
000 INS1 INS2 INS3 INS4 MARGIN input
001 Push-pull logic
input/output
Push-pull logic
input/output
Push-pull logic
input/ output
Push-pull logic
input/output
Push-pull logic
input/output
Push-pull logic
input/output
010
Open-drain
logic
input/output
Open-drain
logic
input/output
Open-drain
logic input/
output
Open-drain
logic
input/output
Open-drain
logic input/
output
Open-drain
logic input/
output
011 Push-pull
Any_Fault output
Push-pull
Any_Fault output
Push-pull
Any_Fault output
Push-pull
Any_Fault output
Push-pull
FAULT1 output
Push-pull
FAULT2 output
100 Open-drain
Any_Fault output
Open-drain
Any_Fault output
Open-drain
Any_Fault output
Open-drain
Any_Fault output
Open-drain
FAULT1 output
Open-drain
FAULT2 output
101 Logic input Logic input Logic input Logic input Logic input Logic input
110 —————
Open-drain,
WDO output
111 MARGINUP
input
MARGINDN
input MR input WDI input Open-drain,
FAULTPU output
Note: The dash “—” represents a reserved GPIO configuration. Do not set any GPIO to these values.
MAX16046/MAX16048
Voltage Tracking Sense (INS_) Inputs
GPIO1–GPIO4 are configurable as feedback sense
return inputs (INS_) for closed-loop tracking. Connect the
gate of an external n-channel MOSFET to each EN_OUT_
configured for closed-loop tracking. Connect INS_ inputs
to the source of the MOSFETs for tracking feedback.
Internal comparators monitor INS_ with respect to a
control tracking ramp voltage for power-up/power-down
and control each EN_OUT_ voltage. Under normal con-
ditions each INS_ voltage tracks the ramp voltage until
the power-good voltage threshold has been reached.
The slew rate for the ramp voltage and the INS_ to
MON_ power-good threshold are programmable. See
the
Closed-Loop Tracking
section.
INS_ connections can also act as 100pulldowns for
closed-loop tracking channels or for other power sup-
plies, if INS_ are connected to the outputs of the sup-
plies. Set the appropriate bits in r4Eh[7:4] to enable
pulldown functionality. See Table 13.
General-Purpose Logic Inputs/Outputs
Configure GPIO1–GPIO6 be used as general-purpose
inputs/outputs. Write values to GPIOs through r1Ah
when operating as outputs, and read values from r1Bh
when operating as inputs. Register r1Bh is read-only.
See Table 6 for more information on reading and writing
to the GPIOs as logic inputs/outputs. Both registers
r1Ah and r1Bh are located in the extended page and
are therefore not loaded from EEPROM on boot-up.
Table 6. GPIO Data-In/Data-Out Data
EXTENDED PAGE
ADDRESS BIT RANGE DESCRIPTION
[0]
GPIO Logic Output Data
0 = GPIO1 is a logic-low output
1 = GPIO1 is a logic-high output
[1] 0 = GPIO2 is a logic-low output
1 = GPIO2 is a logic-high output
[2] 0 = GPIO3 is a logic-low output
1 = GPIO3 is a logic-high output
[3] 0 = GPIO4 is a logic-low output
1 = GPIO4 is a logic-high output
[4] 0 = GPIO5 is a logic-low output
1 = GPIO5 is a logic-high output
[5] 0 = GPIO6 is a logic-low output
1 = GPIO6 is a logic-high output
1Ah
[7:6] Not used
[0] GPIO Logic Input Data
GPIO1 logic-input state
[1] GPIO2 logic-input state
[2] GPIO3 logic-input state
[3] GPIO4 logic-input state
[4] GPIO5 logic-input state
[5] GPIO6 logic-input state
1Bh
[7:6] Not used
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 23
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
24 ______________________________________________________________________________________
Any_Fault Outputs
GPIO1–GPIO4 are configurable as active-low push-pull
or open-drain fault-dependent outputs. These outputs
assert when any monitored input exceeds an overvolt-
age, undervoltage, or early warning threshold.
FAULT1 and FAULT2
GPIO5 and GPIO6 are configurable as dedicated fault
outputs, FAULT1 and FAULT2, respectively. Fault
outputs can assert on one or more overvoltage, under-
voltage, or early warning conditions for selected inputs.
FAULT1 and FAULT2 dependencies are set using reg-
isters r15h to r18h. See Table 7.
If a fault output depends on more than one MON_, the
fault output will assert if one or more MON_ exceeds a
programmed threshold voltage.
Table 7. FAULT1 and FAULT2 Output Configuration and Dependencies
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[0] 1 = FAULT1 is a digital output dependent on MON1
[1] 1 = FAULT1 is a digital output dependent on MON2
[2] 1 = FAULT1 is a digital output dependent on MON3
[3] 1 = FAULT1 is a digital output dependent on MON4
[4] 1 = FAULT1 is a digital output dependent on MON5
[5] 1 = FAULT1 is a digital output dependent on MON6
[6] 1 = FAULT1 is a digital output dependent on MON7
15h
[7] 1 = FAULT1 is a digital output dependent on MON8
[0] 1 = FAULT1 is a digital output dependent on MON9*
[1] 1 = FAULT1 is a digital output dependent on MON10*
[2] 1 = FAULT1 is a digital output dependent on MON11*
[3] 1 = FAULT1 is a digital output dependent on MON12*
[4] 1 = FAULT1 is a digital output that depends on the overvoltage thresholds at the input
selected by r15h and r16h[3:0]
[5] 1 = FAULT1 is a digital output that depends on the undervoltage thresholds at the
input selected by r15h and r16h[3:0]
[6] 1 = FAULT1 is a digital output that depends on the early warning thresholds at the
input selected by r15h and r16h[3:0]
16h
[7] 0 = FAULT1 is an active-low digital output
1 = FAULT1 is an active-high digital output
[0] 1 = FAULT2 is a digital output dependent on MON1
[1] 1 = FAULT2 is a digital output dependent on MON2
[2] 1 = FAULT2 is a digital output dependent on MON3
[3] 1 = FAULT2 is a digital output dependent on MON4
[4] 1 = FAULT2 is a digital output dependent on MON5
[5] 1 = FAULT2 is a digital output dependent on MON6
[6] 1 = FAULT2 is a digital output dependent on MON7
17h
[7] 1 = FAULT2 is a digital output dependent on MON8
MAX16046/MAX16048
Fault-On Power-Up (FAULTPU)
GPIO6 indicates a fault during power-up or power-
down when configured as a “fault-on power-up” output.
Under these conditions, all EN_OUT_ voltages are
pulled low and fault data is saved to nonvolatile
EEPROM. See the
Faults
section.
MARGINUP and MARGINDN
Configure GPIO2 and GPIO3 as margin-up
(MARGINUP) and margin-down (MARGINDN) inputs,
respectively, for margining functionality. Pull
MARGINUP low and pull MARGINDN high to select
DACOUT_ voltage values set in registers r66h to r71h.
Pull MARGINDN low and pull MARGINUP high to select
DACOUT_ values set in registers r72h to r7Dh. Pull
both MARGINUP and MARGINDN high or low to select
DACOUT_ values set in registers r00h to r0Bh. See the
Voltage Margining
section for more information on set-
ting DACOUT_ outputs for margining.
Margin-up and margin-down functionality is controlled
by GPIO2 and GPIO3 when configured for margining
(see Table 8). When MARGINUP or MARGINDN are
asserted, the DAC output switches are automatically
closed and the margin function is enabled. Writing to
the DAC-enabled registers (r1Ch and r1Dh) is not
required to close the DAC switches. See the
MARGIN
section for an explanation of the margin function.
Table 7. FAULT1 and FAULT2 Output Configuration and Dependencies (continued)
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[0] 1 = FAULT2 is a digital output dependent on MON9*
[1] 1 = FAULT2 is a digital output dependent on MON10*
[2] 1 = FAULT2 is a digital output dependent on MON11*
[3] 1 = FAULT2 is a digital output dependent on MON12*
[4] 1 = FAULT2 is a digital output that depends on the overvoltage thresholds at the input
selected by r17h and r18h[3:0]
[5] 1 = FAULT2 is a digital output that depends on the undervoltage thresholds at the
input selected by r17h and 18h[3:0]
[6] 1 = FAULT2 is a digital output that depends on the early warning thresholds at the
input selected by r17h and r18h[3:0]
18h
[7] 0 = FAULT2 is an active-low digital output
1 = FAULT2 is an active-high digital output
*
MAX16046 only
Table 8. MARGINUP and MARGINDN FUNCTION
MARGINUP
(GPIO2)
MARGINDN
(GPIO3) DACOUT REGISTER USED DACOUT
SWITCH STATE
1 1 DACOUT registers r00h to r0Bh Depends on r1Ch, r1Dh*
10MARGINDN registers r72h to r7Dh Closed
01MARGINUP registers r66h to r71h Closed
0 0 DACOUT registers r00h to r0Bh Depends on r1Ch, r1Dh*
*
Note: r1Ch and r1Dh are located in the extended page.
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 25
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
26 ______________________________________________________________________________________
MARGIN
GPIO6 is configurable as an active-low MARGIN input.
Drive MARGIN low before varying system voltages above
or below the thresholds to avoid signaling an error. Drive
MARGIN high for normal operation.
When MARGIN is pulled low or r4Dh[1] is a ‘1,’ the mar-
gin function is enabled. FAULT1, FAULT2, Any_Fault,
and RESET are latched in their current state. Threshold
violations will be ignored, and faults will not be logged.
Manual Reset (MR)
GPIO4 is configurable to act as an active-low manual
reset input, MR. Drive MR low to assert RESET. RESET
remains low for the selected reset timeout period after
MR transitions from low to high. See the
RESET
section
for more information on selecting a reset timeout period.
Watchdog Input (WDI) and Output (WDO)
Set r1Eh[1:0] and register r1Dh[7] to ‘110’ to configure
GPIO6 as WDO. Set r1Dh[6:4] to ‘111’ to configure
GPIO5 as WDI. WDO is an open-drain active-low output.
See the
Watchdog Timer
section for more information
about the operation of the watchdog timer.
Programmable Outputs
(EN_OUT1–EN_OUT12)
The MAX16046 includes twelve programmable outputs,
and the MAX16048 includes eight programmable out-
puts. These outputs are capable of connecting to either
the enable (EN) inputs of a DC-DC or LDO power supply
or to the gates of series-pass MOSFETs for closed-loop
tracking mode, or for charge-pump mode. Selectable out-
put configurations include: active-low or active-high,
open-drain or push-pull. EN_OUT1–EN_OUT4 are also
configurable for closed-loop tracking, and EN_OUT1–
EN_OUT6 can act as charge-pump outputs with no
closed-loop tracking. Use the registers r1Fh to r22h to
configure outputs. See Table 9 for detailed information on
configuring EN_OUT1–EN_OUT12.
Table 9. EN_OUT1–EN_OUT12 Configuration
REGISTER/
EEPROM ADDRESS
BIT
RANGE DESCRIPTION
[2:0]
EN_OUT1 Configuration:
000 = EN_OUT1 is an open-drain active-low output
001 = EN_OUT1 is an open-drain active-high output
010 = EN_OUT1 is a push-pull active-low output
011 = EN_OUT1 is a push-pull active-high output
100 = EN_OUT1 is used in closed-loop tracking
101 = EN_OUT1 is configured with a charge-pump output (MON1 + 5V) capable of
driving an external n-channel MOSFET
110 = Reserved
111 = Reserved
[5:3]
EN_OUT2 Configuration:
000 = EN_OUT2 is an open-drain active-low output
001 = EN_OUT2 is an open-drain active-high output
010 = EN_OUT2 is a push-pull active-low output
011 = EN_OUT2 is a push-pull active-high output
100 = EN_OUT2 is used in closed-loop tracking
101 = EN_OUT2 is configured with a charge-pump output (MON2 + 5V) capable of
driving an external n-channel MOSFET
110 = Reserved
111 = Reserved
1Fh
[7:6]
EN_OUT3 Configuration (LSBs):
000 = EN_OUT3 is an open-drain active-low output
001 = EN_OUT3 is an open-drain active-high output
010 = EN_OUT3 is a push-pull active-low output
011 = EN_OUT3 is a push-pull active-high output
100 = EN_OUT3 is used in closed-loop tracking
101 = EN_OUT3 is configured with a charge-pump output (MON3 + 5V) capable of
driving an external n-channel MOSFET
110 = Reserved
111 = Reserved
MAX16046/MAX16048
Table 9. EN_OUT1–EN_OUT12 Configuration (continued)
REGISTER/EEPROM
ADDRESS
BIT
RANGE DESCRIPTION
[0] EN_OUT3 Configuration (MSB)—see r1Fh[7:6]
[3:1]
EN_OUT4 Configuration:
000 = EN_OUT4 is an open-drain active-low output
001 = EN_OUT4 is an open-drain active-high output
010 = EN_OUT4 is a push-pull active-low output
011 = EN_OUT4 is a push-pull active-high output
100 = EN_OUT4 is used in closed-loop tracking
101 = EN_OUT4 is configured with a charge-pump output (MON4 + 5V) capable of
driving an external n-channel MOSFET
110 = Reserved
111 = Reserved
[6:4]
EN_OUT5 Configuration:
000 = EN_OUT5 is an open-drain active-low output
001 = EN_OUT5 is an open-drain active-high output
010 = EN_OUT5 is a push-pull active low output
011 = EN_OUT5 is a push-pull active-high output
100 = Reserved. EN_OUT5 is not usable for closed-loop tracking.
101 = EN_OUT5 is configured with a charge-pump output (MON5 + 5V) capable of
driving an external n-channel MOSFET
110 = Reserved
111 = Reserved
20h
[7] EN_OUT6 Configuration (LSB)—see r21h[1:0]
[1:0]
EN_OUT6 Configuration (MSBs):
000 = EN_OUT6 is an open-drain active-low output
001 = EN_OUT6 is an open-drain active-high output
010 = EN_OUT6 is a push-pull active-low output
011 = EN_OUT6 is a push-pull active-high output
100 = Reserved. EN_OUT6 is not useable for closed-loop tracking.
101 = EN_OUT6 is configured with a charge-pump output (MON6 + 5V) capable of
driving an external n-channel MOSFET
110 = Reserved
111 = Reserved
[3:2]
EN_OUT7 Configuration:
00 = EN_OUT7 is an open-drain active-low output
01 = EN_OUT7 is an open-drain active-high output
10 = EN_OUT7 is a push-pull active-low output
11 = EN_OUT7 is a push-pull active-high output
[5:4]
EN_OUT8 Configuration:
00 = EN_OUT8 is an open-drain active-low output
01 = EN_OUT8 is an open-drain active-high output
10 = EN_OUT8 is a push-pull active-low output
11 = EN_OUT8 is a push-pull active-high output
21h
[7:6]
EN_OUT9 Configuration*:
00 = EN_OUT9 is an open-drain active-low output
01 = EN_OUT9 is an open-drain active-high output
10 = EN_OUT9 is a push-pull active-low output
11 = EN_OUT9 is a push-pull active-high output
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 27
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
28 ______________________________________________________________________________________
Table 9. EN_OUT1–EN_OUT12 Configuration (continued)
REGISTER/EEPROM
ADDRESS
BIT
RANGE DESCRIPTION
[1:0]
EN_OUT10 Configuration*:
00 = EN_OUT10 is an open-drain active-low output
01 = EN_OUT10 is an open-drain active-high output
10 = EN_OUT10 is a push-pull active-low output
11 = EN_OUT10 is a push-pull active-high output
[3:2]
EN_OUT11 Configuration*:
00 = EN_OUT11 is an open-drain active-low output
01 = EN_OUT11 is an open-drain active-high output
10 = EN_OUT11 is a push-pull active-low output
11 = EN_OUT11 is a push-pull active-high output
[5:4]
EN_OUT12 Configuration*:
00 = EN_OUT12 is an open-drain active-low output
01 = EN_OUT12 is an open-drain active high output
10 = EN_OUT12 is a push-pull active-low output
11 = EN_OUT12 is a push-pull active-high output
22h
[7:6] Reserved
*
MAX16046 only
Charge-Pump Configuration
EN_OUT1–EN_OUT6 can act as high-voltage charge-
pump outputs to drive up to six external n-channel
MOSFETs. During sequencing, an EN_OUT_ output
configured this way drives 6µA until the voltage reach-
es 5V above the corresponding MON_ to fully enhance
the external n-channel MOSFET. For example,
EN_OUT2 will rise to 5V above MON2. See the
Sequencing
section for more detailed information on
power-supply sequencing.
Closed-Loop Tracking Operation
EN_OUT1–EN_OUT4 can operate in closed-loop track-
ing mode. When configured for closed-loop tracking,
EN_OUT1–EN_OUT4 are capable of driving the gates
of up to four external n-channel MOSFETs. For closed-
loop tracking, configure GPIO1–GPIO4 as return-sense
line inputs (INS_) to be used in conjunction with
EN_OUT1–EN_OUT4 and MON1–MON4. See the
Closed-Loop Tracking
section.
Open-Drain Output Configuration
Connect an external pullup resistor from the output to
an external voltage up to 6V (abs max, EN_OUT7 to
EN_OUT12) or 12V (abs max, EN_OUT1 to EN_OUT6)
when configured as an open-drain output. Choose the
pullup resistor depending on the number of devices
connected to the open-drain output and the allowable
current consumption. The open-drain output configura-
tion allows wire-ORed connection.
Push-Pull Output Configuration
The MAX16046/MAX16048s’ programmable outputs
sink 2mA and source 100µA when configured as push-
pull outputs.
EN_OUT_ State During Power-Up
When VCC is ramped from 0V to the operating supply
voltage, the EN_OUT_ output is high impedance until
VCC is approximately 2.4V and then EN_OUT_ will be in
its configured deasserted state. See Figures 3 and 4.
RESET is configured as an active-low open-drain output
pulled up to VCC through a 10kresistor for Figures 3
and 4.
MAX16046/MAX16048
Sequencing
Each EN_OUT_ has one or more associated MON_
inputs, facilitating the voltage monitoring of multiple
power supplies. To sequence a system of power sup-
plies safely, the output voltage of a power supply must
be good before the next power supply may turn on.
Connect EN_OUT_ outputs to the enable input of an
external power supply and connect MON_ inputs to the
output of the power supply for voltage monitoring. More
than one MON_ may be used if the power supply has
multiple outputs.
Sequence Order
The MAX16046/MAX16048 utilize a system of ordered
slots to sequence multiple power supplies. To deter-
mine the sequence order, assign each EN_OUT_ to a
slot ranging from Slot 0 to Slot 11. EN_OUT_(s)
assigned to Slot 0 are turned on first, followed by out-
puts assigned to Slot 1, and so on through Slot 11.
Multiple EN_OUT_s assigned to the same slot turn on at
the same time.
Each slot has a built-in configurable sequence delay
(registers r50h to r54h) ranging from 20µs to 1.6s.
During a reverse sequence, slots are turned off in
reverse order starting from Slot 11. The MAX16046/
MAX16048 may be configured to power-down in simul-
taneous mode or in reverse sequence mode as set in
r54h[4]. See Tables 10, 11, and 12 for the EN_OUT_
slot assignment bits, and Tables 13 and 14 for the
sequence delays.
Monitoring Inputs While Sequencing
An enabled MON_ input may be assigned to a slot rang-
ing from Slot 1 to Slot 12. Monitoring inputs are always
checked at the beginning of a slot. The inputs are given
the power-up fault delay within which they must satisfy
the programmed undervoltage limit; otherwise a fault
condition will occur. The fault occurs regardless of the
critical fault enable bits. This undervoltage limit cannot
be disabled during power-up and power-down.
EN_OUT_s configured for open-drain, push-pull, or
charge-pump operation are always asserted at the end
of a slot, following the sequence delay. See Tables 10,
11, and 12 for the MON_ slot assignment bits.
Slot 0 does not monitor any MON_ input. Instead, Slot 0
waits for the Software Enable bit r4Dh[0] to be a logic
‘0’ and for the voltage on EN to rise above 0.525V
before asserting any assigned outputs. Outputs
assigned to Slot 0 are asserted before the Slot 0
sequence delay. Generally, Slot 0 controls the enable
inputs of power supplies that are first in the sequence.
Similarly, Slot 12 does not control any EN_OUT_ outputs.
Rather, Slot 12 monitors assigned MON_ inputs and then
enters the power-on state. Generally, Slot 12 monitors
the last power supplies in the sequence. The power-up
sequence is complete when any MON_ inputs assigned
to Slot 12 exceed their undervoltage thresholds and the
sequence delay is expired. If no MON_ inputs are
assigned to Slot 12, the power-up sequence is complete
after the slot sequence delay is expired.
The output rail(s) of a power supply should be monitored
by one or more MON_ inputs placed in the succeeding
slot, ensuring that the output of the supply is not checked
until it has first been turned on. For example, if a power
supply uses EN_OUT1 located in Slot 3 and has two
monitoring inputs, MON1 and MON2, they must both be
assigned to Slot 4. In this example, EN_OUT1 turns on at
the end of Slot 3. At the start of Slot 4, MON1 and MON2
must exceed the undervoltage threshold before the pro-
grammed power-up fault delay; otherwise a fault triggers.
MAX16046 fig03
20ms/div
VCC
2V/div
EN_OUT_
2V/div
0V
RESET
2V/div
0V
0V
Figure 3. RESET and EN_OUT_ During Power-Up, EN_OUT_ Is
in Open-Drain Active-Low Configuration
MAX16046 fig04
10ms/div
VCC
2V/div
EN_OUT_
2V/div
0V
RESET
2V/div
0V
0V
HIGH-Z
ASSERTED
LOW
UVLO
Figure 4. RESET and EN_OUT_ During Power-Up, EN_OUT_ Is
in Push-Pull Active-High Configuration
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 29
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
30 ______________________________________________________________________________________
RESET
Deassertion
After any MON_ inputs assigned to Slot 12 exceed their
undervoltage thresholds, the reset timeouts begin. When
the reset timeout completes, RESET deasserts. The reset
timeout period is set in r19h[6:4] (see Table 27).
Power-Down
Power-down starts when EN is pulled low or the
Software Enable bit is set to ‘1.’ RESET asserts as soon
as power-down begins regardless of the reset output
dependencies. Power down EN_OUT_s simultaneously
or in reverse sequence mode by setting the Reverse
Sequence bit (r54h[4]) appropriately. In reverse
sequence mode (r54h[4] set to ‘1’), the EN_OUT_s
assigned to Slot 11 deassert, the MAX16046/
MAX16048 wait for the Slot 11 sequence delay and
then proceed to Slot 10, and so on until the EN_OUT_s
assigned to Slot 0 turn off. When simultaneous power-
down is selected (r54h[4] set to ‘0’), all EN_OUT_s turn
off at the same time.
Table 10. MON_ and EN_OUT_ Slot Assignment Registers
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[3:0] MON1 Slot Assignment Register
56h [7:4] MON2 Slot Assignment Register
[3:0] MON3 Slot Assignment Register
57h [7:4] MON4 Slot Assignment Register
[3:0] MON5 Slot Assignment Register
58h [7:4] MON6 Slot Assignment Register
[3:0] MON7 Slot Assignment Register
59h [7:4] MON8 Slot Assignment Register
[3:0] MON9 Slot Assignment Register*
5Ah [7:4] MON10 Slot Assignment Register*
[3:0] MON11 Slot Assignment Register*
5Bh [7:4] MON12 Slot Assignment Register*
[3:0] EN_OUT1 Slot Assignment Register
5Eh [7:4] EN_OUT2 Slot Assignment Register
[3:0] EN_OUT3 Slot Assignment Register
5Fh [7:4] EN_OUT4 Slot Assignment Register
[3:0] EN_OUT5 Slot Assignment Register
60h [7:4] EN_OUT6 Slot Assignment Register
[3:0] EN_OUT7 Slot Assignment Register
61h [7:4] EN_OUT8 Slot Assignment Register
[3:0] EN_OUT9 Slot Assignment Register*
62h [7:4] EN_OUT10 Slot Assignment Register*
[3:0] EN_OUT11 Slot Assignment Register*
63h [7:4] EN_OUT12 Slot Assignment Register *
*
MAX16046 only
MAX16046/MAX16048
Table 11. MON_ Slot Assignment
CONFIGURATION BITS DESCRIPTION
0000 MON_ is not assigned to a slot
0001 MON_ is assigned to Slot 1
0010 MON_ is assigned to Slot 2
0011 MON_ is assigned to Slot 3
0100 MON_ is assigned to Slot 4
0101 MON_ is assigned to Slot 5
0110 MON_ is assigned to Slot 6
0111 MON_ is assigned to Slot 7
1000 MON_ is assigned to Slot 8
1001 MON_ is assigned to Slot 9
1010 MON_ is assigned to Slot 10
1011 MON_ is assigned to Slot 11
1100 MON_ is assigned to Slot 12
1101 Not used
1110 Not used
1111 Not used
Table 12. EN_OUT_ Slot Assignment
CONFIGURATION BITS DESCRIPTION
0000 EN_OUT_ is not assigned to a slot
0001 EN_OUT_ is assigned to Slot 0
0010 EN_OUT_ is assigned to Slot 1
0011 EN_OUT_ is assigned to Slot 2
0100 EN_OUT_ is assigned to Slot 3
0101 EN_OUT_ is assigned to Slot 4
0110 EN_OUT_ is assigned to Slot 5
0111 EN_OUT_ is assigned to Slot 6
1000 EN_OUT_ is assigned to Slot 7
1001 EN_OUT_ is assigned to Slot 8
1010 EN_OUT_ is assigned to Slot 9
1011 EN_OUT_ is assigned to Slot 10
1100 EN_OUT_ is assigned to Slot 11
1101 Not used
1110 Not used
1111 Not used
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 31
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
32 ______________________________________________________________________________________
Table 13. Sequence Delays and Fault Recovery
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[1:0]
Power-Up Fault Timeout
00 = 25ms
01 = 50ms
10 = 100ms
11 = 200ms
[3:2]
Power-Down Fault Timeout
00 = 25ms
01 = 50ms
10 = 100ms
11 = 200ms
[4]
INS1 Pulldown Resistor Enable
0 = Pulldown resistor for INS1 is disabled
1 = Pulldown resistor for INS1 is enabled
[5]
INS2 Pulldown Resistor Enable
0 = Pulldown resistor for INS2 is disabled
1 = Pulldown resistor for INS2 is enabled
[6]
INS3 Pulldown Resistor Enable
0 = Pulldown resistor for INS3 is disabled
1 = Pulldown resistor for INS3 is enabled
4Eh
[7]
INS4 Pulldown Resistor Enable
0 = Pulldown resistor for INS4 is disabled
1 = Pulldown resistor for INS4 is enabled
[2:0]
Autoretry Timeout
000 = 20µs
001 = 12.5ms
010 = 25ms
011 = 50ms
100 = 100ms
101 = 200ms
110 = 400ms
111 = 1.6s
[3]
Fault Recovery Mode
0 = Autoretry procedure is performed following a fault event
1 = Latch-off on fault
[5:4]
Slew Rate
00 = 800V/s
01 = 400V/s
10 = 200V/s
11 = 100V/s
4Fh
[7:6]
Fault Deglitch
00 = 2 conversions
01 = 4 conversions
10 = 8 conversions
11 = 16 conversions
MAX16046/MAX16048
Table 13. Sequence Delays and Fault Recovery (continued)
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[2:0] Slot 0 Sequence Delay
[5:3] Slot 1 Sequence Delay
50h
[7:6] Slot 2 Sequence Delay (LSBs)
[0] Slot 2 Sequence Delay (MSB)—see r50h[7:6]
[3:1] Slot 3 Sequence Delay
[6:4] Slot 4 Sequence Delay
51h
[7] Slot 5 Sequence Delay (LSB)—see r52h[1:0]
[1:0] Slot 5 Sequence Delay
[4:2] Slot 6 Sequence Delay
52h
[7:5] Slot 7 Sequence Delay
[2:0] Slot 8 Sequence Delay
[5:3] Slot 9 Sequence Delay53h
[7:6] Slot 10 Sequence Delay (LSBs)
[0] Slot 10 Sequence Delay (MSB)—see r53h[7:6]
[3:1] Slot 11 Sequence Delay
[4]
Reverse Sequence
0 = Power down all EN_OUT_s at the same time (simultaneously)
1 = Controlled power-down will be reverse of power-up sequence
54h
[7:5] Not used
Table 14. Slot Sequence Delay Selection
CONFIGURATION BITS SLOT SEQUENCE DELAY
000 20µs
001 12.5ms
010 25ms
011 50ms
100 100ms
101 200ms
110 400ms
111 1.6s
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 33
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
34 ______________________________________________________________________________________
Closed-Loop Tracking
The MAX16046/MAX16048 track up to four voltages
during any time slot except Slot 0 and Slot 12.
Configure GPIO1–GPIO4 as sense line inputs (INS_) to
monitor tracking voltages. Configure GPIO6 as
FAULTPU to indicate tracking faults, if desired. See the
General-Purpose Inputs/Outputs
section for information
on configuring GPIOs.
For closed-loop tracking, use MON1, EN_OUT1, and
INS1 together to form a complete channel. Use MON2,
EN_OUT2, and INS2 to form a second complete chan-
nel. Use MON3, EN_OUT3, and INS3 together to form a
third channel; and use MON4, EN_OUT4, and INS4 to
form a fourth channel.
When configured for closed-loop tracking, assign each
EN_OUT_ to the same slot as its associated single
monitoring input (MON_). For example, if EN_OUT2 is
assigned to Slot 3, the monitoring input is MON2 and
must be assigned to Slot 3. This is because the MON_
input, checked at the start of the slot, must be valid
before tracking can begin. Tracking begins immediate-
ly and must finish before the power-up fault timeout
expires, or a fault will trigger. EN_OUT_ configured for
closed-loop tracking cannot be assigned to Slot 0.
The tracking control circuitry includes a ramp generator
and a comparator control block for each tracked volt-
age (see the
Functional Diagram
and Figure 5). The
comparator control block compares each INS_ voltage
with a control voltage ramp. If INS_ voltages vary from
the control ramp by more than 150mV (typ), the com-
parator control block signals an alert that dynamically
stops the ramp until the slow INS_ voltage rises to with-
in the allowed voltage window. The total tracking time is
extended under these conditions, but must still com-
plete within the selected power-up/power-down fault
timeout. The power-up/power-down tracking fault time-
out period is adjustable through r4Eh[3:0].
A voltage difference between any two tracking INS_
voltages exceeding 330mV generates a tracking fault,
forcing all EN_OUT_ voltages low and generating a
fault log. If configured as FAULTPU, GPIO6 asserts
when a tracking fault occurs.
The comparator control blocks also monitor INS_ voltages
with respect to input (MON_) voltages. Under normal con-
ditions each INS_ tracks the control ramp until the INS_
voltages reach the configured power-good (PG) thresh-
olds, set as a programmable percentage of the MON_
voltage. Use register r64h to set the PG thresholds (Table
15). Once PG is detected, the external n-channel FET sat-
urates with 5V (typ) applied between gate and source.
The slew rate for the control ramp is programmable from
100V/s to 800V/s in r4Fh[5:4] (see Table 13).
Power-down initiates when EN is forced low or when
the Software Enable bit in r4Dh[0] is set to ‘1.’ If the
Reverse Sequence bit is set (r54h[4]) INS_ voltages fol-
low a falling reference ramp to ground as long as
MON_ voltages remain high enough to supply the
required voltage/current. If a monitored voltage drops
faster than the control ramp voltage or the correspond-
ing MON_ voltage falls too quickly, power-down track-
ing operation is terminated and all EN_OUT_ voltages
are immediately forced to ground. If the Reverse
Sequence bit is set to ‘0,’ all EN_OUT_ voltages are
forced low simultaneously.
The MAX16046/MAX16048 include selectable internal
100pulldown resistors to ensure that tracked voltages
are not held high by large external capacitors during a
fault event. The pulldowns help to ensure that monitored
INS_ voltages are fully discharged before the next power-
up cycle is initiated. These pulldowns are high imped-
ance during normal operation. Set r4Eh[7:4] to ‘1’ to
enable the pulldown resistors (Table 13). These pulldown
resistors may also be used with EN_OUT1–EN_OUT4
channels not configured for closed-loop tracking, which
is useful to discharge the output capacitors of a DC-DC
converter during shutdown. For this case, configure the
GPIO as an INS_ input and set the 100pulldown bit,
but do not enable closed-loop tracking. Connect the
INS_ input to the output of the power supply.
MON_ EN_OUT_ INS_
VIN VOUT
REFERENCE
RAMP
LOGIC
ADC MUX
VTH_PG
100
GATE
DRIVE
Figure 5. Closed-Loop Tracking
MAX16046/MAX16048
DAC Outputs
The MAX16046/MAX16048 feature an 8-bit DAC with 12
outputs (MAX16046) or 8 outputs (MAX16048) for volt-
age margining. Program the voltage on the DAC out-
puts (DACOUT1–DACOUT12) to trim external
power-supply voltages, either by connecting through a
series resistor to the feedback node or to the trim input.
DAC outputs are high impedance during power-up to
prevent improper operation of the external power sup-
plies, and must be explicitly enabled by setting the
appropriate DACOUT_ enable bits.
Each DACOUT output has three voltage ranges: 0.4V to
0.8V, 0.6V to 1.2V, and 0.8V to 1.6V. Configure DAC
outputs using registers r12h to r14h (see Table 16).
Calculate DACOUT_ voltages, VDACOUT_, using the fol-
lowing equation:
VDACOUT_ = DACACC (V) + ((DACn- 80h) x
(DACRNG)/255) (V)
where DACACC is the DAC center code absolute accu-
racy and DACRNG is the DAC output voltage range as
listed in the
Electrical Characteristics
table and 07h <
DACn< F8h.
Set any DACOUT_ range configuration register to 00h
to switch off the DACOUT buffer. Set the DACOUT_
enable bit to ‘0’ to leave the DAC output as high imped-
ance. See Table 16 for the registers associated with the
DAC output ranges.
The DAC enable bits are not copied from EEPROM dur-
ing the boot phase; therefore each DACOUT_ output
must be enabled in the r1Ch and r1Dh registers, locat-
ed in the extended page, following power-up. See
Table 17 for the DAC enable bits.
To control the voltage on a particular DAC output, write
the 8-bit binary value to the appropriate output regis-
ter; see Table 18 for the register locations. Although
these registers are located in the default page, they
are not stored in nonvolatile EEPROM and are set to ‘0’
after a POR.
Table 15. Power-Good (PG) Thresholds
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[1:0]
00 = PG is asserted when monitored VMON1 is 95% of VINS1
01 = PG is asserted when monitored VMON1 is 92.5% of VINS1
10 = PG is asserted when monitored VMON1 is 90% of VINS1
11 = PG is asserted when monitored VMON1 is 87.5% of VINS1
[3:2]
00 = PG is asserted when monitored VMON2 is 95% of VINS2
01 = PG is asserted when monitored VMON2 is 92.5% of VINS2
10 = PG is asserted when monitored VMON2 is 90% of VINS2
11 = PG is asserted when monitored VMON2 is 87.5% of VINS2
[5:4]
00 = PG is asserted when monitored VMON3 is 95% of VINS3
01 = PG is asserted when monitored VMON3 is 92.5% of VINS3
10 = PG is asserted when monitored VMON3 is 90% of VINS3
11 = PG is asserted when monitored VMON3 is 87.5% of VINS3
64h
[7:6]
00 = PG is asserted when monitored VMON4 is 95% of VINS4
01 = PG is asserted when monitored VMON4 is 92.5% of VINS4
10 = PG is asserted when monitored VMON4 is 90% of VINS4
11 = PG is asserted when monitored VMON4 is 87.5% of VINS4
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 35
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
36 ______________________________________________________________________________________
Table 16. DACOUT Ranges
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[1:0]
DACOUT1 Range Selection:
00 = DACOUT1 is OFF
01 = 0.4V (min) to 0.8V (max)
10 = 0.6V (min) to 1.2V (max)
11 = 0.8V (min) to 1.6V (max)
[3:2]
DACOUT2 Range Selection:
00 = DACOUT2 is OFF
01 = 0.4V (min) to 0.8V (max)
10 = 0.6V (min) to 1.2V (max)
11 = 0.8V (min) to 1.6V (max)
[5:4]
DACOUT3 Range Selection:
00 = DACOUT3 is OFF
01 = 0.4V (min) to 0.8V (max)
10 = 0.6V (min) to 1.2V (max)
11 = 0.8V (min) to 1.6V (max)
12h
[7:6]
DACOUT4 Range Selection:
00 = DACOUT4 is OFF
01 = 0.4V (min) to 0.8V (max)
10 = 0.6V (min) to 1.2V (max)
11 = 0.8V (min) to 1.6V (max)
[1:0]
DACOUT5 Range Selection:
00 = DACOUT5 is OFF
01 = 0.4V (min) to 0.8V (max)
10 = 0.6V (min) to 1.2V (max)
11 = 0.8V (min) to 1.6V (max)
[3:2]
DACOUT6 Range Selection:
00 = DACOUT6 is OFF
01 = 0.4V (min) to 0.8V (max)
10 = 0.6V (min) to 1.2V (max)
11 = 0.8V (min) to 1.6V (max)
[5:4]
DACOUT7 Range Selection:
00 = DACOUT7 is OFF
01 = 0.4V (min) to 0.8V (max)
10 = 0.6V (min) to 1.2V (max)
11 = 0.8V (min) to 1.6V (max)
13h
[7:6]
DACOUT8 Range Selection:
00 = DACOUT8 is OFF
01 = 0.4V (min) to 0.8V (max)
10 = 0.6V (min) to 1.2V (max)
11 = 0.8V (min) to 1.6V (max)
MAX16046/MAX16048
Table 16. DACOUT Ranges (continued)
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[1:0]
DACOUT9 Range Selection*:
00 = DACOUT9 is OFF
01 = 0.4V (min) to 0.8V (max)
10 = 0.6V (min) to 1.2V (max)
11 = 0.8V (min) to 1.6V (max)
[3:2]
DACOUT10 Range Selection*:
00 = DACOUT10 is OFF
01 = 0.4V (min) to 0.8V (max)
10 = 0.6V (min) to 1.2V (max)
11 = 0.8V (min) to 1.6V (max)
[5:4]
DACOUT11 Range Selection*:
00 = DACOUT11 is OFF
01 = 0.4V (min) to 0.8V (max)
10 = 0.6V (min) to 1.2V (max)
11 = 0.8V (min) to 1.6V (max)
14h
[7:6]
DACOUT12 Range Selection*:
00 = DACOUT12 is OFF
01 = 0.4V (min) to 0.8V (max)
10 = 0.6V (min) to 1.2V (max)
11 = 0.8V (min) to 1.6V (max)
Table 17. DACOUT Enables
EXTENDED PAGE
ADDRESS DACOUT ENABLES
[0] 1 = DACOUT1 is enabled
[1] 1 = DACOUT2 is enabled
[2] 1 = DACOUT3 is enabled
[3] 1 = DACOUT4 is enabled
[4] 1 = DACOUT5 is enabled
[5] 1 = DACOUT6 is enabled
[6] 1 = DACOUT7 is enabled
1Ch
[7] 1 = DACOUT8 is enabled
[0] 1 = DACOUT9 is enabled*
[1] 1 = DACOUT10 is enabled*
[2] 1 = DACOUT11 is enabled*
[3] 1 = DACOUT12 is enabled*
1Dh
[7:4] Reserved
Table 18. DACOUT Voltages
REGISTER
ADDRESS BIT RANGE DESCRIPTION
00h [7:0] DACOUT1 Data
01h [7:0] DACOUT2 Data
02h [7:0] DACOUT3 Data
03h [7:0] DACOUT4 Data
04h [7:0] DACOUT5 Data
05h [7:0] DACOUT6 Data
06h [7:0] DACOUT7 Data
07h [7:0] DACOUT8 Data
08h [7:0] DACOUT9 Data*
09h [7:0] DACOUT10 Data*
0Ah [7:0] DACOUT11 Data*
0Bh [7:0] DACOUT12 Data*
*
MAX16046 only
*
MAX16046 only
*
MAX16046 only
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 37
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
38 ______________________________________________________________________________________
Voltage Margining
Margining is commonly performed while a system is
under development, but margining can also be per-
formed during the manufacturing process. The supply
voltages of external DC-DC regulators can be adjusted
by trimming the regulator’s reference input (for voltage-
regulator modules), altering the voltage regulator’s
feedback node, or adjusting a “brick” power supply’s
trim input. See the
Applications Information
section for
sample circuits.
Margining can be controlled over the serial interface or by
using GPIO2 and GPIO3. Before adjusting the voltages
using the DAC outputs, enable voltage margining func-
tionality by setting the Margin bit at r4Dh[1] to ‘1’ (see
Table 1) or configure GPIO6 as MARGIN (see Tables 4
and 5). Set DACOUT_ voltages to the appropriate values
and then enable the appropriate DAC outputs.
To control margining with external circuitry, configure
GPIO2 and GPIO3 as MARGINUP and MARGINDN
inputs, respectively. Pull MARGINUP low and pull
MARGINDN high to select DACOUT_ voltage values
set in registers r66h to r71h. Pull MARGINDN low and
pull MARGINUP high to select DACOUT_ values set in
registers r72h to r7Dh (see Tables 19 and 20). Pull both
MARGINUP and MARGINDN high or low to select
DACOUT_ values set in registers r00h to r0Bh.
See Table 16 for more information on setting the volt-
age ranges for the DACOUT_ outputs. Table 20 shows
which register values are used for the DAC outputs for
each state of MARGINUP and MARGINDN.
Table 20. DACOUT Margining Output Dependencies
MARGINUP
(GPIO2)
MARGINDN
(GPIO3) DACOUT REGISTER USED DACOUT SWITCH STATE
1 1 DACOUT registers r00h to r0Bh Depends on r1Ch, r1Dh
1 0 MARGIN DN registers r72h to r7Dh Closed
0 1 MARGIN UP registers r66h to r71h Closed
0 0 DACOUT registers r00h to r0Bh Depends on r1Ch, r1Dh
Table 19. DACOUT1–DACOUT12 Margin Data
REGISTER/
EEPROM
ADDRESS
BIT
RANGE DESCRIPTION
66h [7:0] DACOUT1 Margin-Up Data
67h [7:0] DACOUT2 Margin-Up Data
68h [7:0] DACOUT3 Margin-Up Data
69h [7:0] DACOUT4 Margin-Up Data
6Ah [7:0] DACOUT5 Margin-Up Data
6Bh [7:0] DACOUT6 Margin-Up Data
6Ch [7:0] DACOUT7 Margin-Up Data
6Dh [7:0] DACOUT8 Margin-Up Data
6Eh [7:0] DACOUT9 Margin-Up Data*
6Fh [7:0] DACOUT10 Margin-Up Data*
70h [7:0] DACOUT11 Margin-Up Data*
71h [7:0] DACOUT12 Margin-Up Data*
REGISTER/
EEPROM
ADDRESS
BIT
RANGE DESCRIPTION
72h [7:0] DACOUT1 Margin-Down Data
73h [7:0] DACOUT2 Margin-Down Data
74h [7:0] DACOUT3 Margin-Down Data
75h [7:0] DACOUT4 Margin-Down Data
76h [7:0] DACOUT5 Margin-Down Data
77h [7:0] DACOUT6 Margin-Down Data
78h [7:0] DACOUT7 Margin-Down Data
79h [7:0] DACOUT8 Margin-Down Data
7Ah [7:0] DACOUT9 Margin-Down Data*
7Bh [7:0] DACOUT10 Margin-Down Data*
7Ch [7:0] DACOUT11 Margin-Down Data*
7Dh [7:0] DACOUT12 Margin-Down Data*
*
MAX16046 only
MAX16046/MAX16048
Faults
The MAX16046/MAX16048 monitor the input (MON_)
channels and compare the results with an overvoltage
threshold, an undervoltage threshold, and a selectable
overvoltage or undervoltage early warning threshold.
Based on these conditions, the MAX16046/MAX16048
can assert various fault outputs and save specific infor-
mation about the channel conditions and voltages into
the nonvolatile EEPROM. Once a critical fault event
occurs, the failing channel condition, ADC conversions
at the time of the fault, or both may be saved by config-
uring the event logger. The event logger records a sin-
gle failure in the internal EEPROM and sets a lock bit
which protects the stored fault data from accidental
erasure on a subsequent power-up.
The MAX16046/MAX16048 are capable of measuring
overvoltage and undervoltage fault events. Fault condi-
tions are detected at the end of each ADC conversion.
An overvoltage event occurs when the voltage at a
monitored input exceeds the overvoltage threshold for
that input. An undervoltage fault occurs when the volt-
age at a monitored input falls below the undervoltage
threshold. Fault thresholds are set in registers r23h to
r46h as shown in Table 21. Disabled inputs are not
monitored for fault conditions and are skipped over by
the input multiplexer. Only the upper 8 bits of a conver-
sion result are compared with the programmed fault
thresholds. Inputs not assigned to a sequencing slot
are not monitored for fault conditions but are still
recorded in the ADC results registers.
The general-purpose inputs/outputs (GPIO1–GPIO6)
can be configured as Any_Fault outputs or dedicated
FAULT1 and FAULT2 outputs to indicate fault condi-
tions. These fault outputs are not masked by the critical
fault enable bits shown in Table 23. See the
General-
Purpose Inputs/Outputs
section for more information on
configuring GPIOs as fault outputs.
Table 21. Fault Thresholds
REGISTER/
EEPROM ADDRESS DESCRIPTION
23h MON1 Early Warning Threshold
24h MON1 Overvoltage Threshold
25h MON1 Undervoltage Threshold
26h MON2 Early Warning Threshold
27h MON2 Overvoltage Threshold
28h MON2 Undervoltage Threshold
29h MON3 Early Warning Threshold
2Ah MON3 Overvoltage Threshold
2Bh MON3 Undervoltage Threshold
2Ch MON4 Early Warning Threshold
2Dh MON4 Overvoltage Threshold
2Eh MON4 Undervoltage Threshold
2Fh MON5 Early Warning Threshold
30h MON5 Overvoltage Threshold
31h MON5 Undervoltage Threshold
32h MON6 Early Warning Threshold
33h MON6 Overvoltage Threshold
34h MON6 Undervoltage Threshold
REGISTER/
EEPROM ADDRESS DESCRIPTION
35h MON7 Early Warning Threshold
36h MON7 Overvoltage Threshold
37h MON7 Undervoltage Threshold
38h MON8 Early Warning Threshold
39h MON8 Overvoltage Threshold
3Ah MON8 Undervoltage Threshold
3Bh MON9 Early Warning Threshold*
3Ch MON9 Overvoltage Threshold*
3Dh MON9 Undervoltage Threshold*
3Eh MON10 Early Warning Threshold*
3Fh MON10 Overvoltage Threshold*
40h MON10 Undervoltage Threshold*
41h MON11 Early Warning Threshold*
42h MON11 Overvoltage Threshold*
43h MON11 Undervoltage Threshold*
44h MON12 Early Warning Threshold*
45h MON12 Overvoltage Threshold*
46h MON12 Undervoltage Threshold*
*
MAX16046 only
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 39
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
40 ______________________________________________________________________________________
Deglitch
Fault conditions are detected at the end of each con-
version. If the voltage on an input falls outside a moni-
tored threshold for one acquisition, the input multiplexer
remains on that channel and performs several succes-
sive conversions. To trigger a fault, the input must stay
outside the threshold for a certain number of acquisi-
tions as determined by the deglitch setting in r4Fh[7:6]
(see Table 25).
Fault Flags
Fault flags indicate the fault status of a particular input.
The fault flag of any monitored input in the device can
be read at any time from registers r18h and r19h in the
extended page, as shown in Table 22. Clear a fault flag
by writing a ‘1’ to the appropriate bit in the flag register.
Unlike the fault signals sent to the fault outputs, these
bits are masked by the critical fault enable bits (see
Table 23). The fault flag will only be set if the matching
enable bit in the critical fault enable register is also set.
Critical Faults
If a specific input threshold is critical to the operation of
the system, an automatic fault log can be configured to
shut down all the EN_OUT_s and trigger a transfer of
fault information to EEPROM. For a fault condition to
trigger a critical fault, set the appropriate enable bit in
registers r48h to r4Ch (see Table 23).
Logged fault information is stored in EEPROM registers
r00h to r0Eh (see Table 24). Once a fault log event
occurs, the EEPROM is locked and must be unlocked
to enable a new fault log to be stored. Write a ‘1’ to
r5Dh[1] to unlock the EEPROM. Fault information can
be configured to store ADC conversion results and/or
fault flags in registers r01h and r02h. Select the critical
fault configuration in r47h[1:0]. Set r47h[1:0] to ‘11’ to
turn off the fault logger. All stored ADC results are 8
bits wide.
*
MAX16046 only
Table 22. Fault Flags
EXTENDED PAGE
ADDRESS BIT RANGE DESCRIPTION
[0] 1 = MON1 conversion exceeds overvoltage or undervoltage thresholds
[1] 1 = MON2 conversion exceeds overvoltage or undervoltage thresholds
[2] 1 = MON3 conversion exceeds overvoltage or undervoltage thresholds
[3] 1 = MON4 conversion exceeds overvoltage or undervoltage thresholds
[4] 1 = MON5 conversion exceeds overvoltage or undervoltage thresholds
[5] 1 = MON6 conversion exceeds overvoltage or undervoltage thresholds
[6] 1 = MON7 conversion exceeds overvoltage or undervoltage thresholds
18h
[7] 1 = MON8 conversion exceeds overvoltage or undervoltage thresholds
[0] 1 = MON9 conversion exceeds overvoltage or undervoltage thresholds*
[1] 1 = MON10 conversion exceeds overvoltage or undervoltage thresholds*
[2] 1 = MON11 conversion exceeds overvoltage or undervoltage thresholds*
[3] 1 = MON12 conversion exceeds overvoltage or undervoltage thresholds*
19h
[7:4] Not used
MAX16046/MAX16048
Table 23. Critical Fault Configuration and Enable Bits
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[1:0]
Critical Fault Log Control
00 = Failed lines and ADC conversion values save to EEPROM upon critical fault
01 = Failed line flags only saved to EEPROM upon critical fault
10 = ADC conversion values only saved to EEPROM upon critical fault
11 = No information saved upon critical fault
47h
[7:2] Not used
[0] 1 = Fault log triggered when MON1 is below its undervoltage threshold
[1] 1 = Fault log triggered when MON2 is below its undervoltage threshold
[2] 1 = Fault log triggered when MON3 is below its undervoltage threshold
[3] 1 = Fault log triggered when MON4 is below its undervoltage threshold
[4] 1 = Fault log triggered when MON5 is below its undervoltage threshold
[5] 1 = Fault log triggered when MON6 is below its undervoltage threshold
[6] 1 = Fault log triggered when MON6 is below its undervoltage threshold
48h
[7] 1 = Fault log triggered when MON8 is below its undervoltage threshold
[0] 1 = Fault log triggered when MON9 is below its undervoltage threshold*
[1] 1 = Fault log triggered when MON10 is below its undervoltage threshold*
[2] 1 = Fault log triggered when MON11 is below its undervoltage threshold*
[3] 1 = Fault log triggered when MON12 is below its undervoltage threshold*
[4] 1 = Fault log triggered when MON1 is above its overvoltage threshold
[5] 1 = Fault log triggered when MON2 is above its overvoltage threshold
[6] 1 = Fault log triggered when MON3 is above its overvoltage threshold
49h
[7] 1 = Fault log triggered when MON3 is above its overvoltage threshold
[0] 1 = Fault log triggered when MON5 is above its overvoltage threshold
[1] 1 = Fault log triggered when MON6 is above its overvoltage threshold
[2] 1 = Fault log triggered when MON7 is above its overvoltage threshold
[3] 1 = Fault log triggered when MON8 is above its overvoltage threshold
[4] 1 = Fault log triggered when MON9 is above its overvoltage threshold*
[5] 1 = Fault log triggered when MON10 is above its overvoltage threshold*
[6] 1 = Fault log triggered when MON11 is above its overvoltage threshold*
4Ah
[7] 1 = Fault log triggered when MON12 is above its overvoltage threshold*
[0] 1 = Fault log triggered when MON1 is above/below its early earning threshold
[1] 1 = Fault log triggered when MON2 is above/below its early warning threshold
[2] 1 = Fault log triggered when MON3 is above/below its early warning threshold
[3] 1 = Fault log triggered when MON4 is above/below its early warning threshold
[4] 1 = Fault log triggered when MON5 is above/below its early warning threshold
[5] 1 = Fault log triggered when MON6 is above/below its early warning threshold
[6] 1 = Fault log triggered when MON7 is above/below its early warning threshold
4Bh
[7] 1 = Fault log triggered when MON8 is above/below its early warning threshold
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 41
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
42 ______________________________________________________________________________________
*
MAX16046 only
Table 23. Critical Fault Configuration and Enable Bits (continued)
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[0] 1 = Fault log triggered when MON9 is above/below its early warning threshold*
[1] 1 = Fault log triggered when MON10 is above/below its early warning threshold*
[2] 1 = Fault log triggered when MON11 is above/below its early warning threshold*
[3] 1 = Fault log triggered when MON12 is above/below its early warning threshold*
4Ch
[7:4] Not used
*
MAX16046 only
Table 24. Fault Log EEPROM
EEPROM
ADDRESS BIT RANGE DESCRIPTION
[3:0] Power-Up/Power-Down Fault Register
Slot where
p
ower-u
p
/
p
ower-down fault is detected
[4] Tracking Fault Bits
If ‘0,’ trackin
g
fault occurred on MON1/EN_OUT1/INS1
[5] If ‘0,’ tracking fault occurred on MON2/EN_OUT2/INS2
[6] If ‘0,’ tracking fault occurred on MON3/EN_OUT3/INS3
00h
[7] If ‘0,’ tracking fault occurred on MON4/EN_OUT4/INS4
[0] If ‘1,’ fault occurred on MON1
[1] If ‘1,’ fault occurred on MON2
[2] If ‘1,’ fault occurred on MON3
[3] If ‘1,’ fault occurred on MON4
[4] If ‘1,’ fault occurred on MON5
[5] If ‘1,’ fault occurred on MON6
[6] If ‘1,’ fault occurred on MON7
01h
[7] If ‘1,’ fault occurred on MON8
[0] If ‘1,’ fault occurred on MON9*
[1] If ‘1,’ fault occurred on MON10*
[2] If ‘1,’ fault occurred on MON11*
[3] If ‘1,’ fault occurred on MON12*
02h
[7:4] Not used
03h [7:0]
MON_ ADC Fault Information (only the 8 MSBs of converted channels are saved following
a fault event)
MON1 conversion result at the time the fault lo
g
was tri
gg
ered
04h [7:0] MON2 conversion result at the time the fault log was triggered
05h [7:0] MON3 conversion result at the time the fault log was triggered
06h [7:0] MON4 conversion result at the time the fault log was triggered
07h [7:0] MON5 conversion result at the time the fault log was triggered
08h [7:0] MON6 conversion result at the time the fault log was triggered
09h [7:0] MON7 conversion result at the time the fault log was triggered
0Ah [7:0] MON8 conversion result at the time the fault log was triggered
0Bh [7:0] MON9 conversion result at the time the fault log was triggered*
0Ch [7:0] MON10 conversion result at the time the fault log was triggered*
0Dh [7:0] MON11 conversion result at the time the fault log was triggered*
0Eh [7:0] MON12 conversion result at the time the fault log was triggered*
MAX16046/MAX16048
Power-Up/Power-Down Faults
All EN_OUTs are deasserted if an overvoltage or under-
voltage fault is detected during power-up/power-down
(regardless of the critical fault enable bits). Under these
conditions, information of the failing slot is stored in
EEPROM r00h[3:0] unless r47h[1:0] is set to ‘11’ (see
Table 23).
If there is a tracking fault on a channel configured for
closed-loop tracking, a fault log operation occurs and
the bits representing the failed tracking channels are
set to ‘0’ unless r47h[1:0] is set to ‘11’ (see Table 24).
Autoretry/Latch Mode
For critical faults, the MAX16046/MAX16048 can be
configured for one of two fault management methods:
autoretry or latch-on-fault. Set r4Fh[3] to ‘0’ to select
autoretry mode. In this configuration, the device will
shut down after a critical fault event then restart follow-
ing a configurable delay. Use r4Fh[2:0] to select an
autoretry delay from 20µs to 1.6s. See Table 25 for
more information on setting the autoretry delay.
Set r4Fh[3] to ‘1’ to select the latch-on-fault mode. In
this configuration EN_OUT_s are deasserted after a
critical fault event. The device does not re-initiate the
power-up sequence until EN is toggled or the Software
Enable bit is reset to ‘0.’ See the
Enable
section for
more information on setting the Software Enable bit.
If fault information is stored in EEPROM (see the
Critical
Faults
section) and autoretry mode is selected, set an
autoretry delay greater than the time required for the
storing operation. If fault information is stored in
EEPROM and latch-on-fault mode is chosen, toggle EN
or reset the Software Enable bit only after the comple-
tion of the storing operation. If saving information about
the failed lines only, ensure a delay of at least 60ms
before the restart procedure. Otherwise, ensure a mini-
mum 204ms timeout. This ensures that ADC conver-
sions are completed and values are stored correctly in
EEPROM. See Table 26 for more information about
required fault log operation periods.
Table 25. Fault Recovery Configuration
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[2:0]
Autoretry Delay
000 = 20µs
001 = 12.5ms
010 = 25ms
011 = 50ms
100 = 100ms
101 = 200ms
110 = 400ms
111 = 1.6s
[3]
Fault Recovery Mode
0 = Autoretry procedure is performed following a fault event
1 = Latchoff on fault
[5:4]
Slew Rate
00 = 800V/s
01 = 400V/s
10 = 200V/s
11 = 100V/s
4Fh
[7:6]
Fault Deglitch
00 = 2 conversions
01 = 4 conversions
10 = 8 conversions
11 = 16 conversions
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 43
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
44 ______________________________________________________________________________________
RESET
The reset output, RESET, is asserted during power-
up/power-down and deasserts following the reset time-
out period once the power-up sequence is complete.
The power-up sequence is complete when any MON_
inputs assigned to Slot 12 exceed their undervoltage
thresholds. If no MON_ inputs are assigned to Slot 12,
the power-up sequence is complete after the slot
sequence delay is expired.
RESET is a configurable output that monitors selected
MON_ voltages during normal operation. RESET also
depends on any monitoring input that has one or more
critical fault enable bits set. Use r19h[1:0] to configure
RESET to assert on an overvoltage fault, undervoltage
fault, or both. Use r19h[3:2] to configure RESET as an
active-high/active-low push-pull/open-drain output. If
desired, configure GPIO4 as a manual reset input, MR,
and pull MR low to assert RESET. RESET includes a
programmable timeout. See Table 27 for RESET depen-
dencies and configuration registers.
Table 26. EEPROM Fault Log Operation Period
FAULT CONTROL
REGISTER
r47h[1:0]
DESCRIPTION MINIMUM REQUIRED SHUTDOWN PERIOD
(ms)
00 Failed lines and ADC values saved 204
01 Failed lines saved 60
10 ADC values saved 168
11 No information saved N/A
Table 27. RESET Configuration and Dependencies
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[1:0]
RESET OUTPUT CONFIGURATION
00 = RESET is asserted if at least one of the selected inputs exceeds its undervoltage
threshold
01 = RESET is asserted if at least one of the selected inputs exceeds its early warning
threshold
10 = RESET is asserted if at least one of the selected inputs exceeds its overvoltage threshold
11 = RESET is asserted if any of the selected inputs exceeds undervoltage or overvoltage
thresholds
[2] 0 = RESET is an active-low output
1 = RESET is an active-high output
[3] 0 = RESET is a push-pull output
1 = RESET is an open-drain output
[6:4]
RESET TIMEOUT
000 = 25µs
001 = 2ms
010 = 25ms
011 = 100ms
100 = 200ms
101 = 400ms
110 = 800ms
111 = 1600ms
19h
[7] Reserved
MAX16046/MAX16048
Watchdog Timer
The watchdog timer can operate together with or inde-
pendently of the MAX16046/MAX16048. When operat-
ing in dependent mode, the watchdog is not activated
until the sequencing is complete and RESET is de-
asserted. When operating in independent mode, the
watchdog timer is independent of the sequencing oper-
ation and activates immediately after VCC exceeds the
UVLO threshold and the boot phase is complete. Set
r4Dh[3] to ‘0’ to configure the watchdog in dependent
mode. Set r4Dh[3] to ‘1’ to configure the watchdog in
independent mode. See Table 28 for more information
on configuring the watchdog timer in dependent or
independent mode.
Dependent Watchdog Timer Operation
The watchdog timer can be used to monitor µP activity
in two modes. Flexible timeout architecture provides an
adjustable watchdog startup delay of up to 128s, allow-
ing complicated systems to complete lengthy boot-up
routines. An adjustable watchdog timeout allows the
supervisor to provide quick alerts when processor
activity fails. After each reset event (VCC drops below
UVLO then returns above UVLO, software reboot, man-
ual reset (MR), EN input going low then high, or watch-
dog reset) and once sequencing is complete, the
watchdog startup delay provides an extended time for
the system to power up and fully initialize all µP and
system components before assuming responsibility for
routine watchdog updates. Set r55h[6] to ‘1’ to enable
the watchdog startup delay. Set r55h[6] to ‘0’ to disable
the watchdog startup delay.
The normal watchdog timeout period, tWDI, begins after
the first transition on WDI before the conclusion of the
long startup watchdog period, tWDI_STARTUP (Figures 6
and 7). During the normal operating mode, WDO
asserts if the µP does not toggle WDI with a valid transi-
tion (high-to-low or low-to-high) within the standard
timeout period, tWDI. WDO remains asserted until WDI
is toggled or RESET is asserted (Figure 7).
While EN is low, or r55h[7] is a ‘0,’ the watchdog timer is
in reset. The watchdog timer does not begin counting until
the power-on mode is reached and RESET is deasserted.
The watchdog timer is reset and WDO deasserts any time
RESET is asserted (Figure 8). The watchdog timer will be
held in reset while RESET is asserted.
The watchdog can be configured to control the RESET
output as well as the WDO output. RESET is pulsed low
for the reset timeout, tRP, when the watchdog timer
expires and the Watchdog Reset Output Enable bit
(r55h[7]) is set to ‘1.’ Therefore, WDO pulses low for a
short time (approximately 1µs) when the watchdog timer
expires. RESET is not affected by the watchdog timer
when the Watchdog Reset Output Enable bit (r55h[7]) is
set to ‘0.’
See Table 29 for more information on configuring
watchdog functionality.
*
MAX16046 only
Table 27. RESET Configuration and Dependencies (continued)
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[0] RESET DEPENDENCIES
1 = RESET is dependent on MON1
[1] 1 = RESET is dependent on MON2
[2] 1 = RESET is dependent on MON3
[3] 1 = RESET is dependent on MON4
[4] 1 = RESET is dependent on MON5
[5] 1 = RESET is dependent on MON6
[6] 1 = RESET is dependent on MON7
1Ah
[7] 1 = RESET is dependent on MON8
[0] 1 = RESET is dependent on MON9*
[1] 1 = RESET is dependent on MON10*
[2] 1 = RESET is dependent on MON11*
[3] 1 = RESET is dependent on MON12*
1Bh
[7:4] Reserved
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 45
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
46 ______________________________________________________________________________________
LAST MON_
WDI
VTH
tWDI_STARTUP
< tWDI
tRP
RESET
< tWDI
Figure 6. Normal Watchdog Startup Sequence
WDI
WDO
0V
VCC
0V
VCC
< tWDI < tWDI < tWDI < tWDI
> tWDI
< tWDI < tWDI
tWDI
Figure 7. Watchdog Timer Operation
WDI
WDO
0V
0V
VCC
VCC
0V
VCC
< tWDI
1µs
RESET
< tWDI
tWDI tRP < tWDI_STARTUP
Figure 8. Watchdog Startup Sequence with Watchdog Reset Output Enable Bit (r55h[7]) Set to ‘1’
MAX16046/MAX16048
Table 28. Watchdog Mode Selection
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
0
Software Enable Bit
0 = Enabled. EN must also be high to begin sequencing.
1 = Disabled (factory default)
1
Margin Bit
1 = Margin functionality is enabled
0 = Margin disabled
2
Early Warning Selection Bit
0 = Early warning thresholds are undervoltage thresholds
1 = Early warning thresholds are overvoltage thresholds
3
Watchdog Mode Selection Bit
0 = Watchdog timer is in dependent mode
1 = Watchdog timer is in independent mode
4Dh
[7:4] Not used
Table 29. Watchdog Enables and Configuration
REGISTER/ EEPROM
ADDRESS BIT RANGE DESCRIPTION
[2:0]
Watchdog Timeout
000 = 1ms
001 = 4ms
010 = 12.5ms
011 = 50ms
100 = 200ms
101 = 800ms
110 = 1.6s
111 = 3.2s
[4:3]
Watchdog Startup Delay
00 = 25.6s
01 = 51.2s
10 = 102.4s
11 = 128s
[5]
Watchdog Enable
1 = Watchdog enabled
0 = Watchdog disabled
[6]
Watchdog Startup Delay Enable
1 = Watchdog startup delay enabled
0 = Watchdog startup delay disabled
55h
[7]
Watchdog Reset Output Enable
1 = Watchdog timeout asserts RESET output
0 = Watchdog timeout does not assert RESET output
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 47
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
48 ______________________________________________________________________________________
Independent Watchdog Timer Operation
When r4Dh[3] is ‘1’ the watchdog timer operates in the
independent mode. In the independent mode, the
watchdog timer operates as if it were a separate chip.
The watchdog timer is activated immediately upon VCC
exceeding UVLO and once the boot-up sequence is
finished. If RESET is asserted by the sequencer state
machine, the watchdog timer and WDO will not be
affected.
There will be a long startup delay if r55h[6] is a ‘1.’ If
r55h[6] is a ‘0,’ there will not be a long startup delay.
In independent mode, if the Watchdog Reset Output
Enable bit r55h[7] is set to ‘1,’ when the watchdog timer
expires, WDO will be asserted then RESET will be
asserted. WDO will then be deasserted. WDO will be
low for 3 system clock cycles or approximately 1µs. If
the Watchdog Reset Output Enable bit (r55h[7]) is set
to ‘0,’ when the WDT expires, WDO will be asserted but
RESET will not be affected.
Miscellaneous
Table 30 lists several miscellaneous programmable
items. Register r5Ch provides storage space for a user-
defined configuration or firmware version number. Bit
r5Dh[0] locks and unlocks the configuration registers.
Bit r5Dh[1] locks and unlocks EEPROM addresses 00h
to 11h. Write data to EEPROM r5Dh as normally done;
however, to toggle a bit in register r5Dh, write a ‘1’ to
that bit. The r65h[2:0] bits contain a read-only manufac-
turing revision code.
Table 30. Miscellaneous Settings
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
5Ch [7:0] User identification. Eight bits of memory for user-defined identification.
[0]
Configuration Lock
0 = Configuration registers and EEPROM writable.
1 = Configuration registers and EEPROM [except r5Dh] locked.
[1]
EEPROM Fault Data Lock Flag (set automatically after fault log is triggered):
0 = EEPROM is not locked. A triggered fault log stores fault information to EEPROM.
1 = EEPROM addresses 00h to 11h are locked. Write a ‘1’ to this bit to toggle the flag.
5Dh
[7:2] Not used
[2:0] Manufacturing revision code. This register is read only. Not stored in EEPROM.
65h [7:3] Not used
MAX16046/MAX16048
I2C/SMBus-Compatible
Serial Interface
The MAX16046/MAX16048 feature an I2C/SMBus-com-
patible 2-wire serial interface consisting of a serial data
line (SDA) and a serial clock line (SCL). SDA and SCL
facilitate bidirectional communication between the
MAX16046/MAX16048 and the master device at clock
rates up to 400kHz. Figure 1 shows the 2-wire interface
timing diagram. The MAX16046/MAX16048 are trans-
mit/receive slave-only devices, relying upon a master
device to generate a clock signal. The master device
(typically a microcontroller) initiates a data transfer on
the bus and generates SCL to permit that transfer.
A master device communicates to the MAX16046/
MAX16048 by transmitting the proper address followed
by command and/or data words. The slave address
input, A0, is capable of detecting four different states,
allowing multiple identical devices to share the same seri-
al bus. The slave address is described further in the
Slave Address
section. Each transmit sequence is framed
by a START (S) or REPEATED START (SR) condition and
a STOP (P) condition. Each word transmitted over the bus
is 8 bits long and is always followed by an acknowledge
pulse. SCL is a logic input, while SDA is an open-drain
input/output. SCL and SDA both require external pullup
resistors to generate the logic-high voltage. Use 4.7kfor
most applications.
Bit Transfer
Each clock pulse transfers one data bit. The data on
SDA must remain stable while SCL is high (Figure 9);
otherwise the MAX16046/MAX16048 registers a START
or STOP condition (Figure 10) from the master. SDA
and SCL idle high when the bus is not busy.
START and STOP Conditions
Both SCL and SDA idle high when the bus is not busy.
A master device signals the beginning of a transmis-
sion with a START condition by transitioning SDA from
high to low while SCL is high. The master device issues
a STOP condition by transitioning SDA from low to high
while SCL is high. A STOP condition frees the bus for
another transmission. The bus remains active if a
REPEATED START condition is generated, such as in
the block read protocol (see Figure 1).
Early STOP Conditions
The MAX16046/MAX16048 recognize a STOP condition
at any point during transmission except if a STOP condi-
tion occurs in the same high pulse as a START condition.
This condition is not a legal I2C format; at least one clock
pulse must separate any START and STOP condition.
REPEATED START Conditions
A REPEATED START may be sent instead of a STOP
condition to maintain control of the bus during a read
operation. The START and REPEATED START condi-
tions are functionally identical.
DATA LINE STABLE,
DATA VALID
SDA
SCL
CHANGE OF
DATA ALLOWED
Figure 9. Bit Transfer
PS
START
CONDITION
SDA
SCL
STOP
CONDITION
Figure 10. START and STOP Conditions
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 49
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
50 ______________________________________________________________________________________
Acknowledge
The acknowledge bit (ACK) is the 9th bit attached to
any 8-bit data word. The receiving device always gen-
erates an ACK. The MAX16046/MAX16048 generate an
ACK when receiving an address or data by pulling SDA
low during the 9th clock period (Figure 11). When
transmitting data, such as when the master device
reads data back from the MAX16046/MAX16048, the
device waits for the master device to generate an ACK.
Monitoring ACK allows for detection of unsuccessful
data transfers. An unsuccessful data transfer occurs if
the receiving device is busy or if a system fault has
occurred. In the event of an unsuccessful data transfer,
the bus master should reattempt communication at a
later time. The MAX16046/MAX16048 generate a NACK
after the command byte received during a software
reboot, while writing to the EEPROM, or when receiving
an illegal memory address.
Slave Address
Use the slave address input, A0, to allow multiple identi-
cal devices to share the same serial bus. Connect A0 to
GND, DBP (or an external supply voltage greater than
2V), SCL, or SDA to set the device address on the bus.
See Table 31 for a listing of all possible 7-bit addresses.
SCL
1
S
289
SDA BY
TRANSMITTER
SDA BY
RECEIVER
CLOCK PULSE FOR ACKNOWLEDGE
NACK
ACK
Figure 11. Acknowledge
Table 31. Setting the I2C/SMBus Slave
Address
A0 SLAVE ADDRESS
0 1010 00XR
1 1010 01XR
SCL 1010 10XR
SDA 1010 11XR
X = Don’t care, R = Read/write select bit
MAX16046/MAX16048
Send Byte
The send byte protocol allows the master device to
send one byte of data to the slave device (see Figure
12). The send byte presets a register pointer address
for a subsequent read or write. The slave sends a
NACK instead of an ACK if the master tries to send a
memory address or command code that is not allowed.
If the master sends 94h or 95h, the data is ACK,
because this could be the start of the write block or
read block. If the master sends a STOP condition
before the slave asserts an ACK, the internal address
pointer does not change. If the master sends 96h, this
signifies a software reboot. The send byte procedure is
the following:
1) The master sends a START condition.
2) The master sends the 7-bit slave address and a
write bit (low).
3) The addressed slave asserts an ACK on SDA.
4) The master sends an 8-bit memory address or com-
mand code.
5) The addressed slave asserts an ACK (or NACK) on
SDA.
6) The master sends a STOP condition.
Receive Byte
The receive byte protocol allows the master device to
read the register content of the MAX16046/MAX16048
(see Figure 12). The EEPROM or register address must
be preset with a send byte or write word protocol first.
Once the read is complete, the internal pointer increas-
es by one. Repeating the receive byte protocol reads
the contents of the next address. The receive byte pro-
cedure follows:
1) The master sends a START condition.
2) The master sends the 7-bit slave address and a
read bit (high).
3) The addressed slave asserts an ACK on SDA.
4) The slave sends 8 data bits.
5) The master asserts a NACK on SDA.
6) The master generates a STOP condition.
Write Byte
The write byte protocol (see Figure 12) allows the mas-
ter device to write a single byte in the default page,
extended page, or EEPROM page, depending on
which page is currently selected. The write byte proce-
dure is the following:
1) The master sends a START condition.
2) The master sends the 7-bit slave address and a
write bit (low).
3) The addressed slave asserts an ACK on SDA.
4) The master sends an 8-bit memory address.
5) The addressed slave asserts an ACK on SDA.
6) The master sends an 8-bit data byte.
7) The addressed slave asserts an ACK on SDA.
8) The master sends a STOP condition.
To write a single byte, only the 8-bit memory address
and a single 8-bit data byte are sent. The data byte is
written to the addressed location if the memory address
is valid. The slave will assert a NACK at step 5 if the
memory address is not valid.
Read Byte
The read byte protocol (see Figure 12) allows the mas-
ter device to read a single byte located in the default
page, extended page, or EEPROM page depending on
which page is currently selected. The read byte proce-
dure is the following:
1) The master sends a START condition.
2) The master sends the 7-bit slave address and a
write bit (low).
3) The addressed slave asserts an ACK on SDA.
4) The master sends an 8-bit memory address.
5) The addressed slave asserts an ACK on SDA.
6) The master sends a REPEATED START condition.
7) The master sends the 7-bit slave address and a
read bit (high).
8) The addressed slave asserts an ACK on SDA.
9) The slave sends an 8-bit data byte.
10) The master asserts a NACK on SDA.
11) The master sends a STOP condition.
If the memory address is not valid, it is NACKed by the
slave at step 5 and the address pointer is not modified.
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 51
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
52 ______________________________________________________________________________________
Command Codes
The MAX16046/MAX16048 use eight command codes
for block read, block write, and other commands. See
Table 32 for a list of command codes.
To initiate a software reboot, send 96h using the send
byte format. A software-initiated reboot is functionally the
same as a hardware-initiated power-on reset. During
boot-up, EEPROM configuration data in the range of 0Fh
to 7Dh is copied to the same register addresses in the
default page.
Send command code 97h to trigger a fault store to
EEPROM. Configure the Critical Fault Log Control register
(r47h) to store ADC conversion results and/or fault flags
in registers once the command code has been sent.
Using command code 98h allows access to the extend-
ed page, which contains registers for ADC conversion
results, DACOUT enables, and GPIO input/output data.
Use command code 99h to return to the default page.
Send command code 9Ah to access the EEPROM
page. Once command code 9Ah has been sent, all
addresses are recognized as EEPROM addresses only.
Send command code 9Bh to return to the default page.
When accessing any EEPROM location using a read
byte or block read protocol, set the address to the
desired location, send a dummy read byte protocol,
and then set the address to the desired location again.
This primes the device for subsequent read operations.
Block Write
The block write protocol (see Figure 12) allows the
master device to write a block of data (1 byte to 16
bytes) to memory. The destination address should be
preloaded by a previous send byte command; other-
wise the block write command begins to write at the
current address pointer. After the last byte is written,
the address pointer remains preset to the next valid
address. If the number of bytes to be written causes
the address pointer to exceed FFh for EEPROM or 7Dh
for configuration registers, the address pointer stays at
FFh or 7Dh, overwriting this memory address with the
remaining bytes of data. The last data byte sent is
stored at register address FFh. The slave generates a
NACK at step 5 if the command code is invalid or if the
device is busy, and the address pointer is not altered.
The block write procedure is the following:
1) The master sends a START condition.
2) The master sends the 7-bit slave address and a
write bit (low).
3) The addressed slave asserts an ACK on SDA.
4) The master sends the 8-bit command code for
block write (94h).
5) The addressed slave asserts an ACK on SDA.
6) The master sends the 8-bit byte count (1 byte to 16
bytes),
n
.
7) The addressed slave asserts an ACK on SDA.
8) The master sends 8 bits of data.
9) The addressed slave asserts an ACK on SDA.
10) Repeat steps 8 and 9
n
- 1 times.
11) The master sends a STOP condition.
Block Read
The block read protocol (see Figure 12) allows the
master device to read a block of up to 16 bytes from
memory. Read fewer than 16 bytes of data by issuing
an early STOP condition from the master, or by gener-
ating a NACK with the master. The destination address
should be preloaded by a previous send byte com-
mand; otherwise the block read command begins to
read at the current address pointer. If the number of
bytes to be read causes the address pointer to exceed
FFh for the configuration register or EEPROM, the
address pointer stays at FFh and the last data byte
read is from register rFFh. The block read procedure is
the following:
1) The master sends a START condition.
2) The master sends the 7-bit slave address and a
write bit (low).
3) The addressed slave asserts an ACK on SDA.
4) The master sends 8 bits of the block read com-
mand (95h).
5) The slave asserts an ACK on SDA, unless busy.
6) The master generates a REPEATED START condition.
7) The master sends the 7-bit slave address and a
read bit (high).
Table 32. Command Codes
COMMAND CODE ACTION
94h Write block
95h Read block
96h Reboot EEPROM in register file
97h Trigger fault store to EEPROM
98h Extended page access on
99h Extended page access off
9Ah EEPROM page access on
9Bh EEPROM page access off
MAX16046/MAX16048
8) The slave asserts an ACK on SDA.
9) The slave sends the 8-bit byte count (16).
10) The master asserts an ACK on SDA.
11) The slave sends 8 bits of data.
12) The master asserts an ACK on SDA.
13) Repeat steps 11 and 12 up to fifteen times.
14) The master asserts a NACK on SDA.
15) The master sends a STOP condition.
READ BYTE FORMAT
SSLAVE
ADDRESS
SLAVE
ADDRESS
ACK COMMAND ACK SR ACK DATA BYTE NACK P
7 BITS 8 BITS 7 BITS 8 BITS
COMMAND BYTE:
PREPARES DEVICE
FOR FOLLOWING
READ.
DATA BYTE: DATA COMES
FROM THE REGISTER SET BY
THE COMMAND BYTE.
01
BLOCK WRITE FORMAT
S ADDRESS ACK COMMAND ACK BYTE
COUNT= N ACK DATA BYTE
1ACK DATA BYTE
... ACK DATA BYTE
NACK P
7 BITS 8 BITS 8 BITS 8 BITS 8 BITS
COMMAND BYTE:
DESTINATION
ADDRESS
DATA BYTE: DATA GOES INTO THE REGISTER SET BY THE
COMMAND
8 BITS
0
BLOCK READ FORMAT
S ADDRESS ACK COMMAND ACK SR ADDRESS ACK BYTE
COUNT= N ACK ACK ACK NACK P
7 BITS 8 BITS 7 BITS 8 BITS 8 BITS
8 BITS 8 BITS
COMMAND BYTE:
PREPARES DEVICE
FOR BLOCK
OPERATION.
DATA BYTE: DATA IS READ FROM THE REGISTER (OR
EEPROM LOCATION) SET BY THE COMMAND CODE
01
SLAVE TO MASTER
MASTER TO SLAVE
S ADDRESS
7 BITS
SEND BYTE FORMAT
WR ACK DATA
8 BITS
ACK P
DATA BYTE: PRESETS THE
INTERNAL ADDRESS POINTER
OR REPRESENTS A COMMAND.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
DATA BYTE: PRESETS THE
INTERNAL ADDRESS POINTER
OR REPRESENTS A COMMAND.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
0
WRITE BYTE FORMAT
SADDRESS ACK COMMAND ACK DATA ACK P
7 BITS 8 BITS 8 BITS
COMMAND BYTE:
SELECTS REGISTER OR
EEPROM LOCATION
YOU ARE WRITING TO.
DATA BYTE: DATA GOES INTO THE
REGISTER (OR EEPROM LOCATION)
SET BY THE COMMAND BYTE.
0
S = START CONDITION
P = STOP CONDITION
SR = REPEATED START CONDITION
D.C. = DON'T CARE
ACK = ACKNOWLEDGE, SDA PULLED LOW DURING RISING EDGE OF SCL
NACK = NOT ACKNOWLEGE, SDA LEFT HIGH DURING RISING EDGE OF SCL
ALL DATA IS CLOCKED IN/OUT OF THE DEVICE ON RISING EDGES OF SCL
= SDA TRANSISTIONS FROM HIGH TO LOW DURING PERIOD OF SCL
= SDA TRANSISTIONS FROM LOW TO HIGH DURING PERIOD OF SCL
S ADDRESS
7 BITS
RECEIVE BYTE FORMAT
WR
WR
WR
WR
WR WR
WR
ACK DATA
8 BITS
NACK P
1
DATA BYTE
1
DATA BYTE
...
DATA BYTE
N
Figure 12. I2C/SMBus Protocols
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 53
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
54 ______________________________________________________________________________________
JTAG Serial Interface
The MAX16046/MAX16048 contain a JTAG port that
complies with a subset of the IEEE 1149.1 specifica-
tion. Either the I2C or the JTAG interface may be used
to access internal memory; however, only one interface
is allowed to run at a time. The MAX16046/MAX16048
do not support IEEE 1149.1 boundary-scan functionali-
ty. The MAX16046/MAX16048 contain extra JTAG
instructions and registers not included in the JTAG
specification that provide access to internal memory.
The extra instructions include LOAD ADDRESS, WRITE,
READ, REBOOT, SAVE, and USERCODE.
TEST ACCESS PORT
(TAP) CONTROLLER
INSTRUCTION REGISTER
[LENGTH = 5 BITS]
BYPASS REGISTER
[LENGTH = 1 BIT]
IDENTIFICATION REGISTER
[LENGTH = 32 BITS]
USER CODE REGISTER
[LENGTH = 32 BITS]
MEMORY ADDRESS REGISTER
[LENGTH = 8 BITS]
MEMORY READ REGISTER
[LENGTH = 8 BITS]
MEMORY WRITE REGISTER
[LENGTH = 8 BITS]
11111
00000
00011
00100
00101
00110
00111
MUX 2 TDO
TDI
TMS
TCK
01000
REGISTERS
AND EEPROM
01001
01010
01011
01100
MUX 1
00111
01000
01001
01010
01011
01100
REBOOT
SAVE
SETEXTRAM
SETEEPADD
RSTEXTRAM
RSTEEPADD
COMMAND
DECODER
RPU
VDB
Figure 13. JTAG Block Diagram
MAX16046/MAX16048
Test Access Port (TAP)
Controller State Machine
The TAP controller is a finite state machine that
responds to the logic level at TMS on the rising edge of
TCK. See Figure 14 for a diagram of the finite state
machine. The possible states are described below:
Test-Logic-Reset: At power-up, the TAP controller is in
the test-logic-reset state. The instruction register con-
tains the IDCODE instruction. All system logic of the
device operates normally. This state can be reached
from any state by driving TMS high for five clock cycles.
Run-Test/Idle: The run-test/idle state is used between
scan operations or during specific tests. The instruction
register and test data registers remain idle.
Select-DR-Scan: All test data registers retain their pre-
vious state. With TMS low, a rising edge of TCK moves
the controller into the capture-DR state and initiates a
scan sequence. TMS high during a rising edge on TCK
moves the controller to the select-IR-scan state.
Capture-DR: Data can be parallel-loaded into the test
data registers selected by the current instruction. If the
instruction does not call for a parallel load or the select-
ed test data register does not allow parallel loads, the
test data register remains at its current value. On the
rising edge of TCK, the controller goes to the shift-DR
state if TMS is low or it goes to the exit1-DR state if TMS
is high.
TEST-LOGIC-RESET
1
111
0
0
RUN-TEST/IDLE
0
0
0
0
1
1
1
0
0
1
0
1
1
0
10
1
SELECT-DR-SCAN SELECT-IR-SCAN
CAPTURE-DR CAPTURE-IR
SHIFT-DR SHIFT-IR
EXIT1-DR EXIT1-IR
PAUSE-DR PAUSE-IR
EXIT2-DR EXIT2-IR
UPDATE-DR UPDATE-IR
0
0
0
0
1
1
0
1
1
Figure 14. TAP Controller State Diagram
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 55
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
56 ______________________________________________________________________________________
Shift-DR: The test data register selected by the current
instruction connects between TDI and TDO and shifts
data one stage toward its serial output on each rising
edge of TCK while TMS is low. On the rising edge of TCK,
the controller goes to the exit1-DR state if TMS is high.
Exit1-DR: While in this state, a rising edge on TCK puts
the controller in the update-DR state. A rising edge on
TCK with TMS low puts the controller in the pause-DR
state.
Pause-DR: Shifting of the test data registers halts while
in this state. All test data registers retain their previous
state. The controller remains in this state while TMS is
low. A rising edge on TCK with TMS high puts the con-
troller in the exit2-DR state.
Exit2-DR: A rising edge on TCK with TMS high while in
this state puts the controller in the update-DR state. A
rising edge on TCK with TMS low enters the shift-DR
state.
Update-DR: A falling edge on TCK while in the update-
DR state latches the data from the shift register path of
the test data registers into a set of output latches. This
prevents changes at the parallel output because of
changes in the shift register. On the rising edge of TCK,
the controller goes to the run-test/idle state if TMS is
low or goes to the select-DR-scan state if TMS is high.
Select-IR-Scan: All test data registers retain their previ-
ous states. The instruction register remains unchanged
during this state. With TMS low, a rising edge on TCK
moves the controller into the capture-IR state. TMS high
during a rising edge on TCK puts the controller back
into the test-logic-reset state.
Capture-IR: Use the capture-IR state to load the shift
register in the instruction register with a fixed value.
This value is loaded on the rising edge of TCK. If TMS
is high on the rising edge of TCK, the controller enters
the exit1-IR state. If TMS is low on the rising edge of
TCK, the controller enters the shift-IR state.
Shift-IR: In this state, the shift register in the instruction
register connects between TDI and TDO and shifts
data one stage for every rising edge of TCK toward the
TDO serial output while TMS is low. The parallel outputs
of the instruction register as well as all test data regis-
ters remain at their previous states. A rising edge on
TCK with TMS high moves the controller to the exit1-IR
state. A rising edge on TCK with TMS low keeps the
controller in the shift-IR state while moving data one
stage through the instruction shift register.
Exit1-IR: A rising edge on TCK with TMS low puts the
controller in the pause-IR state. If TMS is high on the
rising edge of TCK, the controller enters the update-IR
state.
Pause-IR: Shifting of the instruction shift register halts
temporarily. With TMS high, a rising edge on TCK puts
the controller in the exit2-IR state. The controller
remains in the pause-IR state if TMS is low during a ris-
ing edge on TCK.
Exit2-IR: A rising edge on TCK with TMS high puts the
controller in the update-IR state. The controller loops
back to shift-IR if TMS is low during a rising edge of
TCK in this state.
Update-IR: The instruction code that has been shifted
into the instruction shift register latches to the parallel
outputs of the instruction register on the falling edge of
TCK as the controller enters this state. Once latched,
this instruction becomes the current instruction. A rising
edge on TCK with TMS low puts the controller in the
run-test/idle state. With TMS high, the controller enters
the select-DR-scan state.
Instruction Register
The instruction register contains a shift register as well
as a latched parallel output and is 5 bits in length. When
the TAP controller enters the shift-IR state, the instruc-
tion shift register connects between TDI and TDO. While
in the shift-IR state, a rising edge on TCK with TMS low
shifts the data one stage toward the serial output at
TDO. A rising edge on TCK in the exit1-IR state or the
exit2-IR state with TMS high moves the controller to the
update-IR state. The falling edge of that same TCK
latches the data in the instruction shift register to the
instruction register parallel output. Instructions support-
ed by the MAX16046/MAX16048 and the respective
operational binary codes are shown in Table 33.
MAX16046/MAX16048
USERCODE: When the USERCODE instruction latches
into the parallel instruction register, the user-code data
register is selected. The device user-code loads into
the user-code data register on the rising edge of TCK
following entry into the capture-DR state. Shift-DR can
be used to shift the user-code out serially through TDO.
See Table 35. This instruction may be used to help
identify multiple MAX16046/MAX16048 devices con-
nected in a JTAG chain.
BYPASS: When the BYPASS instruction is latched into
the instruction register, TDI connects to TDO through
the 1-bit bypass test data register. This allows data to
pass from TDI to TDO without affecting the device’s
normal operation.
IDCODE: When the IDCODE instruction is latched into
the parallel instruction register, the identification data
register is selected. The device identification code is
loaded into the identification data register on the rising
edge of TCK following entry into the capture-DR state.
Shift-DR can be used to shift the identification code out
serially through TDO. During test-logic-reset, the
IDCODE instruction is forced into the instruction regis-
ter. The identification code always has a ‘1’ in the LSB
position. The next 11 bits identify the manufacturer’s
JEDEC number and number of continuation bytes fol-
lowed by 16 bits for the device and 4 bits for the ver-
sion. See Table 34.
Table 33. JTAG Instruction Set
Table 34. 32-Bit Identification Code
INSTRUCTION HEX CODE SELECTED REGISTER/ACTION
BYPASS 1Fh Bypass. Mandatory instruction code.
IDCODE 00h Manufacturer ID code and part number
USERCODE 03h User code (user-defined ID)
LOAD ADDRESS 04h Load address register content
READ DATA 05h Memory read
WRITE DATA 06h Memory write
REBOOT 07h Resets the device
SAVE 08h Stores current fault information in EEPROM
SETEXTRAM 09h Extended page access on
RSTEXTRAM 0Ah Extended page access off
SETEEPADD 0Bh EEPROM page access on
RSTEEPADD 0Ch EEPROM page access off
MSB LSB
Version (4 bits) Device ID (16 bits) Manufacturer ID (11 bits) Fixed value (1 bit)
0000 0000000000000001 00011001011 1
Table 35. 32-Bit User-Code Data
MSB LSB
D.C. (don’t cares) I2C/SMBus
slave address User identification (firmware version)
00000000000000000 See Table 31 r5Ch[7:0] contents
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 57
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
58 ______________________________________________________________________________________
LOAD ADDRESS: This is an extension to the standard
IEEE 1149.1 instruction set to support access to the
memory in the MAX16046/MAX16048. When the LOAD
ADDRESS instruction latches into the instruction regis-
ter, TDI connects to TDO through the 8-bit memory
address test data register during the shift-DR state.
READ DATA: This is an extension to the standard IEEE
1149.1 instruction set to support access to the memory
in the MAX16046/MAX16048. When the READ instruc-
tion latches into the instruction register, TDI connects to
TDO through the 8-bit memory read test data register
during the shift-DR state.
WRITE DATA: This is an extension to the standard
IEEE 1149.1 instruction set to support access to the
memory in the MAX16046/MAX16048. When the WRITE
instruction latches into the instruction register, TDI con-
nects to TDO through the 8-bit memory write test data
register during the shift-DR state.
REBOOT: This is an extension to the standard IEEE
1149.1 instruction set to initiate a software controlled
reset to the MAX16046/MAX16048. When the REBOOT
instruction latches into the instruction register, the
MAX16046/MAX16048 resets and immediately begins
the boot-up sequence.
SAVE: This is an extension to the standard IEEE 1149.1
instruction set that triggers a fault log. The current ADC
conversion results along with fault information are
saved to EEPROM depending on the configuration of
the Critical Fault Log Control register (r47h).
SETEXTRAM: This is an extension to the standard
IEEE 1149.1 instruction set that allows access to the
extended page. Extended registers include ADC con-
version results, DACOUT enables, and GPIO input/out-
put data.
RSTEXTRAM: This is an extension to the standard IEEE
1149.1 instruction set. Use RSTEXTRAM to return to the
default page and disable access to the extended page.
SETEEPADD: This is an extension to the standard IEEE
1149.1 instruction set that allows access to the EEPROM
page. Once the SETEEPADD command has been sent,
all addresses are recognized as EEPROM addresses
only. When accessing any EEPROM location, set the
address to the desired location, perform a dummy
READ DATA operation, and then set the address back
to the desired location. This primes the device for a
subsequent series of READ DATA operations.
RSTEEPADD: This is an extension to the standard IEEE
1149.1 instruction set. Use RSTEEPADD to return to the
default page and disable access to the EEPROM.
Applications Information
Unprogrammed Device Behavior
When the EEPROM has not been programmed using
the JTAG or I2C interface, the default configuration of
the EN_OUT_ outputs is open-drain active-low. If it is
necessary to hold an EN_OUT_ high or low to prevent
premature startup of a power supply before the
EEPROM is programmed, connect a resistor to ground
or the supply voltage. Avoid connecting a resistor to
ground if the output is to be configured as open-drain
with a separate pullup resistor.
Device Behavior at Power-Up
When VCC is ramped from 0V, the RESET output is high
impedance until VCC reaches 1.4V, at which point it is
driven low. All other outputs are high impedance until
VCC reaches 2.85V, when the EEPROM contents are
copied into register memory, and after which the out-
puts assume their programmed states.
Margining Power Supplies
The MAX16046/MAX16048 can margin or shift the volt-
ages on external power supplies to facilitate prototyp-
ing or manufacturing tests. There are several different
ways to margin power supplies: One method feeds a
current into the feedback node of a DC-DC converter or
LDO, and another method feeds a current into the trim
input on a DC-DC module.
Feedback Method
See Figure 15 for the connections of the MAX16046/
MAX16048 to a power supply using the feedback node
method. The output voltage, VOUT, can be calculated
using the following formula:
where VREF is the internal reference voltage of the
power supply and VDACOUT_ is the output voltage of
the MAX16046/MAX16048 DACOUT_ output.
Select R1and R2to obtain the desired output voltage
with no trim in effect (VDACOUT_ = VREF). Set the DAC
range bits such that VREF falls approximately halfway
within the DACOUT_ output range (see the
DAC
Outputs
section). The resistor, R3, varies the amount of
control that the DACOUT_ voltage has on the output
voltage of the power supply. Large values of R3corre-
spond to a higher degree of resolution control over the
output voltage, and small values of R3correspond to a
lesser degree of resolution control.
VV1
R
R
R
R
R
RV
OUT REF 1
3
1
2
1
3DACOUT_
=++
MAX16046/MAX16048
Filtering the DAC Outputs
Some applications require filtering of the DAC outputs.
This is especially necessary in applications that require
a large distance between the power supplies to be
margined and the MAX16046/MAX16048, or those that
require immunity to noise. A simple RC filter may be
inserted (see Figure 16).
The calculations change slightly for this configuration.
For DC margining calculations, R3= R3A + R3B. To cal-
culate the lowpass cutoff frequency, use the following
formula:
Place resistor R3A and the capacitor, C, as close as
possible to the feedback node.
Trim Input Method
To connect the MAX16046/MAX16048 to a power sup-
ply using the trim input method, see Figure 17.
Calculate the output voltage, VOUT, as follows:
where VREF is the reference voltage of the power sup-
ply; R1, R2, R3, and R4are resistors internal to the
power supply; R5 is an optional series resistor connect-
ing the trim input to the DACOUT_ output; and
VDACOUT_ is the output voltage of the DACOUT_ output.
Calculate the ratio of R1and R2using the following for-
mula:
Resistors R3and R4and the reference voltage VREF
may be derived from the formulas given in the DC-DC
converter data sheet where trim input functionality is
discussed. DC-DC module data sheets usually include
trim-up and trim-down formulas in the following form:
where is the fraction of the total correction.
Another form of trim-up and trim-down formulas may
appear as follows:
TRIM DOWN:R k R k 100
%Rk
ADJ_DOWN 34
()
=
()
×
()
++
()
(
)
()
=
Rk
TRIM UP:R k V
3
ADJ_UP
OUT_NO
MM3
REF
R k 100 %
V%
Ω∆
()
×+
()
()
Rk
3ΩΩ
()
×+
()
+
()
()
100 R k R k %
%
43
TRIM DOWN:R k 1Rk R
ADJ_DOWN 3 4
()
=
()
kk
TRIM UP:R k V
V1
ADJ_UP OUT_NOM
REF
()
()
=
() (
1Rk Rk
34
1R
R
V
V
1
2
OUT_NOM
REF
+
=
V1
R
R
RV (R R)V
RR
OUT 1
2
3 DACOUT_ 4 5 REF
3
=+
++
+445
R+
f1
2R C
3B
=π
MAX16046
MAX16048
FB
VREF
VDACOUT_
R2
R3
R1
OUT
DC-DC OR LDO
Figure 15. Connections for Margining Using Feedback Method
MAX16046
MAX16048
FB
C
VREF
VDACOUT_
R2
R3A R3B
R1
OUT
DC-DC OR LDO
Figure 16. DACOUT Filter
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 59
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
60 ______________________________________________________________________________________
Set the DACOUT_ range bits (see the
DAC Outputs
section) such that VREF falls approximately halfway
within the DACOUT range. Set R5to vary the amount of
control the DAC has on the output voltage of the power
supply. Large values of R5correspond to higher
degree of resolution control over the output voltage,
and small values of R5correspond to lesser degree of
resolution control. Be sure to respect the minimum and
maximum output voltages that the DC-DC converter is
capable of generating.
The following is an example that illustrates the use of
the formulas for calculating the margin up and margin
down values. This example uses a generic 3.3V DC-DC
converter with a trim input. Below are the margin up
and margin down formulas taken from the data sheet
for the power supply:
By inspecting these formulas, VREF = 1.225V, R3=
1k, and R4= 1k. Set the DACOUT_ range from 0.8V
to 1.6V to fit the reference voltage. The output voltage
of the DC-DC converter is 3.3V; therefore the ratio (1 +
R1/R2) = VOUT/VREF = 3.3/1.225 = 2.69.
Set R5to zero to use the widest trim range possible
(increase R5to decrease the trim range). Insert these
values into the equations for the output voltage:
For VDACOUT_ = 0.8V, VOUT = 2.72V, and for
VDACOUT_ = 1.6V, VOUT = 3.80V. These output volt-
ages correspond with a margin down limit of -17.6%
and a margin up limit of 15.2%. Since the reference
voltage is not exactly in the center of the DACOUT_
range, the margin limits are not symmetrical. To
decrease the margin limits, increase the value of R5.
Maintaining Power During a Fault
Condition
Power to the MAX16046/MAX16048 must be main-
tained for a specific period of time to ensure a success-
ful EEPROM fault log operation during a fault that
removes power to the circuit. The amount of time
required depends on the settings in the fault control
register (r47h[1:0]) according to Table 36.
Maintain power for shutdown during fault conditions in
applications where the always-on power supply cannot
be relied upon by placing a diode and a large capaci-
tor between the voltage source, VIN, and VCC (Figure
18). The capacitor value depends on VIN and the time
delay required, tFAULT_SAVE. Use the following formula
to calculate the capacitor size:
where the capacitance is in Farads and tFAULT_SAVE is
in seconds. ICC(MAX) is 6.5mA, VDIODE is the voltage
drop across the diode, and VUVLO is 2.85V. For exam-
ple, with a VIN of 14V, a diode drop of 0.7V, and a
tFAULT_SAVE of 0.204s, the minimum required capaci-
tance is 127µF.
CtI
VV V
FAULT_SAVE CC(MAX)
IN DIODE UVLO
=×
V2.69
1k V 1k 1.225
2k 2
OUT DACOUT
=
()
×+×
=
ΩΩ
..69 V 1.225
2
DACOUT_
()
+
()
TRIM DOWN:R 100
%2k
TRIM U
ADJ_DOWN =
()
PP:R V (100 %)
1.225 %
100 2
ADJ_UP OUT_NOM
=++
%k
%
()
MAX16046
MAX16048
TRIM
VREF
VDACOUT_
R2
R5
R1
OUT
DC-DC OR LDO
R4
R3
Figure 17. Connections for Margining Using Trim Input Method
Table 36. EEPROM Fault Log Operation
Period
FAULT CONTROL
REGISTER VALUE
r47h [1:0]
DESCRIPTION
REQUIRED
PERIOD
tFAULT_SAVE
(ms)
00 Failed lines and
ADC values saved 204
01 Failed lines saved 60
10 ADC values saved 168
11 No information
saved
MAX16046/MAX16048
Driving High-Side MOSFET Switches
The MAX16046/MAX16048 use external n-channel
MOSFET switches for voltage tracking applications. To
configure the part for closed-loop voltage tracking
using series-pass MOSFETs, configure up to four of the
programmable outputs (EN_OUT1–EN_OUT4) of the
MAX16046/MAX16048 as closed-loop tracking outputs
and configure up to four of the GPIOs as sense-return
inputs (INS1–INS4). Connect the EN_OUT_ output to
the gate of an n-channel MOSFET, connect the source
of the MOSFET to the INS_ feedback input, and monitor
the drain side of the MOSFET with the corresponding
MON_ input (see Figure 19). Both the input and the out-
put must be assigned to the same slot (see the
Closed–Loop Tracking
section). Configure the power-
up and power-down slew rates in the configuration reg-
isters. To provide additional control over power-down,
enable the internal 100pulldown resistors on the INS_
connections.
Up to six of the programmable outputs (EN_OUT1–
EN_OUT6) of the MAX16046/MAX16048 may be config-
ured as charge-pump outputs. In this case, they can
drive the gates of series-pass n-channel MOSFETS with-
out closed-loop tracking functionality. When configured
in this way, these outputs act as simple power switches
to turn on the voltage supply rails. Approximate the slew
rate, SR, using the following formula:
where ICP is the 6µA (typ) charge-pump source cur-
rent, CGATE is the gate capacitance of the MOSFET,
and CEXT is the capacitance connected from the gate
to ground. Power-down is not well controlled due to the
absence of the 100pulldowns.
If more than six series-pass MOSFETs are required for
an application, additional series-pass p-channel
MOSFETS may be connected to outputs configured as
active-low open drain (Figure 20). Connect a pullup
resistor from the gate to the source of the MOSFET, and
ensure the absolute maximum ratings of the
MAX16046/MAX16048 are not exceeded.
SR I
CC
CP
GATE EXT
=+
()
MAX16046
MAX16048
VCC
C
VIN
GND
Figure 18. Power Circuit for Shutdown During Fault Conditions
MON_ EN_OUT_ INS_
VIN VOUT
REFERENCE
RAMP
LOGIC
ADC MUX
VTH_PG
100
GATE
DRIVE
Figure 19. Closed-Loop Tracking
MAX16046
MAX16048
VOUT
R
MON_ EN_OUT_
VIN
Figure 20. Connection for a p-Channel Series-Pass MOSFET
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 61
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
62 ______________________________________________________________________________________
Simple slew-rate control is accomplished by adding a
capacitor from the gate to ground. The slew rate is
approximated by the RC charge curve of the pullup
resistor acting with the capacitor from gate to ground.
Note that the power-off is not well controlled due to the
absence of the 100pulldowns.
Ensure that MOSFETs have a low gate-to-source
threshold (VGS_TH) and RDS(ON). See Table 37 for rec-
ommended n-channel MOSFETs.
Layout and Bypassing
Bypass DBP and ABP each with a 1µF ceramic capacitor
to GND. Bypass VCC with a 10µF capacitor to ground.
Avoid routing digital return currents through a sensitive
analog area, such as an analog supply input return path
or ABP’s bypass capacitor ground connection. Use dedi-
cated analog and digital ground planes. Connect the
capacitors as close as possible to the device.
Table 37. Recommended MOSFETs
MANUFACTURER PART MAX VDS
(V)
VGS
_
TH
(V)
RDS(ON) AT
VGS = 4.5V
(m)
IMAX AT 50mV
VOLTAGE
DROP
(A)
Q
g
(typ)
(nC) PACKAGE
FDC633N 30 0.67 42 1.19 11 Super SOT-6
FDP8030L
FDB8030L 30 1.5 4.5 11.11 120 TO-220
TO-263AB
FDD6672A 30 1.2 9.5 5.26 33 TO-252
Fairchild
FDS8876 30 2.5 10.2 2.94 15 SO-8
Si7136DP 20 3 4.5 11.11 24.5 SO-8
Si4872DY 30 1 10 5 27 SO-8
SUD50N02-09P 20 3 17 2.94 10.5 TO-252Vishay
Si1488DH 20 0.95 49 1.02 6 SOT-363
SC70-6
IRL3716 20 3 4.8 10.4 53
TO220AB
D2PAK
TO-262
IRL3402 20 0.7 10 5 78
(max) TO220AB
IRL3715Z 20 2.1 15.5 3.22 7
TO220AB
D2PAK
TO-262
International
Rectifier
IRLM2502 20 1.2 45 1.11 8 SOT23-3
Micro3
MAX16046/MAX16048
Register Map
PAGE ADDRESS
READ/WRITE
DESCRIPTION
Ext 00h R MON1 ADC Result Register (MSB)
Ext 01h R MON1 ADC Result Register (LSB)
Ext 02h R MON2 ADC Result Register (MSB)
Ext 03h R MON2 ADC Result Register (LSB)
Ext 04h R MON3 ADC Result Register (MSB)
Ext 05h R MON3 ADC Result Register (LSB)
Ext 06h R MON4 ADC Result Register (MSB)
Ext 07h R MON4 ADC Result Register (LSB)
Ext 08h R MON5 ADC Result Register (MSB)
Ext 09h R MON5 ADC Result Register (LSB)
Ext 0Ah R MON6 ADC Result Register (MSB)
Ext 0Bh R MON6 ADC Result Register (LSB)
Ext 0Ch R MON7 ADC Result Register (MSB)
Ext 0Dh R MON7 ADC Result Register (LSB)
Ext 0Eh R MON8 ADC Result Register (MSB)
Ext 0Fh R MON8 ADC Result Register (LSB)
Ext 10h R MON9 ADC Result Register (MSB)*
Ext 11h R MON9 ADC Result Register (LSB)*
Ext 12h R MON10 ADC Result Register (MSB)*
Ext 13h R MON10 ADC Result Register (LSB)*
Ext 14h R MON11 ADC Result Register (MSB)*
Ext 15h R MON11 ADC Result Register (LSB)*
Ext 16h R MON12 ADC Result Register (MSB)*
Ext 17h R MON12 ADC Result Register (LSB)*
Ext 18h R/W Fault Register—Failed Line Flags
Ext 19h R/W Fault Register—Failed Line Flags
Ext 1Ah R/W GPIO Data Out
Ext 1Bh R GPIO Data In
Ext 1Ch R/W DAC Enables
Ext 1Dh R/W DAC Enables
Default 00h R/W DACOUT1
Default 01h R/W DACOUT2
Default 02h R/W DACOUT3
Default 03h R/W DACOUT4
Default 04h R/W DACOUT5
Default 05h R/W DACOUT6
Default 06h R/W DACOUT7
Default 07h R/W DACOUT8
Default 08h R/W DACOUT9*
Default 09h R/W DACOUT10*
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 63
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
64 ______________________________________________________________________________________
Register Map (continued)
PAGE ADDRESS
READ/WRITE
DESCRIPTION
Default 0Ah R/W DACOUT11*
Default 0Bh R/W DACOUT12*
EEPROM 00h R/W Power-Up Fault Registers
EEPROM 01h R/W Failed Line Flags (Fault Registers)
EEPROM 02h R/W Failed Line Flags (Fault Registers)
EEPROM 03h R/W MON1 Conversion Result at Time of Fault
EEPROM 04h R/W MON2 Conversion Result at Time of Fault
EEPROM 05h R/W MON3 Conversion Result at Time of Fault
EEPROM 06h R/W MON4 Conversion Result at Time of Fault
EEPROM 07h R/W MON5 Conversion Result at Time of Fault
EEPROM 08h R/W MON6 Conversion Result at Time of Fault
EEPROM 09h R/W MON7 Conversion Result at Time of Fault
EEPROM 0Ah R/W MON8 Conversion Result at Time of Fault
EEPROM 0Bh R/W MON9 Conversion Result at Time of Fault*
EEPROM 0Ch R/W MON10 Conversion Result at Time of Fault*
EEPROM 0Dh R/W MON11 Conversion Result at Time of Fault*
EEPROM 0Eh R/W MON12 Conversion Result at Time of Fault*
Def/EE 0Fh R/W ADC MON4–MON1 Voltage Ranges
Def/EE 10h R/W ADC MON8–MON5 Voltage Ranges
Def/EE 11h R/W ADC MON12–MON9 Voltage Ranges*
Def/EE 12h R/W DACOUT4–DACOUT1 Voltage Ranges
Def/EE 13h R/W DACOUT8–DACOUT5 Voltage Ranges
Def/EE 14h R/W DACOUT12–DACOUT9 Voltage Ranges*
Def/EE 15h R/W FAULT1 Dependencies
Def/EE 16h R/W FAULT1 Dependencies
Def/EE 17h R/W FAULT2 Dependencies
Def/EE 18h R/W FAULT2 Dependencies
Def/EE 19h R/W RESET Output Configuration
Def/EE 1Ah R/W RESET Output Dependencies
Def/EE 1Bh R/W RESET Output Dependencies
Def/EE 1Ch R/W GPIO Configuration
Def/EE 1Dh R/W GPIO Configuration
Def/EE 1Eh R/W GPIO Configuration
Def/EE 1Fh R/W EN_OUT1–EN_OUT3 Output Configuration
Def/EE 20h R/W EN_OUT3–EN_OUT6 Output Configuration
Def/EE 21h R/W EN_OUT6–EN_OUT9 Output Configuration*
Def/EE 22h R/W EN_OUT10–EN_OUT12 Output Configuration*
Def/EE 23h R/W MON1 Early Warning Threshold
Def/EE 24h R/W MON1 Overvoltage Threshold
Def/EE 25h R/W MON1 Undervoltage Threshold
MAX16046/MAX16048
Register Map (continued)
PAGE ADDRESS
READ/WRITE
DESCRIPTION
Def/EE 26h R/W MON2 Early Warning Threshold
Def/EE 27h R/W MON2 Overvoltage Threshold
Def/EE 28h R/W MON2 Undervoltage Threshold
Def/EE 29h R/W MON3 Early Warning Threshold
Def/EE 2Ah R/W MON3 Overvoltage Threshold
Def/EE 2Bh R/W MON3 Undervoltage Threshold
Def/EE 2Ch R/W MON4 Early Warning Threshold
Def/EE 2Dh R/W MON4 Overvoltage Threshold
Def/EE 2Eh R/W MON4 Undervoltage Threshold
Def/EE 2Fh R/W MON5 Early Warning Threshold
Def/EE 30h R/W MON5 Overvoltage Threshold
Def/EE 31h R/W MON5 Undervoltage Threshold
Def/EE 32h R/W MON6 Early Warning Threshold
Def/EE 33h R/W MON6 Overvoltage Threshold
Def/EE 34h R/W MON6 Undervoltage Threshold
Def/EE 35h R/W MON7 Early Warning Threshold
Def/EE 36h R/W MON7 Overvoltage Threshold
Def/EE 37h R/W MON7 Undervoltage Threshold
Def/EE 38h R/W MON8 Early Warning Threshold
Def/EE 39h R/W MON8 Overvoltage Threshold
Def/EE 3Ah R/W MON8 Undervoltage Threshold
Def/EE 3Bh R/W MON9 Early Warning Threshold*
Def/EE 3Ch R/W MON9 Overvoltage Threshold*
Def/EE 3Dh R/W MON9 Undervoltage Threshold*
Def/EE 3Eh R/W MON10 Early Warning Threshold*
Def/EE 3Fh R/W MON10 Overvoltage Threshold*
Def/EE 40h R/W MON10 Undervoltage Threshold*
Def/EE 41h R/W MON11 Early Warning Threshold*
Def/EE 42h R/W MON11 Overvoltage Threshold*
Def/EE 43h R/W MON11 Undervoltage Threshold*
Def/EE 44h R/W MON12 Early Warning Threshold*
Def/EE 45h R/W MON12 Overvoltage Threshold*
Def/EE 46h R/W MON12 Undervoltage Threshold*
Def/EE 47h R/W Fault Control
Def/EE 48h R/W Faults Causing Emergency EEPROM Save
Def/EE 49h R/W Faults Causing Emergency EEPROM Save
Def/EE 4Ah R/W Faults Causing Emergency EEPROM Save
Def/EE 4Bh R/W Faults Causing Emergency EEPROM Save
Def/EE 4Ch R/W Faults Causing Emergency EEPROM Save
Def/EE 4Dh R/W Software Enable/MARGIN
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 65
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
66 ______________________________________________________________________________________
Register Map (continued)
PAGE ADDRESS
READ/WRITE
DESCRIPTION
Def/EE 4Eh R/W Power-Up/Power-Down Pulldown Resistors
Def/EE 4Fh R/W Autoretry, Slew Rate, and ADC Fault Deglitch
Def/EE 50h R/W Sequence Delays
Def/EE 51h R/W Sequence Delays
Def/EE 52h R/W Sequence Delays
Def/EE 53h R/W Sequence Delays
Def/EE 54h R/W Sequence Delays/Reverse Sequence Bit
Def/EE 55h R/W Watchdog Timer Setup
Def/EE 56h R/W MON2–MON1 Slot Assignment from Slot 1 to Slot 12
Def/EE 57h R/W MON4–MON3 Slot Assignment from Slot 1 to Slot 12
Def/EE 58h R/W MON6–MON5 Slot Assignment from Slot 1 to Slot 12
Def/EE 59h R/W MON8–MON7 Slot Assignment from Slot 1 to Slot 12
Def/EE 5Ah R/W MON10–MON9 Slot Assignment from Slot 1 to Slot 12*
Def/EE 5Bh R/W MON12–MON11 Slot Assignment from Slot 1 to Slot 12*
Def/EE 5Ch R/W Customer Firmware Version
Def/EE 5Dh R/W EEPROM and Configuration Lock
Def/EE 5Eh R/W EN_OUT2–EN_OUT1 Slot Assignment from Slot 0 to Slot 11
Def/EE 5Fh R/W EN_OUT4–EN_OUT2 Slot Assignment from Slot 0 to Slot 11
Def/EE 60h R/W EN_OUT6–EN_OUT5 Slot Assignment from Slot 0 to Slot 11
Def/EE 61h R/W EN_OUT8–EN_OUT7 Slot Assignment from Slot 0 to Slot 11
Def/EE 62h R/W EN_OUT10–EN_OUT9 Slot Assignment from Slot 0 to Slot 11*
Def/EE 63h R/W EN_OUT12–EN_OUT11 Slot Assignment from Slot 0 to Slot 11*
Def/EE 64h R/W INS Power-Good (PG) Thresholds
Def/EE 65h R Manufacturing Revision Code
Def/EE 66h R/W DACOUT1—MARGIN UP
Def/EE 67h R/W DACOUT2—MARGIN UP
Def/EE 68h R/W DACOUT3—MARGIN UP
Def/EE 69h R/W DACOUT4—MARGIN UP
Def/EE 6Ah R/W DACOUT5—MARGIN UP
Def/EE 6Bh R/W DACOUT6—MARGIN UP
Def/EE 6Ch R/W DACOUT7—MARGIN UP
Def/EE 6Dh R/W DACOUT8—MARGIN UP
Def/EE 6Eh R/W DACOUT9—MARGIN UP*
Def/EE 6Fh R/W DACOUT10—MARGIN UP*
Def/EE 70h R/W DACOUT11—MARGIN UP*
Def/EE 71h R/W DACOUT12—MARGIN UP*
Def/EE 72h R/W DACOUT1—MARGIN DN
Def/EE 73h R/W DACOUT2—MARGIN DN
Def/EE 74h R/W DACOUT3—MARGIN DN
Def/EE 75h R/W DACOUT4—MARGIN DN
MAX16046/MAX16048
Register Map (continued)
PAGE ADDRESS
READ/WRITE
DESCRIPTION
Def/EE 76h R/W DACOUT5—MARGIN DN
Def/EE 77h R/W DACOUT6—MARGIN DN
Def/EE 78h R/W DACOUT7—MARGIN DN
Def/EE 79h R/W DACOUT8—MARGIN DN
Def/EE 7Ah R/W DACOUT9—MARGIN DN*
Def/EE 7Bh R/W DACOUT10—MARGIN DN*
Def/EE 7Ch R/W DACOUT11—MARGIN DN*
Def/EE 7Dh R/W DACOUT12—MARGIN DN*
Def/EE 7Eh–93h Reserved
EEPROM 9Ch–FFh R/W User EEPROM
*
MAX16046 only
Note: Ext refers to registers contained in the extended page, Default refers to registers contained in the default page, EEPROM
refers to EEPROM memory locations, and Def/EE refers to locations that are stored in EEPROM and loaded into the same addresses
in the default page on boot-up.
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 67
Chip Information
PROCESS: BiCMOS
Package Information
For the latest package outline information and land patterns, go
to www.maxim-ic.com/packages. Note that a “+”, “#”, or “-” in
the package code indicates RoHS status only. Package draw-
ings may show a different suffix character, but the drawing per-
tains to the package regardless of RoHS status.
PACKAGE
TYPE
PACKAGE
CODE OUTLINE NO. LAND
PATTERN NO.
56 TQFN T5688-3 21-0135 90-0047
64 TQFP C64E+6 21-0084 90-0328
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
68 ______________________________________________________________________________________
4647484950 43444551
29
30
31
32
33
34
35
36
37
38
MON11
SDA
EN_OUT7
TQFN
(8mm x 8mm)
+
TOP VIEW
EN_OUT6
EN_OUT5
EN_OUT4
EN_OUT3
EN_OUT2
EN_OUT1
GPIO4
GPIO3
SCL
TDI
TMS
TDO
TCK
GPIO6
GND
EN
GPIO5
DACOUT2
DACOUT1
DACOUT4
DACOUT3
MON10
MON9
MON8
MON7
MON6
A0
RESET
MON12
MON5
MON4
MON3
MON2
39
MON1
DACOUT8
DACOUT9
DACOUT10
DACOUT11
DACOUT12
ABP
DACOUT5
*EP
*EP = EXPOSED PAD
DACOUT6
DACOUT7
VCC
DBP
GND
GPIO1
GPIO2
52
EN_OUT8
535455
EN_OUT11
EN_OUT10
EN_OUT9
56
EN_OUT12
2019181716 2423222115 2625 2827
40
41
42
11
10
9
8
7
6
5
4
3
2
14
13
12
1
MAX16046
4647484950 43444551
29
30
31
32
33
34
35
36
37
38
N.C.
SDA
EN_OUT7
TQFN
(8mm x 8mm)
+
EN_OUT6
EN_OUT5
EN_OUT4
EN_OUT3
EN_OUT2
EN_OUT1
GPIO4
GPIO3
SCL
TDI
TMS
TDO
TCK
GPIO6
GND
EN
GPIO5
DACOUT2
DACOUT1
DACOUT4
DACOUT3
N.C.
N.C.
MON8
MON7
MON6
A0
RESET
N.C.
MON5
MON4
MON3
MON2
39
MON1
DACOUT8
N.C.
N.C.
N.C.
N.C.
ABP
DACOUT5
*EP
DACOUT6
DACOUT7
VCC
DBP
GND
GPIO1
GPIO2
52
EN_OUT8
535455
N.C.
N.C.
N.C.
56
N.C.
2019181716 2423222115 2625 2827
40
41
42
11
10
9
8
7
6
5
4
3
2
14
13
12
1
MAX16048
Pin Configurations
MAX16046/MAX16048
5859606162 5455565763
38
39
40
41
42
43
44
45
46
47
MON9
SDA
EN_OUT12
TQFP
(10mm x 10mm)
TOP VIEW
EN_OUT11
EN_OUT10
EN_OUT9
EN_OUT8
EN_OUT7
EN_OUT6
EN_OUT5
EN_OUT4
EN_OUT3
5253 49
5051
EN_OUT2
EN_OUT1
GPIO4
GPIO3
N.C.
SCL
TDI
TMS
TDO
TCK
N.C.
GND
GPIO5
GPIO6
DACOUT1
EN
DACOUT3
DACOUT2
DACOUT4
GPIO2
GPIO1
GND
DBP
VCC
ABP
DACOUT12
DACOUT11
DACOUT10
DACOUT9
33
34
35
36
37 DACOUT8
DACOUT7
DACOUT6
DACOUT5
N.C.
MON8
N.C.
N.C.
MON7
MON6
RESET
N.C.
MON12
MON11
MON10
MON5
MON4
MON3
MON2
48 N.C.MON1
64
N.C.
A0
2322212019 2726252418 2928 32313017
11
10
9
8
7
6
5
4
3
2
16
15
14
13
12
1
MAX16046
5859606162 5455565763
38
39
40
41
42
43
44
45
46
47
N.C.
SDA
N.C.
TQFP
(10mm x 10mm)
TOP VIEW
N.C.
N.C.
N.C.
EN_OUT8
EN_OUT7
EN_OUT6
EN_OUT5
EN_OUT4
EN_OUT3
5253 49
5051
EN_OUT2
EN_OUT1
GPIO4
GPIO3
N.C.
SCL
TDI
TMS
TDO
TCK
N.C.
GND
GPIO5
GPIO6
DACOUT1
EN
DACOUT3
DACOUT2
DACOUT4
GPIO2
GPIO1
GND
DBP
VCC
ABP
N.C.
N.C.
N.C.
N.C.
33
34
35
36
37 DACOUT8
DACOUT7
DACOUT6
DACOUT5
N.C.
MON8
N.C.
N.C.
MON7
MON6
RESET
N.C.
N.C.
N.C.
N.C.
MON5
MON4
MON3
MON2
48 N.C.MON1
64
N.C.
A0
2322212019 2726252418 2928 32313017
11
10
9
8
7
6
5
4
3
2
16
15
14
13
12
1
MAX16048
Pin Configurations (continued)
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
______________________________________________________________________________________ 69
MAX16046/MAX16048
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
Maxim cannot assume responsibility for use of any circuitry other than circuitry entirely embodied in a Maxim product. No circuit patent licenses are
implied. Maxim reserves the right to change the circuitry and specifications without notice at any time.
70
____________________Maxim Integrated Products, 120 San Gabriel Drive, Sunnyvale, CA 94086 408-737-7600
© 2010 Maxim Integrated Products Maxim is a registered trademark of Maxim Integrated Products, Inc.
Revision History
REVISION
NUMBER
REVISION
DATE DESCRIPTION PAGES
CHANGED
0 10/07 Initial release
1 2/08 Removed future product designation in the Ordering Information table and
updated Package Information 1, 67, 68
2 4/08
Added TQFP package to the data sheet and updated the General
Description, Ordering Information, Features, Absolute Maximum Ratings, Pin
Description, Pin Configuration, and Selector Guide
1, 2, 11, 12, 65, 66,
67
3 12/08 Updated Pin Descriptions, Register Summary (All Registers 8-Bits Wide)
section, and Revision History 14, 16, 70
4 3/09 Updated Detailed Description, Table 30 and Table 31 17, 29, 30, 39, 43,
44, 48, 50
5 9/10 Updated Electrical Characteristics table, added text to the Command Codes
and Instruction Register sections, style edits, updated Package Information
3, 6, 14, 52, 53,
58, 67