3
Technical Data 2151
Effective February 2016
Three-pole high SCCR UL Type 2 surge protective devices
for three-phase Delta and Wye systems
Eaton.com/bussmannseries
Ordering information:
Nominal system voltage 120/208Vac 240Vac 277/480Vac 480Vac 347/600Vac
Max. Continuous Operating AC Voltage MCOV
(VC) [L-G/L-L] 275/550Vac 275/550Vac 385/770Vac 600/1200Vac 600/1200Vac
Catalog numbers
(base + modules)
W/O remote signaling BSPM3208WYG BSPM3240DLG BSPM3480WYG BSPM3480DLG BSPM3600WYG
W/ remote signaling BSPM3208WYGR BSPM3240DLGR BSPM3480WYGR BSPM3480DLGR BSPM3600WYGR
Replacement module MOV technology BPM275UL BPM275UL BPM385UL BPM600UL BPM600UL
Specifications
Rated voltage 120-127Vac,
208-220Vac 240Vac 277/480Vac 480Vac 347/600Vac
Voltage Protection Rating VPR [L-G/L-L] 1kV/1.8kV 1kV/1.8kV 1.5kV/2.5kV 2kV/4kV 2kV/4kV
SCCR 200kA 200kA 200kA 125kA 125kA
Discharge current Nom. In20kA
Max. Imax 40kA
Response time tA≤25 ns
Frequency 50/60Hz
Number of poles 3
Number of wires/connection points 3 wires / 4 connection points
Operating state/fault indication Green (good) / Red (replace)
Cross-sectional area Min.. 14AWG - Cu stranded, solid or fine
Max.. 2AWG - Cu solid or stranded, 4AWG - Cu fine
Terminal torque 45 lb-in (5.1N•m)
Mounting 35mm DIN-rail per EN 60715
Enclosure material Thermoplastic, UL 94V0
Protection IP20 (finger-safe)
Location Indoor
Capacity 3 Mods, DIN 43880
Application, standard UL Type 2 Component Assembly, UL 1449, 4th Edition
Agency information cURus, RoHS Compliant
Warranty Five years*
Remote contact signaling
Signaling type Changeover contact
Switching capacity
(volts/amps)
AC 250V/0.5A
DC 250V/0.1A; 125V/0.2A; 75V/0.5A
Conductor and cross-sectional area 60/75°C Max. 1.5mm2/14AWG solid/flexible
Ordering information Order from catalog numbers above
* See Eaton Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.