Key Commercial Data
Packing unit 1 pc
Minimum order quantity 10 pc
GTIN
GTIN 4046356758208
Weight per Piece (excluding packing) 36.000 g
Custom tariff number 85364900
Country of origin Poland
Technical data
Dimensions
Width 21.2 mm
Height 27.5 mm
Depth 35.6 mm
Ambient conditions
Ambient temperature (operation) -40 °C ... 55 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection RT I
Coil side
Nominal input voltage UN120 VAC
https://www.phoenixcontact.com/us/products/2903667
03/15/2021Page2/7
Single relay-REL-IR2/L-120AC/2X21-2903667
Technical data
Coil side
Input voltage range in reference to UNsee diagram
Mains frequency 50/60 Hz
Typical input current at UN13 mA
Typical response time 5 ms ... 15 ms (depending on phase relation)
Typical release time range 5 ms ... 20 ms (depending on phase relation)
Status display Yellow LED
Power dissipation for nominal condition 1.56 W
Contact side
Contact type 2 changeover contacts
Type of switch contact Single contact
Contact material AgNi
Maximum switching voltage 250 V AC/DC
Minimum switching voltage 5 V (At 24 mA)
Min. switching current 5 mA (at 24V)
Maximum inrush current 30 A (20 ms, N/O contacts)
Limiting continuous current 12 A
Interrupting rating (ohmic load) max. 288 W (at 24 V DC)
124 W (at 48 V DC)
108 W (at 60 V DC)
52 W (at 110 V DC)
48 W (at 220 V DC)
3000 VA (for 250 V AC)
Switching capacity min. 0.12 W
Motor load according to UL 508 1/2HP, 240VAC
General
Test voltage 2.5 kVrms (50Hz, 1min., winding/contact)
2.5 kVrms (50Hz, 1min., contact/contact)
2.5 kVrms (50Hz, 1min., changeover contact/changeover contact)
Operating mode 100% operating factor
Mechanical service life approx. 2x 107 cycles
Service life, electrical see diagram
Mounting position any
Connection data
Connection method Plug connection
Standards and Regulations
https://www.phoenixcontact.com/us/products/2903667
03/15/2021Page3/7
Single relay-REL-IR2/L-120AC/2X21-2903667
Technical data
Standards and Regulations
Connection in acc. with standard CSA
Standards/regulations IEC60664
IEC 61810
Rated insulation voltage 250 VAC
Rated surge voltage 4 kV
Insulation Basic insulation
Pollution degree 3 (Rated voltage of 230V)
2 (Rated voltage of 400V)
Overvoltage category III
Conformance/approvals
Designation Corrosive gas test
Identification ISA-S71.04. G3 Harsh Group
EN60068-2-60
Environmental Product Compliance
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Circuit diagram
12
A1
11 14
4241 44
A2
Diagram
0,6
0,8
1
1,2
1,4
1,6
1,8
2
2,2
2,4
0 10 20 30 40 50 60 70 80
Ambienttemperature[°C]
CoilvoltageU/UN
DCcoils
ACcoils
Operating voltage range
https://www.phoenixcontact.com/us/products/2903667
03/15/2021Page4/7
Single relay-REL-IR2/L-120AC/2X21-2903667
Diagram
!
0 1 2 3
105
106
107
250VAC,ohmicload
Cycles
Switchingcapacity[kVA]
Electrical service life
Diagram
COS j
Reductionfactor
1
0,9
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1
0,8 0,7 0,6 0,5 0,4 0,3 0,2
Service life reduction factor
Diagram
U [V]
I [A]
0,1
0,2
0,3
0,5
1
2
4
6
10
20
10 20 30 50 70 100 300200
12
Interrupting rating
Curve 1: AC, ohmic load
Curve 2: DC, ohmic load
Classifications
eCl@ss
eCl@ss 10.0.1 27371601
eCl@ss 11.0 27371601
eCl@ss 4.0 27371100
eCl@ss 4.1 27371100
eCl@ss 5.0 27371600
eCl@ss 5.1 27371600
eCl@ss 6.0 27371600
eCl@ss 7.0 27371601
eCl@ss 9.0 27371601
https://www.phoenixcontact.com/us/products/2903667
03/15/2021Page5/7
Single relay-REL-IR2/L-120AC/2X21-2903667
Classifications
ETIM
ETIM 2.0 EC001437
ETIM 3.0 EC001437
ETIM 4.0 EC001437
ETIM 6.0 EC001437
ETIM 7.0 EC001437
UNSPSC
UNSPSC 6.01 30211916
UNSPSC 7.0901 39121515
UNSPSC 11 39121515
UNSPSC 12.01 39121515
UNSPSC 13.2 39122334
UNSPSC 18.0 39122334
UNSPSC 19.0 39122334
UNSPSC 20.0 39122334
UNSPSC 21.0 39122334
Approvals
Approvals
Approvals
CSA / UL Recognized / cUL Recognized / EAC / EAC / VDE Zeichengenehmigung / cULus Recognized
Ex Approvals
Approval details
CSA http://www.csagroup.org/services-industries/product-listing/ 2554095
UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 172140
https://www.phoenixcontact.com/us/products/2903667
03/15/2021Page6/7
Single relay-REL-IR2/L-120AC/2X21-2903667
Approvals
cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 172140
EAC TR_TS_D_00573_c
EAC RU*C-
DE.*08.B.00010
VDE Zeichengenehmigung http://www2.vde.com/de/Institut/Online-Service/
VDE-gepruefteProdukte/Seiten/Online-Suche.aspx 40040427
cULus Recognized
Accessories
Additional products
Relay base-RIF-2-BPT/4X21-2900934
Relay base RIF-2..., for industrial relay with 2 or 4 changeover contacts, Push-in connection, plug-in option for input/
interference suppression modules, for mounting on NS 35/7,5
Relay base-RIF-2-BSC/4X21-2900932
RIF-2... relay base, for industrial relay with 2 or 4 changeover contacts, screw connection, plug-in option for input/
interference suppression modules, for mounting on NS 35/7,5
https://www.phoenixcontact.com/us/products/2903667
03/15/2021Page7/7
Phoenix Contact 2021 © - all rights reserved
http://www.phoenixcontact.com