B7-30-01-80 Mini Contactor 220-240V 40-450Hz
B7-30-01-80
Extended Product TypeB7-30-01-80
Product IDGJL1311001R8010
EAN4013614152047
Catalog DescriptionB7-30-01-80 Mini Contactor 220-240V 40-450Hz
Long Description
The B7-30-01 mini contactor is a compact 3 pole contactor with 1 auxiliary contact and
screw terminals. They are ideally suited for applications where reliability is a must and
space is at a premium. Mini contactors are used in residential buldings, commercial
buildings and industrial applications for the control of single or three-phase loads up to 5.5
kW (AC-3) and 20 A / 690 V (AC-1) or switching of control signals. Further features are the
silent coil, a switch position indication and the integrated possibility for rail or wall mounting.
General Information
PRODUCT-DETAILS
Ordering
1 piece Minimum Order Quantity
85365080 Customs Tariff Number
Popular Downloads
1SBC100173C0201 Data Sheet, Technical
Information
2CDC102047M6801 Instructions and Manuals
GJL1200436F0001 Dimension Diagram
Dimensions
52.5 mm Product Net Width
57.5 mm Product Net Height
46.5 mm Product Net Depth /
Length
0.175 kg Product Net Weight
Technical
4 Number of Poles
Mini Contactor Mini Contactor Type
Auxiliary Circuit 12 ... 240 V DC
Auxiliary Circuit 12 ... 500 V AC/DC
Main Circuit 12 ... 690 V AC/DC
Main Circuit 690 V AC
Rated Operational Voltage
Control Circuit 400 Hz
Control Circuit 50 Hz
Control Circuit 60 Hz
Main Circuit 60 Hz
Main Circuit 50 Hz
Main Circuit DC
Rated Frequency (f)
Auxiliary Circuit 6 kV
Main Circuit 6 kV
Rated Impulse Withstand
Voltage (Uimp)
690 V
acc. to UL/CSA 600 V
Rated Insulation Voltage
(Ui)
0 Number of Main Contacts
NC
3 Number of Main Contacts
NO
(220 / 240 V) 40 °C 20 A
(220 / 240 V) 55 °C 16 A
(380 / 440 V) 40 °C 20 A
(380 / 440 V) 55 °C 16 A
(690 V) 40 °C 6 A
(690 V) 55 °C 6 A
Rated Operational Current
AC-1 (Ie)
(220 / 230 / 240 V) 3 kW
(400 V) 5.5 kW
(400 V) Three Phase 5.5 kW
(440 V) 5.5 kW
(500 V) 5.5 kW
(690 V) 3 kW
Rated Operational Power
AC-3 (Pe)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A Rated Short-time
Withstand Current (Icw)
1 Number of Auxiliary
Contacts NC
0 Number of Auxiliary
Contacts NO
(120 V) 4 A
(220 / 240 V) 4 A
(24 V) 4 A
(380 / 400 V) 3 A
(500 V) 2 A
Rated Operational Current
AC-15 (Ie)
(110 V) 0.7 A
(220 / 240 V) 0.4 A
(24 V) 2.5 A
Rated Operational Current
DC-13 (Ie)
Main Circuit 20 A Conventional Free-air
2
B7-30-01-80
Thermal Current (Ith)
220 ... 240 V AC Rated Control Circuit
Voltage (Uc)
(acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) Coil Operating Limits
Auxiliary Circuit Terminals IP20
Control Circuit Terminals IP20
Main Circuit Terminals IP20
Degree of Protection
10000000 cycle Mechanical Durability
Auxiliary Circuit 17 V
Auxiliary Circuit 5 mA
Minimum Switching
Capacity
AC-1 300 cycles per hour
AC-15 600 cycles per hour
AC-3 600 cycles per hour
DC-1 600 cycles per hour
DC-13 600 cycles per hour
DC-3 600 cycles per hour
Maximum Electrical
Switching Frequency
Flexible with Ferrule 1/2x 1 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 1 ... 2.5 mm²
Flexible 1/2x 1 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Connecting Capacity Main
Circuit
Flexible with Ferrule 1/2x 1 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 1 ... 2.5 mm²
Flexible 1/2x 1 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Connecting Capacity
Auxiliary Circuit
Flexible with Ferrule 1/2x 1 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 1 ... 2.5 mm²
Flexible 1/2x 1 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Connecting Capacity
Control Circuit
Auxiliary Circuit 9 mm
Main Circuit 9 mm
Wire Stripping Length
Auxiliary Circuit 0.8 ... 1.1 N·m
Control Circuit 0.8 ... 1.1 N·m
Main Circuit 0.8 ... 1.1 N·m
Tightening Torque
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting on DIN Rail
at Rated Operating Conditions per Pole 2 W Power Loss
IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
UL 60947-1
UL 60947-4-1
Standards
Technical UL/CSA
Main Circuit 600 V AC Maximum Operating
Voltage UL/CSA
(240 V AC) Single Phase 10 A
(440 ... 480 V AC) Three Phase 7.6 A
Full Load Amps Motor
Use
(208 V AC) Three Phase 3 Hp
(220 ... 240 V AC) Single Phase 1.5 Hp
(220 ... 240 V AC) Three Phase 3 Hp
(440 ... 480 V AC) Three Phase 5 Hp
(550 ... 600 V AC) Three Phase 5 Hp
Horsepower Rating
UL/CSA
(600 V AC) 16 A General Use Rating
UL/CSA
Stranded 1/2x 22-10 AWG
Connecting Capacity Main
Circuit UL/CSA
Stranded 1/2x 22-10 AWG Connecting Capacity
Auxiliary Circuit UL/CSA
3
B7-30-01-80
Auxiliary Circuit 7 in·lb
Control Circuit 7 in·lb
Main Circuit 7 in·lb
Tightening Torque
UL/CSA
Environmental
Operation -25 ... +55 °C
Storage -40 ... +80 °C
Ambient Air Temperature
2000 m Maximum Operating
Altitude Permissible
11 ms Pulse 15g Resistance to Shock acc.
to IEC 60068-2-27
5g / 5 ... 150 Hz Resistance to Vibrations
acc. to IEC 60068-2-6
Following EU Directive 2011/65/EU RoHS Status
Certificates and Declarations (Document Number)
1SAA920000-0204 BV Certificate
1SAA938000-2002 CB Certificate
1SAA938001-3805 CCC Certificate
cUL E191658 cUL Certificate
1SAD938515-0001 Declaration of Conformity
- CE
1SAA938000-0306 DNV GL Certificate
1SAA920000-2702 EAC Certificate
2CDC102047M6801 Instructions and Manuals
1SAA938000-1501 KC Certificate
1SAA938000-0504 LR Certificate
1SAA938000-0704 RMRS Certificate
1SAD938514-0001 RoHS Information
Container Information
10 piece Package Level 1 Units
115 mm Package Level 1 Width
54 mm Package Level 1 Height
280 mm Package Level 1 Depth /
Length
1.82 kg Package Level 1 Gross
Weight
4013614416606 Package Level 1 EAN
Classifications
Q Object Classification Code
EC000066 - Magnet contactor, AC-switching ETIM 4
EC000066 - Magnet contactor, AC-switching ETIM 5
EC000066 - Power contactor, AC switching ETIM 6
EC000066 - Power contactor, AC switching ETIM 7
4
B7-30-01-80
7.0 27371003 eClass
39121529 UNSPSC
Low Voltage Products and Systems
Control Products
Contactors
Mini Contactors
Categories
Accessories
IdentifierDescriptionTypeQuantityUnit Of
Measure
GJL1201317R0002CA6-11E Auxiliary ContactCA6-11E1piece
GJL1201317R0003CA6-11M Auxiliary ContactCA6-11M1piece
GJL1201317R0004CA6-11N Auxiliary ContactCA6-11N1piece
GJL1201330R0002CAF6-11E Auxiliary ContactCAF6-11E1piece
GJL1201330R0003CAF6-11M Auxiliary ContactCAF6-11M1piece
GJL1201330R0004CAF6-11N Auxiliary ContactCAF6-11N1piece
GJL1201330R0006CAF6-20E Auxiliary ContactCAF6-20E1piece
GJL1201330R0007CAF6-20M Auxiliary ContactCAF6-20M1piece
GJL1201330R0008CAF6-20N Auxiliary ContactCAF6-20N1piece
GJL1201330R0010CAF6-02E Auxiliary ContactCAF6-02E1piece
GJL1201330R0011CAF6-02M Auxiliary ContactCAF6-02M1piece
GJL1201330R0012CAF6-02N Auxiliary ContactCAF6-02N1piece
GJL1201904R0001BN6 PlungerBN61piece
GJL1201906R0001LT6-B Cover CapLT6-B1piece
GJL1201907R0001LP6 Connecting LinkLP61piece
5
B7-30-01-80