PHOENIX CONTACT Deutschland GmbH Page 1 / 6
http://www.phoenixcontact.de Feb 9, 2011
Extract from the online
catalog
TT-EX(I)- 24DC
Order No.: 2832124
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2832124
Modular terminal block with three-stage surge protection for a floating
Ex-i signal circuit, separate PE connection, nominal voltage: 24 V DC,
for mounting on NS 35/7.5, terminal block width: 6.2 mm, terminal
block height: 54.6 mm
Commercial data
GTIN (EAN)
4 017918 172831
sales group J305
Pack 10 pcs.
Customs tariff 85363010
Catalog page information Page 101 (TT-2009)
Product notes
WEEE/RoHS-compliant since:
06/28/2006
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Technical data
General
Housing material PA 6.6
Inflammability class acc. to UL 94 V0
Color blue
TT-EX(I)- 24DC Order No.: 2832124
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2832124
PHOENIX CONTACT Deutschland GmbH Page 2 / 6
http://www.phoenixcontact.de Feb 9, 2011
Standards for air and creepage distances EN 50020
VDE 0110-1
DIN EN 60079-11
Total surge current (8/20) µs 10 kA
Ambient temperature (operation) -40 °C ... 85 °C
Mounting type DIN rail: 35 mm
Design Double-level terminal block with PE foot – separate PE
connection
Degree of protection IP20
Direction of action Line-Line & Line-Earth Ground
Width 6.20 mm
Height 54.60 mm
Length 79.60 mm
Protective circuit
IEC category C1
C2
C3
D1
VDE requirement class C1
C2
C3
Nominal voltage UN24 V DC
17 V AC
Maximum continuous operating voltage UC30 V DC
21 V AC
Maximum continuous voltage UC (wire-wire) 30 V DC
21 V AC
Nominal current IN250 mA (40°C)
Operating effective current IC at UC≤ 5 µA
Ground conductor current IPE ≤ 1 µA
Nominal discharge surge current In (8/20) µs
(Core-Core)
5 kA
Nominal discharge surge current In (8/20) µs
(Core-Earth)
5 kA
Total surge current (8/20) µs 10 kA
TT-EX(I)- 24DC Order No.: 2832124
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2832124
PHOENIX CONTACT Deutschland GmbH Page 3 / 6
http://www.phoenixcontact.de Feb 9, 2011
Max. discharge surge current Imax (8/20) µs
maximum (Core-Core)
5 kA
Max. discharge surge current Imax (8/20) µs
maximum (Core-Earth)
5 kA (per path)
Nominal pulse current Ian (10/1000) µs (Core-
Core)
100 A
Nominal pulse current Ian (10/1000) µs (Core-
Earth)
100 A (per path)
Lightning test current (10/350) µs, peak value limp 500 A (per path)
Output voltage limitation at 1 kV/µs (Core-Core)
spike
≤ 50 V
Output voltage limitation at 1 kV/µs (Core-Earth)
spike
≤ 1.7 kV
Output voltage limitation at 1 kV/µs (Core-Core)
static
≤ 50 V
Output voltage limitation at 1 kV/µs (Core-Earth)
static
≤ 1.7 kV
Residual voltage at In, (conductor-conductor) ≤ 40 V
Protection level UP (Core-Core) ≤ 75 V (C2 (10 kV/5 kA))
≤ 50 V (C3 - 25 A)
Protection level UP (Core-Earth) ≤ 2 kV (C2 - 10 kV / 5 kA)
Response time tA (Core-Core) ≤ 1 ns
Response time tA (Core-Earth) ≤ 100 ns
Input attenuation aE, sym. 1 dB (≤ 1 MHz)
0.3 dB (≤ 200 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm
system
Typ. 6 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm
system
Typ. 2 MHz
Capacity (Core-Core) 2.5 nF
Resistance in series 4.7 Ω ±10 %
4.7 Ω
Surge carrying capacity in acc. with IEC 61643-21
(Core-Core)
C2 (10 kV/5 kA)
C1 (1 kV / 500 A)
C3 (25 A)
Surge carrying capacity in acc. with IEC 61643-21
(Core-Earth)
C2 (10 kV/5 kA)
C3 (25 A)
D1 (500 A)
TT-EX(I)- 24DC Order No.: 2832124
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2832124
PHOENIX CONTACT Deutschland GmbH Page 4 / 6
http://www.phoenixcontact.de Feb 9, 2011
Connection data
Type of connection Screw terminal blocks
Connection type IN Screw terminal blocks
Connection type OUT Screw terminal blocks
Screw thread M3
Tightening torque 0.8 Nm
Stripping length 8 mm
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 14
Connection, protective circuit
Standards/regulations IEC 61643-21
EN 50020
General
Maximum inner capacitance Ci2 nF
Maximum inner inductance Li1 µH
Maximum inner time factor (Ri/Li) 0.1 µs
Insulation voltage to ground 500 V 10 %
Conformity / approvals
ATEX Ex II 1G, Ex ia IIC T4...T6
Ex II 1 D, Ex iaD 20 T95...135 °C
Certificates / Approvals
Certification GOST, UCIEE, UL
Certification Ex: CUL-EX LIS, KEMA-EX, UL-EX LIS
TT-EX(I)- 24DC Order No.: 2832124
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2832124
PHOENIX CONTACT Deutschland GmbH Page 5 / 6
http://www.phoenixcontact.de Feb 9, 2011
Accessories
Item Designation Description
Assembly
2838982 D-DEK 1,5 BU Cover for setting the end of a TERMITRAB TT-EX(I)... row of
terminal blocks, color: blue
Additional products
Item Designation Description
Assembly
2838982 D-DEK 1,5 BU Cover for setting the end of a TERMITRAB TT-EX(I)... row of
terminal blocks, color: blue
Diagrams/Drawings
Dimensioned drawing
Circuit diagram
TT-EX(I)- 24DC Order No.: 2832124
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2832124
PHOENIX CONTACT Deutschland GmbH Page 6 / 6
http://www.phoenixcontact.de Feb 9, 2011
Address
PHOENIX CONTACT Deutschland GmbH
Flachsmarktstr. 8
32825 Blomberg,Germany
Phone +49 5235 3 12000
Fax +49 5235 3 41200
http://www.phoenixcontact.de
© 2011 Phoenix Contact
Technical modifications reserved;