2
[Ui] rated insulation
voltage
600 V for signalling circuit conforming to CSA C22.2
No 14
600 V for power circuit conforming to CSA C22.2 No
14
600 V for signalling circuit conforming to UL 508
690 V for signalling circuit conforming to IEC
60947-5-1
690 V for signalling circuit conforming to IEC
60947-4-1
690 V for power circuit conforming to IEC 60947-4-1
600 V for power circuit conforming to UL 508
Electrical durability 1.3 Mcycles 6 A AC-3 at Ue <= 440 V
Mounting support Plate
Rail
Standards BS 5424
IEC 60947
NF C 63-110
VDE 0660
Product certifications CSA
UL
Connections - terminals Screw clamp terminals 2 cable(s) 0.34...1.5 mm² -
cable stiffness: flexible - with cable end
Screw clamp terminals 2 cable(s) 0.75...4 mm² - ca-
ble stiffness: flexible - without cable end
Screw clamp terminals 2 cable(s) 1.5...4 mm² - ca-
ble stiffness: solid
Screw clamp terminals 1 cable(s) 0.34...2.5 mm² -
cable stiffness: flexible - with cable end
Screw clamp terminals 1 cable(s) 0.75...4 mm² - ca-
ble stiffness: flexible - without cable end
Screw clamp terminals 1 cable(s) 1.5...4 mm² - ca-
ble stiffness: solid
Tightening torque 1.3 N.m - on screw clamp terminals - with screwdriv-
er flat Ø 6 mm
1.3 N.m - on screw clamp terminals - with screwdriv-
er Philips No 2
Operating time 30...40 ms coil energisation and NO closing
10...20 ms coil de-energisation and NO opening
Safety reliability level B10d = 20000000 cycles contactor with mechanical
load conforming to EN/ISO 13849-1
B10d = 1369863 cycles contactor with nominal load
conforming to EN/ISO 13849-1
Mechanical durability 30 Mcycles
Operating rate 3600 cyc/h
Complementary
Coil technology Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits 0.1...0.7 Uc at <= 50 °C drop-out
0.7...1.30 Uc at <= 50 °C operational
Inrush power in W 1.8 W at 20 °C
Hold-in power consumption in W 1.8 W at 20 °C
Heat dissipation 1.8 W
Auxiliary contacts type Type instantaneous (1 NC)
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Non overlap distance 0.5 mm
Insulation resistance > 10 MOhm for signalling circuit
Environment
IP degree of protection IP2x conforming to VDE 0106
Protective treatment TC conforming to DIN 50016
TC conforming to IEC 60068
Ambient air temperature for operation -25...50 °C
Ambient air temperature for storage -50...80 °C
Operating altitude 2000 m without derating in temperature