ScotchlokTerminals
MVU14-110DF
Female Disconnect, Vinyl Insulated, Butted Seam
Data Sheet
Specifications
Wire Size: See Table Above
Barrel Seam: Butted
Maximum Operating Temp: 221˚F (105˚C)
Maximum Current: Same as Wire
Insulator Material: Vinyl
Terminal Material: Brass
Plating: Tin
Installation Information
For use on stranded copper wire only.
Strip away the end 3/8 inch of wire insulation.
Make the crimp in the proper station of a recommended
3M crimp tool: TH-440, TH-450 (scissor style) or
TR-490 (ratchet style) hand tools.
L
WARNING
Turn power off before installing or removing ter minal. All electrical
work should be done according to appropriate electr ical codes.
Barrel Crimp (Electrical)
rebmuNtcudorP
eriW egnaR )GWA( baTelaMhtiwsetaM ssenkcihTx)´W(htdiWL
lerraB htgneL lerraB .D.I
mumixaM noitalusnI retemaiD
FD011-41UVM41-61 020.0x011.0 020.0x521.0 18.091.0511.0541.0
Electrical Products Division
6801 River Place Blvd.
Austin, TX 78726-9000
http://www.3M.com/elpd Litho in USA.
© 3M 2002 78-8126-0379-9-A
IMPORTANT NOTICE
Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability
associated with such use.
Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture as of the date of
purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above,
your exclusive remedy shall be, at 3Ms option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except
where prohibited by law, 3M will not be liable for any loss or damage arising from this 3M product, whether direct, indirect,
special, incidental or consequential regardless of the legal theory asserted.
3M and Scotchlok are trademarks of 3M
Engineering Specification
Crimp-Type Female Disconnect Terminals shall,
electrically and mechanically, connect permanently to
a prestripped end of a stranded copper wire: and have
a tongue portion with fingers which grip a Male
Disconnect in a separable, reusable manner, forming a
Quick Connect Wiring Termination.
The connector line shall offer tongue variations (sized
to grip Male Tabs: 0.110˝ x 0.020˝ or 0.110˝ x 0.032˝
per ANSI/NEMA CD-2) and barrel variations
construction (non-insulated, vinyl insulated with
insulation grip, nylon fully insulated, etc.). The tongue
portion shall be marked with the wire range and
manufacturer’s name or trade mark ().
The Vinyl Insulated 0.110˝ Female Disconnect shall be
tin plated 0.010˝ thick brass with a tongue for gripping
a 0.110˝ or 0.125˝ male tab of 0.020˝ thickness and
with a 0.19˝ long barrel covered by a molded vinyl
sleeve, color coded and sized for a specified (AWG)
wire range (16-14).